Ericson Low Voltage Handlamps Catalog Page

94
Low Voltage Handlamps with In-Line Transformer
TEMPORARY LIGHTING
120 V olt AC
To
12 V olt AC
Low voltage hand lamps Vapor Proof Explosion Proof
with 25’ secondary cord 1924-12A 1926-12A with 50’ secondary cord 1924-12B 1926-12B
Specifications:
P
rimary Voltage 120 V, 60Hz 120 V, 60Hz Secondary Voltage 12 V 12 V Maximum Wattage 100 watts 75 watts Primary cord gauge & type #16/3 SOW #16/3 SOW Primary cord length 10 ft. 10 ft. Secondary cord gauge & type #14/3 SOW #14/3 SOW Plug NEMA 5-15 NEMA 5-15
Notes: 1926 lamp assembly only is certified Class I & II, Div 1 & 2. Transformer is not hazardous location rated.
Consult factory for custom assemblies
Isolation Transformer
WEATHERPROOF COVER
GROUNDED SHIELD
SECONDARY (12 Vac 100VAMAX)
LOAD
(12 V LAMP)
NEUTRAL (WHITE)
120 VAC
60HZ
(GREEN)GROUND)
HOT (BLACK)
1924-12A
Notes: 1926 lamp assembly only is
certified Class I & II, Div 1 & 2.
Transformer is not hazar dous
location rated. Consult factory
for custom assemblies
FEATURES:
Step-down transformers reduce 120 VAC line voltage
to12 V A C
Extra-thick walled rubber housing with
non-corr
osive stainless steel hardware protects
transformer from jobsite contaminants
Transformers inc orpor a te a grounded metal shield
between primar
y and secondary windings to ensure the two voltages are isolated providing an added degree of protection
Each transformer is subjected to a factory dielectric test of
1600 volts betw
een primary and secondary windings and
between each winding and ground to ensure safety
1924 Series is vapor proof only
Shock resistant
Made in the USA
OSHA 1926.405(a)(2)(ii)(G): “Portable electric lighting used in wet and/or other conductive locations, as for example,
drums, tanks, and vessels, shall be operated at 12 volts or less. However, 120-volt lights may be used if protected by a ground-fault circuit interrupter.
Loading...