ESL 700 Series, 702RE, 702U, 713-5U, 702RU Installation Sheet

...
Number
Head (sold separately from base)
711U
713
721U
remote test
721UT
731U
741U
photoelectric smoke detector with alarm relay
741UT
731L
Base (sold separately from head)
701U
Number
702E 10PKG
702U
702RE
702RU
Head
TS7
with alarm relay
[1] UL Listed for releasing devices such as electromagnetic door holders, fire dampers, or smoke dampers.
Number
204
211
706U1A
ndicator with red alarm LED, for use with
706U2A
706U3A SM SM
[1] The remote alarm/trouble LED 706U3A models work 741U/741UT models when connected as shown
7 and
Figure
[2] 706U2A and 706U3A only work with the 721U/721UT models, when connected as shown in Figure 6 item 6.
ESL 700 Series Conventional Smoke and Heat Detector Installation Sheet
Description
Six-terminal base for all heads; 4 in. (10 cm)
Six-terminal base for 731U, 4 in. (10 cm)
Six-terminal base for 731U, 6 in. (15 cm)
(NO) output and remote alarm/trouble LED output
Description
The ESL 700 Series smoke or smoke with rate-of-rise heat detectors have field-replaceable optical chambers. The detector uses an optical sensing chamber to detect smoke and a fixed-temperature heat sensor to detect heat from fire. For a list of model numbers, see Table 1. For a list of accessories, see Table 2.
-
Six-terminal base for all heads, 6 in. (15 cm)
with base (sold together)
-4 Four-wire photoelectric smoke detector
High voltage (120 V) base and head
The 702RE and 702RU bases have a special plastic protrusion built in to prevent insertion of a low-voltage detector head into
a base containing damaging high voltages (120 V). These
bases can only be used with 731U heads. The 731U includes auxiliary relay contacts and is only required when connecting high voltage to the auxiliary relay.
Note: The 731U heads can also be used with 702E and 702U
bases for low voltage applications.
Table 1: Model numbers
Description
Two-wire photoelectric smoke detector head
-5U Two-wire rate-of-rise and 57°C (135°F) fixed temperature heat detector head
Two-wire photoelectric smoke detector, with
input and remote alarm/trouble LED output
Two-wire photoelectric, with rate-of-rise heat detector
head with remote test, alarm/trouble LED output
[1] Two-wire photoelectric smoke detector head with
auxiliary relay (NC/NO) output
Four-wire
(NO) output and remote alarm/trouble LED output
Four-wire photoelectric smoke and rate-of-rise heat
detector head, alarm relay (NO) output and remote alarm/trouble LED output
(OEM only, not for resale) see 731U description
Three-terminal base for 711U and 713-5U heads, 6 in.
(15 cm) base, connectors
© 2014 UTC Fire & Security Americas Corporation, Inc. 1 / 6 P/N 13083-EN • REV J • ISS 10APR14
Table 2: Accessories
Description
-12/24V End-of-line, power supervision relay for four-wire applications
-10PKG Replaceable optical chamber for ESL smoke detectors (set of 10)
[1] Remote i
721U and 741UT
[1][2] Remote indicator with red alarm LED and keyed
remote test, for use with 721U and 721UT
[1][2] Remote indicator with red alarm LED, keyed
remote test and reset, for use with 721U and 741UT
-200 Smoke! In A Can (canned smoke) for functional testing of smoke detectors
-EXT1 Extension tube for Smoke! In A Can
on the 706U1A, 706U2A, and
s with both two-wire 721U/721UT and four-wire
in Figure 6 item
7 item 11.
two-wire
Installation
(1) Smooth ceiling (2)
acceptable mounting area
(3) Wall
(5) 12 in. (300 mm) max.
(1) Base cover (2)
the head
(3) Gasket
(5)
(1)
(2)
(3)
(4)
(2)
(3)
(4)
(1)
Notes
Locate detectors in an operating environment as defined in “Specifications” on page 6.
Mount detectors on a firm, permanent surface.
Placement and spacing
Use the following location guidelines to optimize performance and reduce the chance of false alarms.
Smoke detectors:
Locate wall-mounted smoke detectors so the top of the detector is no lower than 12 in. (30 cm) below the ceiling. See Figure 1.
As a guide, space smoke detectors on smooth ceilings 30 ft. (9.1 m) apart. When determining other spacing, consider ceiling height, high air movement, and other
conditions or response requirements. Refer to NPFA 72.
Locate detectors away from air conditioners, heating
registers, and any other ventilation source that may interfere with smoke entering the unit; also away from kitchens, wood stoves, garages, furnaces, and bathrooms.
Heat detectors:
Do not install heat detectors in areas with an ambient temperature above 100°F (38°C).
Figure 1: Smoke detector placement
Gray indicates the
Figure 2: The six-inch diameter mounting base
(4) Floor
Mount heat detectors on the ceiling no closer than 4 in. from the sidewall. On the wall, mount them between 4 and 12 in. from the ceiling.
When determining detector placement, consider ceiling height, construction, and ventilation as these affect a detector’s performance. Refer to NPFA 72.
Installing the base
Select a compatible electrical box for the base. See “Specifications” on page 6 for a list of compatible electrical boxes.
The 6-inch diameter bases have three parts; the base itself that mounts on the electrical box or ceiling, a foam gasket, and the base cover that conceals the mounting screws (see Table 1 for model numbers and descriptions). The 6-inch diameter bases are shipped loosely coupled to the base cover.
Screwdriver slot to unlock
(4) Base
2 / 6 P/N 13083-EN • REV J • ISS 10APR14
To install the base:
(1) To lock, break out this tab with pliers
(1) Head
(2) Base
(1)
(2)
(1)
1. Remove the base cover by simply twisting it counter-
clockwise to unsnap (see Figure 2).
2. Pull the field wires through the electrical box, and then
through the center opening of the base. Connect the wires to the appropriate terminals according to the wiring diagrams (see Figure 6 or Figure 7).
3. Dress the wiring neatly, and then verify that the continuity
switch (jumper wire) is touching both terminal 1 and terminal 2 (see Figure 8). Securely fasten the base with the appropriate hardware.
4. Check all wiring and mounting connections.
5. Install the gasket. Align the molded line on the base with
the base cover, and then twist clockwise to snap in place.
Consider the locking mechanism before installation
Each detector head is equipped with a breakaway locking tab to prevent unauthorized removal of the detector head (see Figure 3). For installations where unauthorized removal of the detector head is not a concern, the head removes by simply turning counterclockwise.
Removing the detector head
To remove the detector head, turn it counterclockwise. If the locking tab was removed, insert a small screwdriver into the locking tab slot on the side of the base, and then press in while simultaneously turning the detector head counterclockwise (see Figure 5).
Figure 5: Removing the detector head with the locking tab removed
However, when the head must lock to the base, break away the locking tab with a pair of pliers. Then, to remove the detector head, insert a small screwdriver into the slot on the side of the base, pressing in while simultaneously turning the detector head counterclockwise (see Figure 5).
Figure 3: Removing the locking tab slot
Installing the detector head
To install a detector head, insert the head and rotate it clockwise to properly align and seat it into the base (see Figure 4). Then rotate it an additional 15 degrees to lock it in place. This action automatically opens the continuity switch in the base and establishes continuity in the system.
Figure 4: Installing the detector head
Wiring
Caution: Risk of system failure. The system may not operate if
the detector is not connected to the control unit initiating device circuit as specified in the detector or control unit literature.
For two-wire installation, see Figure 6.
For four-wire installation, see Figure 7.
For optional four-wire operation, verify that the voltage range of the control panel power supply is within the detector voltage range, and that sufficient current is available to ensure the operation of all detectors.
End-of-line supervision for four-wire systems
NFPA 72 requires supervision of power wiring in four-wire systems. To accomplish this, install a power supervision unit for the appropriate control unit voltage at the end of the detector power circuit. See Figure 7.
The model 204-12/24V power supervision relay accommodates both 12 VDC and 24 VDC operation. See the 204-12/24 V installation sheet for more information.
P/N 13083-EN • REV J • ISS 10APR14 3 / 6
Figure 6: 700 series two-wire wiring diagram
(1) Initiating device circuit from a compatible listed control panel (2) (3) (4) (5) (6)
only in this two-wire application)
(7) Remote LED P/Ns 706U1A, 706U2A ,or 706U3A (for 721U or
741UT detectors only)
Note: Alarm contacts are shown in the normal state.
(7)
6 4
5
6 4
5
701U
702U, 702E
702RU, 702RE,
702U, or 702E
(1)
(6)
(5)
(3)
NO C NC
1 3
2
1 3
2
1 3
2
(8)
(10)(9)
IDC_IN
IDC_IN
1
3
2
6 4
5
1 3
2
6 4
5
(2)
(3)
(4)
(5)
(1)
702U, 702E
702U, 702E
RD
BN BN
BK
(11 )
PWR_IN
PWR_IN
IDC_IN IDC_IN
Figure 7: 700 series four-wire wiring diagram (741UT head)
DC power circuit Continuity switch Power supervision relay (P/N 204-12/24V) End-of-line device Remote test switch P/N 706U2A (for 721U and 721UT detectors
Testing
Prior to testing, remove the red dust cover. The units do not work with the dust cover in place.
Follow the control panel’s recommended test procedure.
To limit inconvenience to building occupants during testing it may be necessary to disable or disconnect the alarm notification appliances, HVAC shutdown, elevator control, releasing service devices, and extinguishing systems prior to detector tests. If these or other functions controlled by the fire system are disconnected during testing, be sure to perform other tests to confirm that these functions will operate during an actual event.
Be sure to enable or reconnect all devices at the conclusion of testing.
4 / 6 P/N 13083-EN • REV J • ISS 10APR14
(8) Base for 711 series and 713-5U detectors (9) Base for 721UT detector only (10) Base for 731U series detectors (11) Remote LED P/Ns 706U1A, 706U2A, or 706U3A (for 741U or
Testing the wiring for continuity
After all universal mounting bases are installed, including the end-of-line device, check the system wiring for continuity.
Verify that the manually operated continuity switch in each
base is in the shorting position — making contact with terminals 1 and 2 (for use at initial installation only). See Figure 8. Use a screwdriver to reset any unshorted continuity switches (reset by prying the jumper wire out of the plastic stopper). This establishes continuity across the alarm initiating circuit at initial installation. The wiring can now be tested for continuity using an ohmmeter or “megger.”
721UT detector only)
Figure 8: Continuity switch
(1) Continuity switch
0 to 1
2 to 3
sensitivity test. If
4 to 7
8 to 9
lean the unit
(1) Test magnet
(1)
(1)
Testing the system
After completing all the connections and checking the wiring per NFPA 72, apply power to the system. There should be no alarm. If there is an alarm, check each detector to see if the alarm LED is active. Reset the control panel and see if the alarm clears. If the alarm does not clear after the panel is reset, power down the system and determine if there is a problem with the wiring. If there is no alarm, go to the last unit and use a voltmeter to check the unit power for the specified voltage.
Testing the smoke detector
Test the units in place annually, using Smoke! In A Can and following the directions on the can.
The unit performs a smoke test every 9 seconds while flashing its LED. If smoke is detected, the rate of sampling increases to every 4.5 seconds. The smoke detector must detect excessive smoke in three consecutive tests for the alarm to sound.
If the test is successful (alarm sounds), the LED stays on. This is a gross, go/no-go test and is not a reliable indication of unit sensitivity. For in-depth sensitivity testing, see “Performing a sensitivity test on a smoke detector” below.
To reset the detector, follow the control panel’s reset
procedure. Resetting the control panel will remove power from
the detector and allow it to reset. For a complete test of each detector, verify the control unit alarm and all ancillary functions.
Performing a sensitivity test on a smoke detector
1. Hold a test magnet near the raised TEST letters on the
detector for more than one second (see Figure 9).
The LED flashes 1 to 9 times.
2. Count the number of LED flashes, and then use Table 3 to
determine the required action.
Table 3: Description of LED flashes
Indication: Unserviceable hardware fault.
Action: Reset and rerun the sensitivity test. If the error persists, replace the unit.
Indication: Unit is becoming insensitive.
Action: Clean and reset the unit. Rerun the the error persists, replace the unit.
Indication: Unit is within normal sensitivity range.
Action: None
Indication: Unit is becoming too sensitive.
Action: Verify that the optical chamber is snapped down securely. If the chamber is correctly installed, c and replace the optical chamber.
After the sequence of flashes, if the detector finds the sensitivity to be within limits and if all other tests pass, the detector goes into alarm until reset by the panel. If the sensitivity is not within limits, or an unserviceable hardware fault is detected, the alarm LED continues to flash once per second until the detector is reset by the panel. If the sensitivity test indicates an unacceptable level, take the action recommended in Table 3. If this action does not result in acceptable sensitivity, replace the unit.
Figure 9: Smoke detector sensitivity level test
Remote LED
Models 721U/721UT and 741U/741UT have connections for an optional remote LED. The remote LED flashes every 9 seconds for a normal state, flashes once every second for a trouble state, and turns on steady in alarm. It does not indicate during loss of power.
Testing the heat detector
The 713-5U heat detector samples for heat continuously. The photoelectric smoke/heat detectors sample for heat every three seconds.
P/N 13083-EN • REV J • ISS 10APR14 5 / 6
To test the heat detector:
1. Aim a hot air gun at the detector from 6 to 10 in. (15 to 25 cm) away, taking care not to melt the plastic.
The detector should go into alarm in less than 30 seconds.
Maintenance
(1) Detector cap
(2) Field-replaceable optical chamber
Voltage
Maximum ripple
Typical average
standby current (24 V)
Typical alarm current
Remote LED output
current
Relay contacts
RFI immunity
Heat detector specifications
Heat detector spacing
Sensitivity
Drift compensation adjustment
Remote test input
Reset voltage
Reset time
Color
Detector head dimensions
Base dimensions
Compatible electrical boxes [
Total height, base together
Field wiring size
Operating environment
Listings
UL two compatibility identifier
(1)
(2)
If a smoke detector drifts beyond its approved sensitivity range for more than 24 hours, or fails internal diagnostic tests during power-up, the unit automatically indicates trouble by flashing its LED every second. Under normal conditions, the LED flashes every nine seconds. Therefore, a visual check of the LED status meets NFPA 72 field sensitivity testing requirements.
In accordance with NFPA 72, visually check the LED flashes for unit sensitivity within one year of installation and every alternate year thereafter for commercial installations, or every three years for residential sites.
Cleaning the smoke detector
The smoke detectors have an optical chamber that unsnaps for easy field cleaning and service. Whenever the LED indicates that cleaning is necessary, follow the steps given below.
To clean the smoke detector:
1. Remove the detector cap (see Figure 10), and then unsnap and throw away the optical chamber.
2. Use compressed air to thoroughly clean the optical base, and then snap a new optical chamber into place.
Note: Be sure the new optical chamber is seated all the
way down.
3. Replace the detector cap and verify sensitivity. See “Performing a sensitivity test on a smoke detector” on page 5.
Figure 10: Optical chamber
Two-wire: 60 mA (max.), if not limited by
control panel
Four-wire: 50 mA (max.) but 15 mA (min.)
5.0 to 8.5 mA
2 A at 30 VDC, 1 A at 120 VAC
20 V/m minimum, 0 to 1,000 MHz
Fixed temperature: 135° ±3°F (57° ±1.7°C)
[1]
1.55 to 3.22%/ft. obscuration
2.5 V max.
1 second min.
White head and base
2]
head and
12 to 24 AWG
Temperature Relative humidity
[1] For models 713-5U, 721UT, and 741UT.
[2] Bases may also be mounted without electrical boxes if the AHJ approves it or if codes allow.
Rate of rise: 15°F/min and > 105°F (8.3°C/min and > 40.6°C)
721UT, 741UT: 50 ft.
713-5U: 70 ft.
1.0%/ft. max. for photoelectric models
100 Ω max.
4 in. (10 cm) diam., 1.75 in. (4.44 cm) height
701U, 702U, 702RU: 6 in. (15.2 cm) diam.,
0.6 in. (1.3 cm) height
702E, 702RE: 4 in. (10 cm) diam., 0.5 in. (1.27 cm) height
701U, 702U, 702RU: Standard single-gang electrical boxes; 4-inch square, round, or octagonal boxes; 3.5-inch octagonal boxes; WIREMOLD 5738A or 5739 fixture boxes
702E, 702RE: 3-inch round electrical boxes
1.98 in. (5 cm)
32 to 100°F (0 to 38°C) 0 to 95% noncondensing
Specifications
8.5 to 33 VDC, not polarity sensitive
10% (Vp-p)
6 / 6 P/N 13083-EN • REV J • ISS 10APR14
711U, 713-5U: 70 μA 721U, 721UT, 731L, 731U, 741U, 741UT: 100 µA
Regulatory information
UL Listed (UL 268 and UL 521)
FM Approved (except for TS7-4 and TS7-4T)
CSFM (California State Fire Marshal) Approved
-wire
S10A for all models except 731U/731L
S11A for 731U/731L
S00 for all bases
Contact information
For contact information, see www.interlogix.com.
Loading...