Esco Medicon Gas Manifold Maintenance manual

Document Number: Issue Status: Date:
Z03G010 I
24/Oct/07
AUTOMATIC GAS MANIFOLDS
INSTALLATION, OPERATION &
MAINTENANCE MANUAL
ALL ESCO AUTOMATIC GAS MANIFOLDS COMPLY WITH THE
STANDARD AS2896-1998
m e d i c o n
INDEX
1.
2.
3.
4.
5.
6.
7.
INTRODUCTION 3
Page
Page 2 of 20
SPECIFICATIONS 3
INSTALLATION 4
OPERATION 5
SERVICE 6
SPARE PARTS 9
SETTING INSTRUCTIONS 10
AUTOMATIC GAS MANIFOLDS
m e d i c o n m e d i c o n m e d i c o n m e d i c o n
1. Introduction
2. Specifications
MAXIMUM INLET (Cylinder) PRESSURE
OUTLET (Line) PRESSURES
OUTLET CONNECTION
EMERGENCY INLET CONNECTION
HEADER BLOCK CONNECTIONS
Esco Automatic Gas Manifold (AGM) systems are designed to supply hospital facilities with Oxygen, Nitrous Oxide, Medical Air and Surgical Tool Air, meeting the requirements of AS2896.
The concept consists of a central control panel with regulators, changeover mechanism, pressure switches, gauges, shut off valves and service inlet facility, all mounted and piped on one easily installed base plate. A screen printed cover illustrating the operation is fitted over the assembly.
After factory assembly, the regulators, pressure switches and relief valves are set and tested prior to despatch as per setting instructions in this manual. No adjustments should be necessary after installation, however, if for some reason the AGM is not performing as per specification, please contact ESCO Industries on (02) 8799 3700.
(a)
(b) Surgical Tool Air 750 & 1,450KPa
Male 5/8” SAE Flare
Sleeve Index,
Nitrous Oxide M16 x 1.5 Oxygen M18 x 1.5 Air M20 x 1.5 Surgical Tool Air M20 x 1.5
Gas specific as per AS2896 Terminal Units
Oxygen, Medical Air & Nitrous Oxide 450KPa
23,000KPa
Page 3 of 20
AUTOMATIC GAS MANIFOLDS
3-Installation
1.
2.
3.
1.
The cylinder size chosen will determine the mounting height of the manifold control panel. “G” size cylinders are normally used, however, we suggest you check before commencing installation.
If “G” size cylinders are to be used, mark the wall at 1800mm above the finished floor level. Temporarily connect a cylinder lead and header block assembly together. Position the header block with bracket fixing holes over the 1800mm mark and confirm cylinder connection height (1460mm) is correct to drawing
32267. Cylinder Lead assemblies are designed to flex vertically approximately 50mm, accounting for slight variations in cylinders.
If correct, remove screen printed cover from the central control panel by removing:
Pipeline Connection:
Then proceed and fix the base plate to wall (M6 Dynabolts) to drawing 32267, spot drilling through slots & holes.
Header Blocks and brackets are supplied assembled, however, you must attach these to the central control panel high pressure blocks (right and left hand) using two header block connection tube assemblies (Z02J008) - refer to drawing 32289. This will position the header block brackets correctly on either side of the central control panel. Lastly, position and fix cylinder racks as per drawing 32267.
The pipeline is connected to the central control panel at the bottom left hand corner via the 5/8” SAE flare tee fitting. The 5/8” Dia. Copper pipeline may exit the unit either horizontally (as supplied) or vertically, simply by rotating the tee fitting through 900 clockwise. A 5/8” SAE flare to 3/4” diameter outlet bend
assembly (Item 59 Dwg 32503) is supplied allowing initial pipework connection with 3/4” copper tube.
a) b) c)
Black selector lever. Two black valve hand wheels. Two M5 button head screws at bottom.
Page 4 of 20
AUTOMATIC GAS MANIFOLDS
4. Operation
High pressure gas (up to 230 bar) is supplied from both banks of cylinders into the manifold as indicated by the two pressure gauges in the top right and left hand corners of the panel.
The “Cylinder Bank Selector” in the centre of the panel determines which bank of cylinders, left or right hand, is the primary bank and which is the secondary. The primary bank will always be the one feeding the system until such time as the pressure in these cylinders drops below; 700KPa (4 Bar) - Oxygen, Air & Nitrous Oxide, or 1200KPa (7 Bar) - Surgical Tool Air, or 1600KPa (14 Bar) - Surgical Tool Air, at which time the secondary bank will automatically take over and continue to feed the system. (At this point the pressure switch in the top left hand corner will open, signalling any remote monitor that empty cylinders require changing).
In the normal course of operation, the “Primary Bank” designation will alternate back and forth between left and right banks, if the operating instructions printed on the front panel are followed.
Safety Precautions: A shuttle valve is built into the tee just before the low pressure regulator, to ensure back pressure does not affect the high pressure regulators during operation. As one regulator is in use, the valve shuts off the opposite regulator from the feed back.
In addition, two pressure relief valves, in parallel, monitor the line pressure to ensure a regulator malfunction does not over-pressure the hospital pipeline system. These relief valves can be removed (cover removal necessary) one at a time for testing, if required. A self sealing valve will prevent loss of gas during removal.
Low Pressure Alarm: The pressure switch on the top right hand side of the central control panel is set to operate at a pressure approx. 25% lower than the set pipeline pressure and in turn will signal any remotely connected alarm panel.
Page 5 of 20
AUTOMATIC GAS MANIFOLDS
5. Service
1. 2.Every six (6) months the manifold system should be inspected / tested for leaks and malfunctions as follows:
For high usage manifolds, we suggest that all three (3) regulators be serviced on a twelve (12) monthly basis. Other manifold service intervals can be extended to suit use. As diaphragm and seat replacement require special tools and test equipment, it is recommended that for service, the entire three regulator unit be removed as a whole and replaced with a changeover unit available from ESCO Industries. (You are invoiced for the exchange unit and credited upon receipt of your used unit).
The part numbers for exchange regulator sets are as follows:
As a guide, usage rates can be qualified as follows:
a) AGM3RS-O-A-NO Automatic Gas Manifold Three Regulator Set - Oxygen, Air or Nitrous Oxide (4 Bar) b) AGM3RS-ST Automatic Gas Manifold Three Regulator Set - Surgical Tool Air (14 Bar)
Up to 4 “G” size cylinders per week. From 4 to 20 “G” size cylinders per week. More than 20 “G” size cylinders per week.
a) Low Usage: b) Medium Usage: c) High Usage:
Please phone Esco Industries for other outlet pressures and for current changeover prices on (02) 8799 3700.
a)
b) c)
d)
e)
Test regulators for external leaks and correct pressure reduction. Test all pipe connections for leaks. Test the system failure pressure switch (right hand switch) for correct setting and operation. Test non return valves in header block nipples for proper closure. Note: these valves do not seal completely. Inspect cylinder extension leads for flexibility, metal fatigue and thread damage at cylinder connections. Note: any damaged leads should be replaced immediately.
Page 6 of 20
AUTOMATIC GAS MANIFOLDS
m e d i c o n m e d i c o n m e d i c o n m e d i c o n m e d i c o n
Loading...
+ 14 hidden pages