ESAB CANopen I/O Profile Instruction manual

GB
ESAB CANopen I/O Profile
Aristot
Rev . 1.100459 572 074 GB 080115
1 INTRODUCTION TO CANopen 3......................................
1.2 T echnical features for CANopen 3.............................................
2 UNIT OVERVIEW 4...................................................
2.1 Functional overview 4........................................................
2.2 Mechanical overview 4.......................................................
3 INSTALLATION AND CONFIGURATION 5..............................
3.1 Fieldbus connector 5........................................................
3.2 Configuration 5.............................................................
3.3 LED indicators 6............................................................
3.4 EDS file 7..................................................................
4 I/O DATA MAP 7.....................................................
4.1 IN I/O from Controller to Welding Equipment 7..................................
4.2 OUT I/O from Welding Equipment to Controller 7................................
5 FUNCTIONAL DESCRIPTION OF I/O 9.................................
5.1 IN I/O from Controller to Welding Equipment 9..................................
5.2 OUT I/O from Welding Equipment to Controller 1 1................................
Appendix 1 15..........................................................
Rights reserved to alter specifications without notice.
TOCe
-- 2 --
1 INTRODUCTION TO CANopen
CANopen is an open communication profile based on the Controller Area Network (CAN) bus system. It is internationally standardized in ISO 11898.
CANopen has an international user organization called CAN in Automation (CiA). For further information regarding CANopen matters not associated with this ESAB product, please contact CiA on e--mail: headquarters@can--cia.dewww.can.cia.de. There is also information of a general kind available on the Internet at .
1.1 Network overview
The media of the fieldbus system is a shielded copper cable consisting of one twisted pair of communication cable and two cables for external power supply. As standard, the CANopen Esab products do not use external power supply.
The power supply for the bus is galvanically isolated with a DC/DC converter inside the Esab equipment. The number of devices participating in each network is logically limited by CANopen to 128, but physically the present generation of drives allows up to 64 nodes in one network segment.
The baud rate can be changed from 10 kbit/s to 1Mbit/s at discrete levels. The maximum possible size of the network for any particular data rate is limited by the signal transit time required on the bus medium corresponding to the following table:
The baud rate and the node address for the welding node is set inside the Control box (see chapter XX). The CANopen protocol supports both master--slave and slave--slave communications. The data on the CANopen bus is updated when a change is made or on request from another node.
1.2 Technical features for CANopen
Here follows a short list of some important features with the CANopen communication standard:
S
CANopen specific cable (twisted pair).
S Access intelligence in low--level devices.
S Master--Slave and Peer--to--Peer capabilities.
S Selectable baud rates from 10kbit/s to 1Mbit/s.
S Max distance 5000m.
S Node removal without damaging the network.
S Use of scaled and open--styled connectors.
S Provision for the typical request /response oriented network communications.
S Provision for the efficient movement of I/O data.
S Fragmentation for moving larger bodies of information.
bi10d001e
-- 3 --
2 UNIT OVERVIEW
This chapter provides an overview over the ESAB Aristo CANopen unit.
2.1 Functional overview
The ESAB unit for CANopen is a slave node that can be read and written to from a CANopen master/slave. Via the host connector, the unit is connected to an application that gets instant connection to a CANopen network.
2.2 Mechanical overview
DIP- switches and inditation LED
Connection box
bi10d001e
-- 4 --
3 INSTALLATION AND CONFIGURATION
3.1 Fieldbus connector
9--pin male D--sub connector
Connector pin
1 -- Reserved 2 CAN_L CAN_L Bus line (dominant low) 3 CAN_GND CAN ground 4 -- Reserved 5 CAN_SHIELDOptional CAN Shield
6 GND Optional ground 7 CAN_H CAN_H Bus line (dominant
8 -- Reserved 9 CAN_V+ Optional CAN external power
Signal Description
high)
supply
3.2 Configuration
Node Address
The Network node address is set with two rotary switches inside the Weld Data Unit (ADDRESS_HIGH and ADDRESS_LOW), see Figure 1. Possible node addresses is between 1--99 in decimal format. ADDRESS_HIGH is the one in the middle and ADDRESS_LOW is the one to the right.
The node address is calculated in the following way:
Node address = ADDRESS_HIGH * 10 + ADDRESS_LOW * 1
Note: PDO 3 – 8 only have default COB--ID’s if the node address is less than 64.
Note: The node address can only be changed during operation.
bi10d001e
-- 5 --
Baudrate
The baud rate is configured with one decimal rotary switch inside the Weld Data Unit. See table below for supported baud rates. The baud rate switch is the one to the left.
Switch setting
0 Not available 1 10 kbit/s 2 20 kbit/s 3 50 kbit/s 4 125 kbit/s 5 250 kbit/s 6 500 kbit/s 7 800 kbit/s 8 1 Mbit/s 9 Not available
Baudrate
Termination
CANopen uses standard CAN termination on the first and last node on the network. The termination resistor should be 120 ohm. This should be connected between CAN_H and CAN_L on the bus.
Note that the termination resistor is only used when the machine is the first or last on the bus.
3.3 LED indicators
The node inside the Weld Data Unit is equipped with four bi--color status and indication LED’s mounted at the front of the module.
During start--up a LED, test will be performed to make sure the LED’s are working. Test sequence is: Red – Green – Off.
There is also an additional bi--color Watchdog LED on the module inside the Weld Data Unit for development purposes.
LED 2
Color Frequency Description
Green 1Hz Module in ‘Pre--Operation’ state Green 2Hz Module in ‘Prepared’ state Green Steady on Module in ‘Operational’ state Red 1Hz Bus initialization failed
bi10d001e
-- 6 --
LED 3
Color Frequency Description
Green 1Hz Bus off / Error Passive Green Steady on Bus Running Red 1Hz Other Error Off -- Power off or module not
initialized
LED 4
Color Frequency Description
Off -- No power to device Green Steady on Module has power
3.4 EDS file
This file is used to configuring the network. If standard configuration is used this file is not required. If a standard CANopen configurator is used an EDS file is required. The latest version of the EDS file can be received by contacting ESAB.
4I/ODATAMAP
4.1 IN I/O from Controller to Welding Equipment
Receive PDO 1, COB--ID 200 h + Node Address
Byte 0 Weld On Quick Stop Emerg. Stop Inching Gas purge Clean Inch Reverse (Reset Error) Byte 1 Wire Feed 1 Wire Feed 2 Wire Feed 3 Wire Feed 4 Touch sense (Simulation) (Rel Wire) Analog Active Byte 2 Weld Data Number Byte 3 Reserved Byte 4 Reserved Byte 5 Reserved Byte 6 Reserved Byte 7 Reserved
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
Receive PDO 2, COB--ID 300 h + Node Address
Byte 0 Voltage Low Byte(SINT) Byte 1 Voltage High Byte (SINT) Byte 2 Wire Feed Speed Low Byte(USINT) Byte 3 Wire Feed Speed High Byte (USINT) Byte 4 Reserved Byte 5 Reserved Byte 6 Reserved Byte 7 Reserved
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
4.2 OUT I/O from Welding Equipment to Controller
Transmit PDO 1, COB--ID 180 h + Node Address
Byte 0 Weld Bus y Arc Ackn. TS resp
Byte 1 Error Type 1 Error Type 2 Error Type 3 Error Type 4 Error Type 5 Error Type 6 Error Type 7 Error Type 8 Byte 2 Error WDU Error PS Error WF Byte 3 Reserved Byte 4 Reserved Byte 5 Reserved Byte 6 Reserved Byte 7 Reserved
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
bi10d001e
-- 7 --
Transmit PDO 2, COB--ID 280 h + Node Address
Byte 0 Voltage Low Byte (Measured) Byte 1 Voltage High Byte (Measured) Byte 2 Current Low Byte (Measured) Byte 3 Current High Byte (Measured) Byte 4 Power Low Byte (Measured) Byte 5 Power High Byte (Measured) Byte 6 Reserved Byte 7 Reserved
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
Transmit PDO 3, COB--ID 1C0h + Node Address
Byte 0 Voltage Low Byte(SINT) Byte 1 Voltage High Byte (SINT) Byte 2 Wire Feed Speed Low Byte(USINT) Byte 3 Wire Feed Speed High Byte (USINT) Byte 4 Synergic Voltage Low Byte (SINT) Byte 5 Synergic Voltage High Byte (SINT) Byte 6 Reserved Byte 7 Reserved
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
Transmit PDO 4, COB--ID 2C0h + Node Address
Byte 0 Weld Data Number Byte 1 Reserved Byte 2 Reserved Byte 3 Reserved Byte 4 Reserved Byte 5 Reserved Byte 6 Reserved Byte 7 Reserved
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
Transmit PDO 5, COB--ID 3C0h + Node Address
Byte 0 Weld Data Unit Error Mask Byte 1 Weld Data Unit Error Mask Byte 2 Weld Data Unit Error Mask Byte 3 Weld Data Unit Error Mask Byte 4 Weld Data Unit Error Mask Byte 5 Weld Data Unit Error Mask Byte 6 Reserved Byte 7 Reserved
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
Transmit PDO 6, COB--ID 440h + Node Address
Byte 0 Power Source Error Mask Byte 1 Power Source Error Mask Byte 2 Power Source Error Mask Byte 3 Power Source Error Mask Byte 4 Power Source Error Mask Byte 5 Power Source Error Mask Byte 6 Reserved Byte 7 Reserved
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
Transmit PDO 7, COB--ID 4C0h + Node Address
Byte 0 Wire Feeder Error Mask Byte 1 Wire Feeder Error Mask Byte 2 Wire Feeder Error Mask Byte 3 Wire Feeder Error Mask Byte 4 Wire Feeder Error Mask Byte 5 Wire Feeder Error Mask Byte 6 Reserved Byte 7 Reserved
Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7
bi10d001e
-- 8 --
5 FUNCTIONAL DESCRIPTION OF I/O
5.1 IN I/O from Controller to Welding Equipment
Weld Status Bits
Weld On
This bit starts a Welding procedure. Before a welding procedure is started the Quick Stop bit and Emergency stop bits are checked.
Quick Stop
This bit performs a Quick Stop if the Equipment is in a welding procedure. T his means that the Welding Equipment will do a normal stopping procedure without Craterfilling.
This function is used when a fast stop is required but it will handle Burnback the normal way to avoid that the wire is left frozen in the weld pool. This bit will also block a start command.
Emergency Stop
This bit performs a Emergency Stop if the Equipment is in a Welding procedure. This means that the welding equipment will shut off the arc, wire feeding and gas flow without any burnback time. This bit will also block a start command.
Inching
This bit makes the wire feeder to start feed the wire without activating the power source. The feeder will feed the wire at the adjusted speed. If this bit is activated during a welding procedure, this command will be ignored.
If both Weld On and Inching is a ctivated at the same time the equipment will ignore the Inch command and start a welding procedure.
Gas Purge
The gas control works in parallel with the regular gas handling timers which means that the gas inputs can be left unused.
A weld start will always start with opening the gas valve if it not already is opened by activating the input. In similar fashion the end of gas post flow timer will always close the gas valve if it is not already closed by deactivating the gas input.
Accordingly when you what this input to control the gas valve operations the gas pre flow time shall be set at minimum and the gas post flow time shall be set at maximum.
Clean
This bit controls a valve for spatter cleaning gas. The function is not implemented in the current version of the system.
Inch Reverse
This input bit will control backward--jogging movement to position the wir e end before weld start. This function is not implemented in the current version of the system .
bi10d001e
-- 9 --
Wire Feed 1--4
These bits are used to change active wire feeder. If more than one is activated the wire feeder with the lowest I/O number will be activated. If non are activated it will default to the lowest numbered feeder that are present in the system.
Release Wire
This function will execute a current pulse to burn off a wire that is frozen in the weld pool if previous weld is ended in a not normal way. The release pulse is only executed if ”Weld On” is off. This function is not implemented in the current version of the system.
Touch Sense
When this input is activated the power source will output a weak power to detect if there is contact in the welding circuit. As long as this function is engaged the output bit ”Touch Sense Response” will be changed according to the condition in the welding circuit. This function is not implemented in the current version of the system .
Reset Error
This input bit will reset the error indication. Only error indications that do not have any other way of resetting than reboot of the system are affected by this reset. This function is not implemented in the current version of the system.
Analog Active
This input is used to switch between analog active mode and normal mode. When using the Analog Active mode the machine will not use the pre--stored values for Wire Feed Speed and Voltage when a new Weld Data Set is selected.
The machine will always use the values on the Wire Feed Speed and Voltage inputs in this mode. When using the Normal mode the machine will set the Wire Fe ed Speed and Voltage to the values stored in the set.
If the inputs for Wire Feed Speed and Voltage are changed after the Weld Data Set is changed the machine will use the new values.
Weld Data Number
This byte is used to recall a complete set of weld data from the weld data memory in the Weld Data Unit. A complete set of weld data includes all settings that can be made in the Weld Data Unit.
Among a large number of setting values this includes:
S Wire Type S Wire Dimension S Gas Type S Use of synergic mode or non--synergic mode S Pulse Welding or Dip/Spray Welding S Start Data S Stop Data
bi10d001e
-- 1 0 --
Numerical Welding Parameters
Voltage
This 16--bit signed value is used to adjust the voltage value. The scaling factor is 100 so if 20 V is wanted, the value should be 2000. The resolution within the machine is ¼ V. This means that if you set 10,6 V the value displayed will be 10,5 V.
If the machine is in non--synergic mode the equipment will simply use the value set. If the equipment is in synergic mode the machine will use the value as an offset from the synergic value. The synergic value can be read from the output I/O area.
Wire Feed Speed
This 16--bit unsigned value is used to adjust the wire feed value. The scaling factor is 100 so if 15 m/min is wanted, the value should be 1500. The resolution within the machine is ¼ m/min.
5.2 OUT I/O from Welding Equipment to Controller
Weld Status Bits
Weld Busy
This signal indicates that the welding equipment is occupied with welding. If a stuck wire or a burn through will break the welding circuit then the power source will go on trying to weld until it gets a stop command.
A condition that makes the Arc acknowledge signal to fall does not stop the welding equipment from continuing the attempts to weld.
As a default value, the weld busy signal is activated when the gas preflow begins until the gas postflow stops. By chosing Weld Busy in the configuration menu, it is possible to choose to have the weld busy signal activated when the power source outputs power, until the gas postflow stops. In the menu you can also choose to have the weld busy signal activated when the power source outputs power, until the power source shuts down the power output.
Arc Acknowledge
This signal will be activated when the arc is established at a weld start and it will fall when voltage and current variations indicate that there can not be welding any longer.
The criteria for arc established is that the process control has passed its start procedure which means that it is not enough with just a short--circuit to fulfill the criteria. Typical delay times from first contact to Arc acknowledge (wire feed time till first contact not included) is in the r ange 2 to 20 ms. In case of a bad start the Arc acknowledge signal will be more delayed.
The Arc acknowledge signal will stay on until either the weld is interrupted or the welding is stopped the normal way. At a normal stop the Arc acknowledge signal will fall when the finalizing procedures are ended (i.e. craterfill, burnback) and the power source cuts the arc.
An interrupted weld is detected if abnormal conditions during welding makes the weld process control deviate significantly from a normal working point. A certain filtering time is used for this detection.
bi10d001e
-- 1 1 --
One example is if the wire is stuck and the Power Source keeps an arc between workpiece and contact nozzle so that a normal current detection would indicate that current is flowing and arc is assumed OK. In this case the Arc acknowledge signal will fall due to that the weld controller has deviated to much from normal welding conditions.
Touch Sense Response
This output bit will indicate contact in welding circuit as long as input bit ”Touch Sense ” is active It will be ”0” all other time. This function is not implemented in the current version of the system.
Error of type 1--8
There is an error of the indicated type in one of the err o r masks. Which error that will be caught can be configured with a service function. With this feature it is possible to configure, for example, one error type to be a general error and another error type to be gas error and so on.
As a default the error types are configured as follows:
Error type 1 Error type2Error type3Error type4Error type5Error type6Error type7Error type8Reset
Error 1 Error 2 Error 3 Error 4 Error 5 Error 6 Error 7 Error 8 Error 9 Error 10 Error 11 Error 12 Error 13 Error 14 Error 15 Error 16 Error 17 Error 18 Error 19 Error 20 Error 21 Error 22 Error 23 Error 24 Error 25 Error 26 Error 27 Error 28 Error 29 Error 30 Error 31 Error 32 Error 33 Error 34 Error 35 Error 36 Error 37 Error 38 Error 39
Error
ErrorinWeldDataUnit
Change in Weld Data Unit Errors. Is set to 1 when there is a change in the Weld Data Unit bit mask. Does not matter if a specific error arises or disappears.
bi10d001e
-- 1 2 --
Error in Power Source Unit
Change in Power Source Unit Errors. Is set to 1 when there is a change in the Weld Data Unit bit mask. Does not matter if a specific error arises or disappears.
Error in Wire Feed Unit
Change in Wire F eed Unit Errors. Is set to 1 when there is a change in the Weld Data Unit bit mask. Does not matter if a specific error arises or disappears.
Weld Data Number
This byte is updated every time there has been a successful recall of a Weld Data Set. In case that the desired Weld Data Set does not exist in the Weld Data Memory, the old number will remain.
Note that if the controller recall a Weld Data Set and the Operator uses the Weld Data Unit to change any individual parameter, the Weld Data in the Operating Weld Data Memory and the Weld Data in the Weld Data Set indicated by this byte will not be consistent.
Numerical Welding Parameters
Voltage
This 16--bit unsigned value indicates which voltage the welding machine is using. If a value is set with RPDO 2 that are outside limits, this value will be set to the nearest allowed value.
Wire Feed Speed
This 16--bit signed value indicates which wire feed speed the wire feeder is using. If a value is set with RPDO 2 that are outside limits, this value will be set to the nearest allowed value.
Synergic Voltage
This 16--bit unsigned value indicates the result of the calculations preformed by the welding equipment. The difference between this value and the voltage is the offset set with RPDO2. This value is only valid when running in synergic mode.
Measured Values
Voltage
This value is measured by the welding equipment. In pulse welding it can be configured if the value presented should be the average value or the pulse value.
Current
This value is measured by the welding equipment.
Power
This value is measured by the welding equipment.
Error Mask, Weld Data Unit
This error mask indicates which errors that are presently activated in the Weld Data Unit. These error codes can be interpreted with the table in Appendix 1.
Error Mask, Power Source
This error mask indicates which errors that are presently activated in the Power Source. These error codes can be interpreted with the table in Appendix 1.
bi10d001e
-- 1 3 --
Error Mask, Wire Feeder
This error mask indicates which errors that are presently activated in the Wire Feed Unit. These error codes can be interpreted with the table in Appendix 1.
bi10d001e
-- 1 4 --
Appendix 1
Specification of error codes in LUD
Error code Description SLUD LUD MEK
1 EPROM
2 RAM
3 External RAM
4 Power supply voltage 5V
5 High DC voltage
6 High temperature
7 High primary current
8 DC Voltage 1*
9 DC Voltage 2*
10 DC Voltage 3*
11 Current--servo / Wire speed--servo
12 Communication error ( warning -- internal bus )
14 Communication error ( bus off -- internal bus )
15 Message lost ( internal bus )
Appendix 1
17 Lost contact with MEK
18 Lost contact with LUD
19 Error in battery--driven memory
20 Unaccepted setting values
21 Incompatible setting values
22 Spill in transmit buffer
23 Spill in receive buffer
25 Incompatible weld data format
26 Watchdog
27 No more wire detected
28 Stack overflow
29 No more water flow
30 Lost contact with TIG-- card
31 No answer from display card
32 Error detected in gas flow
33 Hardware check failed in fieldbus interface
34 Memory test failed in fieldbus interface
35 Initialisation failed in fieldbus interface
36 Watchdog timeout in fieldbus interface
37 Fieldbus interface initialisation lost.
38 Bus Off in fieldbus interface.
39 Lost contact with analog remote node.
*)
Unit DC voltage 1 DC voltage 2 DC voltage 3
SLUD 3 V (batt) LUD +15VC --15V +15VB MEK 15V 20V
bi10d001e
-- 1 5 --
ESAB subsidiaries and representative offices
Europe
AUSTRIA
ESAB Ges.m.b.H Vienna--Liesing Tel: +43 1 888 25 11 Fax: +43 1 888 25 11 85
BELGIUM
S.A. ESAB N.V . Brussels Tel: +32 2 745 11 00 Fax: +32 2 745 11 28
THE CZECH REPUBLIC
ESAB VAMBERK s.r.o. Prague Tel: +420 2 819 40 885 Fax: +420 2 819 40 120
DENMARK
Aktieselskabet ESAB Herlev Tel:+4536300111 Fax:+4536304003
FINLAND
ESAB Oy Helsinki Tel: +358 9 547 761 Fax: +358 9 547 77 71
FRANCE
ESAB France S.A. Cergy Pontoise Tel:+33130755500 Fax:+33130755524
GERMANY
ESAB GmbH Solingen Tel: +49 212 298 0 Fax: +49 212 298 218
GREAT BRITAIN
ESAB Group (UK) Ltd Waltham Cross Tel: +44 1992 76 85 15 Fax: +44 1992 71 58 03
ESAB Automation Ltd Andover Tel: +44 1264 33 22 33 Fax: +44 1264 33 20 74
HUNGARY
ESAB Kft Budapest Tel:+3612044182 Fax:+3612044186
ITALY
ESAB Saldatura S.p.A. Mesero (Mi) Tel:+3902979681 Fax:+390297289181
THE NETHERLANDS
ESAB Nederland B.V. Utrecht Tel: +31 30 2485 377 Fax: +31 30 2485 260
NORWAY
AS ESAB Larvik Tel:+4733121000 Fax:+4733115203
POLAND
ESAB Sp.zo.o. Katowice Tel: +48 32 351 11 00 Fax: +48 32 351 11 20
PORTUGAL
ESAB Lda Lisbon Tel: +351 8 310 960 Fax: +351 1 859 1277
SLOVAKIA
ESAB Slovakia s.r.o. Bratislava Tel:+421744882426 Fax:+421744888741
SPAIN
ESAB Ibérica S.A. Alcalá de Henares (MADRID) Tel: +34 91 878 3600 Fax: +34 91 802 3461
SWEDEN
ESAB Sverige AB Gothenburg Tel:+4631509500 Fax:+4631509222
ESAB international AB Gothenburg Tel:+4631509000 Fax:+4631509360
SWITZERLAND
ESAB AG Dietikon Tel: +41 1 741 25 25 Fax: +41 1 740 30 55
North and South America
ARGENTINA
CONARCO Buenos Aires Tel: +54 11 4 753 4039 Fax: +54 11 4 753 6313
BRAZIL
ESAB S.A. Contagem--MG Tel: +55 31 2191 4333 Fax: +55 31 2191 4440
CANADA
ESAB Group Canada Inc. Missisauga, Ontario Tel: +1 905 670 02 20 Fax: +1 905 670 48 79
MEXICO
ESAB Mexico S.A. Monterrey Tel: +52 8 350 5959 Fax: +52 8 350 7554
USA
ESAB Welding & Cutting Products Florence, SC Tel: +1 843 669 44 11 Fax: +1 843 664 57 48
Asia/Pacific
CHINA
Shanghai ESAB A/P Shanghai Tel: +86 21 5308 9922 Fax: +86 21 6566 6622
INDIA
ESAB India Ltd Calcutta Tel: +91 33 478 45 17 Fax: +91 33 468 18 80
INDONESIA
P.T. ESABindo Pratama Jakarta Tel: +62 21 460 0188 Fax: +62 21 461 2929
JAPAN
ESAB Japan Tokyo Tel: +81 3 5296 7371 Fax:+81352968080
MALAYSIA
ESAB (Malaysia) Snd Bhd Selangor Tel: +60 3 8027 9869 Fax:+60380274754
SINGAPORE
ESAB Asia/Pacific Pte Ltd Singapore Tel:+6568614322 Fax: +65 6861 31 95
SOUTH KOREA
ESAB SeAH Corporation Kyungnam Tel: +82 55 269 8170 Fax: +82 55 289 8864
UNITED ARAB EMIRATES
ESAB Middle East FZE Dubai Tel: +971 4 887 21 11 Fax: +971 4 887 22 63
Representative offices
BULGARIA
ESAB Representative Office Sofia Tel/Fax: +359 2 974 42 88
EGYPT
ESAB Egypt Dokki--Cairo Tel: +20 2 390 96 69 Fax: +20 2 393 32 13
ROMANIA
ESAB Representative Office Bucharest Tel/Fax: +40 1 322 36 74
RUSSIA
LLC ESAB Moscow Tel: +7 095 543 9281 Fax: +7 095 543 9280
LLC ESAB St Petersburg Tel: +7 812 336 7080 Fax: +7 812 336 7060
Distributors
For addresses and phone numbers to our distributors in other countries, please visit our home page
www.esab.com
ESAB AB SE--695 81 LAXÅ SWEDEN Phone +46 584 81 000
www.esab.com
060517
Loading...