ESAB Fabricator EM 401i, Fabricator EM 501i Instruction manual

Page 1
Fabricator EM 401i, Fabricator EM 501i
Instruction manual
0446 455 101  GB  20220303
Valid for: Serial number: from OP110YY-,
OP210YY-XXXXXX
Page 2
Page 3

TABLE OF CONTENTS

1 SAFETY
1.1 Meaning of symbols
1.2 Safety precautions
2 INTRODUCTION
2.1 Equipment
3 TECHNICAL DATA
4 INSTALLATION
4.1 Location
......................................................................................................................................
....................................................................................................
......................................................................................................
.........................................................................................................................
....................................................................................................................
.....................................................................................................................
...........................................................................................................................
........................................................................................................................
4.2 Feeder mounting bracket instructions
4.3 Lifting instructions
4.4 Mains supply
5 OPERATION
...............................................................................................................................
......................................................................................................
................................................................................................................
5.1 Connections and control devices
5.2 Welding control mode
.................................................................................................
5.3 Connection of welding and return cable
5.4 Symbols and functions
5.5 Thermal protection
5.6 Fan control
...................................................................................................................
5.7 Usage of the cooling unit
5.8 Coolant connection
...............................................................................................
......................................................................................................
............................................................................................
....................................................................................................
5.9 Coolant pressure controller
6 MAINTENANCE
6.1 Maintenance
6.2 Routine maintenance
6.3 Power source
6.4 Cooling unit
6.5 Filling the coolant
7 TROUBLESHOOTING
8 ORDERING SPARE PARTS
ORDERING NUMBERS
BLOCK DIAGRAM
ACCESSORIES
..........................................................................................................................
.................................................................................................................
..................................................................................................
...............................................................................................................
..................................................................................................................
........................................................................................................
................................................................................................................
.......................................................................................................
.........................................................................................................................
.................................................................................................................................
.....................................................................................................................................
......................................................................
..............................................................................
...................................................................
......................................................................................
4
4
4
7
7
8
11
11
11
12
13
15
15
18
20
21
21
21
22
22
22
23
23
23
23
25
25
27
30
31
32
33
0446 455 101
© ESAB AB 2022
Page 4
1  SAFETY

1 SAFETY

1.1 Meaning of symbols

As used throughout this manual: Means Attention! Be Alert!
DANGER! Means immediate hazards which, if not avoided, will result in immediate, serious personal injury or loss of life.
WARNING! Means potential hazards which could result in personal injury or loss of life.
CAUTION! Means hazards which could result in minor personal injury.
WARNING!
Before use, read and understand the instruction manual and follow all labels, employer´s safety practices and Safety Data Sheets (SDSs).

1.2 Safety precautions

Users of ESAB equipment have the ultimate responsibility for ensuring that anyone who works on or near the equipment observes all the relevant safety precautions. Safety precautions must meet the requirements that apply to this type of equipment. The following recommendations should be observed in addition to the standard regulations that apply to the workplace.
All work must be carried out by trained personnel well-acquainted with the operation of the equipment. Incorrect operation of the equipment may lead to hazardous situations which can result in injury to the operator and damage to the equipment.
1 Anyone who uses the equipment must be familiar with:
its operation
location of emergency stops
its function
relevant safety precautions
welding and cutting or other applicable operation of the equipment
2 The operator must ensure that:
no unauthorised person is stationed within the working area of the equipment when it is started up
no-one is unprotected when the arc is struck or work is started with the equipment
3 The workplace must:
be suitable for the purpose
be free from drafts
4 Personal safety equipment:
Always wear recommended personal safety equipment, such as safety glasses, flame-proof clothing, safety gloves
Do not wear loose-fitting items, such as scarves, bracelets, rings, etc., which could become trapped or cause burns
5 General precautions:
Make sure the return cable is connected securely
Work on high voltage equipment may only be carried out by a
qualified electrician
0446 455 101
© ESAB AB 2022
Page 5
1  SAFETY
Appropriate fire extinguishing equipment must be clearly marked and close at hand
Lubrication and maintenance must not be carried out on the equipment during operation
If equipped with ESAB cooler
Use ESAB approved coolant only. Non-approved coolant might damage the equipment and jeopardize product safety. In case of such damage, all warranty undertakings from ESAB cease to apply.
For ordering information, see the "ACCESSORIES" chapter in the instruction manual.
WARNING!
Arc welding and cutting can be injurious to yourself and others. Take precautions when welding and cutting.
ELECTRIC SHOCK - Can kill
Do not touch live electrical parts or electrodes with bare skin, wet gloves or wet clothing
Insulate yourself from work and ground.
Ensure your working position is safe
ELECTRIC AND MAGNETIC FIELDS - Can be dangerous to health
Welders having pacemakers should consult their physician before welding. EMF may interfere with some pacemakers.
Exposure to EMF may have other health effects which are unknown.
Welders should use the following procedures to minimize exposure to EMF: ○ Route the electrode and work cables together on the same side
of your body. Secure them with tape when possible. Do not place your body between the torch and work cables. Never coil the torch or work cable around your body. Keep welding power source and cables as far away from your body as possible.
○ Connect the work cable to the workpiece as close as possible
to the area being welded.
FUMES AND GASES - Can be dangerous to health
Keep your head out of the fumes
Use ventilation, extraction at the arc, or both, to take fumes and gases away from your breathing zone and the general area
ARC RAYS - Can injure eyes and burn skin
Protect your eyes and body. Use the correct welding screen and filter lens and wear protective clothing
Protect bystanders with suitable screens or curtains
0446 455 101
NOISE - Excessive noise can damage hearing
Protect your ears. Use earmuffs or other hearing protection.
© ESAB AB 2022
Page 6
1  SAFETY
MOVING PARTS - Can cause injuries
Keep all doors, panels and covers closed and securely in place. Have only qualified people remove covers for maintenance and troubleshooting as necessary. Reinstall panels or covers and close doors when service is finished and before starting engine.
Stop engine before installing or connecting unit.
Keep hands, hair, loose clothing and tools away from moving parts.
FIRE HAZARD
Sparks (spatter) can cause fire. Make sure therefore that there are no inflammable materials nearby
Do not use on closed containers.
HOT SURFACE - Parts can burn
Do not touch parts bare handed.
Allow cooling period before working on equipment.
To handle hot parts, use proper tools and/or insulated welding gloves to prevent burns.
MALFUNCTION - Call for expert assistance in the event of malfunction.
PROTECT YOURSELF AND OTHERS!
CAUTION!
This product is solely intended for arc welding.
CAUTION!
Class A equipment is not intended for use in residential locations where the electrical power is provided by the public low-voltage supply system. There may be potential difficulties in ensuring electromagnetic compatibility of class A equipment in those locations, due to conducted as well as radiated disturbances.
NOTE! Dispose of electronic equipment at the recycling facility!
In observance of European Directive 2012/19/EC on Waste Electrical and Electronic Equipment and its implementation in accordance with national law, electrical and/or electronic equipment that has reached the end of its life must be disposed of at a recycling facility.
As the person responsible for the equipment, it is your responsibility to obtain information on approved collection stations.
For further information contact the nearest ESAB dealer.
ESAB has an assortment of welding accessories and personal protection equipment for purchase. For ordering information contact your local ESAB dealer or visit us on our website.
0446 455 101
© ESAB AB 2022
Page 7
2  INTRODUCTION

2 INTRODUCTION

The Fabricator EM 401i and Fabricator EM 501i are welding power sources intended for MIG/MAG welding, welding with powder filled cored wire (FCAW-S) and welding with coated electrodes (MMA). The power sources are intended for use with the following wire feed units:
Fabricator Feed 304
Fabricator Feed 304w
EM 401i is available with and without built-in cooling unit.
EM 501i is available only with built-in cooling unit.
ESAB accessories for the product can be found in the "ACCESSORIES" chapter of this manual.

2.1 Equipment

The power source is supplied with:
5m (16ft) return cable with earth clamp
5m (16ft) mains cable
Instruction manual
Quick start guide
Safety instruction
0446 455 101
© ESAB AB 2022
Page 8
3  TECHNICAL DATA

3 TECHNICAL DATA

FabricatorEM 401i / EM 401i with cooling unit
Mains voltage 380-415V ±10%, 50/60Hz
Mains supply S
Primary current I
scmin
max
1.9MVA
380V 400V 415V
MIG/MAG 28 A 27A 25A
MMA 29 A 28A 26A
Setting range (DC)
MIG/MAG 30A/15.5V-400A/34.0V
MMA 30A/21.2 V-400A/36.0V
Permissible load at MIG/MAG
60% duty cycle 400 A/34.0 V
100% duty cycle 310 A/29.5 V
Permissible load at MMA
60% duty cycle 400 A/36.0 V
100% duty cycle 310 A/32.4 V
Power factor at maximum current 0.91
Maximum input power at idle mode <35 W
Efficiency at maximum current 86%
Open-circuit voltage 65.0V
Recommended wire 0.8 -1.2 mm
Operating temperature -10 to +40°C (14 to 104 °F)
Transportation temperature -40 to +70 °C (-40 to 158 °F)
Dimensions l × w × h 1035×500×1015mm (40.7×19.6×39.9in.)
Weight
Weight without cooling unit 102.0 kg (225 lbs)
Weight with cooling unit without coolant 107.5 kg (237 lbs)
Weight with cooling unit with coolant 111.5 kg (246 lbs)
Insulation class H
Enclosure class IP 23
Application class
FabricatorEM 501i with cooling unit
Mains voltage 380-415V ±10%, 50/60Hz
Mains supply S
Primary current I
scmin
max
6.2MVA
380V 400V 415V
MIG/MAG 39 A 37A 36A
MMA 41 A 38A 37A
Setting range (DC)
0446 455 101
© ESAB AB 2022
Page 9
3  TECHNICAL DATA
FabricatorEM 501i with cooling unit
MIG/MAG 30A/15.5V-500A/39.0V
MMA 30A/21.2 V-500A/40.0V
Permissible load at MIG/MAG
60% duty cycle 500 A/39.0 V
100% duty cycle 390 A/33.5 V
Permissible load at MMA
60% duty cycle 500 A/40.0 V
100% duty cycle 390 A/35.6 V
Power factor at maximum current 0.91
Maximum input power at idle mode <35W
Efficiency at maximum current 87%
Open-circuit voltage 78.0V
Recommended wire 1.0-1.6 mm
Operating temperature -10 to +40°C (14 to 104 °F)
Transportation temperature -40 to +70 °C (-40 to 158 °F)
Dimensions l × w × h 1035×500×1015mm (40.7×19.6×39.9in.)
Weight
Weight with cooling unit without coolant 111.5 kg (246 lbs)
Weight with cooling unit with coolant 115.5 kg (255 lbs)
Insulation class H
Enclosure class IP 23
Application class
Cooling unit (500A - 60% duty cycle) Only for power sources with cooling units
Cooling power 1 kW at 25°C ambient temperature
Coolant ESABs ready mixed coolant
Coolant quantity 4.5 l
Maximum water flow 1.8 l/min
Maximum pressure lift for torch Q
Mains supply, S
sc min
max
66.7 PSI (4.6 bar)
Minimum short circuit power on the network in accordance with IEC 61000-3-12.
Duty cycle
The duty cycle refers to the time as a percentage of a ten-minute period that you can weld or cut at a certain load without overloading. The duty cycle is valid for 40°C/104°F, or below.
Enclosure class
The IP code indicates the enclosure class, i.e. the degree of protection against penetration by solid objects or water.
Equipment marked IP23 is intended for indoor and outdoor use.
0446 455 101
© ESAB AB 2022
Page 10
3  TECHNICAL DATA
Application class
The symbol indicates that the power source is designed for use in areas with increased electrical hazard.
0446 455 101
- 10 -
© ESAB AB 2022
Page 11
4  INSTALLATION

4 INSTALLATION

The installation must be carried out by a professional.
CAUTION!
This product is intended for industrial use. In a domestic environment this product may cause radio interference. It is the user's responsibility to take adequate precautions.

4.1 Location

Position the power source so that cooling air inlets and outlets are not obstructed.

4.2 Feeder mounting bracket instructions

WARNING!
Do not operate the equipment without the feeder mounting bracket.
0446 455 101
- 11 -
© ESAB AB 2022
Page 12
4  INSTALLATION

4.3 Lifting instructions

WARNING!
Secure the equipment - particularly if the ground is uneven or sloping.
0446 455 101
- 12 -
© ESAB AB 2022
Page 13
4  INSTALLATION

4.4 Mains supply

NOTE!
This equipment does not comply with IEC 61000-3-12. If it is connected to a public low voltage system, it is the responsibility of installer or the user of the equipment to ensure, by consultation with the distribution network if necessary, that the equipment may be connected.
Make sure that the welding power source is connected to the correct supply voltage and that it is protected by the correct fuse rating. A protective earth connection must be made in accordance with regulations.
The power source will automatically adjust to the supplied input voltage.
Recommended MCB sizes and minimum cable area
Fabricator EM 401i / EM 401i with cooling unit
Mains voltage 380V 3~50/60Hz 400V3~ 50/60Hz 415V3~ 50/60Hz
Mains cable area 4×6 mm
2
4×6 mm
2
4×6 mm
2
Maximal current rating I
I
1eff
max
29A 28A 26A
MIG/MAG 21A 20A 19A
MMA 22A 21A 20A
Input protection device (distribution box) Miniature circuit
Type Cand32A
breaker (MCB)
Fabricator EM 501i with cooling unit
Mains voltage 380V3~ 50/60Hz 400V3~ 50/60Hz 415V3~ 50/60Hz
Mains cable area 4×6mm
Maximal current rating I
I
1eff
max
41A 38A 38A
2
4×6mm
2
4×6mm
2
MIG/MAG 30A 28A 27A
MMA 31A 29A 28A
Input protection device (distribution box) Miniature circuit
TypeCand32A
breaker (MCB)
NOTE!
The mains cable areas and fuse sizes as shown above are in accordance with Swedish regulations. For other regions, supply cables must be suitable for the application and meet local and national regulations.
Supply from power generators
The power source can be supplied from different types of generators. However, some generators may not provide sufficient power for the welding power source to operate correctly. Generators with Automatic Voltage Regulation (AVR) or with equivalent or better type of regulation, with rated power ≥40 kW, are recommended.
0446 455 101
- 13 -
© ESAB AB 2022
Page 14
4  INSTALLATION
Connection instruction
WARNING!
The mains supply must be disconnected during installation.
WARNING!
Wait until the DC bus capacitors are discharged. The DC bus capacitor discharge time is at least 2 minutes!
If the mains cable needs to be changed, the earth connection to the bottom plate and the ferrites must be installed correctly. See the picture below for the installation order of the ferrites, washers, nuts and screws.
0446 455 101
- 14 -
© ESAB AB 2022
Page 15
5  OPERATION

5 OPERATION

General safety regulations for handling the equipment can be found in the "SAFETY" chapter of this manual. Read it through before you start using the equipment!
NOTE!
When moving the equipment use intended handle. Never pull the cables.
WARNING!
Electric shock! Do not touch the workpiece or the welding head during operation!

5.1 Connections and control devices

1 Connection (+): MIG/MAG: Welding cable,
MMA: Welding cable or return cable
2 Connection (-): MIG/MAG: Return cable, MMA:
Return cable or welding cable 3 Indicating LED, Overheating 10 Coolant filling 4 Connection of wire feed unit 11 Min/Max of coolant 5 Fuse for the gas regulator input supply 12 Connection RED for coolant (return) to cooling
6 Mains power supply switch, ON/OFF 13 Connection BLUE for coolant from cooling unit 7 Mains cable inlet
WARNING!
Do not use DC- in MIG mode, if DC- needed, please contact authorised ESAB local service.
0446 455 101
8 24 V AC power supply socket for gas regulator
9 Cooling unit mains switch ON/OFF
unit
- 15 -
© ESAB AB 2022
Page 16
5  OPERATION
The following figure shows the front control panel and the buttons on the control panel of the welder.
S.no. Name Function
1 Ending arc current Adjusts the Ending arc current in 4T and 4T repeat mode
2 Ending arc voltage Adjusts the Ending arc voltage in 4T and 4T repeat mode
3 Arc force The arc force is important in determining how the current changes in
response to a change in the arc length. A lower value gives a calmer arc with less spatter. It only applies to MMA welding.
4 Inductance Sets the dynamic of arc. Lower inductance will give hard arc and higher
inductance will give soft arc.
5 Wire diameter Selects the diameter of the welding wire. Only applicable for MIG
welding
6 Welding process /
Wire type and gas
Selects the welding process
Solid wire-CO2, (MIG/MAG)
Solid-Mix gas, (MIG/MAG)
Cored wire (MIG/MAG)
MMA welding
If MMA mode to be selected, press and hold for 2 seconds. To come out from MMA mode again press once.
NOTE!
Gas options are only for solid wires and not for cored wires.
7 Welding control Selects the welding control mode (2T, 4T, 4T repeat).
See chapter "5.3 Welding control mode".
0446 455 101
- 16 -
© ESAB AB 2022
Page 17
5  OPERATION
S.no. Name Function
8 Gas detection Detects gas flow.
9 Value adjusting
knob
Manually adjusts
the current for MMA process
the ending arc voltage, ending arc current, Inductance for MIG/MAG process and
the current and voltage within specified ranges.
Internal menu feature
1 Press the arc current and arc voltage buttons (see items 1 and 2 in the "Connections
and control devices" chapter) at the same time for 3 seconds to enter the internal menu and press the arc current and arc voltage buttons at the same time to exit the internal menu settings.
2 In the internal menu setting, use the knob on the panel to switch between menu
options at the same level and adjust parameter values.
3 In the internal menu setting, the inductance button on the panel is used as the
parameter selection confirmation button.
4 When setting each parameter in the internal menu, when the digital display shows
"OFF", the current parameter is the default parameter of the welding power source, and when the digital display shows other values, it is the user setting parameter.
Code Description Default Range Internal Menu Explanation
F01 Restore factory
settings
F02 Given wire feeding
SPd
speed
Slow wire feeding
F10
speed
(Creep start) m/min
F11 Pre-gas time
OFF 1.4–18
OFF
0–25s MIG/MAG: Gas delivery time before
MIG/MAG: The wire feed speed before the welding arc ignites or before the filler wire comes in contact with the workpiece
arc starts
F14 Post-gas time OFF 0–25s MIG/MAG: Gas delivery time after
arc ends
F20 DC burn back
voltage
OFF 12–45V MIG/MAG: The voltage at the end
of welding, to melt a part of wire at the tip to prevent the wire from sticking to the workpiece
F21 DC burn back time OFF 0 – 1.00 s MIG/MAG: Time for DC burn back
voltage. Longer time will lead to melt the contact tip
F22 DC chopping time OFF 0–1.00s MIG/MAG: The function is to
prevent obvious small balls at the end of the wire after welding and improve the success rate of arc starting next time. This parameter is used in conjunction with burn-back voltage and burn-back time
0446 455 101
- 17 -
© ESAB AB 2022
Page 18
5  OPERATION
Code Description Default Range Internal Menu Explanation
F25 Arc Start voltage OFF 12–38V(EM401i)
12–45V(EM501i)
F26 Arc Start current OFF 30–400A (EM401i)
30–500A (EM501i)
F27 Arc Start time OFF 0–10.0s MIG/MAG: The duration of arc-start
F50 Arc Striking current OFF 30–400A (EM401i)
30–500A (EM501i)
F51 Hot Start current OFF 0–100A MMAW: Additional current during
FB0 Board software
and hardware version query
FB1 Fault record query Err – For service purpose
FB2 Machine model
query
–
C50 For service purpose
010 – 104
110 – 102
210 – 103
300 – 201
MIG/MAG: Higher arc-start current and arc-start voltage to improve the arc-start fusion effect.
current and arc-start voltage.
MMAW: Current at the moment when electrode contacts base metal
arc start, based on the given welding current.
For service purpose

5.2 Welding control mode

2-stroke
With 2-stroke, gas pre-flow starts when the welding torch trigger switch is pressed. The welding process then starts. Releasing the trigger switch stops welding entirely and starts gas post-flow.
4-stroke
With 4 stroke, the gas pre-flow starts when the welding torch trigger switch is pressed in and the wire feed starts when it is released. The welding process continues until the switch is pressed in again, the wire feed then stops and when the switch is released the gas post-flow starts.
4-stroke repeat
When the torch trigger switch is pressed in, the gas flow starts and an arc is generated. When the trigger switch is released the arc generation is locked. When the trigger switch is pressed in again, the ending arc is generated using the ending arc voltage and current. When the switch is released again, the welding stops. When the trigger switch is pressed in again within two seconds and holding it, welding with repeated ending arc starts. When the switch is released the repeated ending arc stops. If the switch is not pressed in again within 2 seconds, the welding with repeated ending arc stops.
0446 455 101
- 18 -
© ESAB AB 2022
Page 19
5  OPERATION
2-stroke mode (welding without ending arc)
4-stroke mode (welding with ending arc)
0446 455 101
- 19 -
© ESAB AB 2022
Page 20
5  OPERATION
4-stroke repeat mode (Welding with repeated ending arc)

5.3 Connection of welding and return cable

The power source has two outputs, a positive terminal (+) and a negative terminal (-), for connecting welding and return cables.
Connect the return cable to the negative terminal on the power source. Secure the return cable's contact clamp to the work piece and ensure that there is good contact between the work piece and the output for the return cable on the power source.
Recommended maximum welding current values for the welding/return cable(copper) at an ambient temperature of +25°C and normal 10minutes cycle
Cable size mm
2
100% 60% 35%
50 290 A 320 A 370 A 0.35V/100A
70 360 A 400 A 480 A 0.25V/100A
95 430 A 500 A 600 A 0.19V/100A
Recommended maximum welding current values for the welding/return cable(copper) at an ambient temperature of +40°C and normal 10minutes cycle
Cable size mm
2
100% 60% 35%
Duty cycle
Voltage drop/10m
Duty cycle
Voltage drop/10m
50 250 A 280 A 320 A 0.35V/100A
70 310 A 350 A 420 A 0.25V/100A
95 380 A 440 A 530 A 0.19V/100A
0446 455 101
- 20 -
© ESAB AB 2022
Page 21
5  OPERATION

5.4 Symbols and functions

Mains power supply switch Overheating (3)
Protective earth Positioning of lifting eye
Arc force Inductance
Gas detection MMA welding
Arc-closing current / Ending arc current
Arc-closing voltage / Ending arc voltage

5.5 Thermal protection

The welding power source has overheating protection that operates if the temperature becomes too high. When this occurs, the welding current is interrupted, and an overheating Indication lamp is lit. The overheating protection resets automatically when the temperature has fallen with in its normal working temperature.

5.6 Fan control

The fan will run during the startup of the machine and will continue to run only for 10 minutes if there is no operation.
In Fabricator EM 401i when the welding current is less than 200A, the fan will run at low speed, if the welding current goes above 200A, the fan will run at high speed.
In Fabricator EM 501i when the welding current is less than 300A, the fan will run at low speed, if the welding current goes above 300A, the fan will run at high speed.
After the welding stops, the fan will continue to run for 10 minutes and the power source switches to idle mode (energy-saving mode).
0446 455 101
- 21 -
© ESAB AB 2022
Page 22
5  OPERATION

5.7 Usage of the cooling unit

CAUTION! Important! Turn OFF the cooling unit when welding MMA or using air cooled MIG/TIG welding
torches to avoid excessive wear of the pump. Otherwise, the pump will work against a closed valve.
Turn ON the cooling unit when using a water cooled MIG welding torch to avoid damages on the cable set.

5.8 Coolant connection

For problem-free operation it is recommended that the height from the cooling unit to the water-cooled MIG/MAG torch is of 8.5m.

5.9 Coolant pressure controller

The pump has an enclosed pressure relief valve. The valve opens gradually when the pressure is too high. This can occur if a hose is folded, which causes the flow to fail or stop.
0446 455 101
- 22 -
© ESAB AB 2022
Page 23
6  MAINTENANCE

6 MAINTENANCE

6.1 Maintenance

WARNING!
The mains supply must be disconnected during cleaning and maintenance.
CAUTION!
Only persons with the appropriate electrical knowledge (authorised personnel) may remove the safety plates.
CAUTION!
The product is covered by manufacturer's warranty. Any attempt to carry out repair work by non-authorised service centers or personnel will invalidate the warranty.
NOTE!
Regular maintenance is important for safe and reliable operation.
NOTE!
Perform maintenance more often during severe dusty conditions.
Before each use - make sure that:
Product and cables are not damaged,
The torch is clean and not damaged.

6.2 Routine maintenance

Maintenance schedule during normal conditions. Check equipment prior to every use.
Interval Area to maintain
Every 3 months
Clean weld terminals. Check or replace weld cables.
Every 6 months
Clean inside equipment. Use dry compressed air with 4bar pressure.

6.3 Power source

To maintain the performance and increase the lifetime of the power source it is mandatory to clean it regularly. How often depends on:
the welding process
the arc time
0446 455 101
- 23 -
© ESAB AB 2022
Page 24
6  MAINTENANCE
the working environment
the surrounding environment, that is among others grinding.
Tools needed for the cleaning procedure:
torx screwdriver, T25 and T30
dry compressed air at a pressure of 4 bar
protective equipment like ear plugs, safety glasses, masks, gloves and safety shoes
CAUTION!
Make sure that the cleaning procedure is done in a suitable prepared workspace.
Cleaning procedure
CAUTION!
The cleaning procedure should be carried out by authorised service technician.
1 Disconnect the mains supply.
WARNING!
Wait until the DC bus capacitors are discharged. The DC bus capacitor discharge time is at least 2 minutes!
2 Remove the side panels on the power source. 3 Remove the top panel on the power source. 4 Remove the plastic cover between the heat sink and fan (1). 5 Clean the power source with dry compressed air (4 bar) as follows:
The upper rear part.
From the rear panel through the secondary heat sink.
The inductor, transformer and current sensor.
The power components side, from the rear side behind PCB15AP1.
The PCBs at both sides.
6 Make sure that there is no dust left on any part.
0446 455 101
- 24 -
© ESAB AB 2022
Page 25
6  MAINTENANCE
7 Install the plastic cover between the heat sink and the fan (1) and make sure it is
correctly fitted against the heat sink.
8 Reassemble the power source after cleaning and perform testing according to IEC
60974-4. Follow the procedure in section “After repair, inspection and test” in the Service manual.

6.4 Cooling unit

Dust, grinding, swarf
The air stream through the cooling unit carries particles that become trapped in the cooling element, particularly in dirty working environments. This results in reduced cooling capacity. For this reason, blow clean using compressed air at regular intervals.
The coolant system
The recommended coolant must be used in the system otherwise clumps can be created that block the pump, water connections or elements. Flushing can only be performed via red water connection. Then drain the tank manually, that is empty via the tank’s filling hole.

6.5 Filling the coolant

Only use ESAB’s ready mixed coolant, see the “ACCESSORIES” chapter.
Fill with coolant. (The fluid level must not exceed the upper marking but must not be below lower marking.)
0446 455 101
CAUTION!
The coolant must be handled as chemical waste.
- 25 -
© ESAB AB 2022
Page 26
6  MAINTENANCE
NOTE!
Coolant must be topped up if connecting a welding torch or coolant hosed that are 5 meters in length or longer. When adjusting the water level by topping up, the coolant hosed do not need to be disconnected.
0446 455 101
- 26 -
© ESAB AB 2022
Page 27
7  TROUBLESHOOTING

7 TROUBLESHOOTING

Perform these checks and inspections before sending for an authorised service technician.
The following table describes the welder error code, as well as the causes and solutions
Error Code
F00 F00 None Power-on self-test
E1 E1 None Welding torch fault When the equipment
E2 E2 None Output terminal
Displayed Content
Left
display
Right
display
Fault Cause Solution
over-temperature
is turned on, the welding torch trigger switch is on. the switch may be faulty.
The OKC terminal and welding cable is not connected properly. The copper cross-sectional area of the output power cable is too small. The output cable OKC fails to meet the specification requirement. The fan does not work or slows down.
Turn off the switch. Replace the welding torch.
Verify the OKC terminal and welding cable is connected properly. Use cables with correct cross-sectional areas. Select suitable cable OKC. Verify that the fan blades are not stuck with any foreign objects.
E3 E3 None Abnormal input
power
0446 455 101
- 27 -
The input power cable is not connected properly. Input power overvoltage occurs. Input power under voltage occurs. Input power phase imbalance occurs. The input power frequency exceeds the range.
Verify that the input cables are connected properly. Verify that all the three input phases are present.
© ESAB AB 2022
Page 28
7  TROUBLESHOOTING
Error Code
Left
display
Right
display
E4 E4 None IGBT or diode
over-temperature
Fault Cause Solution
The rated duty cycle is exceeded. The air vent of the housing is blocked. The fan does not work or slows down.
E5 E5 1 - 8 Button error Button is not
working. Button does not rebound after being pressed.
E6 E6 None Output overcurrent The output is
short-circuited, or the current is too high.
Displayed Content
Ensure that the user does not exceeds the rated duty cycle range. Verify that the air vent is not blocked. Verify that the fan blades are not stuck with any foreign objects that the fan blades are not stuck with any foreign objects.
Check the button and make sure it does not stick.
Verify that the output is not short-circuited.
E7 E7 None Input power fault The input power
cable is not connected properly. Input power phase loss or phase imbalance occurs.
E8 E8 None Output overvoltage The input voltage is
too high. The output cables are not connected correctly.
E9 E9 None Primary side
overcurrent
E10 E10 None Primary side
overvoltage
E11 E11 None Current sensor
disconnection
The output is short-circuited.
The input voltage is too high.
The connector on the current sensor is disconnected or damaged.
E12 E12 None PCB not registered The PCB is not
certified.
E13 E13 None Overcurrent of wire
feeder motor
The welding wire is blocked or jammed
Verify that the input cables are connected properly. Verify that the input power is normal.
Verify that the input voltage is normal. Verify that the output cables are connected correctly.
Verify that the output is not short-circuited.
Verify that the input voltage is normal.
Refer note below the table
Refer note below the table
Check whether the welding wire is blocked or jammed
0446 455 101
- 28 -
© ESAB AB 2022
Page 29
7  TROUBLESHOOTING
Error Code
Left
display
Right
display
E14 E14 1/2 Gas solenoid valve
on Wire feeder
Fault Cause Solution
Gas solenoid valve short Circuit or damage;/ Gas solenoid valve open circuit or cable disconnect
Check whether the valve is short-circuited or damaged;/ Check whether the valve is open or whether the cable is disconnected;
Displayed Content
E17 E17 None The encoder of the
wire feeder motor has an open circuit problem
Loose control cable or wire
Check whether the control cable is loose, or the wire feeder is stuck
NOTE!
Call ESAB authorised service personnel.
Perform these checks and inspections before sending for an authorised service technician.
Type of fault Corrective action
No arc. Check that the mains power supply switch is turned on.
Check that the mains, welding and return cables are correctly connected.
Check that the correct current value is set.
Check the mains power supply fuses.
The welding current is interrupted during welding.
The thermal protection trips frequently
Check whether the thermal protection trip has operated (indicated by the orange LED on the front).
Make sure that you are not exceeding the rated data for the power source (i.e. that the unit is not being overloaded).
Check that the ambient temperature is not above the one for the rated duty cycle 40°C/104°F.
Poor welding performance Check that the welding current supply and return cables
are correctly connected.
Check that the correct current value is set.
Check that the correct welding wires are being used.
Check the main power supply fuses.
Poor cooling effect. Clean the cooling element using compressed air
Check the coolant level
Check the on/off switch on the cooling unit is set to ON
CAUTION!
Repair and electrical work should be performed by an authorised ESAB service technician. Use only ESAB original spare and wear parts.
0446 455 101
- 29 -
© ESAB AB 2022
Page 30
8  ORDERING SPARE PARTS

8 ORDERING SPARE PARTS

CAUTION!
Repair and electrical work should be performed by an authorised ESAB service technician. Use only ESAB original spare and wear parts.
The FabricatorEM 401i/EM 401i with cooling unit / EM 501i with cooling unit is designed and tested in accordance with international standards ENIEC60974-1, ENIEC60974-2 and ENIEC60974-10. On completion of service or repair work, it is the responsibility of the person(s) performing the work to ensure that the product still complies with the requirements of the above standards.
Spare parts and wear parts can be ordered through your nearest ESAB dealer, see esab.com. When ordering, please state product type, serial number, designation and spare part number in accordance with the spare parts list. This facilitates dispatch and ensures correct delivery.
0446 455 101
- 30 -
© ESAB AB 2022
Page 31
APPENDIX
APPENDIX

ORDERING NUMBERS

Ordering number Denomination Type Notes
0446 400 884 Power source Fabricator EM 401i CE
0446 400 883 Power source Fabricator EM 401i with cooling unit CE
0446 400 882 Power source Fabricator EM 501i with cooling unit CE
0446 455 * Instruction manual
0463 802 001 Service manual
0463 810 001 Spare parts list
The three last digits in the document number of the manual show the version of the manual. Therefore they are replaced with * here. Make sure to use a manual with a serial number or software version that corresponds with the product, see the front page of the manual.
Technical documentation is available on the Internet at: www.esab.com
0446 455 101
- 31 -
© ESAB AB 2022
Page 32
APPENDIX

BLOCK DIAGRAM

0446 455 101
- 32 -
© ESAB AB 2022
Page 33
APPENDIX

ACCESSORIES

0446 401 881 Fabricator Feed 304
0446 401 882 Fabricator Feed 304w
Connection set, 70mm2, 19 poles
0459 836 880 2 m
0459 836 881 5 m
0459 836 882 10 m
0459 836 884 25 m
Connection set water, 70mm2, 19 poles
0459 836 890 2 m
0459 836 891 5 m
0459 836 892 10 m
0459 836 894 25 m
Connection set water, 95mm2, 19 poles
0459 836 990 2 m
0459 836 991 5 m
0459 836 992 10 m
0459 836 994 25 m
0465 720 002 ESAB ready mixed coolant (10l/2.64gal)
Use of any other cooling liquid than the prescribed one might damage the equipment. In case of such damage, all warranty undertakings from ESAB cease to apply.
0447 014 001 Converter plug for gas heater supply
0446 455 101
- 33 -
© ESAB AB 2022
Page 34
ESAB AB, Lindholmsallén 9, Box 8004, 402 77 Gothenburg, Sweden, Phone +46 (0) 31 50 90 00
http://manuals.esab.com
For contact information visit http://esab.com
Loading...