MAGPRO-4i0O
EN54-18
!
Dimensions
176mm
!
Installation
IP40
-10°C ÷ +60°C
~320g
126mm 57mm
Indoor use
Outdoor use
Installation Instructions
!
ATTENTION
The MAGPRO-4i0O addressable module must be connected only to fire panels
from MAGPRO Series!
General Description
MAGPRO-4i0O is an addressable inputs module. The module monitors 4 analogue input signals.
MAGPRO-4i0O is powered on from the fire panel and can be controlled via the communication protocol.
The module is mounted is a separate small plastic box suitable for wall mounting.
Installation
Attention: Power off the loop circuit before installing the MAGPRO-4i0O addressable module!
1.Choose the proper place for installation of the module. Undo the screws of the cover and open the box.
2. Set the module address using MAGPRO-PROG programming tool. The address must be in the range from
1 to 250. The set address is one for the entire module.
3. Dismount the module’s PCB from the box bottom. Mark mounting holes on the installation surface. Drill
holes at the appropriate box side and run the cables to the module’s loop and input terminals.
4. Mount the box bottom at the place of installation. Mount the PCB back on place.
5. Connect the cables to the loop and input terminals of the module according the shown Connection
diagrams.
6. Close the cover of the plastic box and fix it to the bottom with the supplied screws.
7. Test the module for proper operation and LED indication.
TECHNICAL SPECIFICATIONS
Operating voltage . . . . . . . . . . . . . . . . . . . . . 15÷ 32 VDC
Consumption stand-by mode . . . . . . . . . . . . 300µА@27VDC
Nom. current consumption . . . . . . . . . . . . . . 330µА@27VDC
Current consumption with 1 LED on . . . . . . . 4mA
Current consumption with 2 LEDs on . . . . . . 7mA
Installation wires . . . . . . . . . . . . . . . . . . . . . . 0,4mm ÷ 2.0mm
Relative humidity . . . . . . . . . . . . . . . . . . . . . . ≤93% @ +40°C
Material (plastic) . . . . . . . . . . . . . . . . . . . . . . PS
Color . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Gray
Standard . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN54-18
2 2
1293-CPD-0258
Distributor: Elite Security Products Ltd, Unit 7 Target Park, Shawbank Road Lakeside, Redditch B98 8YN, UK http://www.espuk.com
Manufacturer: Teletek Electronics JSC, 14 Srebarna Str., 1407 Sofia, Bulgaria, http://www.teletek-electronics.com
18020168; RevC; 03/2017
1 2
Open the box
Address programming
- Use the cable with
5-pin terminal.
Line + >
Line - >
Izolator >
Line + >
Line - >
Up
Esc
Right
Modify
MAGPRO-
PROG
3
Mounting and Cable holes
Down
Enter
Possible places for
drilling of cable holes
Mounting
holes
4
Installation
Fix the
box on the
installation
surface
Run the
cables
!
LED Indication
The RED LED Lights on, when at least one of
the inputs is turned on (state ON)
The YELLOW LED Lights on, when at least one
of the inputs is in SHORT or OPEN condition,
i.e. there is an input in fault condition
The RED LED is blinking when communication
between the module and fire panel is running on
NOTE: In situations when both the red and yellow LEDs
are lighting on the actual color is recognized as orange
!
INPUTS Status
Status Description
SHORT
NORMAL
OPEN
* R - resistance between the input and GND
** I - current at the input
ON
Short circuit
Activation
Stand-by mode
Open circuit
R* I**
<13k
13k - 36k
36k - 90k
>90k
>54µA
38µA - 54µA
23µA - 38µA
<23µA
5
Connection diagrams
LED
(red-yellow)
Input 1 Input 2 Input 3 Input 4
56k
56k
ATTENTION: When you use the integrated short circuit isolation module connect one
of the “+Loop” loop lead to the “Isolator” terminal of the module.
56k
56k
Loop IN
Line +
Loop
Line -
Isolator
Line +
Isolator
Loop
Loop OUT
Line -
56k
56k
56k
56k