ESP Ecocent 100L Installation And Operation Manual

1 of 42
V 1.9
www.esavep.com PASHW-003-100LD
ESP ECOCENT 100L
Installation and
Operation Manual
2 of 42
V 1.9
www.esavep.com PASHW-003-100LD
WARNING !
READ THIS BEFORE INSTALLING
THE
UNIT.
All un-vented water heating systems above 15 litres (this includes the ESP E c o c e n t Hot Water ASHP’s) MUST be installed to meet the requirements of the local area Building Regulations. It is a legal requirement that the local Building Control Officer be notified of any proposed installation of un-vented water heating systems over 15 litre capacity.
Furthermore, it must be fitted by an installer who has successfully completed a recognised course in the installation of un-vented heating systems such as CITB and be familiar with installing the Ecocent unit. Failure to properly fit the unit may affect its safety, efficiency and invalidate any guarantee.
Safety requirements in the UK call for an expansion space (internal or external), safety devices to prevent the stored water exceeding 100°C, and pipe work to convey discharged hot water safely away from the safety devices.
THE UNIT MUST BE INSTALLED, COMMISSIONED AND MAINTAINED BY A COMPETENT INSTALLER IN ACCORDANCE WITH BUILDING REGULATION G3 (ENGLAND AND WALES), TECHNICAL STANDARD P3 (SCOTLAND) OR BUILDING REGULATION P5 (NORTHERN IRELAND) AND THE WATER FITTING REGULATIONS (ENGLAND AND WALES) OR WATER BYELAWS (SCOTLAND). FOLLOWING INSTALLATION AND COMMISSIONING, THE OPERATION OF THE UNIT SHOULD BE EXPLAINED TO THE USER AND THESE INSTRUCTIONS LEFT WITH THEM FOR FUTURE REFERENCE.
3 of 42
V 1.9
www.esavep.com PASHW-003-100LD
Contents Page 1.0 Preface
2.0 General Notes
2.1 Safety Precautions
2.2 Installation Notes
2.3 Operating Notes
2.4 Moving and Repair Notes
2.5 Siting and Safety Notes
2.6 General Requirements
3.0 Siting the Unit
3.1 Heat Source
3.2 Dehumidification
3.3 Cooling
3.4 Siting Guidance
4.0 Installation
4.1 Ducting
4.2 Water Supply
4.3 Outlet Fittings
4.4 Limitations
4.5 Regulations
4.6 Package Contents
5.0 Specifications
5.1 Appearance
5.2 Features
6.0 Technical Specifications
7.0 Performance
7.1 Technical Performance
7.2 Standing Heat Losses
7.3 DHW Recovery Times
7.4 Performance Graphs
8.0 Functions
9.0 Physical Installation
4 of 42
V 1.9
www.esavep.com PASHW-003-100LD
9.1 Schematic Diagram
9.2 Pipe Fittings
9.3 Cold Water Supply
9.4 G3 Requirements
9.5 G3 Guidance
10.0 Moving the unit
10.1 Storage and Transport
10.2 Using a Forklift
10.3 Transporting for Installation
11.0 Hydraulic Connection
11.1 Connection Diagram
12.0 Wiring
12.1 Wiring Diagram
12.2 Earthing
13.0 Operating the Unit
14.0 Troubleshooting
15.0 Maintenance
15.1 The Cylinder
15.2 Safety Valves
15.3 The Strainer
15.4 Draining The Unit
15.5 Descaling the Immersion
15.6 Refilling the Unit
15.7 Log Book
15.8 Maintenance Requirements.
16.0 Fault Finding
17.0 Guarantee
17.1 Guarantee Terms
18.0 Environmental Information
19.0 Spare Parts
5 of 42
V 1.9
www.esavep.com PASHW-003-100LD
1.0 PREFACE
This manual includes the necessary information about installation
and maintenance of the Ecocent. Please read this manual carefully
before you install or carry out maintenance on the unit.
When installing the unit, please carry out the work strictly in
accordance with the manual, relevant Regulations and good practice.
Please do not switch the unit on until you are sure that it has been
properly installed, electrically and mechanically and there is water in the system.
The installer should explain to the end user how to operate and
maintain the unit before handing over the unit to the end user. Also, the installer should advise the end user to read the manual fully before operating the unit.
Further, improper installation, operation and/or maintenance, and
failure to maintain the unit as per this manual will invalidate any unit warranty or guarantee.
The manual may be altered and/or updated in any way at the sole
discretion of the supplier and/or ESP without notice.
2.0 GENERAL NOTES
2.1 Safety Precautions
Below you will find information that is critical for the safe and proper installation and use of the unit. Please make sure that you understand the contents because it is written to help avoid the risk of injury or damage to the unit/other property.
6 of 42
V 1.9
www.esavep.com PASHW-003-100LD
2.2 Installation Notes
Professional & qualified installer is required
The heat pump must only be installed by a suitably qualified engineer. Failure to ensure this can cause damage to the unit and may cause serious injury. The warranty on the unit will also be invalidated if a suitably qualified engineer is not engaged to install it.
Earthing required
Please make sure that the unit and power supply are properly earthed.
Refrigerant
If you are installing the unit in a small room, please give full consideration to adequate ventilation being available in the event of a refrigerant leak.
Installation Site
Do not install the unit near a gas installation. This unit is designed to be installed inside a building.
Site consideration
Ensure that this unit is fixed securely to a suitable wall that is capable of taking the load of the unit when full of water. Make sure that you have a suitable facility to cater for the disposal of condensate from the condensate drain on the unit.
Circuit Breaker
Make sure that this unit is connected to the power supply via a fused switched spur and a 13A Type C MCB.
Unit Upright
The unit must be installed level across the whole diameter. Failure to install the unit level will mean that condensate can spill over the lip of the cylinder.
Do NOT
Do not push anything into the fan blades when running and make sure that children cannot access the unit or play close to the unit.
Shut off the power supply
If there is an unusual sound or smell coming from the unit, shut off the power supply immediately and call your installation engineer.
Caution
This unit has a high centre of gravity. This unit must be strapped down to prevent it falling over when in transit.
Suitably qualified engineer
When moving the unit or carrying out repair work please be sure to use only a suitably qualified engineer.
2.3 Operating Notes
2.4 Moving and Repair Notes
7 of 42
V 1.9
www.esavep.com PASHW-003-100LD
Do NOT
Do NOT try to install, move or repair the unit yourself – it is NOT worthwhile running the risk of injury.
Transporting the Unit
The unit must be transported in the vertical position. It can be tilted up to 60° from the horizontal axis (see section 11.3).
Siting the Unit
The unit must only be installed indoors – the unit is not designed for, or suitable for installation outside. The Unit needs to be sited where the ambient temperature never goes below 5 degrees. If the unit is to be left unused for any significant period of time during which the ambient temperature could cause the unit or pipe work from the unit to freeze, it should be drained down.
Shut off the power
When cleaning the unit, shut off the power supply.
You MUST
You must use a suitable power supply that is appropriately fused.
2.5 Siting and Safety Notes
2.6 General Requirements
IMPORTANT: PLEASE READ AND ENSURE THAT YOU UNDERSTAND THESE INSTRUCTIONS BEFORE INSTALLING THE ESP Ecocent (“DHW
ASHP” or “unit”). INCORRECT INSTALLATION WILL INVALIDATE ANY
GUARANTEE.
PLEASE NOTE THAT THERE ARE ESSENTIALLY 2 UNITS COMBINED INTO ONE IN THE ESP ECOCENT AND YOU MUST BE SURE TO UNDERSTAND BOTH ELEMENTS - THE INDIRECT HOT WATER CYLINDER AND THE AIR SOURCE HEAT PUMP. PLEASE ALSO NOTE THE ECOCENT CAN BE INSTALLED IN EITHER A VENTED OR UNVENTED SYSTEM
IMPORTANT NOTE: DO NOT SITE THE UNIT IN THE SAME ROOM AS AN APPLIANCE WITH AN OPEN FLUE OR IN A ROOM FROM WHICH AN OPEN FLUED APPLIANCE TAKES ITS COMBUSTION AIR, UNLESS THE
8 of 42
V 1.9
www.esavep.com PASHW-003-100LD
MATTER HAS BEEN CAREFULLY CONSIDERED AND ADEQUATE DUCTING AND VENTILATION HAS BEEN PROVIDED FOR THE UNIT (THE DHW ASHP) AND THAT THE OPEN FLUED APPLIANCE IS FULLY CATERED FOR IN TERMS OF SUITABLE AIR SUPPLY.
Please be sure to use appropriate lifting equipment when moving the unit.
3.0 SITING THE UNIT
The unit is designed to be wall mounted. It can be placed anywhere convenient provided the discharge pipe(s) from its safety valves and air handling duct work can be correctly installed. Areas that are subject to freezing must be avoided. Ensure that the wall is of sufficient strength to support the weight of the unit when full with water. Pipe run lengths should be kept as short as possible for maximum economy and efficiency: the use of secondary returns should be avoided. Access to associated controls and indirect controls must be possible for servicing and maintenance of the unit. Please do not install valves or pipe work
(except discharge pipe) within 50mm (2”) of the T&P relief valve to
allow insulation to be fitted. The insulation is important to avoid heat loss.
Consideration must be given to the use of insulated ducting to carry air to and from the unit. Insulated ducting must be used where condensate may form on the duct work.
9 of 42
V 1.9
www.esavep.com PASHW-003-100LD
3.1 Heat Source
The Ecocent can receive ducted waste heat from another area in the building – duct work can be fixed to the top of the unit and may be up to 8m long without an additional in-line fan in the ductwork being needed. The Ecocent can also draw heat from the room in which it is sited. (See Picture 1)
Always be sure to site the unit and arrange duct work to allow adequate heat availability to allow the Ecocent to operate efficiently (inlet air should not be below 8° C.)
The secondary coil in the Ecocent enables direct connection to a second stable heat source, e.g. a solar heating system or a boiler.
Under no circumstances is the Ecocent to be installed onto an uncontrolled heat source e.g wood burner or back boiler
10 of 42
V 1.9
www.esavep.com PASHW-003-100LD
Picture 1
3.2 Dehumidification – The Ecocent can be used to dehumidify rooms that are hot and damp – e.g. Laundry room (See Picture 2). The unit is equipped with a condensate drain that must be properly directed to a suitable waste pipe where the condensate water (non acidic) can drain away. If the drain is into a main sewer it must have a trap installed to prevent back smell through the Ecocent.
Picture 2
3.3 Cooling (picture 3) The Ecocent can extract warm air and place cooled, dehumidified, outlet air back in to the same room – this is perfect for cellars and gymnasiums. Any cold air exhaust air ducting must be lagged when passing through a warmer
11 of 42
V 1.9
www.esavep.com PASHW-003-100LD
area to prevent the formation of condensate. All ducting should be 150mm or split into two 75-80mm ducts.
Picture 3
3.4 Siting Guidance
1. Decide upon the right route to be taken to move the unit in to the chosen position.
2. Try to move the unit in its original case to avoid damage.
3. Be sure to have the unit and electrics fitted by qualified electrician.
4. Ensure that no building materials or debris are allowed to enter the air
ducts at the top of the unit or any extension of the ducts.
4.0 INSTALLATION
4.1 Ducting
Air ducts to and from the heat pump should be 150mm pipe.
The outlets should be fitted with a suitable gravity vent to prevent rain, debris, animals and plants entering the ducts.
You can use rigid or flexible ducting. It is always best to use insulated ducting so that condensation is avoided.
12 of 42
V 1.9
www.esavep.com PASHW-003-100LD
When servicing the unit, ducting should be checked to make sure that it is clear and obstructions removed.
4.2 Water Supply
Bear in mind that the mains water supply to the property will be supplying both the hot and cold water requirements simultaneously. Therefore, it is important that the maximum water demand be assessed and the water supply checked to ensure that it can meet peak demand.
NOTE: A high mains water pressure will not always guarantee high flow rates. The main supply pipe to the unit must be in 22mm. The minimum mains water supply requirements should be 0.15 MPa (1.5 bar) working pressure and 20 litres per minute flow-rate at the unit. At these levels, outlet flow rates may be poor if several outlets are used simultaneously - the higher the available pressure and flow-rate the better the system performance will be.
The unit has a design operating pressure of 3 bar which is controlled by the Cold Water Combination Valve on the cold water feed pipework. The Cold Water Combination Valve can be connected to a maximum mains supply pressure of 1.6 MPa (16 bar). The water supply must be of wholesome water quality (Fluid Category 1 as defined by the Water Supply Regulations
1999).
The unit MUST be level horizontally, and vertically upright, otherwise this could cause problems with condensate draining from the heat pump section of the unit into the condensate drain.
An inline strainer (if open vented) and scale inhibitor (WRAS approved) must be fitted in line” on the water supply to the unit. Failure to fit these will invalidate the unit warranty/guarantee. All fittings must be WRAS approved.
13 of 42
V 1.9
www.esavep.com PASHW-003-100LD
If installing the unit in unvented configuration, an “unvented Pack”,
containing the required safety valves must be supplied with the unit and there is likely to be an additional cost for this.
4.3 Outlet Fittings
The unit can be used in conjunction with most types of terminal fittings. It is helpful in many mixer showers to have balanced hot and cold water supplies; in these instances the balanced cold water supply can be taken from the tapping on the combination valve. Branches to cold drinking water outlets should be taken before the combination valve.
NOTE: Accessories should have a rated operating pressure of at least
0.8 MPa (8 bar).
4.4 Limitations
The unit should not be used in any of the following instances:
• With a water supply from solid fuel boilers or any other boiler in which
the energy input is not under effective thermostatic control, unless additional, necessary and appropriate safety measures are installed.
• With gravity circulation primaries unless a good head of pressure is
available.
• With a steam heating plant unless additional and appropriate safety devices are installed.
• With ascending spray type bidets or any other facility where there is a Class 5 back-siphoning risk requiring that an appropriate air gap be employed.
• With water supplies that have either inadequate pressure or where
the supply may be intermittent.
• In situations where it is not possible to pipe away any discharge from the safety valves safely.
Loading...
+ 29 hidden pages