EST SIGA2-PHS(B) Installation Sheet

SIGA2-PHS(B) Intelligent 3D Multisensor Photo­Heat Detector Installation Sheet

Installation

Notes
This detector does not operate without electrical power. As fires frequently cause power interruption, discuss further safeguards with the local fire protection specialist.
This detector does not sense fires in areas where smoke

Description

The Signature Series Intelligent 3D Multisensor Photo-Heat Detector is an intelligent device that contains a photoelectric smoke sensor and a fixed-temperature heat sensor. There are two models: SIGA2-PHS is white; SIGA2-PHSB is black.
displays the following states:
Normal: Green LED indicator flashes, no action.
Alarm/active: Red LED indicator flashes, evacuate the area.
Stand-alone alarm: Red LED indicator turns on, evacuate the area.
Figure 1: SIGA2-PHS(B) features
or heat cannot reach the detector. Smoke or heat from fires in walls, roofs, or on the opposite side of closed doors may not reach the detector.
Photoelectric detectors have a wide range of sensing capabilities, and are best suited for detecting slow, smoldering fires. The heat sensor in this device provides a source of supplemental information. The heat sensor by itself does not provide life safety protection.
To ensure proper operation, store the detector within the recommended ranges. Allow the detector to stabilize to room temperature before applying power.
The dust cover (supplied) must remain on the detector during installation and be removed prior to commissioning and service. The dust cover is not a substitute for removing the detector during new construction or heavy remodeling.
In Canada, install according to the CAN/ULC-S524
Standard for the Installation of Fire Alarm Systems, the CSA C22.1 Canadian Electrical Code, and the local
authority having jurisdiction.
1
3
1. Tamper-resist lever arm on base
2. Access slot for tamper-resist mechanism
3. LED indicator
© 2011 U
TC Fire & Security. All rights reserved. 1 / 4 P/N 3101548 • REV 2.0 • ISS 10AUG11
Upon completion of the original installation and following any modifications or additions to the system, perform a calibrated sensitivity test per NFPA code. Signature Series
2
devices can perform this test and the panel can generate a system sensitivity report.
To permanently disable the tamper-resist mechanism prior to placing the detector in difficult to reach locations, break and remove the plastic lever arm from the base. See Figure 1, item 1.
To install the detector:
1. Install and wire the base, as described on the installation sheet supplied with the base.
2. Remove the serial number label from the detector and attach it to the project documentation.
3. Attach the detector to the base by rotating the detector clockwise until it snaps into the locked position.

Testing

Before testing, notify the proper authorities that the fire alarm system is undergoing maintenance and will be temporarily out of service.
Test each sensor in the detector. In the following steps, xxx indicates a variable related only to marketplace.
Caution: Heat damage. Excessive heat may damage the
detector outer cover. Do not apply excessive heat when using a hair dryer. When using a Testifire detector tester, you must install a SIGA2 Testifire Adapter Assembly.
Make sure the SIGA2 Testifire Adapter Assembly (model SIGA2-TSTSPACER) is installed in the Testifire detector tester before testing. Refer to the SIGA2 Testifire Adapter Assembly Installation Sheet (P/N 3101942) for further details.
To perform an initial installation test:
1. Remove the detector from its base and verify that the proper detector address, trouble signals, and messages are reported.
2. If wired for Class A operation, verify that the detector continues to operate first with SLC_IN disconnected, and then with SLC_OUT disconnected. (Refer to the installation sheet for the base.)
3. Place a momentary ground fault on the SLC circuit to verify operation of the ground fault detection circuitry.
4. Run a system detector sensitivity report on all detectors and verify that readings fall within acceptable limits.
5. Perform a sensor function test, as described below.
To perform sensor function tests:
1. If desired, use the fire alarm control panel to put the detector or zone into a service group for testing. (Refer to the panel technical reference manual for instructions.)
2. Activate the smoke sensor using No Climb Products model CHEK02-xxx smoke aerosol spray, a smoke generator, or the Testifire detector tester per the manufacturer’s instructions.
3. Activate the heat sensor using a hair dryer (maintaining a distance of three inches) or using a Testifire detector tester per the manufacturer’s instructions.

Maintenance

To ensure proper operation, plan maintenance in accordance with the requirements of the authority having jurisdiction. Refer
to CAN/ULC-S536 Standard for the Inspection and Testing of
Fire Alarm Systems and NFPA 72 National Fire Alarm and Signaling Code.
Refer to Technical Bulletin P/N 270145 REV 4.0 or later for additional information and cleaning instructions.
Smoke chamber replacement
Replace the smoke chamber whenever cleaning the detector does not restore the panel to normal conditions. Replace with model number 2-SPRC1 using installation sheet P/N 3101860.

Specifications

Operating voltage 15.20 to 19.95 VDC
Current Normal operating current Alarm Stand-alone alarm current
Air velocity [1] 0 to 4,000 ft./min (0 to 20.32 m/s)
Maximum spacing 50 ft. (15.2 m) centers
Wall mount distance from ceiling
Compatible bases [2] Standard Relay Isolator Audible
Compatible detector testers [3] Testifire 1000, Testifire 2000
Operating environment Temperature Relative humidity
Storage temperature 4 to 140°F (20 to 60°C)
Environmental compensation Automatic
[1] For duct installation, use a SIGA-DMP duct detector mounting plate and install per P/N 387053P.
[2] When using the black detector, the SIGA-TSB Detector Trim Skirt (black) can provide a finished look and hide the white base.
[3] Requires the SIGA2-TSTSPACER Testifire adapter assembly.
45 µA 45 µA
18.3 mA
12 in. (305 mm) max.
SIGA-SB, SIGA-SB4 SIGA-RB, SIGA-RB4 SIGA-IB, SIGA-IB4 SIGA-AB4, SIGA-AB4G
32 to 100°F (0 to 38°C) 0 to 93% noncondensing

Regulatory information

Manufacturer Edwards, A Division of UTC Fire & Security
Year of manufacture
North American standards
UL/ULC smoke sensitivity range
UL/ULC fixed­temperature alarm rating
UL/ULC Actual alarm point
FCC compliance This device complies with part 15 of the FCC
Americas Corporation, Inc. 8985 Town Center Parkway, Bradenton, FL 34202, USA
The first two digits of the date code (located on the product identification label) are the year of manufacture.
CAN/ULC-S529-09, CAN/ULC-S530-M91, UL 268, UL 268A, UL 521
0.85 to 4.00 %/ft. (2.7 to 12.5 %/m) obscuration
135°F (57.2°C)
129 to 141°F (53.9 to 60.6°C)
Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
2 / 4
P/N 3101548 • REV 2.0 • ISS 10AUG11
Loading...
+ 2 hidden pages