RECOMMENDED ROUTINE TEST PROCEDURE
The following test is designed to ensure the continued protection of your premises and occupants. Because of the possibility of a failure of the normal lighting supply occurring shortly after a period of testing, all tests should whenever possible, be undertaken at times of least risk, e.g during daylight hours.
ONCE A DAY
Visual inspection of battery charge led
www.espuk.com
Each unit should be energised from its battery for about 30 seconds by simulation of a failure of the normal lighting supply, to ensure the lamp operates in the emergency condition.
TWICE A YEAR
Each unit should be energized from its battery for a continuous period of at least one hour. Inspect if the LED light source works well. It is recommended that LED light source is inspected twice for no more than one year to retain the design photometric characteristics. If one or more LEDs fail to work normally, customers can decide to replace them or not according to if there is enough lumen output for emergency lighting.
Eventually, you may want to replace this light tting:
When your light tting and or battery pack come to the end of their life or you choose to update or upgrade the tting by replacing it, please
do not dispose of it with your normal household waste, please recycle
where facilities exist. When you need to dispose of this tting, check with
your retailer or local authority for suitable options. New regulations will encourage the recycling of waste from Electrical and Electronic Equipment. (European “WEEE Direction” effective August 2005).
EMLED5W NM&M FLUSH
EMERGENCY LIGHTING
LUMINAIRE INSTRUCTIONS AND TEST PROCEDURES
MAINTAINED/NON MAINTAINED EMERGENCY LIGHT
DURATION: 3 HOURS 220-240 AC 50/60HZ
Unit 7 | Target Park | Shawbank Road | Lakeside | Redditch | B98 8YN | United Kingdom
T: +44 (0)1527 51 51 50 F: +44 (0)1527 51 51 43
E: sales@espuk.com
INSTALLATION
OPERATION
1. Remove the diffuser from the body by easing each of the 4 ‘lugs’ off the
body clips using a 5mm at blade screwdriver.
2. Release gear tray by easing plastic clips away from the metal tray and lifting the metal tray away from the base.
3. Fix base to wall or ceiling either direct or via conduit box having cleared an access hole in the body for the cable.
4. ISOLATE THE A.C. SUPPLY and connect unit. An unswitched 240V A.C. supply must be connected to the live(L). Earth and neutral(N)
terminals tted to the PCB of all variants. On maintained variants continuous
illumination is provided by the white link ready connected, this can be replaced by a simple switch for on/off control.
5. Plug battery lead into connector on PCB.
6. Ret the gear tray into the body making sure the two plastic clips capture
it correctly.
7. Ret diffuser and press each of the 4 ‘lugs’ to ensure they are fully
located.
8. Check operation - restore the A.C. supply check the indicator LED is ‘on’. Leave for 30 minutes, remove power, the lamp should illuminate for a few seconds.
NON - MAINTAINED
Lamp normally off and battery on automatic charge (LED ‘on’) when the A.C. supply is healthy. Solid state circuitry automatically switches the lamp on when the A.C. supply is interrupted.
MAINTAINED
Emergency lamp normally on, when the supply to switched live is on. The battery is on automatic charge (LED ‘on’). Lamp will switch on or remain on if A.C. supply is interrupted.
MONITORING
Green indicator lamp (LED) normally continuously ‘on’. Indicator lamp goes out if A.C. supply or charger fails.
BATTERY
Sealed Nickel - Cadmium rechargeable battery pack.
TEMPERATURE
Performance gures measured at 25 degrees C
FAULT FINDING AND CORRECTIVE ACTION
MONITORING LED NOT ILLUMINATED
A.C. supply not healthy. Battery not connected. Charger failed
9. Restore the A.C. supply, and check that the indicator LED is ‘on’.
10. For maintained installation:
Remove white link connected across the two terminals marked SW and connect to the live AC 240V provided. (See diagram below)
Liv e (AC 240 V)
SW
SW
UNIT NOT MEETING REQUIRED EMERGENCY PERIOD
May need cycling: Discharge then, recharge for full 24 hours. Retest, battery pack may need replacing if emergency duration still not met.
LAMP NOT FULLY ILLUMINATED
If tube ends blackened replace tube. If illumination is hesitant and of a low level, either the battery pack or (less likely) the printed circuit board needs replacing.