ESP MAG816 Installation Instructions

Page 1
FIRE CONTROL PANEL
MAG816
INSTALLATION AND OPERATION
MANUAL
READ THIS MANUAL BEFORE CONNECTING THE
EQUIPMENT AND KEEP IT SAFE FOR FUTURE REFERENCE.
To call our technical support line dial:
+44 (0) 1527 51 51 50
Page 2
Contents
Installer Instruction
GUARANTEE ...............................................................................................................3
1. GENERAL INFORMATION ......................................................................................4
2. TECHNICAL SPECIFICATIONS ..............................................................................4
2.1 General Technical Specications of MAG816 ...........................................4
2.2 General Technical Specications of Relay Module MR8 ...........................5
3. INSTALLING MAG816 .............................................................................................6
3.1 Wall Mounting .............................................................................................7
3.2 Flush Mounting ...........................................................................................7
3.3 Conguration of the Basic Modules ............................................................8
3.4 Control Module ...........................................................................................9
3.5 Main Power Source ....................................................................................10
Connecting of the Main Power Source .........................................................10
Connecting to the Battery .............................................................................10
3.6 4-Zone Expander ........................................................................................11
Connecting of Additional 4-Zone Expander ..................................................11
3.7 4-Sounder Expander ..................................................................................12
Performance and Connecting of 4-Sounder Expander.................................12
4. CONNECTING
4.1 Relay Module MR8 .....................................................................................13
4.2 Repeater Panel...........................................................................................15
4.3 Class Change Mode ...................................................................................16
4.4 Connecting the Zone and Sounder Circuits................................................16
5. SYSTEM PROGRAMMING
5.1 Sounder Delay ............................................................................................18
5.2 Double Action Mode ...................................................................................19
5.3 Instant Action Mode ....................................................................................19
5.4 Master Panel Mode ....................................................................................20
5.5 Repeater Panel Mode.................................................................................20
5.6 Single Panel Mode .....................................................................................20
6. OPERATION INSTRUCTIONS
6.1 Initial Start-up of MAG816 ..........................................................................21
6.2 Front Panel .................................................................................................21
6.3 Buttons .......................................................................................................22
6.4 LED Indication ............................................................................................22
6.5 Sound Signal ..............................................................................................23
6.6 Service Modes ............................................................................................23
7. INDICATION
7.1 Faults Indication .........................................................................................26
7.2 Indication of the Operation Modes..............................................................27
GENERAL CONNECTION CIRCUIT OF MAG816 ......................................................28
FIRE ALARM RECORD ...............................................................................................29
SERVICE RECORD .....................................................................................................30
FIRE ALARM EVENT LOG ..........................................................................................30
SPARE PARTS KITS ...................................................................................................31
Page 3
MAG816 - Installation and Operation Manual 3
GUARANTEE
During the guarantee period the manufacturer shall, at its sole discretion, replace or repair any defective product when it is returned to the factory. All parts replaced and/or repaired shall be covered for the remainder of the original guarantee, or for ninety (90) days, whichever period is longer. The original purchaser shall immediately send manufacturer a written notice of the defective parts or workmanship, which written notice must in all cases be received prior to expiry of the guarantee.
INTERNATIONAL GUARANTEE
Foreign customers shall enjoy the same guarantee rights as those enjoyed by any customer in Bulgaria, except that manufacturer shall not be liable for any related customs duties, taxes or VAT, which may be payable.
GUARANTEE PROCEDURE
This guarantee will be granted when the appliance in question is returned. The manufacturer shall accept no product whatsoever, of which no prior notice has been received.
CONDITIONS FOR WAIVING THE GUARANTEE
This guarantee shall apply to defects in products resulting only from improper materials or workmanship, related to its normal use. It shall not cover:
• Damages resulting from improper transportation and handling;
• Damages caused by natural calamities, such as re, oods, storms, earthquakes or lightning;
• Damages caused by incorrect voltage, accidental breakage or water; beyond the control of the manufacturer;
• Damages caused by unauthorized system incorporation, changes, modications or surrounding objects;
• Damages caused by peripheral appliances unless such peripheral appliances have been supplied by the manufacturer;
• Defects caused by inappropriate surrounding of installed products;
• Damages caused by failure to use the product for its normal purpose;
• Damages caused by improper maintenance;
• Damages resulting from any other cause, bad maintenance or product misuse.
In the case of a reasonable number of unsuccessful attempts to repair the product, covered by this guarantee, the manufacturer’s liability shall be limited to the replacement of the product as the sole compensation for breach of the guarantee. Under no circumstances shall the manufacturer be liable for any special, accidental or consequential damages, on the grounds of breach of guarantee, breach of agreement, negligence, or any other legal notion.
WAIVER
This Guarantee shall contain the entire guarantee and shall be prevailing over any and all other guarantees, explicit or implicit (including any implicit guarantees on behalf of the dealer, or adaptability to specic purposes), and over any other responsibilities or liabilities on behalf of the manufacturer. The manufacturer does neither agree, nor empower, any person, acting on his own behalf, to modify or alter this Guarantee, nor to replace it with another guarantee, or another liability with regard to this product.
UNWARRANTED SERVICES
The manufacturer shall repair or replace unwarranted products, which have been returned to its factory, at its sole discretion under the conditions below. The manufacturer shall accept no products for which no prior notice has been received.
The products, which the manufacturer deems repairable, will be repaired and returned. The manufacturer has prepared a price list and those products, which can be repaired, shall be paid for every repaired appliance.
The closest equivalent product, available at the time, shall replace the products manufacturer deems un-repairable. The current market price shall be charged for every replaced product.
ATTENTION This manual contains an information about the limitations in using and operation of the product, as and information about the limits in the responsibility of the manufacturer. Please read the operation manual carefully before starting the installation.
Page 4
1. GENERAL INFORMATION
The MAG816 is a conventional microprocessor fire control panel, designed according to EN54 Standard requirements. The panel provides for monitoring and reporting fire events in up to 16 separate zones, depending on the installed configuration.
The MAG816 must be installed according to the Fire Alarm Installation Regulations, mandatory for the territory of the respective country. The electrical power supply to the panel must be isolated and must not be capable of being accidentally switched off. The power switch-off board should display a clear FIRE ALARM - DO NOT
SWITCH OFF label.
2. TECHNICAL SPECIFICATIONS
2.1 General Technical Specications of MAG816
Maximum number of detectors per zone: - Up to 32 conventional detectors with consumption < 200µА at a normal mode;
- Unlimited number of manual call points.
Thresholds for zone conditions:
• 0 ÷ 2 mA - Open circuit fault condition.
• 2 ÷ 10 mA - Normal condition.
• 10 ÷110 mA - Fire alarm condition.
• > 110 mA - Short circuit condition.
Power Supply:
Main Power Supply ~ 230V AC ±10%
2А Fuse, T -Type.
• Stand-by Power Supply 1 Accumulator battery 12V/ 18Ah Dimensions - 167х181х76mm Voltage Output - U
Current Output - I
7А Fuse, Resettable (PTC) Battery connection: with a at terminal
lug Ø5mm
Consumption from 230V in normal working mode and a fully charged battery:
At 4 zones (1 Zone Expander) 2,1VA
At 16 zones (4 Zone Expanders) 4,2VA Consumption from the battery at mains
power supply failure in normal working mode:
With connected 1 Zone Expander 130mA
With connected 4 Zone Expanders 260mA Consumption from the battery in Fire alarm
condition:
At 1 Zone Expander, Fire in 1 zone 330mA
At 1 Zone Expander, Fire in 4 zones 720mAOutputs:
Sounder circuits SND1÷SND4 +24V/ 0.3A
(control module) Resettable (PTC) Fuse
CHARGE
MAX
= 13,8V
= 2A
Page 5
MAG816 - Installation and Operation Manual 5
Sounder circuits SND1÷SND4 +24V/ 0.15A
!
(4-Sounder Expander) Fuse, Resettable (PTC)
Fault Relay, volt free changeover contacts* +12V/ 1A or 24V/ 0.5A
U
= 125V; I
MAX
MAX
= 2A
Fire Relay, volt free changeover contacts* +12V/ 1A or 24V/ 0.5A
U
= 125V; I
MAX
MAX
= 2A
* Note: These functions may not be used to
provide any “Options with requirements” as
specied in EN54-2.
• Auxiliary output +24V DC/ 0,3А Fuse, Resettable (PTC)
Cabling of the main power supply:
Recommended wires cross section 1.5mm
2
Terminal maximum wire diameter Ø2.5mm Environment:
Working temperature -5 ÷ +40ºС
Storage temperature -20 ÷ +60ºС
Humidity Up to 93% (non condensing)
2.2 General Technical Specications of Relay Module MR8
Number of relays: 8 Power supply: 24VCurrent consumption in normal condition: 8mAAdditional current consumption for every
relay switched ON: 10mA Maximum ratings of volt-free changeover contacts: 12V/ 1A or 24V/ 0.5A
Maximum voltage: 125VMaximum consumption: 2ACabling:
Recommended wires cross section 1.5mm
Terminal maximum wire diameter Ø2.5mm Environment:
Working temperature -5 ÷ +40ºС
Storage temperature -20 ÷ +60ºС
Humidity Up to 93% (non condensing)
2
WARNINGS:
Prior to connecting the MAG816 Fire Alarm Panel, perform a thorough test of the all wiring integrity of the entire system.
Should a fault arise during installation and connection, which cannot be removed, stop the installation and call the producer or his regional authorized representative!
TECHNICAL SUPPORT HELP
TEL.: +44 (0) 1527 51 51 50
Page 6
3. INSTALLING MAG816
• Select the best location for the panel away from sources of heat, environmental dust and potential water ingress, with an ambient temperature of between -5°C and + 40°C,
Figure 1.
• Undo the two secure bolts - Figure 2. Use the instrument supplied for the purpose in the set (hexagonal tool No. 2).
• Open the front panel and disconnect the earth cables: from the 230 V clamps, from the metal bottom clamps and from the chassis.
• Disconnect the indication ribbon cable.
• Remove the front panel by undoing the screws of the hinges - Figure 3. (NB. The
screws at the metal bottom can also be undone. What is special here is that there are two plastic pads under the every hinge. These pads need to be placed back again under the hinges when mounting the front panel.)
• Select the input openings for the cables and place a plastic cap, provided with the panel accessories, on those which are not going to be used, see Position 9 from the spare parts kit on page 31.
• Perform an exposed or ushed mounting (option) - see items 3.1 and 3.2.
• Run all external cables into the box to establish connection but do not connect them
at this stage yet. Run the mains cable through the chosen opening but keep it away from the low voltage wirings.
• Connect the mains supply and earth to the main terminal block but do not switch the main electrical supply on at this stage.
• Place the plastic lightpipe (see Positions 7, 11 and 15, page 31), provided with the spare parts kit, at their designated locations on the main module, zone and/or sounder expanders.
• Position the battery and secure it with the clamp - Figure 9, Position 1.
• Connect the zone and sounder circuits and program the panel according to the specic
application.
• Mount the front panel back onto the hinges and connect the indication ribbon cable and the earth cables: to the 230 V clamps, to the metal bottom clamps and to the chassis.
• After all system programming and testing operation are complete, screw both secure bolts with the help of the hexagonal tool supplied.
Figure 1. Figure 2. Figure 3.
Page 7
MAG816 - Installation and Operation Manual 7
3.1 Wall Mounting
WASHER
METAL BOX
25mm THICK DRYWALL
SCREWS FOR FLUSH MOUNTING
SCREWS FOR HANGER FIXING
HANGER
TEMPLATE
DRILL HERE
FLUSH MOUNTING
• Use the template supplied to determine the openings of the metal bottom onto the
wall - Figure 4.
• Drill Ø6-8mm diameter openings in the wall and x the box using the provided anchors and screws (Positions 2 and 4, page 31) - Figure 5.
Figure 4. Figure 5.
3.2 Flush Mounting (option)
The accessory set provided contains two special hangers for ushed wall mounting (position 20, page 31) of the re alarm panel on 25 mm thick drywall.
• Use the dimension shown in Figure 6 to draw and cut out the mounting openings in the drywall.
• Attach the hangers to the internal side of the wall and x them with the screws (Position 19, page 31), as shown in Figure 7, Position 1.
• Run all external cables in the box and then place it into the mounting opening. Fix the bottom using the mounting screws and washers (Positions 17 and 18, page 31) - Figure 7, Position 2.
Figure 6. Figure 7.
Page 8
Figure 8. Flush mounting holes.
Main view of the xed to the wall hangers and the bolts supporting the metal box.
3.3 Conguration of the Basic Modules
Figure 9.
• 1 - Metal clamp for supporting the battery.
2 - Clamp for supporting the main power supply cable.
3 - Terminal for connecting between the mains power supply and the power source. T-type fuse 2A (Position 3, page 31).
4 - Earthing point.
Page 9
MAG816 - Installation and Operation Manual 9
3.4 Control Module
Table for Sounder
Delay Programming
(in minutes).
Rx/Tx - Terminals for connecting of Repeater, Relay Module or a combined connection between them (see items 4.1 and 4.2);
CC (Class change) - Terminal for connecting of a switch (see item 4.3);
GND - Grounding;
• +AUX - Auxiliary output, +24V DC / 0,3A;
FAULT RELAY - Fault Relay, +12V / 1A or +24V / 0,5A;
FIRE RELAY - Fire Relay, +12V / 1A or +24V / 0,5A;
SND 1 ÷ SND 4 - Sounder outputs, +24V / 0,3A; Mount the resistors R-10K from the supplied spare parts kit (position 1, page 31) to the sounder terminals;
DOUBLE - Double Action Mode (see item 5.2);
MASTER - Master Panel Mode (see item 5.4);
SLAVE - Repeater Panel Mode (see item 5.5);
• TIME DELAY - Sounder Delay Programming.
MAG816
Figure 10.
- LED Indication of the operation modes, lightpipe mounted (Position 7, page 31); - Faults LED indication, see item 7.1; - Jumper for enable/disable Earth Fault Indication; - Resettable (PTC) fuses; - Connector for connecting the main power source; - Connector for connecting 4-zone / 4-sounder expander; - Connector for connecting the control panel keypad.
Page 10
10 MAG816 - Installation and Operation Manual
3.5 Main Power Source
!
Connecting of the Main Power Source
Figure 11.
Connecting to the Battery
The yellow-green earthing cable of the main power source must be connected to the middle point of the terminal!
Figure 12.
Attention: It is possible that the battery might not be charged at the panel initial start-up.
In this case the BATT LOW/LOST at the control module and the GENERAL FAULT at
the front panel will light on until the battery will be charged up to the required level.
Page 11
MAG816 - Installation and Operation Manual 11
4-Zone Expander
!
3.6
1 - Mounting holes for xing the expander to the chassis.
2 - Connector for connecting of additional 4-zone / 4-sounder expander.
3 - Jumpers for Instant action mode
programming.
Example: To program ZONE1 in Instant action mode set a jumper on the z1 position.
4 - Connector for connecting: а) To the control module, when the 4-zone
expander is the rst module in the panel conguration.
b) To a previous 4-zone expander;
5 - Mounting holes for placing a lightpipe for the front panel LED indication, see Position 11 of the additional components included, page 31.
6 - LEDs Zone status indication.
Figure 13.
Connecting of Additional 4-Zone Expander
Figure 14.
• 1 - Connect the connectors of the expanders.
• 2 - Fix the second 4-zone expander with screws from the spare parts kit
(position 10, page 31) to the metal box frame.
• 3 - Mount the EOL-modules from the supplied spare parts kit (position 12, page 31) to the zone expander’s terminals as observe the polarity.
4 - Place the lightpipe (Position 11, page 31).
ATTENTION: Do not connect or disconnect the expander when the power is on! Before connecting or disconnecting the expander you SHOULD check whether the main and the stand-by power supplies are OFF!
The metal box of MAG816 can accommodate up to 4 zone expanders. To each zone can be connected up to 32 conventional detectors with consumption <200µA at normal operation mode and unlimited number of manual call points.
Page 12
12 MAG816 - Installation and Operation Manual
First
4 Zone
Expander
Second
4 Zone
Expander
First
4 Sounder
Expander
Control
panel
1234 5678
1234
zones
sounders
3.7 4-Sounder Expander
!
First
4 Zone
Expander
First
4 Sounder
Expander
Second 4 Zones
Expander
Control
panel
1234
sounders
1234
zones
5678
zones
!
1 - Mounting holes.
2 - Connector for connecting of additional 4-sounder expander.
3 - LED indication for troubles in the sounder circuits. In case of a trouble in any of the sounder
circuit SND1 - 4 the LED of the respective sounder circuit will light on together with
GENERAL FAULT and SOUNDER FAULT/ DISABLE indicators on the front panel.
4 - Connector for connecting:
а) To a 4-zone expander.
b) To a previous 4-sounder expander. c) To the control module.*
5 - Mounting holes for placing a lightpipe for the front panel LED indication, Position 15, page 31.*
6 - LEDs Sounder status indication.*
* Note: Just in case, when the panel is in Repeater Mode (a jumper is set on the SLAVE
Figure 15.
position).
Performance and Connecting of the 4-Sounder Expander
There is a correspondence between the zone numbers and the sounders - ZONE 1 of the 4-zone expander corresponds to SOUNDER 1 of the 4-sounder expander, ZONE 2 to SOUNDER 2, and so on. In case of re in ZONE 1, SOUNDER 1 will operate continuously and Sounders 2 ÷ 4 of the expander will be pulse activated - 2 sec. sound/
2 sec. silent.
The method of adding of 4-sounder expander is analogical to that of adding a 4-zone expander module, see Figure 14. Note: At Step 3 mount the resistors R-10K from the supplied spare parts kit (position 16, page 31) to the sounder expander terminals.
ATTENTION: Do not connect or disconnect the expander when the power is on! Before connecting or disconnecting the expander you SHOULD check whether the main and the stand-by power supplies are OFF!
Note: Only a module of the same type can be added to the 4-sounder
expander. For the proper performance of the re alarm panel observe
the connection sequence presented in Figure 16a. In case of improper connection (Figure 16b), an error signal will be generated when the power supply is switched on - the LEDs of the zones connected after the 4-sounder expander will begin to blink and the GENERAL FAULT LED remains permanently lit.
а)
Figure 16.
b)
Page 13
MAG816 - Installation and Operation Manual 13
4. CONNECTING
!
4.1 Relay Module MR8
MR8 is a supplementary module which is located outside the MAG816 Alarm Panel box. The MR8 contains 8 changeover contact relays. When using all 16 zones, the MAG816 needs two relay modules. The technical specications of the MR8 module relays are described in item 2.2.
Conguring the MR8 outputs
Should zones numbered 1 to 8 be used, a jumper is set at outputs 1÷8 of the MR8 mother board; should the jumper be set at outputs 9÷16, zones numbered 9 to 16 will
be used - Figure 17.
The MR8 relay contact type (normally closed or normally open) is determined by conguring the NO/NC outputs. Setting the jumper at the NO output will normally open the contact; setting the jumper at the NC output will normally close the contact - Figure
17.
Special jumper J1 - when this jumper is set, the rst zone relay is activated by the module relays after the button
upon an alarm event.
(see item 6.2) on the control panel is pressed
Performance of the MR8 Module Relays
The MR8 Relays are activated upon an alarm event (re) in the respective zone they are
connected to.
• If a sounder delay is set in the main control panel, this delay will also reect on the relay activation of the rst alarm - it shall delay by the same duration.
• The relay activation delay is eliminated by pressing the the sounders are immediately enabled.
• Once a re signal has been generated and there is a sounder delay set off, the following MR8 relays will be activated immediately.
• The activation of the respective relay is immediately after the sounders are activated. Where there is any delay, it shall apply only to the relay of the zone that rst entered the
alarm mode.
• The relay will restore its normal state only after the initial start-up of the control panel.
Pressing the
button will not restore the relay.
button - the relay and
In order to operate together with the MR8, the MAG816 Fire Alarm Panel must be in Master Panel mode - a jumper is set at the Master position.
The connecting between one Relay Module MR8 and Master Panel MAG816 is shown on Figure 18.
The connecting between two Relay Modules MR8 and Master Panel MAG816 is shown
on Figure 19.
Page 14
14 MAG816 - Installation and Operation Manual
Figure 17.
Terminals and jumper
conguration of MR8.
Figure 18.
Master
panel
Connecting between one Relay Module and Master Panel.
Master
panel
Figure19. Connecting between two Relay Modules and Master Panel.
Page 15
MAG816 - Installation and Operation Manual 15
4.2 Repeater Panel
A second MAG816 can be connected to the MAG816 Fire Alarm panel as Slave. The function of the Slave is to double the light and sound indication and the button control of the rst panel at a distance up to 1000 m. For the purpose, to both of the panels have to be assigned specic priorities: The rst re alarm panel shall be the system Master and the second - Slave.
The Master panel is congured by setting a jumper on the Master position of the main module, and the Slave - with a jumper on the Slave position (see Figure 10).
Figure 20 shows the connection between the Master and Slave MAG816 panels.
Connecting of Repeater Panel
When adding a repeater panel in the re system:
• Turn off the main and the stand-by power supplies.
• Connect the repeater to the rst MAG816 - see Figures 20, 21 and 22.
• Set a jumper on the Master position of the main panel - see Figures 10 and 20.
• Set a jumper on the Slave position of the second panel - see Figures 10 and 20.
• Turn on the main and the stand-by power supplies of the Slave panel.
• Turn on the main and the stand-by power supplies of the Master panel.
Figure 20. Connecting between Repeater and Master
MAG816
Panel.
Master
panel
Figure 21. Connecting between one Relay Module, Repeater and Master Panel.
Figure 22. Connecting between two Relay Modules, Repeater and Master Panel.
Page 16
16 MAG816 - Installation and Operation Manual
4.3 Class Change Mode
!
!
To use the class change function connect the terminals of a switch with normally open contacts to the CC (Class Change) clamps of the main module terminal (Figure 10). The working mode of the sounders will be:
- when the switch is pressed - one second sounder on, one second sounder off;
- when the switch is depressed - the sounder is off.
4.4 Connecting the Zone and Sounder Circuits
Verify the normal functioning of the panel before connecting circuits to zones and sounders:
• Connect the battery to the power unit terminals - Figure 12.
• Check the availability and condition of the fuse, a 2A T-type, located in the clamp for connecting the power unit to the main electric network.
• Turn on the main power supply.
In normal operation mode only the “POWER SUPPLY 230V” LED lights
up on the front panel of the re alarm station.
NOTE: In case other indicators are also lit and the internal buzzer has been activated:
• Disable the buzzer with the
• Check the mains fuse.
• Check the electrical connections within the station box.
• Check for any activated FAULTS LEDs of the main module, see Figure 10. Specify the faults according to the Faults Indication Table on page 26.
button on the front panel.
• Press the
button (see item 6.2) on the front panel to reset the system.
Connecting the Zone Circuits
Up to 32 conventional re detectors and an unlimited number of manual call points can be connected to each circuit. Figure 23 shows how to connect detectors within a zone.
Figure 23. Connecting of detectors (D1÷N) and manual call points (CP1÷N) to the zone circuit.
Attention: During DOUBLE ACTION mode of operation, where the zone expander has NO jumper set for instant action of any zone on the terminal, ONLY detectors can be connected to its circuit. If a jumper has been set - detectors and call points.
Example: If there are call points connected in ZONE 1, for the system to function properly there must be a jumper set at its zone expander at z1 position, see also Figure 26.
Page 17
MAG816 - Installation and Operation Manual 17
In order to connect the zone circuits:
!
!
brown
black
red
10K
LEGEND
Sounders
S1 S2 SN
• Shut down the mains supply and disconnect the terminals of the power unit to the battery.
• One by one remove the EOL-modules from the 4-zone expander connecting clamps and t them to the last detector of each of the circuits as observe the polarity - Figure
23.
• Connect each circuit to a separate zone on the terminal of the 4-zone expander.
• Connect the battery to the power source and apply mains power to the panel.
After powering up the panel should be in normal operation mode and the “POWER SUPPLY 230V” LED lights up on the front panel of MAG816.
NOTE: If the GENERAL FAULT LED lights up and a fault indicator has been activated
for one or more zones on the front panel, the problem lies with the connection of the circuits in these zones. Check the polarity of the connection of the devices and whether there is a detector removed from its base.
• Activate one or more detectors to each connected zone to verify that re signals are generated and also that the panel operates correctly.
Connecting of FAULT and FIRE Relays
The relays with changeover contacts are intended for control of low voltage devices.
Attention: No mains power should be supplied to the clamps of the FAULT and FIRE relays. After the connection is established, test each of the circuits for external device control.
Connecting of Sounder Circuits
Figure 24 shows how to connect the sounders. One R=10K resistor is connected to the end of each circuit as shown in the diagram.
Figure 24. Connecting of sounders to SND1÷SND4 outputs of the control module
and the output of the 4-sounder expander.
Page 18
18 MAG816 - Installation and Operation Manual
In order to connect the sounder circuits:
!
• Shut down the mains supply and disconnect the terminals of the power unit to the battery.
• One by one remove the resistors (R=10K) from the sounder connecting clamps (SND1÷SND4) on the main module and connect them in parallel to the last sounder of each of the circuits. Connecting the sounders to outputs of 4-sounder expander is done
in an analogical manner.
• Connect the sounder circuits to the SND1÷SND4 clamps on the main module and/or on the 4-sounder expander by observing the polarity.
• Connect the battery to the power unit and apply the main power supply.
After powering up the panel should be in normal operation mode and the “Power Supply 230V” LED lights up on the front panel of MAG816.
NOTE: If the GENERAL FAULT LED lights up on the front panel together with any of
the FAULTS LEDs of the main module and/or the 4-sounder expander - SND1÷SND4, perhaps there is a problem in the connection. Check the polarity of the connection to the terminal of the main module of the panel, as well as the connection to the 4-sounder expander.
5. SYSTEM PROGRAMMING
5.1 Sounder Delay
This is an option for setting a delay on the Sounders activation when the panel enters “Fire” mode. The indication on the front panel - the FIRE LEDs, however, will light up immediately in case of a re event, regardless of whether a delay has been set to enable the sounders. After the programmed delay period expires, during which the user can possibly nd out the cause for the alarm event, the panel enables the sounders. The
sounders can be silenced by pressing the
In case of a false re alarm the user must press the working mode.
In order to program MAG816 for Sounder Delay over an interval between 1 and 10
minutes:
• Examine the Table of Instructions for programming sounder delay, shown on
Figure 10.
• Depending on the selected time delay, set a jumper at the TIME DELAY
terminals, marked in Figure 10 as 1, 2, 3, and 4.
• Press
Example: In order to program sounder delay of 3 minutes, set jumpers on positions 1
and 2.
to introduce changes.
(see item 6.2) on the front panel.
button to return to normal
Page 19
MAG816 - Installation and Operation Manual 19
5.2 Double Action Mode
Time Time
The purpose of introducing a DOUBLE Action mode is to avoid false alarms. Where MAG816 has been programmed to function in this mode, in the case of a re signal, the panel does not alarm at once but waits for the alarm event to be repeated within a specic time interval - Figure 25. The time interval has been set by default and cannot
be adjusted. For MAG816 it is 3 minutes.
In order to program the re alarm panel for Double Action mode:
Set a jumper on the DOUBLE terminal of the main module - Figure 10.
• Press
to introduce changes.
Figure 25.
EXAMPLE 1: In this case the re panel will not activate the sounders and the signalization
on the front panel because during time interval 2 no second alarm signal is generated. EXAMPLE 2: In this case the re panel will activate the sounders and the signalization on the front panel because during time interval 2, two alarm signals are generated.
5.3 Instant Action Mode
Where in the armed site there are zones, which need the sounders and the light indicators to be enabled instantaneously, the panel provides instant action working mode. This mode can be programmed individually for every single zone, depending on its designation. In instant action mode, in case of an alarm event occurring in the zone, the sounders are immediately enabled, i.e. this mode is of priority by zones compared to
Double Action and Sounder Delay modes.
In DOUBLE action mode of operation, where there is NO jumper on instant action
terminals of the zone expander, ONLY detectors can be connected to each zone circuit, and if a jumper has been set - that allows connecting both detectors and call points.
In order to program Instant Action mode for a selected zone:
• Set a jumper on the terminal that corresponds to the number of the zone - Figure 13.
• Press
to introduce changes.
Example: If there are call points connected in ZONE 1, for the system to function properly there must be a jumper at its zone expander at z1 position.
Page 20
20 MAG816 - Installation and Operation Manual
Figure 26. Example for Instant Action Mode Programming.
5.4 Master Panel Mode
When connecting two MAG816 panels in a common system, the rst must be pro­grammed as Master and the second as Slave.
In order to program the Master Panel mode:
• Set a jumper on the Master position of the main module - Figure 10.
• Press
The connection between the Master Panel and the MR8 module relays is described in item 4.1, and the connection between the Master Panel and the Slave - in item 4.2.
to introduce changes.
5.5 Repeater Panel Mode
In order to program the Repeater Panel mode:
• Set a jumper on the Slave position of the main panel module - Figure 10.
• Press
The connection between the Master Panel and the Slave is described in item 4.2.
to introduce changes.
5.6 Single Panel Mode
No jumper is set on the Master or Slave position in Single Panel Mode of the MAG816.
In order to program the Single Panel mode:
• Check whether there are jumpers set on the Master or Slave position. Remove them if any.
• Press
to introduce changes.
Page 21
MAG816 - Installation and Operation Manual 21
6. OPERATION INSTRUCTIONS
6.1 Initial Start-Up of MAG816
The panel is enabled by supplying main and stand-by power supply. An initial start-up procedure will begin to execute, which runs as follows:
1. For about 2 seconds all LEDs will light up; it is possible for a sound signal to be activated.
2. All LEDs light up for 1 second - on the main panel (except uPFault) and for the zone or sounder expanders (the dichromatic LEDs of the zone/ sounder expanders light up in orange). The sound signalisation is activated.
3. For about 5 seconds the following LEDs light up:
On the main module - all except uPFault;
On the 4-zone expanders - the LEDs of zones programmed in Instant Action mode (i.e. with a set jumper) light up in orange, and all the rest - in red;
On the 4-sounder expanders - the Fault LED (SND1 - SND4).
4. The following LEDs light up for 1 second:
On the main panel - all except uPFault and Fire;
On the 4-zone expanders - all LEDs are lit off;
On the 4-sounder expanders - the Fault LED (SND1 - SND4). At the end of the initial start-up procedure only the POWER SUPPLY 230V LED lights
on. All other LEDs have to be lit off. The Fire Alarm panel is in Normal Operating mode.
6.2 Front Panel
- Switch for changing over between Access Levels 1 and 2. In OFF position (Access
Level 1) only the button is active and in ON position (Access Level 2) all buttons are active.
- Operation modes LED indication. - LED indication on zone status. - Control buttons. - Instructions for working with the fire panel.
Page 22
22 MAG816 - Installation and Operation Manual
6.3 Buttons
Button Description
Activating sounders.
Deactivating sounders.
Deactivating the internal buzzer.
Initializing of the start-up procedure. Conrming the introduced changes.
Enabling / Disabling of zones / sounders.
Test Mode; scroll forward zones.
6.4 LED Indication
LED Description
FIRE
(two red)
GENERAL FAULT
(yellow)
SOUNDER FAULT/DISABLE
(yellow)
OUTPUT DELAY (yellow)
ENABLE/DISABLE
(yellow)
TEST
(yellow)
POWER SUPPLY 230V
(green)
LED 1- 16
(yellow-red)
Fire in the premises.
Main Fault indicator.
Lights permanently at disabled sounders. Blinks at trouble in the sounder circuit.
Lights permanently at programmed outputs time de-
lay (a jumper is set on the TIME DELAY terminal).
Lights permanently at disabled zones/sounders. Blinks during enabling/disabling of zones or sound­ers.
Blinks during “One Man” Test of a zone.
Blinks permanently in normal operating mode, indi-
cates presence of main power supply 230V.
Zone indication. Lights up in red at Fire in the zone. Lights up in yellow at disabled zone. Blinks in yellow:
- 1 blink per second at trouble in the zone;
- 2 blinks per second at “One Man” Test and
disabling of zones.
Page 23
MAG816 - Installation and Operation Manual 23
6.5 Sound Signal
• Short beeps - After pressing the and upon the initial start-up of the panel
• Continuous beep - Fire and/ or Fault status. The signal can be stopped by pressing the
button, but the LED indication remains.
• Interrupted beep - After pressing the
ers and the be stopped by pressing the
button to access “One Man” test mode of zones. The signal can
button, but the LED indication remains.
button to enable/disable zones/sound-
6.6 Service Modes
Zone Enable / Disable
Each zone of MAG816 can be enabled or disabled.
To disable a zone:
• Press
The ZONE 1 LED blinks in yellow (2 blinks per second) if ZONE 1 is enabled and lights permanently if ZONE 1 is disabled.
• Press
the zone which has to be disabled: The respective zone LED blinks in yellow
Press
Press start-up of the panel (item 6.1).
At this point the zone is disabled.
To enable a zone:
Press
The ZONE 1 LED blinks in yellow (2 blinks per second) if ZONE 1 is enabled and lights permanently if ZONE 1 is disabled.
• Press the disabled zone: The LED of the disabled zone lights
permanently in yellow.
• Press
(2 blinks per second).
button: DISABLE/ ENABLE LED blinks.
button, until you reach
(2 blinks per second).
button: The LED of the disabled zone lights
permanently in yellow.
button: That will run the procedure for initial
button: DISABLE/ ENABLE LED blinks.
button until you reach
button: The zone LED will start blinking in yellow
Press and introduce the changes (item 6.1).
At this point the zone is enabled.
button: That will initialize the start-up procedure
Page 24
24 MAG816 - Installation and Operation Manual
Sounders Enable/Disable
To disable the sounders:
• Press
The ZONE 1 LED blinks in yellow (2 blinks per second) if ZONE 1 is enabled and lights permanently if ZONE 1 is disabled.
• Press reach the last zone in the system - 8, 12 or 16.
button: DISABLE/ ENABLE LED blinks.
button until you
• Press
will start blinking.
• Press
up permanently.
Press
sounder disabling mode: That will initialize the start-up procedure
and introduce the changes (item 6.1).
At this point the sounders are disabled.
You can exit the sounder disabling mode also by pressing the
case the procedure for initial start-up will not run.
To enable the sounders:
• Press
The ZONE 1 LED blinks in yellow (2 blinks per second) if ZONE 1 is enabled and lights permanently if ZONE 1 is disabled.
• Press reach the last zone in the system - 8, 12 or 16.
• Press
lights up permanently in yellow.
• Press
start blinking.
Press
sounder enabling mode: That will initialize the start-up procedure
and introduce the changes (item 6.1).
At this point the sounders are enabled.
You can exit the sounder enabling mode also by pressing the
case the procedure for initial start-up will not run.
button once again: The SOUNDER FAULT/ DISABLE LED
button: The SOUNDER FAULT/ DISABLE lights
button to exit the
button, as in that
button: DISABLE/ ENABLE LED blinks.
button until you
button once again: The SOUNDER FAULT/ DISABLE LED
button: The SOUNDER FAULT/ DISABLE will
button to exit the
button, as in that
Page 25
MAG816 - Installation and Operation Manual 25
“One Man” Test
!
The “One Man” Test mode gives the installer the possibility to test the efciency of the system - whether the detectors react to smoke, heat, etc.
To “One Man” Test a zone:
• Press
The ZONE 1 LED blinks in yellow
(2 blinks per second).
ZONE 1 is in test mode. Test a detector from this zone whether it react to smoke, heat, etc.
MAG816 will activate the sounders for about 2 seconds to conrm the provoked re alarm.
button: TEST LED will start blinking.
• Press
with the system testing: TEST LED will continue blinking.
The ZONE 1 LED lights out (the zone is
The ZONE 2 LED blinks in yellow
(2 blinks per second).
ZONE 2 is in test mode. Test a detector from this zone whether it react to smoke, heat, etc.
MAG816 will activate the sounders for about 2 seconds to conrm the provoked re alarm.
Continue the system testing by pressing the Man” Test mode is automatic after the end of the test procedure in the last zone, or at
any time by pressing
button to continue
not longer in test mode).
button. The exit from the “One
button.
A sound signalization is activated at every Service Mode entering .
The signalization is deactivated by pressing
button.
Page 26
26 MAG816 - Installation and Operation Manual
7. INDICATION
!
7.1 Faults Indication
Indication on the front
panel
GENERAL FAULT + blinking in yellow (1 blink per second) LED of the zone, where the fault is occurred.*
GENERAL FAULT On + blinking SOUNDER FAULT/
DISABLE
GENERAL FAULT On + POWER SUPPLY 230V Off
GENERAL FAULT On + POWER SUPPLY 230V On
GENERAL FAULT
GENERAL FAULT
GENERAL FAULT RPТ LED***
GENERAL FAULT AUX LED Auxiliary supply fault. GENERAL FAULT EARTH LED Short circuit to earth. GENERAL FAULT uPFAULT LED Processor fault.
* It is possible for a fault to arise simultaneously in several zones - the LEDs of the zones with fault will blink.
** Where the fault has occurred in the sounder circuit of the expander, the SND1, SND2, SND3 or SND4 LEDs of the specic module, depending of the number of the circuit.
*** Only in Master or Slave modes.
The fuses used in the system are resettable (PTC) except the one for the main power supply. In case of a overload condition the PTCs will reset themselves - the GENERAL FAULT LED lights on. After the PTCs resetting the panel shall automatically return to
NORMAL MODE.
Indication on the
control module
-
LED SND1, SND2, SND3 or SND4, de-
pending on the number
of the circuit.** АС LED lights perma-
nently.
АС LED blinking. Battery charging fault.
ВАТТ LOW/LOST LED
lights permanently. ВАТТ LOW/LOST LED
blinking.
Fault description
- Zone fault - open or short
circuit.
- Detector head removed.
Sounder circuit fault - open
or short circuit.
Mains supply loss.
Battery loss.
Low battery charge level.
- No connection with the Repeater panel.
- Repeater fault.
NOTE: The fault indication does not show immediately. There is a delay in reporting depending on the type of the fault. After all faults are corrected the panel automatically returns to NORMAL MODE.
Page 27
MAG816 - Installation and Operation Manual 27
7.2 Indication of the Operation Modes
Operation
Mode
Normal Mode
FIRE
A FIRE relay is activated.
FAULT
A FAULT relay is activated.
TEST
Tests the sys­tem for proper
operational
efciency
LED Indication Sound Signalization
The POWER SUPPLY 230V green
LED lights on the front panel.
• The two red FIRE LEDs light up si­multaneously - the FIRE LED and the zone/zones LED (also in red) where the
alarm occurred.
• The LEDs will remain lit even after the
button has been pressed.
• The GENERAL FAULT yellow LED and the fault LED according to the Ta­ble in item 7.1 light up simultaneously.
• The two yellow LEDs blink simultane­ously - the TEST LED and the zone LED (also in yellow, 2 blinks per sec­ond) where the test is conducted.
-
• The sounders are activated.
They can be disabled by
pressing the
ton and can then be enabled
by pressing the
• The internal buzzer is acti-
vated. It is disabled by press-
ing the
• The internal buzzer is acti­vated. It is disabled by press-
ing the
• The internal buzzer is acti­vated. It is disabled by press-
ing the
but-
.
button.
button.
button.
• The ENABLE/DISABLE yellow LED
DISABLE
Disabled
zones and/or
sounders.
is lit on.
• The respective zone LEDs light up in yellow to indicate disabled zones.
• The yellow SOUNDER FAULT/DISA- BLE LED lights up to indicate disabled
sounders.
-
Page 28
28 MAG816 - Installation and Operation Manual
Expander
Zones / 4 Sounders4
CALL
POINTS
ZONE
Expander
Zones / 4 Sounders4
Expander
Zones / 4 Sounders4
Expander
Zones / 4 Sounders4
SND 1
324V / 0, A
SND 2
324V / 0, A
SND 3
324V / 0, A
SND 4
324V / 0, A
FAULT
RELAY
FIRE
RELAY
Rx
Tx
NO
NC
NC
NO
COM
COM
CC
GND
+AUX
MAG8plus MAIN BOARD
MASTER
SLAVE
DOUBLE
123
4
POWER
EXP
uPFault
SND1
SND2
SND3
SND4
FAULTS
EARTH
AUX
RPTACBATT LOW/LOST
Jumper to Enable/Disable
Earth Fault Indication
AC 230V/50-60 Hz
FUSE:
(T) 230V
A2
LN
NL
ZONE NUMBERS: 1, 2, 3, 4, 5 ... 16
SOUNDER NUMBERS: 1, 2, 3 ... (16 - ZONENUMBERS)
Connection Diagram
Expander4Zones
Connection Diagram
Expander4Sounders
R=10K
Thresholds for
zone conditions:
10
10
I<2mA
I=2- mA
I= -110 mA
I>110 mA
Open circuit
fault condition
Normal condition
Fire alarm condition
Short circuit condition
EOL
RED
BLACK
DETECTOR DETECTOR
CALL
POINT
CALL
POINT
LAST DEVICE
ON ZONE
RECOMMENDED USE SCHOTTKY
DIODE TYPE BYV-1060
ZONE
FIRE ALARM
CONTROL PANEL
TIME
(min )
DELAY
in utes
Up to 32 conventional
detectors, with
consumption<200 Aat
normal state and unlimited
number of manual
call points.
µ
BROWN
BLACK
RED
Expander
4 Sounders
SND 1
1524V /0, A
SND 2
1524V /0, A
SND 3
1524V /0, A
SND 4
1524V /0, A
SND1
SND2
SND3
SND4
ZONE1
ZONE2
ZONE3
ZONE4
DD
EOLDDEOLDDEOLDDEOL
D
Expander
4 Zones
EN54-2: 1997+AC:1999+A1:2006
EN54-4: 1997+AC:1999+A1:2002+A2:2006
MAG816
GENERAL CONNECTION CIRCUIT OF MAG816
Page 29
MAG816 - Installation and Operation Manual 29
FIRE ALARM RECORD
Installation address ....................................................................................................
....................................................................................................
Contact person: ..........................................................................................................
Telephone: ...................................................................................................................
Fax: ..............................................................................................................................
Date completed:..........................................................................................................
Commissioned by.......................................................................................................
Contract reference: ....................................................................................................
Service intervals: Monthly / Quarterly / Half yearly / Annually.
DETECTOR TYPE and
ZONE
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
TOTAL:
Ion - Ionisation sensor
Ph - Photoelectric sensor
RoR - Rate of Rise sensor
F/T - Fixed Temperature sensor
CP - Call Point
LOCATION
System installed by: .........................................................................................
Telephone/Fax: .........................................................................................
QUANTITY PER ZONE
Ion Ph RoR F/T CP
Page 30
30 MAG816 - Installation and Operation Manual
SERVICE RECORD
Faults Rectied Signature of Engineer Next Due
Zones
Tested
Name:
13 14 15 16
8 9 10 11 12
1 2 3 4 5 6 7
Name:
13 14 15 16
8 9 10 11 12
1 2 3 4 5 6 7
Name:
13 14 15 16
8 9 10 11 12
1 2 3 4 5 6 7
FIRE ALARM EVENT LOG
Fault yes/no and Type Action Taken Name
Zone
number
Date Visit
Completed
Date Time Fire
Page 31
MAG816 - Installation and Operation Manual 31
MAG816 Spare Parts Kit
1. Resistor 10K ±1%, 0,25W 2
2. Anchors 6х30mm 4
3. Fuse 2А, T-Type 5x20mm 1
4. Self tapping screw М4,2х35 cross slot DIN7981 4
5. Jumper 2
6. Cable tie 2,5/160mm 2
7. Lightpipe for indication 5
8. EOL - module 2
9. Plastic cap 21
4-Zone Expander MAG816 Spare Parts Kit
10. Screw М3х6 DIN7985 4
11. Lightpipe for indication 1
12. EOL - module 4
13. Jumper 1
4-Sounder Expander MAG816 Spare Parts Kit
14. Screw М3х6 DIN7985 4
15. Lightpipe for indication 1
16. Resistor 10K ±1%, 0,25W 4
Hanger for Flush Mounting Spare Parts Kit
17. Screw М4х40 cross slot DIN7985 4
18. Washer М4 DIN522 4
19. Screw М4х30 cross slot DIN965 2
20. Hanger for ush mounting, 300x41x18mm 2
Page 32
18020607 Rev.D 07/2013
Loading...