Distributed by Danfoss in Nort h America
www.NA.Heating.Danfoss.com
SERIES CRA112
Setpoint Temperature Controller
Series CRA112
LVD 2006/95/EC
EMC 2004/108/EC
RoHS 2002/95/EEC
Ambient temp: 23°F to 131°F (-5°C to 55°C)
Flow temp. range: 41°F to 200°F (5°C to 95°C)
Power supply: 24 ± 10%, 60 Hz
Power consumption: 3VA
Max run time at max speed: 30 seconds
Weight: 2 lbs (0,9 kg)
Torque: 53.1 in.lbs (6 Nm)
Enclosure rating: NEMA 2 (IP41)
Mountable to ESBE 3MG, 4MG, Type G and VRG valves up to 2"
Temperature Sensor Installation
Mtrl.nr. 9814 09 32 Ritn.nr. 8419 utg. A • Rev. 1506
Selection Operation
Wrap the sensor
Start up
1. Set the required rotation
of the controller by pushing
24V
the rocker to the right for
clockwise opening or left for
A
— +
counter clockwise opening (A).
2. Keep the rocker in the
desired direction and connect
power (B).
3. Wait 2 seconds before
releasing the rocker ( C ), the
B
desired controller rotation
is now set.
C
Maximum Temperature Limitation
= MAX
4 seconds
Press and hold Press and holdPress Press
Minimum Temperature Limitation
T
°F
°
Max°F
Default: 120F (49C)
Maximum temperature
setting: 200F (95C)
t
Return to
Setpoint Display
4 seconds
MAX
OK
—
+
OK
20 seconds
Wait
Adjust
T
°F
Default: 41F (5C)
= MIN
°
Min °F
Minimum temperature
setting: 41F (5C)
t
Return to
4 seconds
Press and hold Scroll
—
+
OK
Press Adjust
—
+
OK
20 seconds
Wait
Press and hold
Setpoint Display
4 seconds