![](/html/32/32c5/32c5e3c64ed8db553555feb3eb83ab8c747c7c13a5c97cea10ddd62fb6670dfb/bg1.png)
1
MA00613903
ESYLUX GmbH | An der Strusbek 40
22926 Ahrensburg | Germany
info@esylux.com | www.esylux.com
Detailed operating instructions
MD 360/8 Basic
EB10430404
MD 360i/8 Basic
EB10430428
MD 360/24 Basic
EB10430848
MD 360i/24 Basic
EB10430862
MD 360/24 Basic SMB
EB10430886
MD 360i/24 Basic SMB
EB10430909
MD 360/8 Basic SMB
EB10430497
MD 360i/8 Basic SMB
EB10430466
![](/html/32/32c5/32c5e3c64ed8db553555feb3eb83ab8c747c7c13a5c97cea10ddd62fb6670dfb/bg2.png)
GB
MD 360/8 Basic MD 360i/24 Basic MD 360/24 Basic SMB
MD 360i/8 Basic MD 360/8 Basic SMB MD 360i/24 Basic SMB
MD 360/24 Basic MD 360i/8 Basic SMB
Table of contents
1 Description 3
2 Safety instructions 3
3 Operation / functionality 4
3.1 Conditions in which the lighting is switched on 4
3.2 Conditions in which the lighting is switched off 4
3.3 Switching delay – not in pulse mode 4
4 Installation / connection 5
4.1 Masking the field of detection 7
5 Activation 7
5.1 Overview of factory settings 7
6 Settings 8
6.1 Control via external “S” button 8
6.2 Configuring parameters via remote control 8
6.3 Mobil-PDi/MDi 8
6.4 Mobil-PDi/MDi temporary settings 9
6.5 Programming the Mobil-PDi/MDi 9
6.6 Mobil-PDi/MDi-universal 11
6.7 Mobil-PDi/MDi-universal temporary settings 11
6.8 Programming the Mobil-PDi/MDi-universal 13
7 Technical data 15
8 Troubleshooting 15
8.1 Maintenance 16
8.2 Cleaning 16
9 ESYLUX manufacturer's guarantee 17
![](/html/32/32c5/32c5e3c64ed8db553555feb3eb83ab8c747c7c13a5c97cea10ddd62fb6670dfb/bg3.png)
GB
MD 360/8 Basic MD 360i/24 Basic MD 360/24 Basic SMB
MD 360i/8 Basic MD 360/8 Basic SMB MD 360i/24 Basic SMB
MD 360/24 Basic MD 360i/8 Basic SMB
1 Description
The ESYLUX ceiling-mounted motion detector is a passive infrared presence detector
that responds to moving heat sources, such as people walking.
The motion detector is designed for areas with low levels of natural light, such as
hallways, cellars, staircases, changing rooms, toilets, garages etc.
Note: Use this product only as intended (as described in the user instructions).
The device must not be changed, modified or painted – doing so will void any warranty
claims. You must check the device for damage immediately after unpacking it. If there
is any damage, you should not install the device under any circumstances.
If you suspect that safe operation of the device cannot be guaranteed, you should turn
the device off immediately and make sure that it cannot be operated unintentionally.
2 Safety instructions
• Work on the 230-V power system must be carried out by authorised personnel only, with
due regard to the applicable installation regulations / standards
• Switch off the power supply before installing the system
• On the input side, the device is to be protected against short circuits with a 10-A circuit
breaker
• Protection type IP 40 for interior use
![](/html/32/32c5/32c5e3c64ed8db553555feb3eb83ab8c747c7c13a5c97cea10ddd62fb6670dfb/bg4.png)
GB
MD 360/8 Basic MD 360i/24 Basic MD 360/24 Basic SMB
MD 360i/8 Basic MD 360/8 Basic SMB MD 360i/24 Basic SMB
MD 360/24 Basic MD 360i/8 Basic SMB
3 Operation / functionality
• 360° field of detection, 8 m / 24 m range at an installation height of 2.5 m
• Automatically controlled lighting channels when motion is detected
• With zero-cross switching
3.1 Conditions in which the lighting is switched on
The lighting is switched on if the target brightness value is below the preset lux
value and movement is detected in the field of detection. Further movement is
acknowledged by the sensor with two short flashes of the red LED (the LED can be
switched off; see “Configuring parameters via remote control”).
Once the lighting has been switched on, the sensor deactivates light measurement for
this period.
3.2 Conditions in which the lighting is switched off
The lighting is switched off if no movement is detected in the field of detection and
the preset switch-off delay time has elapsed
3.3 Switching delay – not in pulse mode
When persons are present, in order to avoid sudden changes in brightness caused by
undesired switching on / off of the lighting, the detector will only be triggered after a
time delay.
Example: a passing cloud could potentially cause unnecessary switching.
Time delay from light to dark: 30 sec. = red LED lights up during this period.
Time delay from dark to light: none = only switch-off delay active.
![](/html/32/32c5/32c5e3c64ed8db553555feb3eb83ab8c747c7c13a5c97cea10ddd62fb6670dfb/bg5.png)
GB
MD 360/8 Basic MD 360i/24 Basic MD 360/24 Basic SMB
MD 360i/8 Basic MD 360/8 Basic SMB MD 360i/24 Basic SMB
MD 360/24 Basic MD 360i/8 Basic SMB
4 Installation / connection
Note: Switch off the power supply before installing the system.
• The detectors can be flush mounted or surface mounted, and are also suitable for
recessed ceiling mounting using accessories
Recessed mounting Recessed ceiling mounting (see accessories)
for suspended ceilings
Surface mounting Surface mounting
with spacers
![](/html/32/32c5/32c5e3c64ed8db553555feb3eb83ab8c747c7c13a5c97cea10ddd62fb6670dfb/bg6.png)
GB
MD 360/8 Basic MD 360i/24 Basic MD 360/24 Basic SMB
MD 360i/8 Basic MD 360/8 Basic SMB MD 360i/24 Basic SMB
MD 360/24 Basic MD 360i/8 Basic SMB
• Specifications regarding the range of the detector relate to an ambient temperature
of approx. 20°C
• Movement crossways to the detector is optimal for triggering the detector; head-on
approaches to the detector are more difficult to detect and therefore the range of
the detector is significantly reduced
• The detector should be positioned depending on the available space and usage
requirements
• Make sure that the detector has a clear line of sight, as infrared beams cannot
penetrate solid objects
• Connect the detector in accordance with the circuit diagram
Single connection
Parallel connection
L Phase, 230 V
Lighting
Neutral conductor
Push button
24 m
8 m