As used throughout this manual: Means Attention! Be Alert!
DANGER!
Means immediate hazards which, if not avoided, will result in immediate, serious
personal injury or loss of life.
WARNING!
Means potential hazards which could result in personal injury or loss of life.
CAUTION!
Means hazards which could result in minor personal injury.
WARNING!
Before use, read and understand the instruction manual and follow
all labels, employer´s safety practices and Safety Data Sheets
(SDSs).
1.2Safety precautions
Users of ESAB equipment have the ultimate responsibility for ensuring that anyone who works on or
near the equipment observes all the relevant safety precautions. Safety precautions must meet the
requirements that apply to this type of equipment. The following recommendations should be observed
in addition to the standard regulations that apply to the workplace.
All work must be carried out by trained personnel well-acquainted with the operation of the equipment.
Incorrect operation of the equipment may lead to hazardous situations which can result in injury to the
operator and damage to the equipment.
1. Anyone who uses the equipment must be familiar with:
•its operation
•location of emergency stops
•its function
•relevant safety precautions
•welding and cutting or other applicable operation of the equipment
2. The operator must ensure that:
•no unauthorised person is stationed within the working area of the
equipment when it is started up
•no-one is unprotected when the arc is struck or work is started with the
equipment
•Always wear recommended personal safety equipment, such as safety
glasses, flame-proof clothing, safety gloves
•Do not wear loose-fitting items, such as scarves, bracelets, rings, etc.,
which could become trapped or cause burns
5. General precautions:
•Make sure the return cable is connected securely
•Work on high voltage equipment may only be carried out by a
qualified electrician
•Appropriate fire extinguishing equipment must be clearly marked and
close at hand
•Lubrication and maintenance must not be carried out on the equipment
during operation
WARNING!
Wire feeders are intended to be used with power sources in MIG/MAG mode only.
If used in any other welding mode, such as MMA, the welding cable between wire feeder and
power source must be disconnected, or else the wire feeder becomes live or energized.
If equipped with ESAB cooler
Use ESAB approved coolant only. Non-approved coolant might damage the equipment and jeopardize
product safety. In case of such damage, all warranty undertakings from ESAB cease to apply.
For ordering information, see the "ACCESSORIES" chapter in the instruction manual.
WARNING!
Arc welding and cutting can be injurious to yourself and others. Take precautions when
welding and cutting.
ELECTRIC SHOCK - Can kill
•Do not touch live electrical parts or electrodes with bare skin, wet gloves
or wet clothing
•Insulate yourself from work and ground.
•Ensure your working position is safe
ELECTRIC AND MAGNETIC FIELDS - Can be dangerous to health
•Welders having pacemakers should consult their physician before welding.
EMF may interfere with some pacemakers.
•Exposure to EMF may have other health effects which are unknown.
•Welders should use the following procedures to minimize exposure to
EMF:
○ Route the electrode and work cables together on the same side
of your body. Secure them with tape when possible. Do not
place your body between the torch and work cables. Never coil
the torch or work cable around your body. Keep welding power
source and cables as far away from your body as possible.
○ Connect the work cable to the workpiece as close as possible
to the area being welded.
0447 209 001
FUMES AND GASES - Can be dangerous to health
•Keep your head out of the fumes
•Use ventilation, extraction at the arc, or both, to take fumes and gases
away from your breathing zone and the general area
•Protect your eyes and body. Use the correct welding screen and filter lens
and wear protective clothing
•Protect bystanders with suitable screens or curtains
NOISE - Excessive noise can damage hearing
Protect your ears. Use earmuffs or other hearing protection.
MOVING PARTS - Can cause injuries
•Keep all doors, panels and covers closed and securely in place. Have only
qualified people remove covers for maintenance and troubleshooting as
necessary. Reinstall panels or covers and close doors when service is
finished and before starting engine.
•Stop engine before installing or connecting unit.
•Keep hands, hair, loose clothing and tools away from moving parts.
FIRE HAZARD
•Sparks (spatter) can cause fire. Make sure therefore that there are no
inflammable materials nearby
•Do not use on closed containers.
HOT SURFACE - Parts can burn
•Do not touch parts bare handed.
•Allow cooling period before working on equipment.
•To handle hot parts, use proper tools and/or insulated welding gloves to
prevent burns.
MALFUNCTION - Call for expert assistance in the event of malfunction.
PROTECT YOURSELF AND OTHERS!
CAUTION!
This product is solely intended for arc welding.
CAUTION!
Class A equipment is not intended for use in residential locations
where the electrical power is provided by the public low-voltage
supply system. There may be potential difficulties in ensuring
electromagnetic compatibility of class A equipment in those
locations, due to conducted as well as radiated disturbances.
NOTE!
Dispose of electronic equipment at the recycling facility!
In observance of European Directive 2012/19/EC on Waste
Electrical and Electronic Equipment and its implementation in
accordance with national law, electrical and/or electronic equipment
that has reached the end of its life must be disposed of at a
recycling facility.
As the person responsible for the equipment, it is your
responsibility to obtain information on approved collection stations.
For further information contact the nearest ESAB dealer.
CAUTION!
This equipment does not comply with IEC 61000-3-12:2011. If it is connected to a public low
voltage system, it is the responsibility of the installer or user of the equipment to ensure, by
consultation with the distribution network operator, that the equipment may be connected.
ESAB has an assortment of welding accessories and personal protection equipment for
purchase. For ordering information contact your local ESAB dealer or visit us on our website.
Minimum short circuit power on the network in accordance with IEC 61000-3-12.
Duty cycle
The duty cycle refers to the time as a percentage of a ten-minute period that you can weld or cut at a
certain load without overloading. The duty cycle is valid for 40°C/104°F, or below.
Enclosure class
The IP code indicates the enclosure class, i.e. the degree of protection against penetration by solid
objects or water.
Equipment marked IP21S is intended for indoor use.
Equipment marked IP23S is intended for indoor and may be used outdoors if sheltered during
precipitation.
Application class
The symbolindicates that the power source is suitable for welding in an environment with an
increased risk of electric shock.
The installation must be carried out by a professional.
CAUTION!
This product is intended for industrial use. In a domestic environment this product may cause
radio interference. It is the user's responsibility to take adequate precautions.
4.1Location
Position the power source so that its cooling air inlets and outlets are not obstructed.
A. Minimum 200 mm (8 in.)
B. Minimum 200 mm (8 in.)
WARNING!
Secure the equipment - particularly if the
ground is uneven or sloping.
Mechanical lifting must be done with both outer handles.
4.3Mains supply
NOTE!
Mains supply requirements
This equipment complies with IEC 61000-3-12 provided that the short-circuit power is greater
than or equal to S
It is the responsibility of the installer or user of the equipment to ensure, by consultation with
the distribution network operator if necessary, that the equipment is connected only to a supply
with a short-circuit power greater than or equal to S
TECHNICAL DATA chapter.
Make sure it is protected by the correct fuse rating. A protective earth connection must be made, in
accordance with regulations.
at the interface point between the user's supply and the public system.
The power source can be supplied from different types of generators. However, some generators may
not provide sufficient power for the welding power source to operate correctly. Generators with
Automatic Voltage Regulation (AVR) or with equivalent or better type of regulation, with rated power 30
kW, are recommended.
max
32A
32A
100m/330 ft.
2
4.5Connect with Cool 2 using adaptor
Make sure the power source is turned off.
1. Connect the Cool2 (0465 427 880) with the Cool2Adaptor (0447 248 001):
a. Pull the cable out of the cooling unit through the adaptor.
b. Set the adaptor on the cooling unit.
c. Connect the adaptor to the cooling unit by the provided M6×10 screws.
2. Connect the Cool2Adaptor to the FabricatorET410iP:
a. Remove the feet from the power source and install on the cooling unit.
General safety regulations for handling the equipment can be found in the "SAFETY" chapter
of this manual. Read it through before you start using the equipment!
NOTE!
When moving the equipment use intended handle. Never pull the cables.
WARNING!
Electric shock! Do not touch the workpiece or the welding head during operation!
5.1Connections and control devices
1. Setting panel6. Positive welding terminal
2. Gas valve (outlet)7. Mains cable
3. Connection for 2 pin torch8. Mains power supply switch, ON/OFF
4. Connection for remote control unit or
8pintorchconnector
5. Negative welding terminal
9. Gas valve (inlet)
5.2TIG welding
TIG welding melts the metal of the workpiece, using an arc initiated from a
non-consuming tungsten electrode. The weld pool and electrode are protected by a
shielding gas that usually consists of an inert gas.
For TIG welding, the welding power source shall be supplemented with:
MMA welding may also be referred to as welding with covered electrodes. The arc melts
the electrode as well as a local part of the workpiece. The coverage, when melting,
forms a protective slag and creates a shielding gas to protect the weld pool from
atmospheric contamination.
For MMA welding, the welding power source shall be supplemented with:
•welding cable with electrode holder
•return cable with clamp
5.4Connection of welding and return cables
The power source has two outputs, a positive welding terminal (+) and a negative welding terminal (-),
for connecting welding and return cables. The output to which the welding cable is connected depends
on the welding method or type of electrode used.
Connect the return cable to the other output on the power source. Secure the return cable's contact
clamp to the work piece and ensure that there is good contact between the work piece and the output
for the return cable on the power source.
•For TIG welding, the negative welding terminal (-) is used for the welding torch and
the positive welding terminal (+) is used for the return cable.
•For MMA welding, the welding cable can be connected to the positive welding
terminal (+) or negative welding terminal (-) depending on the type of electrode used.
The connecting polarity is stated on the electrode packaging.
5.5Turning the mains power ON/OFF
Turn ON the mains power by turning the switch to the ”ON”.
Turn the unit OFF by turning the switch to the ”OFF” position.
Regardless the mains supply is interrupted abnormally, or the power source is switched off in the
normal manner, the welding data will be stored, so it will be available next time the unit is turned ON.
CAUTION!
Do not turn OFF the power source during welding (with load).
5.6Fan control and Cool 2
The power source has an automatic thermal control. When turning ON the main power switch, the fan
will run for 10 seconds and then stop. Once welding start, the fan continues to run for a few minutes
after welding has stopped while the power source switches to energy-saving mode. The fan starts
again when welding restarts. When Cool 2 is connected to the power source, Cool 2 will be synced
with the fan.
5.7Thermal protection
The power source includes thermal protection against overheating. When temperature is
up to 80% limitation, the overheating indicator on the panel will blink; once temperature
exceeds the limitation, the welding is stopped and overheating indicator will be lit and an
error message shows in the display. The protection is automatically reset when the
temperature has been sufficiently reduced.
The VRD function ensures that the open-circuit voltage does not exceed 15V when
welding is not being carried out. This is indicated by a lit VRD indicator on the panel.
Default setting for VRD is ON. When VRD function is on, the green led is lit, when VRD
is off the red led is lit. VRD switch S1 is on the control PCB. It can be turned off by
switching it to off position.
5.9Remote control
Connect the remote control on the front panel of the power source and activate the
remote control by pressing the remote control button on the panel (remote control
indicator being lit when activated). When the remote control is activated, the welding
current is controlled by remote device.
In DC TIG mode the minimum remote current is set by initial current and the maximum
remote current is limited by local set current. For example, in local mode set the "initial
current" to 50A and set the "set current" to 200A then switch to remote mode. The
current range in remote mode is changed from 50A to 200A. The initial current
(minimum current in remote mode) can be set on local mode and remote mode, but the
set current (maximum current in remote mode) only can be set in local mode.
In Pulse TIG mode, the ratio between background and set current is the same as local
mode, for example, if in local mode, the background current is set to 50A, the set
current is set to 100A, and the ratio is 0.5, if adjusting the set current or background
current in remote mode, the ratio will keep the same. By adjusting either of them, the
other one will change accordingly.
5.10Memory
Ten weld programs can be saved in the memory from Pr0 to Pr9.
To active the memory function, press the memory button (9) and Pr0 will be displayed.
To change memory channel, rotate the control knob (11). Press save button (8) longer
than 2 seconds, until the display shows: ---. All the settings of current welding process
are saved into this channel, then exits the memory function.
To load a welding process which was saved previously, press memory button (9) to
active memory function and Pr0 will be displayed. To change memory channel, rotate
the control knob (11). Select the channel you want to load, press the load button (8)
shortly, it will load previously saved settings. If this channel did not have any settings
before, the display shows: ---, and no settings will be loaded.
To exit memory function, press the memory button (9) shortly.
1. VRD OFF indicator.17. High frequency arc start mode selection button
and indicator. It is used to select
highfrequency arc start mode or
LiftTIGmode.
2. VRD ON indicator.18. 2T/4T/4TS/Spot mode selection button. Press
to select 2T, 4T, 4TS or Spot mode (TIG only).
3. Power ON indicator.19. Welding process selection button. Press to
select DCTIG, pulse TIG or MMA.
4. Fault indicator. It shows over temperature.20. Gas post flow indicator.
5. Display. It shows set or measured value and
error codes.
6. Local control indicator. When it is lit the current
is controlled by the control knob.
7. Remote control indicator. When it is lit, the
current is controlled by the remote device.
8. Gas purge/load/save button and indicator. In
DCTIG and PulseTIG modes, press for gas
purge. In memory mode, press once for
loading memory and press longer for saving to
memory.
9. Memory button. Press to load or save process. 25. Background current indicator.
10. Forward button. Press to select the adjustable
parameter.
11. Control knob. Press to set data.27. Slope up indicator.
12. Set indicator. When is it lit, the value can be
adjusted with the control knob.
13. A/V/Backward button. Press to select current
or voltage displayed on the display when
welding. In setting mode (indicator 13 is lit),
press to selectthe adjustable parameter
backward.
14. S/%/Hz indicator.30. Arc force indicator.
15. Voltage indicator.31. Start pulse indicator.
16. Amplifier indicator.32. Gas pre flow indicator.
21. Final current indicator.
22. Slope down indicator.
23. Pulse Hz indicator.
24. Duty of pulse indicator.
26. Set current indicator.
28. Spot time indicator.
29. Initial current.
6.1.1Navigation
Parameter selection
By pressing the button (10) different values can be shown and changed. Use the knob (11) to change
the values.
Set parameter
The set indicator (13) will be lit when a displayed value can be changed. Trying to change a value
while in measured value mode will result in automatically move to set current value mode.
The set indicator (13) is off when measured values are shown.
Weld parameters
The weld parameters are stored for pulse and no pulse respectively. The values are changed when
changing between pulse and no pulse.
The HF ON function initiates the arc by using a high frequency voltage pilot arc. This will reduce the
risk of tungsten contamination in the starts. The high frequency voltage might disturb other electrical
equipment in the surrounding area.
HF OFF
When HF is set to OFF, it initiates the arc when the tungsten electrode is brought into contact with the
workpiece, the trigger switch is pressed, and the tungsten electrode is lifted away from the workpiece.
In order to minimize the risk of tungsten contaminations, the start current is limited to 25A, and will
slope to the set current.
2T NORMAL/DC TIG
In 2T normal DC TIG mode, press the TIG torch trigger switch (1) to start the shielding gas flow and
initiate the arc. The current goes to start pulse for 20 ms, then goes to initial current, then slopes up to
set current. Release the trigger switch (2) to start to slope down the current and terminate the arc. The
shielding gas will continue to flow in order to protect the weld and the tungsten electrode.
4T LATCH/DC TIG
In 4T latch/ DC TIG mode, press the TIG torch trigger switch (1) to start the shielding gas flow and
initiate the arc. The current goes to start pulse for 20ms, then goes to initial current. Release the
trigger switch (2) to slope up the current to set current value. To stop the welding, press the trigger
switch again (3), the current will slope down to the final current. Release the trigger switch (4) to
terminate the arc. The shielding gas will continue to flow in order to protect the weld and the tungsten
electrode.
In 2T normal pulse TIG mode, press the TIG torch trigger switch (1) to start the shielding gas flow and
initiate the arc. The current goes to start pulse for 20ms then goes to initial current, then slopes up to
set current, the current changs between set current and background current. Release the trigger
switch (2) to start to slope down the current and terminate the arc. The shielding gas will continue to
flow in order to protect the weld and the tungsten electrode.
4T LATCH/PULSE TIG
In 4T latch/PULSE TIG mode, press the TIG torch trigger switch (1) to start the shielding gas flow and
initiate the arc. The current goes to start pulse for 20ms then goes to initial current. Release the
trigger switch (2) to slope up the current to set current value. The current changes between set current
and background current. To stop the welding, press the trigger switch again (3), the current will slope
down to the final current. Release the trigger switch (4) to terminate the arc. The shielding gas will
continue to flow in order to protect the weld and terminate the arc.
4TS/PULSE TIG
In 4TS/PULSE TIG mode, 4TS mode is a special 4T mode. Press the TIG torch trigger switch (1) to
start the shielding gas flow and initiate the arc. The current goes to start pulse for 20ms then goes to
initial current. Release the trigger switch (2) to slope up the current to set current value. Press the
switch (3) for less than 0.5 s and release, the current switches from set current to background current.
Press the switch less than (4) for 0.5 s and release, the current switches from background current to
set current. Press the switch less than (5) for 0.5 s and release, the current switches from set current
to background current. Press the switch less than (6) for 0.5 s and release, the current switches from
background current to set current. Press the switch (7) for more than 0.5 s, the current slopes down to
final current and keeps the current at final current as long as the trigger pressed. Release the trigger
switch (8) again to terminate the arc. The shielding gas will continue to flow in order to protect the weld
and tungsten electrode.
In SPOT/DC TIG mode, press the TIG torch trigger switch (1) to start the shielding gas flow and initiate
the arc. The current goes to start pulse for 20ms then goes to set current. Keep pressing the trigger
switch, the machine will terminate the arc automatically according to the spot time setting time. The
shielding gas will continue to flow in order to protect the weld and the tungsten electrode.
SPOT/PULSE TIG
In SPOT/PULSE TIG mode, press the TIG torch trigger switch (1) to start the shielding gas flow and
initiate the arc. The current goes to start pulse for 20ms then goes to set current. The current change
between set current and background current. Keep pressing the trigger switch, the machine will
terminate the arc automatically according to the spot time setting time. The shielding gas will continue
to flow in order to protect the weld and the tungsten electrode.
Gas pre flow
The gas pre flow function controls the time during which shielding gas flows before the arc is initiated.
Gas post flow
The gas post flow function controls the time during which shielding gas flows after the arc is
terminated.
Initial current
It is used to set the start current for TIG, or minimum current range in DC TIG remote mode.
Slope up
The slope up function is used to control the time of the current increase in the weld initiation process
to avoid any possible damage to the tungsten electrode.
Slope down
The slope down function is used to control the time of the current decrease in the weld termination
process to avoid any pipes and/or cracks.
Pulse TIG
In order to set a pulsed current, four parameters are required: set current, background current, pulse
duty cycle and pulse frequency.
Set current
The higher of the two current values when using a pulsed current or the maximum current range in DC
TIG remote mode.
Background current
The lower of the two current values when using a pulsed current.
% Pulse is the ratio between set current and background current in a pulse cycle. In
order to control the energy of the arc and the size of the weld pool, pulse duty cycle is
adjustable by setting the percentage of the set current in a pulse cycle.
For example: If the pulse duty cycle is set to 50%, the time of the set current and the
background current will be distributed equally in the pulse cycle. If the pulse duty
cycle is set to 90%, the time of the set current will be 90% of the pulse cycle and the
background current will only be 10%.
Pulse frequency
The amount of pulse cycles in a time period. The higher the frequency, the more
pulse cycles per time period. When the pulse frequency is set low, the weld pool will
have time to partially solidify between each pulse. If the frequency is set high, a more
focused arc can be obtained.
Remote current
This is used to set the current for the foot pedal or remote control device.
In DC TIG mode, the minimum remote current is set by initial current and the maximum remote current
is limited by local set current. For example, in local mode set the "initial current" to 50A and set the
"set current" to 200 A then switch to remote mode. The current range in remote mode is set from 50A
to 200A. the initial current (minimum current in remote mode) can be set on local mode and remote
mode but the set current (maximum current in remote mode) only can be set in local mode.
In Pulse TIG mode, the ratio between background and set current are the same as in local mode. For
example, if in local mode, the background current is set to 50A, the set current is set to 100A, and the
ratio is 0.5. Adjusting the set current or background current in remote mode, the ratio will keep the
same. By adjusting either of them, the other one will change accordingly.
6.4MMA settings
IndicatorFunctionSetting rangeSetting stepDefault value
Set currentSet current (A)30-4101100
Arc forceArc force (%)0-100% of set
current
Start pulseStart pulse current
(A)
0-100130
6.4.1Measured values
Measured current
Measured value in the display for welding current A is arithmetic average value.
130
0447 209 001
Measured voltage
Measured value in the display for arc voltage V is arithmetic average value.
The arc force function determines how the current changes in response to variations in arc length
during welding. Use a low value of arc force to get a calm arc with little spatter and use a high value to
get a hot and digging arc.
Arc force only applies to MMA welding.
START PULSE
The start pulse (similar to hot start) function temporarily increases the current in the beginning of the
weld, thus reducing the risk of lack of fusion in the starting point.
The mains supply must be disconnected during cleaning and maintenance.
CAUTION!
Only persons with the appropriate electrical knowledge (authorised personnel) may remove
the safety plates.
CAUTION!
The product is covered by manufacturer's warranty. Any attempt to carry out repair work by
non-authorised service centers or personnel will invalidate the warranty.
NOTE!
Regular maintenance is important for safe and reliable operation.
NOTE!
Perform maintenance more often during severe dusty conditions.
Before each use - make sure that:
•Product and cables are not damaged,
•The torch is clean and not damaged.
7.1Routine maintenance
Maintenance schedule during normal conditions. Check equipment prior to every use.
The error code is used to indicate that a fault has occurred in the equipment. Errors are indicated by
the text "E-" followed by the error code number shown in the display.
If several errors have been detected only the code for the last occurring error is displayed.
Error codes that the user can handle are listed below. If any other error code appears, contact an
authorised ESAB service technician.
E-0
The power supply to the power source loses any phase. One phase is lost during 3-phase operation.
1.Make sure the power supply is stable, all leads are connected, that the mains voltage (all 3
E-1
The power supply to the power source is too high voltage (more than 480 V).
1.Make sure the power supply is stable, and the input voltage is in the range of 320V-480V.
E-2
The power supply to the power source is too low voltage (less than 320 V).
1.Make sure the power supply is stable, and the input voltage is in the range of 320V-480V.
E-3
The temperature of the power source is too high. A LED indicating temperature fault is also lit on the
panel. A temperature fault is indicated by the overheating indicator on the control panel.
Power supply phase loss protection
phases) are OK and restart the system. If the error persists, contact a service technician.
Over voltage protection
Under voltage protection
Temperature fault
1.The error code will automatically disappear and the LED indicating temperature fault will be
turned off when the power source has cooled down and it is ready for use again. If the error
persists, contact a service technician.
Repair and electrical work should be performed by an authorised ESAB service technician.
Use only ESAB original spare and wear parts.
The FabricatorET410iP is designed and tested in accordance with the international IEC 60974-1.
On completion of service or repair work, it is the responsibility of the person(s) performing the work to
ensure that the product still complies with the requirements of the above standards.
Spare parts and wear parts can be ordered through your nearest ESAB dealer, see esab.com. When
ordering, please state product type, serial number, designation and spare part number in accordance
with the spare parts list. This facilitates dispatch and ensures correct delivery.