ERICO TDX50 User Manual

Installation Instructions
TDX50 Series
This CRITEC TDX50 Surge Protection Device (SPD) is a high-performance Transient Voltage Surge Suppressor (TVSS), designed to provide protection for sensitive electronic loads connected to distribution panelboards or switchboards or where the SPD is directly connected to the electronic device. Maximum protection will only be achieved if the SPD is properly installed. Please read the installation instructions carefully and follow the instructions.
DANGER: Electrical shock or burn hazard. The installation of this TVSS device should be made by qualified personnel. Failure to lockout electrical power during installation or maintenance can result in fatal electrocution or severe burns.
CAUTION: Check to make sure line voltage does not exceed TVSS voltage requirement.
CAUTION: This unit must be installed in accordance with the National Electrical Code (ANSI/NFPA-70) and applicable local codes, and must be installed on the load side of the main over-current protection.
CAUTION: Do not install on unground ed electrical systems.
NOTICE: Do not cut wires until the SPD is mounted and minimum wire lengths have been verified. All
connection leads should be cut to minimum possible length; never coil or push aside excess length.
INSTALLATION INSTRUCTIONS
1. Verify line voltage by measuring L-N, L-G, L-L and N-G of the system. Confirm that the SPD is correctly rated for the system to which it is to be connected by comparing the measured voltages to the SPD voltage ratings shown on the product side rating label. The (MCOV) maximum continuous operating voltage specifications must not be exceeded.
2. Identify proper location for SPD. Locate as close as physically possible to panel being protected. Mount top and bottom SPD flanges securely. Mount as close to the electrical connection as possible avoiding excess distance and avoiding the need for sharp bends in the wires. (Note: Refer to installation diagram on SPD.) Use appropriate conduit fittings to preserve the SPD/panel NEMA enclosure rating.
3. Connect proper ground. An insulated grounding conductor that is identical in size and insulating material and thickness to the grounded and ungrounded circuit supply conductors, except that it is green with or without one or more yellow stripes, is to be installed as part of the circuit that supplies the filter. The TDX is supplied with 914mm (3ft) long of #10AWG, in accordance with Table 250-122 of the National Electrical Code", for this purpose. The housing of the TDX unit is bonded to the grounding conductor for equipment safety ground purposes as per National Electrical Code. The grounding conductor is to be grounded to earth at the service equipment or other acceptable building earth ground such as the building frame in the case of a high-rise steel-frame structure. Attach the grounding conductor to the panel’s ground bus for proper operation. Wire length should be minimized to improve performance. There is no minimum wire length requirement.
Note: For isolated ground systems, bond the grounding co nductor from the TDX unit to the non-isolated equipment ground, not the isolated equipment ground.
34600 Solon Road HBCR1591 REV 5
Solon, Ohio 44139 (440) 248-0100
www.erico.com
Installation Instructions
TDX50 Series
4. Connect neutral conductor. The TDX units
are supplied with 10AWG leads. The white Neutral conductor is 914mm (3ft) long. Wire length should be minimized to improve performance. There is no minimum wire length requirement. Measure and trim the neutral conductor to be as straight and short as possible. Connect the neutral conductor of the SPD to the neutral lug on the panel.
5. Connect phase conductors. All connection leads should be cut to minimum length; never coil or push aside excess length. Multiple phase devices may be connected without regard to phase A, B, C. With the POWER OFF, connect each black phase lead via: a. 30 Amp circuit breakers. Use a multi-
pole circuit breaker, do not connect to individual single-pole breakers for each line.
b. or 30 Amp fused disconnected switch. c. or if installed in compliance with Article
240-21, the NEC “tap rule”, over-current protection may be omitted*.
* Note: In Australia, New Zealand and other countries it is not permitted to omit over­current protection.
The TDX units are supplied with 10AWG leads. Phase conductors are 610mm (2ft) long. Wire length should be minimized to improve performance. There is no minimum wire length requirement.
6. Nearby Attachment-Plug Receptacles Any attachment -plug receptacles in the vicinity of the filter are to be of a grounding type, and the grounding conductors serving these receptacles are to be connected to earth ground at the service equipment or other acceptable building earth ground such as the building frame in the case of a high­rise steel-frame structure.
7. Connector and Lugs Pressure terminals or pressure splicing connectors and soldering lugs used in the installation of the filter shall be identified as being suitable for the material of the conductors. Conductors of dissimilar metals shall not be intermixed in a terminal or splicing connector where physical contact occurs between dissimilar conductors unless the device is identified for the purpose and conditions of use.
8. Activate unit. When power is applied, diagnostic light(s) will indicate that each phase is protected. If light(s) do not illuminate, recheck fusing, the phase, neutral and ground connections.
9. Flush Panel Mounting. For flush panel mounting please order flush cover plate and follow supplied instructions.
10. Problem Diagnostics. If problems continue after checking the electrical connections, contact your local ERICO representative.
11. No Neutral. For 480V Motor C ontrol applications with no neutral, use the TDX50 277/480, but do not connect the neutral conductor (white conductor). The neutral conductor should be capped/insulated
34600 Solon Road HBCR1591 REV 5
Solon, Ohio 44139 (440) 248-0100
www.erico.com
Loading...
+ 2 hidden pages