ERICO TDS-MOVTEC Surge Diverters User Manual

SURGE DIVERTERS
INSTALLATION INSTRUCTIONS
Includes MPM Movtec Protection Module Instructions
www.erico.com
Handbook No:
Handbook No:
HB-HBCR-111
HB-HBCR-111
© Copyright
© Copyright
INSIDE FRONT COVER
(Blank)
CONTENTS
Page
1. Warnings ... ... ... ... ... ... ... ... ... ... ... 4
2. Introduction ... ... ... ... ... ... ... ... ... ... 5
3. Protection Concepts .. ... ... ... ... ... ... ... 7
4. Mounting and Cautions ... ... ... ... ... ... 9
5. Voltage Ratings .. ... ... ... ... ... ... ... ... 10
6. Protection Mode .. ... ... ... ... ... ... ... ... 13
7. Connection Method ... ... ... ... ... ... ... 15
8. RCD, ELCB ... ... ... ... ... ... ... ... ... ... 20
Page
9. Isolation and Fusing ... ... ... ... ... ... ... 20
10. Status Indication and Alarms
... ... ... 22
11. MPM, Movtec Protection Module ... ... 24
12. Maintenance and Testing .. ... ... ... ... 27
13. Extended Warranty ... ... ... ... ... ... ... 28
14. Six Point Plan ... ... ... ... ... ... ... ... 29
15. Use of Mimic Panels ... ... ... ... ... ... 30
PAGE 3
GLOBAL LIGHTNING TECHNOLOGIES
1. WARNINGS
• Prior to installation ensure that the Movtec is of the correct voltage and frequency, and is the type recommended for the local power distribution, and for the equipment being protected.
• Hazardous voltages may exist internally to the units. The units should be installed (and replaced) only by qualified personnel in accordance with all relevant Electricity Safety Standards.
• Do not power MPMs and three phase connected Movtecs (Ph-N) without the upstream neutral connected. Failure to do so may damage the Movtecs and/or the load.
• Where the MPMs/Movtecs are connected to an earth, this must be a low impedance earth (<10 ) for correct operation.
PAGE 4
• X1-X4 connections may be at phase voltages dependant upon connection method.
• If connecting to the Movtec alarm outputs do not exceed the maximum permissible ratings as damage may occur.
• Movtecs must be installed in an enclosure or panel, ensure this does not cause their environmental ratings to be exceeded.
• Do not “Megger” or “Flash Test” circuits with Movtecs installed.
• The DINLINE Surge Counter (DSC) should not be used in voltage sensing mode with TDS-Movtecs. Voltage sensing mode is not compatible with TDS-Movtecs.
• All instructions must be followed to ensure correct and safe operation.
• Diagrams are illustrative only, and should not be relied on in isolation.
DINLINE INSTALLATION INSTRUCTIONS
2. INTRODUCTION
Movtecs are designed to protect mains powered equipment from the damaging effects of lightning and transients. They are ideal for point-of-entry shunt protection applications where robustness and high surge ratings are required.
The Movtec family is designed to suit many distribution systems including TN-C, TN-S, TN-C-S and TT. They can be selected for use with distribution systems with nominal voltages of 110/120V, 220/240V and 277Vrms at frequencies of 50/60 Hz.
The TDS Technology (Transient Discriminating Suppressor) units are specifically designed for distribution systems that may feature poor voltage regulation where the actual supply voltage may exceed the nominal ratings for extended periods.
This Installation Manual details the preferred procedure for the installation of the family of Critec Movtec™ Surge Diverters.
The Critec Movtec family includes:
• Critec Movtec, Single Mode, enhanced MOV technology units eg. (MT275V-135K-A)
• Critec TDS-Movtec, Single Mode, TDS technology unit featuring high over-voltage withstand for added robustness (TDS-MT-
277)
• Critec TDS-Movtec, Three Mode, TDS technology unit featuring high over-voltage withstand for added robustness (TDS-MTU)
TDS-Movtec units are coloured blue for easy identification, while enhanced MOV technology units are coloured red.
In this manual, reference to “ Movtec” also includes “TDS-Movtec”.
PAGE 5
GLOBAL LIGHTNING TECHNOLOGIES
This manual also details the installation of the MPM (Movtec Protection Module). The MPM is a supplied enclosure with three Movtecs and a high energy neutral to earth protection device for three phase protection. The MPM is often used where Movtecs can not be fitted in an existing switchboard and must be mounted externally. Therefore the Movtec installation instructions are also applicable to the MPM. Section 11 gives details which are specific to the MPM.
Two standard MPMs are available:
• Critec TDS-MPM, Single Mode, TDS Technology unit (uses 3 x TDS-MT-277)
• Critec MPM-275V, Single Mode, Enhanced MOV Technology unit (uses 3 x MT275V­135K-A)
PAGE 6
Alarm Contact Terminals
T2 Terminal
X3-X4 For A-N/A/N-E configeration option
Status Indicator
X1-X2 For connection to optional Mimic Panel (Ref. Section 15)
SINGLE MODE
MOVTEC
T1 Terminal
DINLINE INSTALLATION INSTRUCTIONS
Alarm Contact Terminals
Phase Terminal
Status Indicator
Earth Terminal
THREE MODE
MOVTEC
Neutral Terminal
3. PROTECTION CONCEPTS
To optimise effectiveness of installed protection a concept of “Unprotected” and “Protected” wiring should be followed.Wiring from the transient source to the Movtec should be considered “Unprotected” and kept remote from all other wiring (approximately 300mm) where possible. Wiring on the equipment side of the Movtec should be considered “Protected”.
The separation of “Protected” from “Unprotected” wiring is recommended in order to minimise the risk of transients conducted on “Unprotected” wiring cross coupling on to “Protected” circuits, thus compromising the level of protection available from the Movtec.
PAGE 7
PAGE 8
GLOBAL LIGHTNING TECHNOLOGIES
Keep other cables and equipment away from this area.
Unprotected zone Protected zone
DINLINE INSTALLATION INSTRUCTIONS
4. MOUNTING & CAUTIONS
The performance of surge diverters can be dramatically affected by the method of connection (refer section 7). Where possible select a mounting method that allows the Movtec to be connected in the “Preferred Connection Method”.
Failure of a Movtec under severe AC over­voltage, such as 11kV on 240V mains, can result in the generation of significant heat. Consideration should be given to ensure that Movtecs are not installed in close proximity to combustible materials.
Units must be installed in an enclosure or panel to provide the appropriate degree of electrical and environmental protection.
Only use enclosures that:
• Do not cause the Movtec temperature to exceed 60 deg C
• Provide adequate electrical and safety protection
• Prevent the ingress of moisture and water
• Allow Movtec Status Indication to be inspected
PAGE 9
GLOBAL LIGHTNING TECHNOLOGIES
5 VOLTAGE RATINGS
The TDS (Transient Discriminating Suppressor) technology has been specifically developed to cater for abnormal over-voltage conditions that may occur on sites with poor voltage regulation, or due to wiring or distribution faults. The TDS units feature an extremely high over-voltage withstand to eliminate heat build up that can occur with standard technologies when the protection devices start to clamp on the peak of each abnormal mains cycle.
Traditional MOV technology (eg MT-275V/ 135K/A) is not suitable in applications where sustained over-voltage conditions can be experienced.
PAGE 10
Examples of poorly regulated voltage environments include:
• Smaller power generation supplies
• Sites with large earth currents
• Variable motor speed control circuits
• High harmonic voltage environments (non-
linear loads)
The TDS range of Movtecs with a higher over-voltage withstand may be able to be used in these environments following advice.
Transient protection devices are usually rated to protect against non-repetitive pulses from such sources as direct or induced lightning strikes. They are not designed to provide protection against repeated cyclic anomalies. Nor are they designed to provide protection
Loading...
+ 22 hidden pages