ESL 700 Series, 702RE, 702U, 713-5U, 702RU Installation Sheet

...
Number
Head (sold separately from base)
711U
713
721U
remote test
721UT
731U
741U
photoelectric smoke detector with alarm relay
741UT
731L
Base (sold separately from head)
701U
Number
702E 10PKG
702U
702RE
702RU
Head
TS7
with alarm relay
[1] UL Listed for releasing devices such as electromagnetic door holders, fire dampers, or smoke dampers.
Number
204
211
706U1A
ndicator with red alarm LED, for use with
706U2A
706U3A SM SM
[1] The remote alarm/trouble LED 706U3A models work 741U/741UT models when connected as shown
7 and
Figure
[2] 706U2A and 706U3A only work with the 721U/721UT models, when connected as shown in Figure 6 item 6.
ESL 700 Series Conventional Smoke and Heat Detector Installation Sheet
Description
Six-terminal base for all heads; 4 in. (10 cm)
Six-terminal base for 731U, 4 in. (10 cm)
Six-terminal base for 731U, 6 in. (15 cm)
(NO) output and remote alarm/trouble LED output
Description
The ESL 700 Series smoke or smoke with rate-of-rise heat detectors have field-replaceable optical chambers. The detector uses an optical sensing chamber to detect smoke and a fixed-temperature heat sensor to detect heat from fire. For a list of model numbers, see Table 1. For a list of accessories, see Table 2.
-
Six-terminal base for all heads, 6 in. (15 cm)
with base (sold together)
-4 Four-wire photoelectric smoke detector
High voltage (120 V) base and head
The 702RE and 702RU bases have a special plastic protrusion built in to prevent insertion of a low-voltage detector head into
a base containing damaging high voltages (120 V). These
bases can only be used with 731U heads. The 731U includes auxiliary relay contacts and is only required when connecting high voltage to the auxiliary relay.
Note: The 731U heads can also be used with 702E and 702U
bases for low voltage applications.
Table 1: Model numbers
Description
Two-wire photoelectric smoke detector head
-5U Two-wire rate-of-rise and 57°C (135°F) fixed temperature heat detector head
Two-wire photoelectric smoke detector, with
input and remote alarm/trouble LED output
Two-wire photoelectric, with rate-of-rise heat detector
head with remote test, alarm/trouble LED output
[1] Two-wire photoelectric smoke detector head with
auxiliary relay (NC/NO) output
Four-wire
(NO) output and remote alarm/trouble LED output
Four-wire photoelectric smoke and rate-of-rise heat
detector head, alarm relay (NO) output and remote alarm/trouble LED output
(OEM only, not for resale) see 731U description
Three-terminal base for 711U and 713-5U heads, 6 in.
(15 cm) base, connectors
© 2014 UTC Fire & Security Americas Corporation, Inc. 1 / 6 P/N 13083-EN • REV J • ISS 10APR14
Table 2: Accessories
Description
-12/24V End-of-line, power supervision relay for four-wire applications
-10PKG Replaceable optical chamber for ESL smoke detectors (set of 10)
[1] Remote i
721U and 741UT
[1][2] Remote indicator with red alarm LED and keyed
remote test, for use with 721U and 721UT
[1][2] Remote indicator with red alarm LED, keyed
remote test and reset, for use with 721U and 741UT
-200 Smoke! In A Can (canned smoke) for functional testing of smoke detectors
-EXT1 Extension tube for Smoke! In A Can
on the 706U1A, 706U2A, and
s with both two-wire 721U/721UT and four-wire
in Figure 6 item
7 item 11.
two-wire
Installation
(1) Smooth ceiling (2)
acceptable mounting area
(3) Wall
(5) 12 in. (300 mm) max.
(1) Base cover (2)
the head
(3) Gasket
(5)
(1)
(2)
(3)
(4)
(2)
(3)
(4)
(1)
Notes
Locate detectors in an operating environment as defined in “Specifications” on page 6.
Mount detectors on a firm, permanent surface.
Placement and spacing
Use the following location guidelines to optimize performance and reduce the chance of false alarms.
Smoke detectors:
Locate wall-mounted smoke detectors so the top of the detector is no lower than 12 in. (30 cm) below the ceiling. See Figure 1.
As a guide, space smoke detectors on smooth ceilings 30 ft. (9.1 m) apart. When determining other spacing, consider ceiling height, high air movement, and other
conditions or response requirements. Refer to NPFA 72.
Locate detectors away from air conditioners, heating
registers, and any other ventilation source that may interfere with smoke entering the unit; also away from kitchens, wood stoves, garages, furnaces, and bathrooms.
Heat detectors:
Do not install heat detectors in areas with an ambient temperature above 100°F (38°C).
Figure 1: Smoke detector placement
Gray indicates the
Figure 2: The six-inch diameter mounting base
(4) Floor
Mount heat detectors on the ceiling no closer than 4 in. from the sidewall. On the wall, mount them between 4 and 12 in. from the ceiling.
When determining detector placement, consider ceiling height, construction, and ventilation as these affect a detector’s performance. Refer to NPFA 72.
Installing the base
Select a compatible electrical box for the base. See “Specifications” on page 6 for a list of compatible electrical boxes.
The 6-inch diameter bases have three parts; the base itself that mounts on the electrical box or ceiling, a foam gasket, and the base cover that conceals the mounting screws (see Table 1 for model numbers and descriptions). The 6-inch diameter bases are shipped loosely coupled to the base cover.
Screwdriver slot to unlock
(4) Base
2 / 6 P/N 13083-EN • REV J • ISS 10APR14