ERICO Universal Pedestal Clamp User Manual

INSTRUCTION SHEET
Universal Pedestal Clamp
Part Number
MBNUPCJ82
MBNUPCJ240

UPCJ

1. Stranded conductors #8 - #2 AWG: 7 or 19 strands.
2. Solid Conductors: #2 AWG; Stranded Conductors: #2 AWG: 7 or 19 strands #1 - 4/0 AWG: 7, 19 or 37 strands
Pedestal Size
(Round or Square)
7
8
" - 2"
7
" - 2"
8
7
8
" - 2"
Bonding Conductor
#8 AWG - #2 AWG
#2 AWG - 4/0 AWG
MBNUPCJ82
Conductor
Type
Solid, Stranded
Solid, Stranded
- -
UPCJ
1
2
Load
Rating
50 lbs
50 lbs
50 lbs
MBNUPCJ240
Notes:
MBNUPCJ82, MBNUPCJ240 & UPCJ are UL® Listed per UL 2239 for support of any combination of
UL® Listed CADDY® CAT LINKS J-hooks with a maximum total load rating of 50lbs.
MBNUPCJ82 includes the MBNC82 ground clamp which is UL® Listed per ANSI®/UL 467
MBNUPCJ240 includes the MBNC240 ground clamp which is UL® Listed per ANSI®/UL 467
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2. All instructions must be
3. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4. damage, serious bodily injury and death. Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment.
5. All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any
6.
other purpose.
NOTE: All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted.
The customer is responsible for: a. Conformance to all governing codes. b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified engineer. c. Using appropriate industry standard hardware as noted above.
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
CADDY, CADWELD, CRITEC, ERICO, ERITECH, ERIFLEX, and LENTON are registered trademarks of ERICO International Corporation.
ANSI is a registered trademark of American National Standards Institute UL is a registered trademark of UL LLC
and from your ERICO customer service representative.
completely
TECHNICAL SUPPORT
www.erico.com
followed to ensure proper and safe installation and performance.
IP8170_G
1 OF 2
©2010, 2011, 2012 ERICO International Corporation
INSTRUCTION SHEET
1
Installation:
1.
2.
3.
2
40 in-lbs [4.5 Nm]
R
For simplest installation CADDY® CAT LINKS J-Hooks, if specified, should be attached to pedestal clamp before installation on the pedestal. Attachment of clamp to pedestal:
Secure nuts finger tight approximately equal distance on L-bolt.
• Using a 9/16" wrench or socket, torque nuts to 40 in-lbs [4.5 N-m]
Conductor installation in MBNUPCJ82
Install parallel conductors on the same plane.
• Using a 5/8" deep well socket torque nuts to 150 in-lbs [17 N-m]
• Conductors must extend at least 1" outside of connector
CORRECT
(MBNUPCJ82 Only)
X
INCORRECT
(MBNUPCJ82 Only)
P 150 in-lbs [17N-m]
P 150 in-lbs [17N-m]
3
TECHNICAL SUPPORT
www.erico.com
IP8170_G
2 OF 2
©2010, 2011, 2012 ERICO International Corporation
Loading...