2.0 GENERAL REQUIREMENTS
2.1 COMPONENTS SUPPLIED
1. Unvented water cylinder incorporating
cylinder heater and thermal controls
2. Factory tted Temperature/Pressure Relief Valve
3. T&P Valve insulation and housing.
4. Cold Water Combination Valve.
5. Expansion Vessel and mounting bracket.
6. Tundish.
7. Compression nuts and olives
8. Cylinder heater key spanner
2.2 SITING THE UNIT
The unit must be installed vertically. Although location is not critical, the following points should be
considered:
• The unit should be sited to ensure minimum dead
leg distances, particularly to the point of most frequent
use.
• Avoid siting where extreme cold temperatures
will be experienced. All exposed pipework should be
insulated.
• The discharge pipework from the safety valves
must have minimum fall of 1:200 from the unit and
terminate in a safe and visible position.
• Access to associated controls and cylinder heater
should be possible to allow for periodic servicing and
maintenance.
• Ensure that the base chosen for the unit is level
and capable of permanently supporting the weight
when full of water (see Table 2).
2.3 WATER SUPPLY
Bear in mind that the mains water supply to the
property will be supplying both the hot and cold water requirements simultaneously. It is recommended
that the maximum water demand is assessed and the
water supply checked to ensure this demand can be
satisfactorily met.
NOTE: A high mains water pressure will not always
guarantee high ow rates.
Wherever possible the mains supply pipe should be
22mm. We suggest the minimum supply requirements
should be 0.15MPa (1.5 bar) pressure and 20 litres
per minute owrate. However, at these values outlet
owrates may be poor if several outlets are used si-
multaneously. The higher the available pressure and
owrate the better the system performance.
The unit has an operating pressure of 0.35MPa (3.5
bar) that is controlled by the Cold Water Combination
Valve. The Cold Water Combination Valve can be
connected to a maximum mains pressure of 1.6MPa
(16 bar).
2.4 OUTLET/TERMINAL FITTINGS (TAPS, ETC.)
The unit can be used with most types of terminal ttings. It is advantageous in many mixer showers to
have balanced hot and cold water supplies. In these
instances a balanced pressure cold water connection
should be placed between the Cold Water Combination
Valve and the water cylinder. Outlets situated higher
than the unit will give outlet pressures lower than that
at the cylinder, a 10m height difference will result in a
0.1MPa (1 bar) pressure reduction at the outlet.
2.5 LIMITATIONS
The unvented water cylinder should not be used in
association with any of the following:
• Ascending spray type bidets or any other class 1
back syphonage risk requiring that a type A air gap
be employed.
• Situations where maintenance is likely to be
neglected or safety devices tampered with.
• Water supplies that have either inadequate pres-
sure or where the supply may be intermittent.
• Situations where it is not possible to safely pipe
away any discharge from the safety valves.
• In areas where the water consistently contains a
high proportion of solids, e.g. suspended matter that
could block the strainer, unless adequate ltration can
be ensured.
Table 3: Standing heat losses
Table 2: Unit weights
Based on an ambient air temperature of 20oC and a
stored water temperature of 65oC