ESPRIT 738 ultra, 728 ultra Programming Manual

Page 1
Esprit 728 Ultra & 738 Ultra - 1 - Programming Guide
System Programming Guide
Software Versions 4.4 (728ULT) and 4.1 (738ULT)
Installer Code (Default - 728 Ultra: 282828; 738 Ultra: 383838)
Full access to programming, except user access codes (PINs). No access to arming/disarming. Use only numeric keys from [0] to [9].
Zone Recognition
Streamlined Section Programming
The keypad will not display the current data in the Streamlined Section Programming method.
Table 1: Zone Recognition
Device connected to which input? 728 Ultra
No A TZ
728 Ultra With ATZ
738 Ultra No ATZ
738 Ultra With ATZ
Control Panel
Input 1 = Zone 1 Zones 1 & 2 Zone 1 Zones 1 & 9 Input 2 = Zone 2 Zones 3 & 4 Zone 2 Zones 2 & 10 Input 3 = Zone 3 Zones 5 & 6 Zone 3 Zones 3 & 11 Input 4 = Zone 4 Zones 7 & 8 Zone 4 Zones 4 & 12 Input 5 = N/A N/A Zone 5 Zones 5 & 13 Input 6 = N/A N/A Zone 6 Zones 6 & 14 Input 7 = N/A N/A Zone 7 Zones 7 & 15 Input 8 = N/A N/A Zone 8 Zones 8 & 16
Keypad
Zone 1 = Zone 5 Zone 9 Zone 9 Zone 17 Zone 2 = Zone 6 Zone 10 Zone 10 Zone 18
Table 2: Streamlined Section Programming Method
1. Press [
ENTER] + [INSTALLER CODE] (Default - 728 Ultra: 282828; 738 Ultra: 383838) + [7].
2. The [
ENTER] and [2ND] keys will flash to indicate you are in programming mode (LED keyp ad only).
3. Enter 2-digit [
SECTION] (00 to 67).
4. The [ENTER] key will remain on while the [2ND] key will be off (LED keypad only).
5. Enter 8-digit [
DATA] to program the section.
6. The keypad will beep to indicate that the section has been programmed, data is saved and the software has advanced to the next section.
7. Return to step 4 or press [
CLEAR] to exit programming mode.
&
Page 2
Esprit 728 Ultra & 738 Ultra - 2 - Programming Guide
Keypad Trouble Display
Press the [TBL]/[TRBL] key to view the trouble. Any illuminated keys represent a specific trouble as indicated in Table 3 below. Press the [CLEAR] button to exit the trouble display.
Hex Programming
This is an alternate method to the Streamlined Section Programming (see page 1). Addresses 000 to 043 and 300 to 527 can be programmed using the Hex Programming method. In this mode, you can enter any hexadecimal digit from 0 to F where keys [1] to [9] represent digits 1 to 9 respectively; the other keys represent hexadecimal digits A to F as shown in Figure 1 below.
Figure 1: Hex Digit Data Entry and Data Display for LED Keypads
Table 3: Trouble Display
[1]
- No Battery or Low Voltage
[7]
- Communicator Report Failure
[2]
- Power Failure
[8]
- Timer Loss* (to clear , see [MEM] key in Table 11 on page 11)
[4]
- Bell Output Disconnected
[9]
- Tamper or Zone Wiring Failure
[5]
- Exceeded Maximum Bell Current
[10]
- Telephone Line Monitoring Failure
[6]
- Exceeded Maximum Auxiliary Current
[11]
- Fire Loop Trouble
Table 4: Hex Programming Method
1. Press [
ENTER] + [INSTALLER CODE] (Default - 728 Ultra: 282828; 738 Ultra: 383838).
2. The [
ENTER] key will flash indicating you are in programming mode (LED keypad only).
3. Enter the desired 3-digit [ADDRESS].
4. The keypad will display the 2-digit data currently saved at this address as described in Figure 1 below.
5. Enter 2-digit [
DATA] and do not press [ENTER], the software automatically saves the data.
6. Return to step 2 or press [CLEAR] to exit programming mode.
Therefore 2-digit data = 7A
= First digit = 4 + 2 + 1 = 7
= Second digit = 8 + 2 = 10
Note: Values 10 to 15 represent hex digits A to F respectively. See keypad to the left.
Each key in the first 2 rows of the keypad represents a specific value when the key is lit, as shown above. If the key isn’t lit, the key represents 0. The sum of the values of the lit keys in the first row correspond to the second hex digit. The sum of the values of the lit keys in the second row correspond to the first hex digit as shown in the example below.
Sum of the second row = first hex digit
Sum of the first row = second hex digit
If the key is not lit, value = 0
Note: LCD keypads will display current data on the screen.
Page 3
Esprit 728 Ultra & 738 Ultra - 3 - Programming Guide
INSTALLER / Panel Answer Options
Telephone and Account Numbers
If only one monitoring station phone number is used, program the same number for telephone numbers 1 and 2. If only one account number is required, the same number must be entered for both accounts "A" and "B".
[0] to [9] = numeric value [
BYP] = switch from pulse to tone while dialing
[
STAY] = * [MEM] = pause 4 seconds
[AWAY]/[FORCE] = # [TBL]/[TRBL] = end of number
Streamline Section Data
Description
Address Answering Machine Override
___ / ___ Installer code (1st, 2nd digit) 000
[2ND] or [1] = disabled [5] = 40 seconds
___ / ___ Installer code (3rd, 4th digit) 001
[2] = 16 seconds [6] = 48 seconds
___ / ___ Installer code (5th, 6th digit) 002
[3] = 24 seconds [7] = 56 seconds
___ / ___ Panel answer options
003
[4] = 32 seconds [8] to [F] = 60 seconds
Number of rings (Max. 15)
Streamline Section Data
Description
Address
___ / ___ Panel Identifier (1st, 2nd digit) 004 ___ / ___ Panel Identifier (3rd, 4th digit)
005
___ / ___ PC Password (1st, 2nd digit) 006 ___ / ___ PC Password (3rd, 4th digit)
007
Computer Telephone Number
(View at addresses
008
to
015
)
Streamline Section Streamline Section
Press the [TBL]/[TRBL] key to end phone number if less than 16 digits are programmed.
02
__/__/__/__/__/__/__/__
03
__/__/__/__/__/__/__/__
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Monitoring Station Telephone Number 1
(View at addresses
016
to
023
)
Streamline Section Streamline Section
Press the [TBL]/[TRBL] key to end phone number if less than 16 digits are programmed.
04
__/__/__/__/__/__/__/__
05
__/__/__/__/__/__/__/__
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Monitoring Station Telephone Number 2
(View at addresses
024
to
031
)
Streamline Section Streamline Section
Press the [TBL]/[TRBL] key to end phone number if less than 16 digits are programmed.
06
__/__/__/__/__/__/__/__
07
__/__/__/__/__/__/__/__
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Accounts “A” and “B” (View at addresses 032 to 035)
Streamline Section
For 3-digit account numbers, enter “skip” ([2
ND]) as first digit.
The Standard Pulse report format can support 3- or 4-digit account numbers. The Ademco Express, Ademco Contact ID and the Pager report formats only support 4­digit account numbers.
08
__/__/__/__ __/__/__/__
1234 5678
AB
00
01
{
Identifies the control panel to the PC.
{
Identifies the PC to the control panel.
First digit disables “Answering Machine Override” (key [2
ND] or key [1]), or determines period of time
between first and second call. Second digit determines number of rings required before panel will answer. If [2
ND][2ND] is entered, panel will not
answer (Default value is [2
ND] [8]).
Page 4
Esprit 728 Ultra & 738 Ultra - 4 - Programming Guide
Streamline Section Data
Description
Address
[2
ND] / [2ND] Future Use 036
___ / ___ 1st digit: Pager Delay (see table at right)
2nd digit: Time correction (see table at right)
037
___ / ___ 1st digit: Communicator Format 1
2nd digit: Communicator Format 2
038
___ / ___ 1st digit: PGM1 type
2nd digit: PGM2 type (738 Ultra only)
039
Streamline Section Data
Description
Address
___ / ___ PGM1 040 ___ / ___ PGM2 (738 Ultra only) 041 ___ / ___ PGM Mask 1 042 ___ / ___ PGM Mask 2 (738 Ultra only) 043
Communicator Formats
(* = supports 4-digit account codes only)
Key Key
[2
ND] = ADEMCO slow (1400Hz, 1900Hz, 10bps) [6] = RADIONICS with PARITY (1400Hz, 40bps)
[1] = (1400Hz, 1800Hz, 10bps) [7] = RADIONICS with PARITY (2300Hz, 40bps) [2] = SILENT KNIGHT fast (1400Hz, 1900Hz, 20bps) [8] = * ADEMCO express [3] = SESCOA (2300Hz, 1800Hz, 20bps) [9] = * ADEMCO contact ID (programmable codes) [4] = RADIONICS (40bps with 1400Hz handshake) [0] = * ADEMCO contact ID (all codes) [5] = RADIONICS (40bps with 2300Hz handshake) [
TBL] / [TRBL] = * PAGER FORMAT (personal dialing)
Programmable Contact ID Event Codes
All addresses from 300 to 527 (sections 11 to 67) programmed with values other than [2ND] [2ND] will report the contact ID codes corresponding to the values programmed. Values to be programmed should be selected from this table.
CID Reporting Code Prog. Value CID Reporting Code Prog. Value
100: A
UXILIARY ALARM [2ND] / [1] 300: SYSTEM TROUBLE [2] / [2]
110: F
IRE ALARM [2ND] / [2] 301: AC LOSS [2] / [3]
111: F
IRE SMOKE [2ND] / [3] 302: LOW SYSTEM BATTERY [2] / [4]
112: C
OMBUSTION [2ND] / [4] 305: SYSTEM RESET [2] / [5]
113: W
ATER FLOW [2ND] / [5] 306: PROGRAM CHANGED [2] / [6]
114: H
EAT [2ND] / [6] 309: BATTERY TEST FAIL [2] / [7]
115: P
ULLSTATION [2ND] / [7] 320: SOUNDER/REL AY TROUBLE [2] / [8]
116: D
UCT [2ND] / [8] 321: BELL 1 TROUBLE [2] / [9]
117: F
LAME [2ND] / [9] 323: ALARM RELAY TROUBLE [2] / [0]
118: N
EAR ALARM [2ND] / [0] 350: COMMUNICATION TROUBLE [2] / [STAY]
120: P
ANIC ALARM [2ND] / [STAY] 351: TELCO 1 FAULT [2ND] / [AWAY] OR [FORCE]
121: D
URESS [2ND] / [AWAY] OR [FORCE] 354: FAIL TO COMMUNICATE [2] / [BYP]
122: S
ILENT PANIC [2ND] / [BYP] 370: PROTECTION LOOP TROUBLE [2] / [MEM]
123: A
UDIBLE PANIC [2ND] / [MEM] 371:
P
ROTECTION LOOP OPEN
[2] / [TRBL]
130: B
URGLARY [2ND] / [TRBL] 372: PROTECTION LOOP SHORT [3] / [2ND]
131: P
ERIMETER BURGLARY [1] / [2ND] 373: FIRE LOOP TROUBLE [3] / [1]
132: I
NTERIOR BURGLARY [1] / [1] 382: SENSOR TROUBLE [3] / [2]
133: 24H
R BURGLARY [1] / [2] 383: SENSOR TAMPER [3] / [3]
136: B
URGLARY OUTDOOR [1] / [3] 400: OPEN / CLOSE [3] / [4]
137: B
URGLARY TAMPER [1] / [4] 401: OPEN / CLOSE BY USER # [3] / [5]
138: B
URGLARY NEAR ALARM [1] / [5] 402: GROUP OPEN / CLOSE [3] / [6]
140: G
ENERAL ALARM [1] / [6] 403: AUTOMATIC OPENING / CLOSING [3] / [7]
150: 24 H
OUR AUXILIARY [1] / [7] 404: LATE TO OPEN / CLOSE [3] / [8]
151: G
AS DETECTED [1] / [8] 407: REMOTE ARM DOWNLOAD [3] / [9]
152: R
EFRIGERATION [1] / [9] 410: REMOTE ACCESS [3] / [0]
153: L
OSS OF HEAT [1] / [0] 441: OPEN / CLOSE - STAY MODE [3] / [STAY]
154: W
ATER LEAKAGE [1] / [STAY] 570: BYPASS [3] / [AWAY] OR [FORCE]
155: F
OIL BREAK ALARM [1] / [AWAY] OR [FORCE] 572: 24 HOUR ZONE BYPASS [3] / [BYP]
156: D
AY TROUBLE ALARM [1] / [BYP] 573: BURGLARY BYPASS # [3] / [MEM]
157: L
OW GAS LEVEL [1] / [MEM] 574: GROUP BYPASS [3] / [TRBL]
158: H
IGH TEMPERATURE [1] / [TRBL] 601: MANUAL TEST [4] / [2ND]
159: L
OW TEMPERATURE [2] / [2ND] 602: PERIODIC TEST [4] / [1]
161: L
OSS AIR FLOW [2] / [1] 625: TIME / DATE RESET [4] / [2]
654: S
YSTEM INACTIVITY [4] / [3]
09
10
[2ND] or [1] = 8s [2] = 16s [3] = 24s [4] = 32s [5] = 40s [6] = 48s [7] = 56s [8] = 64s
[2
ND] = No adjustment
[1] = Plus 4s [2] = Plus 8s [3] = Plus 12s [4] = Plus 16s [5] = Plus 20s [6] = Plus 24s [7] = Plus 28s
[8] = Minus 4s [9] = Minus 8s [0] = Minus 12s [
STAY] = Minus 16s
[
FORCE] = Minus 20s
[
BYP
]
= Minus 24s
[
MEM
]
= Minus 28s
[
TRBL
]
= Minus 32s
Time Correction Table (2nd digit)
Pager Delay Table (1st digit)
[9] = 72s [0] = 80s [
STAY] = 88s
[
FORCE]/[AWAY] = 96s
[
BYP] = 104s
[
MEM] = 112 s
[
TBL]/[TRBL] = 120s
Page 5
Esprit 728 Ultra & 738 Ultra - 5 - Programming Guide
Reporting Codes
All digits from [1] to [F] are valid. [2ND] = digit will not be reported except for Contact ID programmable codes. For single digit reporting, enter “skip” ([2ND]) as the first digit (Default = [2ND] / [2ND]).
Enter FF to program the default Ademco Contact ID report code when using the Ademco Contact ID (programmable codes) or Pager report formats. If the Contact ID Format (all codes) is selected, addresses 300 to 527 (sections 11 to 67) do not have to be programmed. To select Contact ID (all codes) you must set key [0] at section 09/address 038 for both monitoring station numbers (see page 4).
Arming (Closing) Report Codes:
Streamline
Section
Data Description Address
Streamline
Section
Data Description Address
___ / ___ Auto / Espload 300 ___ / ___ User Code 23 324 ___ / ___ Master 301 ___ / ___ User Code 24 325 ___ / ___ User Code 1 302 ___ / ___ User Code 25 326 ___ / ___ User Code 2 303 ___ / ___ User Code 26 327
___ / ___ User Code 3 304 ___ / ___ User Code 27 328 ___ / ___ User Code 4 305 ___ / ___ User Code 28 329 ___ / ___ User Code 5 306 ___ / ___ User Code 29 330 ___ / ___ User Code 6 307 ___ / ___ User Code 30 331
___ / ___ User Code 7 308 ___ / ___ User Code 31 332 ___ / ___ User Code 8 309 ___ / ___ User Code 32 333 ___ / ___ User Code 9 310 ___ / ___ User Code 33 334 ___ / ___ User Code 10 311 ___ / ___ User Code 34 335
___ / ___ User Code 11 312 ___ / ___ User Code 35 336 ___ / ___ User Code 12 313 ___ / ___ User Code 36 337 ___ / ___ User Code 13 314 ___ / ___ User Code 37 338 ___ / ___ User Code 14 315 ___ / ___ User Code 38 339
___ / ___ User Code 15 316 ___ / ___ User Code 39 340 ___ / ___ User Code 16 317 ___ / ___ User Code 40 341 ___ / ___ User Code 17 318 ___ / ___ User Code 41 342 ___ / ___ User Code 18 319 ___ / ___ User Code 42 343
___ / ___ User Code 19 320 ___ / ___ User Code 43 344 ___ / ___ User Code 20 321 ___ / ___ User Code 44 345 ___ / ___ User Code 21 322 ___ / ___ User Code 45 346 ___ / ___ User Code 22 323
___ / ___ User Code 46 347
___ / ___ User Code 47 348 ___ / ___ User Code 48 / 349
(Duress)
Continues in next section.
Disarming (Opening) Report Codes (reset code “empty”):
Streamline
Section
Data Description Address
Streamline
Section
Data Description Address
See previous section ___ / ___ User Code 5 356
___ / ___ Auto / Espload 350 ___ / ___ User Code 6 357 ___ / ___ Master
351
___ / ___ User Code 7
358
___ / ___ User Code 8
359
___ / ___ User Code 1 352 ___ / ___ User Code 9 360 ___ / ___ User Code 2 353 ___ / ___ User Code 10 361 ___ / ___ User Code 3 354 ___ / ___ User Code 11 362 ___ / ___ User Code 4 355 ___ / ___ User Code 12 363
11 17
12 18
13 19
14 20
15 21
16 22
23
23
25
24
26
Page 6
Esprit 728 Ultra & 738 Ultra - 6 - Programming Guide
* = Fire zone for 4-wire smoke detectors or 2-wire smoke detectors (with no ATZ enabled—728 Ultra only). ** = Fire zone for 2-wire smoke detectors (address 086, key [BYP]) only when A TZ is enabled (address 090, key [8]). Applies only to 728 Ultra. † = Zones 1 to 10 for the 728 Ultra and Zones 1 to 18 for the 738 Ultra
Disarming (Opening) Report Codes (reset code “empty”): (continued)
Streamline
Section
Data Description Address
Streamline
Section
Data Description Address
___ / ___ User Code 13 364 ___ / ___ User Code 29 380 ___ / ___ User Code 14 365 ___ / ___ User Code 30 381 ___ / ___ User Code 15 366 ___ / ___ User Code 31 382 ___ / ___ User Code 16 367 ___ / ___ User Code 32
383
___ / ___ User Code 17 368 ___ / ___ User Code 33 384 ___ / ___ User Code 18 369 ___ / ___ User Code 34 385 ___ / ___ User Code 19 370 ___ / ___ User Code 35 386 ___ / ___ User Code 20 371 ___ / ___ User Code 36 387
___ / ___ User Code 21 372 ___ / ___ User Code 37 388 ___ / ___ User Code 22 373 ___ / ___ User Code 38 389 ___ / ___ User Code 23 374 ___ / ___ User Code 39 390 ___ / ___ User Code 24 375 ___ / ___ User Code 40 391
___ / ___ User Code 25 376 ___ / ___ User Code 41 392 ___ / ___ User Code 26 377 ___ / ___ User Code 42 393 ___ / ___ User Code 27 378 ___ / ___ User Code 43 394 ___ / ___ User Code 28 379 ___ / ___ User Code 44 395
___ / ___ User Code 45 396 ___ / ___ User Code 46 397 ___ / ___ User Code 47 398 ___ / ___ User Code 48 /
(Duress)
399
Alarm Report Codes For Zones 1 to 10 (18) †: Alarm Restore Repo rt Codes For Zones 1 to 10 (18) †:
Streamline
Section
Data Description Address
Streamline
Section
Data Description Address
___ / ___ Zone 1 400 ___ / ___ Zone 1 424 ___ / ___ Zone 2 401 ___ / ___ Zone 2 425 ___ / ___ Zone 3/Fire zone*
(fire address 100)
402 ___ / ___ Zone 3/Fire zone*
(fire address 100)
426
___ / ___ Zone 4 403 ___ / ___ Zone 4 427 ___ / ___ Zone 5/Fire zone** 404 ___ / ___ Zone 5/Fire zone** 428
___ / ___ Zone 6 405 ___ / ___ Zone 6 429 ___ / ___ Zone 7 406 ___ / ___ Zone 7 430 ___ / ___ Zone 8 407 ___ / ___ Zone 8 431
___ / ___ Zone 9 408 ___ / ___ Zone 9 432 ___ / ___ Zone 10 409 ___ / ___ Zone 10 433 ___ / ___ Zone 11
(738 Ultra only) 410 ___ / ___ Zone 11 (738 Ultra only) 434
___ / ___ Zone 12
(738 Ultra only) 411 ___ / ___ Zone 12 (738 Ultra only) 435
___ / ___ Zone 13 412 ___ / ___ Zone 13 436 ___ / ___ Zone 14 413 ___ / ___ Zone 14 437 ___ / ___ Zone 15 414 ___ / ___ Zone 15 438 ___ / ___ Zone 16 415 ___ / ___ Zone 16 439
___ / ___ Zone 17 416 ___ / ___ Zone 17 440 ___ / ___ Zone 18
417
___ / ___ Zone 18 441
41 Future Use 418 - 423 47 Future Use 44 2 - 447
27 31
28 32
29 33
30 34
35
36
42
37 43
38 44
39
738 Ultra
only
45
738 Ultra
only
40
738 Ultra only
46
738 Ultra only
Page 7
Esprit 728 Ultra & 738 Ultra - 7 - Programming Guide
Zones 1 to 10 (18)† Shutdown Report Codes: Tampers 1 to 4, 5 and 7 (8)‡ Report Codes:
Streamline
Section
Data Description Address
Streamline
Section
Data Description Address
___ / ___ Zone 1 448 ___ / ___ Tamper 1 472 ___ / ___ Zone 2 449 ___ / ___ Tamper 2 473 ___ / ___ Zone 3 450 ___ / ___ Tamper 3 474 ___ / ___ Zone 4 451 ___ / ___ Tamper 4 475
___ / ___ Zone 5 452 ___ / ___ Tamper 5 476 ___ / ___ Zone 6 453 ___ / ___ Tamper 6
(738 Ultra only) 477
___ / ___ Zone 7 454 ___ / ___ Tamper 7 478 ___ / ___ Zone 8 455 ___ / ___ Tamper 8
(738 Ultra only) 479
___ / ___ Zone 9 456 56 to 59 Future Use 4 80 - 495 ___ / ___ Zone 10 457 ___ / ___ Zone 11
(738 Ultra only) 458
___ / ___ Zone 12
(738 Ultra only) 459
___ / ___ Zone13 460
= Zones 1 to 10 for the 728 Ultra and
Zones 1 to 18 for the 738 Ultra
___ / ___ Zone 14 461 ___ / ___ Zone 15 462
= Zones 1 to 4, 5 and 7 for 728 Ultra and
Zones 1 to 8 for 738 Ultra
___ / ___ Zone 16 463 ___ / ___ Zone17 464
___ / ___ Zone 18 465
53 Future Use 466 - 471
Trouble Rep ort Codes:
Streamline
Section
Data Description Address
Streamline
Section
Data Description Address
___ / ___ Max. aux. current 496 ___ / ___ Fire loop trouble 500 ___ / ___ Bell disconnect /
max. bell current
497 ___ / ___ Timer loss 501
___ / ___ Battery disconnect /
low voltage
498 [2ND]/[2ND] Future Use 502
___ / ___ Power failure 499
[2ND]/[2ND] Future Use 503
Trouble Res to re Re p ort Code s:
Streamline
Section
Data Description Address
Streamline
Section
Data Description Address
___ / ___ Max. aux. current 504 ___ / ___ Fire loop trouble 508 ___ / ___ Bell disconnect /
max. bell current
505 ___ / ___ Timer
programmed
509
___ / ___ Battery disconnect /
low voltage
506 ___ / ___ Tamper / wiring fault 510
___ / ___ Power failure 507 ___ / ___ TLM resto re 511
Special Report Codes:
Streamline
Section
Data Description Address
Streamline
Section
Data Description Address
___ / ___ Test report 512 ___ / ___ Duress 520 ___ / ___ Panic 1 513 ___ / ___
Closing Delinquency
521
___ / ___ Panic 2 514
[2ND]/[2ND] Future Use 522
___ / ___ Panic 3
515
[2ND]/[2ND] Future Use
523
___ / ___ Late to close 516 ___ / ___ Login (Espload) 524 ___ / ___ No movement 517 ___ / ___ Program Change 525 ___ / ___ Partial Arming 518
[2ND]/[2ND] Future Use 526
___ / ___ Recent Close 519
[2ND]/[2ND] Future Use 527
48 54
49 55
50
51
738 Ultra
only
52
738 Ultra only
60 61
62 63
64 66
65 67
Page 8
Esprit 728 Ultra & 738 Ultra - 8 - Programming Guide
Decimal Programming
The decimal programming method is used to program all of the system’s timers. This method uses a 3-digit address from 044 to 061 and each address is programmed with a value from 000 to 255.
Figure 2: Decimal Display For LED Keypads
Table 5: Decimal Programming Method
1. Press [
ENTER] + [INSTALLER CODE] (Default - 728 Ultra: 282828; 738 Ultra: 383838)
2. The [ENTER] key will flash to indicate that you are in programming mode (LED keypad only).
3. Enter 3-digit [ADDRESS] (044 to 061).
4. The keypad displays the current 3-digit data saved at this address as described in Figure 2 below.
5. Enter 3-digit [
DATA] (000 to 255) and do not press [ENTER]. The software will automatically save the data.
6. Return to step 2 or press [
CLEAR] to exit programming mode.
Address Data
Description Default
044 ___ / ___ / ___ (hours) Auto arm time (between "000" and "023") 000 045 ___ / ___ / ___ (minutes) Auto arm time (between "000" and "059") 000 046 ___ / ___ / ___ (days or hours) Auto test report every ? (between "001" and "254") (000 = disabled)
If address 090 key [3] OFF = address 046 in days (see page 10) If address 090 key [3] ON = address 046 in hours (see page 10) 738 Ultra only: Enter “255” to enable a Timed T est T ransmission when the system is armed or disarmed (see the 728 Ultra/738 Ultra Reference & Installation Manual for more information)
000
047 ___ / ___ / ___ (hours) Auto test report (between "000" and "023")
738 Ultra only: (minutes) If address 046 = 255 and the system is armed, Armed Test Report
(between “001” and “255”)
000
048 ___ / ___ / ___ (minutes) Auto test report (between "000" and "059")
738 Ultra only: (minutes) If address 046 = 255 and the system is disarmed, Disarmed Test
Report (between “001” and “255”)
000
049 ___ / ___ / ___ (seconds) Exit delay 60 seconds 050 ___ / ___ / ___ (seconds) Entry delay 1 45 seconds 051 ___ / ___ / ___ (seconds) Entry delay 2 45 seconds 052 ___ / ___ / ___ (minutes) Bell cut-off time 5 minutes 053 ___ / ___ / ___ (x 15 ms) Zone speed 600 ms 054 ___ / ___ / ___ (minutes) Power failure report delay (000 = disabled) 30 minutes 055 ___ / ___ / ___ (x 15 minutes) No movement Auto-Arm time (000 = disabled) Disabled 056 ___ / ___ / ___ PGM timer setting (001 to 127 for seconds and 129 to 255 for minutes)
Add 128 to desired value in minutes (i.e. for 5 minutes: enter 5 + 128 = 133)
5 seconds
057 ___ / ___ / ___ Intellizone delay (in seconds, minimum = 10 seconds) 48 seconds 058 ___ / ___ / ___ Installer code lock (147 = locked, 000 = unlocked). When Installer Lock is enabled on a control
panel: For 4 seconds during power up, the STATUS LED flashes while the dialer relay opens and closes making a clicking noise.
Unlocked
059 ___ / ___ / ___ (seconds) Programmable delay before alarm transmission (005 to 063 seconds)
(000 = disabled)
Disabled
060 ___ / ___ / ___ (seconds) Recent closing delay (000 = disabled) Disabled 061 ___ / ___ / ___ (days or hours) Closing delinquency timer (System A)
If address 090 key [3] OFF = address 061 in days (see page 10) If address 090 key [3] ON = address 061 in hours (see page 10)
Disabled
Each key in the first 2 rows of the keypad represents a specific value when the key is lit, as shown below left. When the key isn’t lit, the key represents 0. Add the values of the lit keys to obtain the entered data value as shown in the example below right.
Note: LCD keypads will display current data on the screen.
Example:
Therefore 8 + 1 + 32 + 16 = 057
Page 9
Esprit 728 Ultra & 738 Ultra - 9 - Programming Guide
Feature Select Programming
Addresses 062 to 126 are programmed using the Feature Select Programming method. In this method, every key on the keypad in each address represents an option or feature. Pressing a key will display it on the keypad and pressing it again will extinguish the key. The ON or OFF status of each key determines the selected feature. Addresses 080 to 085 are reserved for future use. To program using the Feature Select Programming method:
Table 7: Code Priority For System “A” / STAY
Table 8: Code Priority For System “B” / AWAY / FORCE
Table 9: Code Priority for Codes with Bypass Access
Table 6: Feature Select Programming Method
1. Press [
ENTER] + [INSTALLER CODE] (Default - 728 Ultra: 282828; 738 Ultra: 383838)
2. The [
ENTER] key will flash to indicate you are in programming mode (LED keypad only).
3. Enter 3-digit [ADDRESS] (062 to 126).
4. After entering the address, the keypad will display the feature selection status. Turn the keys ON or OFF by pressing the appropriate key until the desired options are set. Press the [
ENTER] key to accept,
there will be a confirmation beep indicating the options have been accepted. The [ENTER] key will flash to indicate that the software is awaiting the next address entry.
5. Return to step 3 to continue programming or press [
CLEAR] to exit programming mode.
KEY SELECT:
[1][2][3][4][5][6][7][8][9][0][STAY]
[
AWAY]/
[
FORCE]
[
BYP][MEM][TRBL
]
[2ND]
User #: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
062
NNNNNNNNNN N N N N N N
User #: 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
064
NNNNNNNNNN N N N N N N
User #: 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
066:
NNNNNNNNNN N N N N N N
KEY SELECT:
[1][2][3][4][5][6][7][8][9][0][STAY]
[
AWAY]/
[FORCE]
[BYP][MEM]
[
TRBL
]
[2ND]
User #: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
068:
NNNNNNNNNN N N N N N N
User #: 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
070:
NNNNNNNNNN N N N N N N
User #: 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
072:
NNNNNNNNNN N N N N N N
KEY SELECT:
[1][2][3][4][5][6][7][8][9][0][STAY]
[
AWAY]/
[FORCE]
[BYP][MEM]
[
TRBL
]
[2ND]
User #: 1 2 3 4 5 6 7 8 9 10 11 1 2 13 14 15 16
074:
NNNNNNNNNN N N N N N N
User #: 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
076:
NNNNNNNNNN N N N N N N
User #: 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
078:
NNNNNNNNNN N N N N N N
Page 10
Esprit 728 Ultra & 738 Ultra - 10 - Programming Guide
U
= default
KEY
086:
OFF / ON
See “TLM” table at right
U
[2ND]
N
U
[1]
N
Keyswitch = Regular arm
U
[2]
N
Stay arm / System A
Keyswitch arming
U
[3]
N
Enabled
Call back
U
[4]
N
Enabled
Auto arm on time
U
[5]
N
Enabled
Auto arm on no movement
U
[6]
N
Enabled
Pulse dialing
U
[7]
N
Tone dialing (DTMF)
Partitioning
U
[8]
N
Enabled
Silent zone/panic generates a silent alarm
U
[9]
N
Generates only a report
(1:2) Pulse Europe
U
[0]
N
(1:1.5) Pulse USA
See “Reporting Options” table at right
U
[STAY]
N
U
[AWAY]/ [
FORCE]
N
2-wire smoke detector (input 3)
U
[BYP]
N
Enabled
Bell squawk on arm/disarm
U
[MEM]
N
Enabled
Auto zone shutdown
U
[TRBL]
N
Enabled
088:
OFF / ON
Automatic event buffer transmission
U
[2ND]
N
Enabled
Panic 1 (keys [1] and [3])
U
[1]
N
Enabled
Panic 2 (keys [4] and [6])
U
[2]
N
Enabled
Panic 3 (keys [7] and [9])
U
[3]
N
Enabled
Panic 1 silent
U
[4]
N
Audible
Panic 2 silent
U
[5]
N
Audible
Panic 3 silent
U
[6]
N
Fire
Key [0]/[
ARM] - Regular arming
U
[7]
N
Enabled
Key [
STAY] - Stay or system A arm
U
[8]
N
Enabled
6-digit access codes
U
[9]
N
4-digit access codes
Tamper Recognition
U
[0]
N
U
[STAY]
N
Beep on exit delay
U
[AWAY]/ [
FORCE]
N
Enabled
Report zone restore on bell cut-off
U
[BYP]
N
On zone closure
Zones with EOL (1k9)
N
[MEM]
U
No EOL
Always report disarm
U
[TRBL]
N
Only after alarm
090:
OFF / ON
Exclude power failure from trouble display
U
[2ND]
N
Enabled
Zone 4
(728 Ultra)/Zone 11 (738 Ultra)* enabled
U
[1]
N
Disabled*
* NOTE 1: When ATZ is enabled (address 090 key [8] ON) and zone 3 is defined as a 4-wire fire zone, if you are not using zone 4 (728 Ultra) or 11 (738 Ultra), it must be disabled.
Auto arm = Regular arm
U
[2]
N
Stay / System A
Auto test report / Closing delinquency timer in days
U
[3]
N
In hours
Restrict arming on battery failure
U
[4]
N
Enabled
Restrict arming on tamper trouble**
U
[5]
N
Enabled**
No tamper bypass
U
[6]
N
Tamper follows zone bypass definition
Zone doubling (ATZ) wiring in series
U
[7]
N
Parallel
Zone doubling (ATZ)
U
[8]
N
Enabled
** NOTE 2: Only the installer can clear a tamper trouble
Audible trouble warning
U
[9]
N
Enabled
Duress
U
[0]
N
Enabled
Keypad zone 1 supervision
U
[STAY]
N
Enabled
Keypad zone 2 supervision
U
[AWAY]/ [
FORCE]
N
Enabled
Master code lock
U
[BYP]
N
Enabled
Pager format (wait delay)
U
[MEM]
N
Personal dialing (during delay)
Pager report alarms only
U
[TRBL]
N
All events
Telephone Line Monitoring (TLM)
(address 086, key [9] has to be OFF)
KEY
[2
ND][1]
OFF OFF - TLM disabled OFF ON - TLM generates trouble only
ON OFF - generates an alarm if armed ON ON - silent alarm becomes audible
R
eporting Options
* On alarm, all reports are made to Tel. #1 until system is disarmed. Once disarmed, system reports are made to Tel. #2.
KEY
[
STAY][AWAY]/[FORCE]
OFF OFF - Reporting disabled OFF ON - Regular reporting
ON OFF - Split* reporting (Alarms & System) ON ON - Double reporting
Report Dialing Sequence (tel. no.) Regular: 1,2,1,2,1,2,1,2, fail to comm. Split*: Alarms - 1,1,1,1,1,1,1,1, fail to comm
System - 2,2,2,2,2,2,2,2, fail to comm
Double: 1,1,1,1,1,1,1,1, fail to comm
2,2,2,2,2,2,2,2, fail to comm
Tamper / Wire Fault Definitions
KEY
System Armed [0] [
STAY] System Disarmed*
Alarm as per individual zone definitions
OFF OFF - Tamper supervision
disabled
Always generate trouble and alarm, audible or silent as per individual zone definitions
OFF ON - No alarm. Trouble
code reported
ON OFF - Silent alarm.
Trouble & alarm codes reported
ON ON - Audible alarm.
Trouble & alarm codes reported**
* Exception: for 24 hour zones, the tamper definition will follow the audible/silent alarm definition of the 24 hour zone.
** Silent zones will generate a silent alarm.
Page 11
Esprit 728 Ultra & 738 Ultra - 11 - Programming Guide
Table 10: Zone Definition
Do not use the Intellizone feature and an entry delay for the same zone, otherwise an alarm may occur as a user tries to disarm the system. Zones that are not selected at addresses 100 to 112 (728 Ultra) or 114 (738 Ultra) become “Delay 1” zones.
Key Access Programming
Programs features quickly, without entering addresses or sections numbers. To activate Key Access Programming, press [ENTER] followed by the Installer code, Master code or User code 1 (code required depends on the desired feature; see below). Press the key corresponding to the desired feature. Press [
ENTER] or [CLEAR] to exit. When communicating with Espload, it is impossible to enter
programming mode.
Address
KEY SELECT:
[1] [2] [3] [4] [5] [6] [7] [8] [9] [0] [STAY][FORCE]
/[
AWAY]
[1] [2] [3] [4] [5] [6]
Zone: 1234567891011 12 13 14 15 16 1718
092:
Intellizone =
ON
092: NNNNNNNNNN N N 094: NN N NNN
Zone: 1234567891011 12 13 14 15 16 17 18
096:
Silent = ON 096: NNNNNNNNNN N N 098: NN NNNN
Zone: 1 2 3* 4567891011 12 13 14 15 1617 18
100:
24Hr./Fire = ON 100: NNNNNNNNNN N N 102: NN NNNN
Keypad zones cannot be set as 24Hr zones.
* When zone 3 is defined as “24Hr”, it becomes a 4-wire smoke detector fire zo ne (2-wire smoke detector support must be disabled, address 086 key [
BYP] = OFF).
If using 2-wire smoke detectors and ATZ is enabled, zone 3 can be defined as “24Hr” (728 Ultra only).
Zone: 1234567891011 12 13 14 15 16 17 18
104:
Instant = ON 104: NNNNNNNNNN N N 106: NN N NNN
Zone: 1234567891011 12 13 14 15 16 17 18
108:
Follow = ON 108: NNNNNNNNNN N N 110: NN N NNN
Zone: 1234567891011 12 13 14 15 16 17 18
112:
Delay 2 = ON 112: NNNNNNNNNN N N 114: NN N NNN
SYSTEM A / STAY
(if ON, zone is armed on Stay or “System A” arming)
Zone: 1234567891011 12 13 14 15 16 17 18
116:
116: NNNNNNNNNN N N 118: NN NNNN
SYSTEM B
(if ON, zone is armed in “System B” arming)
Zone: 1234567891011 12 13 14 15 16 17 18
120:
120: NNNNNNNNNN N N 122: NN N NNN
Zone: 1234567891011 12 13 14 15 16 17 18
124:
Bypass = ON 124: NNNNNNNNNN N N 126: NN NNNN
Fire zones cannot be bypassed.
Ta ble 11: Key Access Programming
Key Feature
Codes that can access feature
[8]
Installer Test Mode
Installer Code Only
In Installer Test mode, a confirmation beep (intermittent) indicates that the test mode is enabled. A rejection beep indicates that the test mode is disabled. The bell will squawk during walk testing to indicate opened, functional zones.
[9]
“Auto Arming” Time Program
Installer Code, Master Code or User Code 1
Key [9] flashes. Enter 2-digit hour (00 to 23) and 2-digit minutes (00 to 59).
[MEM]
Panel Time Programming
Installer Code, Master Code or User Code 1
[MEM] key flashes. Enter 2-digit hour (00 to 23) and 2-digit minutes (00 to 59).
[BYP]
Test Report
Installer Code, Master Code or User Code 1
Reporting is enabled at address 086, keys [STAY] and [AWAY]/[FORCE] (see page 10). A value must be entered at address 512 (page 7) and both telephone and account numbers must be programmed.
[TRBL]
Call Espload Via Telephone
Installer Code, Master Code or User Code 1
Panel identifier and PC password (addresses 004 to 007 on page 3) and computer telephone number (addresses 008 to 015 on page 3) must be programmed.
[AWAY]
Answer Espload
Installer Code, Master Code or User Code 1
This feature is available when using the ADP-1 ad apter. In Espload, “blind dial” must be activated in the “modem setup” section and panel phone number programmed.
[STAY]
Cancel Communication Attempts
Until next reportable event.
Master Code/User Code 1 only cancel calls to Espload The Installer Code can cancel all communications
Page 12
Esprit 728 Ultra & 738 Ultra - 12 - Programming Guide
Connection Diagrams
The system hardware will recognize the following zone conditions:
Single Zone Connections
Figure 3: N.C. Contacts, without EOL Resistor Figure 4: N.C. Contacts, with EOL Resistor (UL/cUL)
Figure 5: N.O. Contacts, with EOL Resistor (UL/cUL) Figure 6: N.C. Contacts, without EOL Resistor, with Tamper
Recognition
Figure 7: N.C. Contacts, with EOL resistor, with Tamper and Wire
Fault Recognition (UL/cUL)
Address 088,[MEM] = “ON” (EOL resistor disabled)
[0] = “OFF” [
STAY] = “OFF”
Address 090,[8] = “OFF” (ATZ disabled)
Tamper/Wire Fault disabled.
Address 088,[MEM] = “OFF” (EOL resistor enabled)
[0] = “OFF” [
STAY] = “OFF”
Address 090,[8] = “OFF” (ATZ disabled)
Tamper/Wire Fault disabled.
Address 088,[MEM] = “OFF” (EOL resistor enabled)
[0] = “OFF” [
STAY] = “OFF”
Address 090,[8] = “OFF” (ATZ disabled)
Tamper/Wire Fault disabled.
Address 088,[MEM] = “ON” (EOL resistor disabled)
[0] = (See Tamper/Wire Fault definitions on [
STAY] = page 10.)
Address 090,[8] = “OFF” (ATZ disabled)
Address 088,[MEM] = “OFF” (EOL resistor enabled)
[0] = (See Tamper/Wire Fault definitions on [
STAY] = page 10.)
Address 090,[8] = “OFF” (ATZ disabled)
Page 13
Esprit 728 Ultra & 738 Ultra - 13 - Programming Guide
Advanced Technology Zone (ATZ) Connections
Other Connection Diagrams
Figure 8: N.C. Contacts, without EOL Resistor Figure 9: N.C. Contacts, without EOL Resistor, with Tamper
Recognition
Figure 10: N.C. Contacts, with EOL Resistor, with Tamper and Wire
Fault Recognition (UL/cUL)
Figure 11: Parallel Wiring
Figure 12: Connecting Keypad Zone(s)
Address 088,[MEM] = “ON” (EOL resistor disabled)
[0] = “OFF” [
STAY] = “OFF”
Address 090,[8] = “ON” (ATZ enabled)
[7] = “OFF” (ATZ wiring in serial)
Tamper/Wire Fault disabled.
Address 088,[MEM] = “ON” (EOL resistor disabled)
[0] = (See Tamper/Wire Fault definitions on [
STAY] = page 10.)
Address 090,[8] = “ON” (ATZ enabled)
[7] = “OFF” (ATZ wiring in serial)
Address 088,[MEM] = “OFF” (EOL resistor enabled)
[0] = (See Tamper/Wire Fault definitions on [
STAY] = page 10.)
Address 090,[8] = “ON” (ATZ enabled)
[7] = “OFF” (ATZ wiring in serial)
Address 088,[MEM] = “OFF” (EOL resistor enabled)
[0] = “OFF” [
STAY] = “OFF”
Address 090,[8] = “ON” (ATZ enabled)
[7] = “ON” (ATZ wiring in parallel)
Tamper/Wire Fault disabled.
Page 14
Esprit 728 Ultra & 738 Ultra - 14 - Programming Guide
It is recommended that the smoke detectors be connected using a daisy chain configuration.
Figure 13: LED Keypad Anti-Tamp er Switch Co nnection Figure 14: PGM Output Relay Figure 15: Ground Start Circuit
Figure 16: 4-Wire Smoke Detector Connections (Fire Zone) Figure 17: 4-Wire Smoke Detector Fire Reset
Figure 18: 2-Wire Smoke Detector Connections (Fire Zone)
Address 086; key [BYP] ON (728 Ultra)
Connect the two-wire smoke detector to input 3. Without ATZ, zone 3 is used by the two-wire smoke det ector. With ATZ enabled, zo ne 5 is used by the 2-wire smoke detect or and zone 6 will be disabled automatically.
2-Wire Smoke Detector Fire Reset: Simultaneously press and hold for 3 seconds the [
ENTER] and
[
CLEAR] keys on any keypad to conduct a 30 second reset.
Address 086; key [BYP] ON (738 Ultra)
Connect the two-wire smoke detector to input 3. Zone 3 is used by the two-wire smoke detector. With ATZ enabled, zone 11 will be disabled automatically.
UL Warnings. For UL/cUL installations:
- The operating voltage of the fire circuit must be between 11 to 12Vdc.
- Use only the Hochicki model SLR 835BH-2 2-wire smoke detector.
- 2-wire smoke detectors of different models other than the Hochicki model are not to be used.
- Both the 728 Ultra and the 738 Ultra control panels support a maximum of five 2-wire smoke detectors per control panel.
Page 15
Esprit 728 Ultra & 738 Ultra - 15 - Programming Guide
728 Ultra Wiring Diagram
Keypads
- LED Keypads 636 and 646
- LCD Keypad 642
The maximum number of keypads per installation is dependent on the auxiliary output, which is not to exceed 450mA. Refer to the 728 Ultra & 738 Ultra Reference & Installation Manual for the current consumption table. Refer to Figure 12 on page 13 for information on keypad zone connections.
Please refer to Inset 1 for the input terminals. For the hardwired connections, refer to Single Zone
Connections on page 12 and Advanced Technology Zone (ATZ) Connections on page 13.
Note: T o use you must disable the PGM. To do so, program [2
ND] [2ND] in sections 039, 040 and 042.
For use with the 708, Esprint and SRI-18 PGM expander
Disconnect the battery before replacing the fuse
Rechargeable Acid/ Lead or Gel Cell Backup Battery
Improper connection may result in damage to the system.
AUX POWER: 450mA maximum. UL/cUL: 250mA maximum for 24Hr Stand-by. To connect additional wiring to the auxiliary power, use the red (+) and the black (-) keyp ad connectors. AUX power will shutdown if current exceeds 650mA.
For UL and cUL warnings, refer to the Warnings section in the Esprit 728
Ultra & 738 Ultra Reference and Installation Manual.
Bell/Siren
The
BELL output
will shutdown if the current exceeds 3A.
To provide maximum lightning protection we strongly recommend having separate earth connections for the dialer and zone ground terminals.
To metallic
enclosure
Cold water
pipe or
grounding rod
Ground clamp
Disconnect the telephone line before servicing.
AWG# 14 single conductor solid copper wire
STATUS LED:
Flash once every second = normal Toggle ON 1s / OFF 1s = trouble Always ON = panel is using phone line Fast flash 4s after power up = installer lock enabled
Note: For UL installations, the metallic enclosure must be grounded to the cold water pipe or to the grounding rod.
**
** UL Note:
Do not connect this ground with UL installations.
Page 16
Esprit 728 Ultra & 738 Ultra - 16 - Programming Guide
738 Ultra Wiring Diagram
Keypads
- LED Keypads 636 and 646
- LCD Keypad 642
The maximum number of keypads per installation is dependent on the auxiliary output, which is not to exceed 500mA. Refer to the 728 Ultra & 738 Ultra Reference & Installation Manual for the current consumption table. Refer to Figure 12 on page 13 for information on keypad zone connections.
Please refer to Inset 1 for the input terminals. For the hardwired connections, refer to Single
Zone Connections on page 12 and Advanced Technology Zone (ATZ) Connections on
Note: To use you must disable the PGM. To do so, program [2
ND] [2ND] in sections 040 and 042.
For use with the 708, Esprint and SRI-18 PGM expander
Caution:
Disconnect the battery before replacing the fuse
Rechargeable
Acid/Lead or
Gel Cell
Backup Battery
Improper connection may result in damage to the system.
AUX POWER: 500mA maximum. 250mA maximum for 24Hr Stand-by. To connect additional wiring to the auxiliary power, use the red (+) and the black (-) keypad connectors. AUX power will shutdown if current exceeds 700mA.
For UL and cUL warnings, refer to the Warnings section in the Esprit 728 Ultra &
738 Ultra Reference and Installation Manual.
Bell/Siren
The
BELL output
will shutdown if the current exceeds 3A.
To provide maximum lightning
protection we strongly recommend
having separate earth connections
for the dialer and zone ground
terminals.
To metallic
enclosure
Cold water
pipe or
grounding rod
Ground clamp
WARNING:
Disconnect the telephone line before servicing.
AWG# 14 single conductor solid copper wire
STAT US LED:
Flash once every second = normal Toggle ON 1s / OFF 1s = trouble Always ON = panel is using phone line Fast flash 4s after power up = installer lock enabled
UL approval pending
Page 17
Esprit 728 Ultra & 738 Ultra - 17 - Programming Guide
Power Down Reset
Performing a power down reset will set the Installer and Master codes to factory default. Values entered at addresses 008 to 043, 062 to 124, 300 to 527 and all user codes will be set to factory defaults. Programmed values at addresses 003 to 007 do not change. T o perform
a reset, the installer lock must be disabled. To perform a power down reset perform the following:
1. Verify installer lock is disabled.
2. Remove the battery and AC power from the control panel.
3. Remove all connected wires and devices from the PGM (PGM1 for 738 Ultra) and zone 1 terminals.
4. Short the PGM (PGM1 for 738 Ultra) and zone 1 terminals with a wire.
5. Reconnect the AC and battery power to the control panel.
6. Wait for 10 seconds and remove the wire. Figure 19: Power Down Reset for 728 Ultra or 738 Ultra
Warranty
Paradox Security Systems Ltd. (“Seller”) warrants its products to be free from defects in materials and workmanship under normal use for a period of one year. Except as specifically stated herein, all express or implied warranties whatsoever, statutory or otherwise , including without limitat ion, any implied wa rranty of merchant ability a nd fitness for a particular purpose, are expressly excluded. Because Seller does not install or connect the products and because the products may be used in conjunction with pr oducts not manufactured by Seller, Seller cannot guarantee the performance of the security system and shall not be responsible for circumstances resulting from the product’s inability to operate. Seller obligation and liability under this warranty is expressly limited to repairing or replacing, at Seller's option, any product not meeting th e specifications. Returns must include proof of purchase and be within the warranty period. In no event shall the Seller be liable to the buyer or any other person for any loss or damages whether direct or indirect or consequential or incidental, including without limitation, any damages for lost profits stolen goods, or claims by any other party, caused by defective goods or otherwise arising from the improper, incorrect or otherwise faulty installation or use of the merchandise sold.
Notwithstanding the preceding paragraph, the Seller’s maximum liability will be strictly limit ed to the purchase price of the defective product. Your use of this product signifies your acceptance of this warranty.
BEWARE: Dealers, installers and/or others sellin g the product are not authorized to modify this warranty or make additional warranties that are binding on the Seller. © 2003-2005 Paradox Security Systems Ltd. All rights reserved. Specifications may change without prior notice. One or more of the following US patents may apply: 6215399,
6111256, 5751803, 5721542, 5287111, 5119069, 5077549, 5920259 and 5886632. Canadian and international patents may also apply. Esprit is a trademark or registered trademark of Paradox Security Systems Ltd. or its affiliates in Canada, the United States and/or other countries.
1. Remove power.
2. Remove all connected wires and devices from the PGM (PGM1 for 738 Ultra) and zone 1 terminals.
3. Short the PGM (PGM1 for 738 Ultra) and zone 1 terminals.
4. Reconnect power.
5. Wait 10 seconds and remove wire.
Page 18
Notes
Page 19
Page 20
780 Industriel Blvd., Saint-Eustache (Quebec) J7R 5V3 CANADA Tel.: (450) 491-7555 Fax: (450)491-2313
www.paradox.ca
PRINTED IN CANADA - 03/2005 7X8ULT-EP01
Loading...