CHIMNEY AND FLUE
The installer has a responsibility under the Health
and Safety at Work Act 1974 to provide for the
safety of persons carrying out the installation.
Attention is drawn to the fact that fire cement is
caustic and hands must be washed thoroughly after
use. The appliance is heavy and care must be taken
during handling. Although the appliance does not
contain asbestos products, it is possible that
asbestos may be disturbed in existing installations
and every precaution must be taken.
These instructions give a guide for the installation
of the appliance but in no way absolves the installer
from responsibilities to conform to British
Standards, in particular BS8303 and BS6461,
relating to the installation of solid fuel appliances.
The installation should also comply with local
Building Regulations and Local Authority ByeLaws.
Any adjacent combustible material should be far
enough away from the cooking stove so as not to
rise 60°C above the room temperature when the
cooking stove is in operation. If necessary, any
adjoining walls should be protected from the
effects of heat.
The successful operation of the cooking stove relies
on the adequate performance of the chimney to
which it is connected. The chimney must:
● Have an internal cross section of no less than 320
cm.sq (200mm dia.). (If a flue liner is used it
should be 6” diameter and suitable for solid fuel).
● Be a minimum 4.6m high from hearth level to pot.
● Be terminated at least 1m above roof level so
that the chimney does not terminate in a
pressure zone. See Figure 6 on page 10.
● Be free from cracks, severe bends, voids, and
obstructions.
● Be connected to this one appliance only.
● New chimneys must be built in accordance with
local building regulations.
● If the cooking stove is installed as a freestanding
appliance, it should not support any part of the
chimney.
● Voids in the chimney should be avoided as these
will prevent a steady flue draught. The cooking
stove flue pipe should pass beyond the
narrowing of the chimney.
● A flue/chimney access point may also be
required so that the state of the chimney can be
checked and any fallen soot removed.
● External flues must be insulated to prevent heat loss.
FLUE DRAUGHT
The chimney can be checked, before the cooking
stove is installed, with a smoke match. If the
chimney doesn’t pull the smoke it may suggest the
chimney needs attention (see the Flue Diagnosis
Table on page 11).
Note: This test is only a guide as an apparently
poor flue may improve once the cooking stove is
installed, lit and the flue is warmed. If, once the
cooking stove is installed, there is any doubt that
the chimney is providing an adequate draught, a
flue draught reading should be taken.
9