F-15-683
April, 2001
P/N-0558002693
-
P/N 0558002695
REGULATOR FLASH ARRESTORS
Includes: Flash Arrestor, Oxygen
Flash Arrestor Acetylene/Fuel Gas - P/N0558002694
Oxygen....................................................................................... 150 psig
Acetylene ..................................................................................... 15 psig
Other Fuel Gases......................................................................... 50 psig
Oxygen............................................................... CGA-022 (9/16-18 RH)
Acet/F.G .............................................................. CGA-023 (9/16-18 LH)
lator and tighten firmly with a wrench. DO NOT overtighten.
ening the hose nut firmly with the other wrench.
Instructions for
F-15-683
April, 2001
SPECIFICATIONS
P/N-0558002693
-
P/N 0558002695
Welding Capacity..................................................................................... 1-in.
Cutting Capacity .................................................................................... 12-in.
Maximum Inlet Pressure
Connections (female inlet: male outlet)
Assembly and Fitting Instructions
Designed to be fitted to oxygen and acet/fuel gas regulator outlets. Each con-
tains a sintered steel flame barrier and a spring-loaded reverse flow check valve.
In the event of a flashback, the barrier will stop the flame from reaching the
check valve and regulator. The check valve will prevent one gas from flowing
into the other regulator. A check valve alone will not stop a flashback.
INSTALLATION
1. Assemble appropriate flash arrestor to each outlet connection of the regu-
2. Connect the proper hose to each flash arrestor with one wrench while tight-
Instructions for
REGULATOR FLASH ARRESTORS
Includes: Flash Arrestor, Oxygen
Flash Arrestor Acetylene/Fuel Gas - P/N0558002694
SPECIFICATIONS
Welding Capacity..................................................................................... 1-in.
Cutting Capacity .................................................................................... 12-in.
Maximum Inlet Pressure
Oxygen....................................................................................... 150 psig
Acetylene ..................................................................................... 15 psig
Other Fuel Gases......................................................................... 50 psig
Oxygen............................................................... CGA-022 (9/16-18 RH)
Connections (female inlet: male outlet)
Acet/F.G .............................................................. CGA-023 (9/16-18 LH)
Assembly and Fitting Instructions
Designed to be fitted to oxygen and acet/fuel gas regulator outlets. Each con-
tains a sintered steel flame barrier and a spring-loaded reverse flow check valve.
In the event of a flashback, the barrier will stop the flame from reaching the
check valve and regulator. The check valve will prevent one gas from flowing
into the other regulator. A check valve alone will not stop a flashback.
INSTALLATION
1. Assemble appropriate flash arrestor to each outlet connection of the regu-
lator and tighten firmly with a wrench. DO NOT overtighten.
ening the hose nut firmly with the other wrench.
2. Connect the proper hose to each flash arrestor with one wrench while tight-

a flashback resulting in damage to equipment. If they appear clean, reconnect
the arrestor to the regulator.
discolored by heat, they should be replaced by new flash arrestors. Clogged
flash arrestors can cause excess pressure drop, overheating, and may not stop
examine inside each flash arrestor If they appear clogged with carbon soot or
MAINTENANCE
Every six months or after 50 flashbacks, whichever occurs first, remove and
For No.100 welding heads, increase pressure by 40%. Do not use flash arres-
tors when welding or heating larger than No.100. The combination of the arres-
tor and large heads can cause severe overheating and possible damage to the
equipment.
up through size No.70 and cutting tips to compensate for pressure drop through
the flash arrestor.
Increase recommended operating pressure by 20% when using welding heads
OPERATION
F-15-683 4/01F-15-683 4/01
a flashback resulting in damage to equipment. If they appear clean, reconnect
the arrestor to the regulator.
discolored by heat, they should be replaced by new flash arrestors. Clogged
flash arrestors can cause excess pressure drop, overheating, and may not stop
examine inside each flash arrestor If they appear clogged with carbon soot or
MAINTENANCE
Every six months or after 50 flashbacks, whichever occurs first, remove and
For No.100 welding heads, increase pressure by 40%. Do not use flash arres-
tors when welding or heating larger than No.100. The combination of the arres-
tor and large heads can cause severe overheating and possible damage to the
equipment.
up through size No.70 and cutting tips to compensate for pressure drop through
the flash arrestor.
Increase recommended operating pressure by 20% when using welding heads
OPERATION