ERICO TDS-DINLINE Surge Suppressor User Manual

Page 1
SURGE SUPPRESSOR
Handbook No:
HB-HBCR-109
© Copyright
INSTALLATION INSTRUCTIONS
Includes TDS-AR Alarm Relay and TDS-SC Surge Counter
ISSUE: 3 April 2003
Page 2
INSIDE FRONT COVER
(Blank)
Page 3
CONTENTS
Page
Page
1. Warnings ... ... ... ... ... ... ... ... ... ... ... 4
2. Introduction ... ... ... ... ... ... ... ... ... ... 5
3. Quick Installation Guide ... ... ... ... ... ... 5
4. Protection Concepts .. ... ... ... ... ... ... ... 6
5. Mounting ... ... ... ... ... ... ... ... ... ... ... 7
6. Voltage Ratings ... ... ... ... ... ... ... ... ... 8
7. Protection Modes .. ... ... ... ... ... ... ... ... 8
8. Conductor Sizes ... ... ... ... ... ... ... ... ... 10
9. Conductor Length ... ... ... ... ... ... ... ... 11
10. RCD, ELCB ... ... ... ... ... ... ... ... ... ... 14
11. Isolation and Fusing .. ... ... ... ... ... ... 15
12. Status Indication ... ... ... ... ... ... ... ... 17
13. Maintenance & Testing .. ... ... ... ... ... 18
14. Alarm Relay (TDS-AR) .. ... ... ... ... ... 19
15. Surge Counter (TDS-SC) ... ... ... ... ... 26
16. Typical Domestic Installation ... ... ... 29
17. Extended Warranty ... ... ... ... ... ... ... 30
18. Six Point Plan ... ... ... ... ... ... ... ... ... 31
PAGE 3
Page 4
DSD INSTALLATION INSTRUCTIONS
1. WARNINGS
• Prior to installation ensure that the unit is of the correct voltage and frequency, and is the type recommended for the local power distribution, and for the equipment being protected.
• Hazardous voltages may exist internally to the modules. The units should be installed (and replaced) only by qualified personnel in accordance with all relevant Electricity Safety Standards.
• Do not power three phase connected units without the upstream neutral connected. Failure to do so may damage the units and/ or the load.
• Where the unit has an earth terminal, this must be connected to a low impedance earth (<10 ) for correct operation.
PAGE 4
• If connecting to the TDS Opto-coupler alarm outputs do not reverse the +/­connections or exceed the maximum permissible ratings as damage may occur.
• Use only the TDS-AR Alarm Relay with TDS-DINLINE.
• Use only TDS-SC Surge Counter with TDS DINLINE.
• Units must be installed in an enclosure or panel, ensure this does not cause the units environmental ratings to be exceeded.
• Do not “Megger” or “Flash Test” circuits with TDS-DINLINE units installed.
• All instructions must be followed to ensure correct and safe operation.
• Diagrams are illustrative only, and should not be relied on in isolation.
Page 5
2. INTRODUCTION
This Installation Manual details the preferred procedure for the installation of TDS­DINLINE™ SURGE SUPPRESSORS and options.
The TDS-DINLINE SURGE SUPPRESSORS are available in a variety of surge ratings, which are packaged in the 2M, 4M and 8M “DIN 43 880” compliant enclosures. They are designed to suit many distribution systems including TN-C, TN-S, TN-C-S (MEN) and TT. They can be selected for use with distribution systems with nominal RMS voltages of 110/ 120, 220/230/240V or 277V at frequencies of 50/60 Hz.
Recommended installation and connection of the ALARM RELAY (TDS-AR) is detailed in
Section 14. Installation and connection of the Surge Counter (TDS-SC) is detailed in section
15.
3. QUICK INSTALLATION GUIDE
Install in the following manner:
1. Ensure that power is removed from the area and circuits to be connected.
2. Install the DIN mounting rail, if not fitted.
3. Snap lock the Surge Suppressor to the rail.
4. Connect wiring to the indicated terminals.
5. Ensure compliance with supplied instructions.
6. Apply power and observe correct operation of Status Indicators, and alarm facilities if utilised.
PAGE 5
Page 6
DSD INSTALLATION INSTRUCTIONS
4. PROTECTION CONCEPTS
To optimise effectiveness of installed protection a concept of “Unprotected” and “Protected” wiring should be followed. Wiring from the transient source to the Surge Suppressor should be considered “Unprotected” and kept remote from all other wiring (approximately 300mm) where possible. Wiring on the equipment side of the Surge Suppressor should be considered “Protected”.
The separation of “Protected” from “Unprotected” wiring is recommended in order to minimise the risk of transients conducted on “Unprotected” wiring cross coupling on to “Protected” circuits, thus compromising the level of protection available from the Surge Suppressor.
PAGE 6
Keep other cables and equipment away from this area.
Unprotected zone Protected zone
Page 7
5. MOUNTING
Surge Suppressors are designed to clip to 35mm top hat DIN rails (to Standard EN50022). Unless otherwise mechanically restrained, use horizontal DIN rails with the
Surge Suppressor fixing clip to the bottom, ie label text the correct way up.
Units must be installed in an enclosure or panel to provide the appropriate degree of electrical and environmental protection.
35 mm DIN rail (EN50022)
1
Only use enclosures that:
• Do not cause the internal temperature to exceed 55 deg C.
• Provide adequate electrical and safety
2
protection.
• Prevent the ingress of moisture and water.
• Allow Surge Suppressor Status Indication to be inspected.
PAGE 7
Page 8
DSD INSTALLATION INSTRUCTIONS
6. VOLTAGE RATINGS
Ensure that the correct voltage rating unit is installed. Exceeding the nominal voltage rating under transient conditions may affect product life. Do not exceed the Maximum Permissible Abnormal Over Voltage rating.
Model Nominal Voltage Permissible
TDS XXX-120 110-120 Vac 240Vac
TDS XXX-208 208 Vac 260 Vac
TDS XXX-240 220-240 Vac 415 Vac
TDS XXX-277 220-277 Vac 480 Vac
PAGE 8
Maximum
Abnormal
Over Voltage
7. PROTECTION MODES
Protection Modes refers to how the internal protection is arranged and applied to the circuit to be protected.
TDS-DINLINE Surge Suppressors are Single Mode units which provide protection between two conductors connected to the terminals marked T1 and T2. These units can be connected to provide protection from Phase­Neutral* or Phase-Earth* or Neutral-Earth. To allow the status indication and alarm circuitry to operate, a neutral connection is required for Phase-Earth* configured units, and a Phase* connection is required for Neutral-Earth configured units.
* Note. Some users may be used to the
terminology “Active” or “Line”, in place of “Phase”. For consistency “Phase” is used throughout this documentation.
Page 9
SINGLE MODE UNITS
CONNECTION OPTIONS
Protection
T1
T2
X
Status
Electronics
Ph-E ProtectionPh-N Protection N-E Protection Ph-Ph Protection
Ph
NPh
E
Ph N
T1 T2 XT1 T2 X
PROTECTION MODE
Terminals Ph-N Ph-E N-E Ph
T1 Ph E E Ph
T2 NPhNPh
X PhNPhPh
NPh
E
T1 T2 X
Ph
x
T1 T2 X
PhyPh
x - Phy
PAGE 9
x
x
y
x
Page 10
DSD INSTALLATION INSTRUCTIONS
Phase to Phase protection can also be provided by Surge Suppressors, provided that the nominal and maximum voltage ratings are not exceeded.
8. CONDUCTOR SIZES
Each Surge Suppressor terminal is designed to accept wire sizes from 1.5mm2 to 6mm2, solid or stranded conductor. Insulation should be stripped back 8mm before terminating into the tunnel terminal.
Where two conductors require termination in the same tunnel terminal, conductors should be limited to a maximum size of 4mm2.
Do not use excessive force when tightening the terminal.
PAGE 10
8mm
Insulation cut back too far
1.5-6 mm
Correct
2
conductor
Insulation not cut back far enough
Page 11
9 CONDUCTOR LENGTH
To optimise transient performance, attempt to connect units in the “Preferred” fashion as depicted on pages 11 and 12. Some units have double terminals to facilitate this. Take care not to run parallel “protected” and “unprotected” wiring.
Where this is not possible due to layout or conductor sizing, use the “Non-preferred” “T” connection method as depicted on page 13. With this connection method, the “T” lead length should be kept as short as practicable (less than 100mm) and wires should be bundled together. The “T” conductor should be equal in size to the main conductor, up to a maximum of 6mm2.
PREFERRED CONNECTION METHOD
Separate wires
Ph Ph Ph
Ph
Ph Ph
CORRECT
INCORRECT
NON-PREFERRED CONNECTION METHOD
Keep Short
Keep Close
T1 T2
T1 T2
CORRECT
INCORRECT
PAGE 11
Page 12
Supply Ph
N E
DSD INSTALLATION INSTRUCTIONS
PREFERRED CONNECTION METHOD EXAMPLE FOR Ph-E PROTECTION
Supply
Ph
N E
Maximum conductor size 6mm
T2T
T
1T1
X
2
Maximum
2
conductor size 2x4 mm or 1x6 mm
T2T1X
Protected Equipment
Maximum conductor size 4mm
2
Protected Equipment
2
2
PAGE 12
TD140-2S
TDS1160-8S
Page 13
Supply Ph
N E
Bundle together
NON-PREFERRED "T" CONNECTION METHOD EXAMPLE FOR Ph-E PROTECTION
Supply
Protected Equipment
Keep as short as practical
Ph
N E
Bundle together
Protected Equipment
Keep as short as practical
T2T1X T2T
2
Maximum conductor size 6mm
Maximum conductor size 6mm
TDS 140-2S
T1T
1
2
TDS1160-8S
X
2
PAGE 13
Page 14
DSD INSTALLATION INSTRUCTIONS
10. RCD, ELCB
Where RCDs/ELCBs (Residual Current Devices / Earth Leakage Circuit Breakers) are fitted the Surge Suppressor units should be installed in the circuit prior to these devices
RCD
ELCB
Protected Equipment
CORRECT
PAGE 14
(ie upstream). Where this can not be avoided and RCDs/ELCBs are installed upstream, nuisance tripping of the RCD/ELCB may occur during transient activity.
Contact your local representative for advice if upstream RCDs/ELCBs can not be avoided.
RCD
ELCB
PhPh
INCORRECT
Page 15
11. ISOLATION AND FUSING
Overcurrent and short circuit protection must be provided to protect the Surge Suppressor and associated wiring if a fault develops. The overcurrent protection should be installed in such a manner to also provide a means of isolating the TDS-DINLINE module from the mains supply. This is an important safety consideration and is required in the event that any future maintenance or testing is needed.
For Surge Suppressors installed in the “preferred” connection method (page 12), upstream overcurrent protection should be installed based on the maximum current carrying capacity of the conductors. Australian regulations AS3000-1991, Table B2 specifies the following upstream protection for the protection of single phase circuits.
A mm
Ph
2
A mm
Ph Ph
2
Conductor Size Required Fuse
2
CB or Fuse Rewirable Fuse
A mm
2
1.5 mm
2
2.5 mm
2
4.0 mm
2
6.0 mm
Fuse selection based on maximum current carrying capacity of conductor. Smaller rated fuse may be selected if required. CB = Circuit Breaker.
16A 12A
20A 16A
25A 20A
32A 25A
PAGE 15
Page 16
DSD INSTALLATION INSTRUCTIONS
For Surge Suppressors installed in the “non­preferred” connection method (page 13), depending upon the size and fusing in the main circuit, the “T” connection may require independent fusing to be installed.
Circuits with upstream protection rated at greater than 100A must have a 100A HRC fuse or circuit breaker installed in the T connection as detailed by the following diagram.
Warning:
Isolation/fusing installed in the “T” connection may disconnect the Surge Suppressor from the circuit/equipment to be protected. The remote alarm contacts of the ALARM RELAY (TDS­AR) should be used to detect this occurrence. Operation of the isolation/fuse will remove the protection from the circuit.
PAGE 16
Supply
A
A mm
2
B
B mm
2
Ph
Supply Upstream* T-Connection Required Conductor Protection Size T-Connection Size Fuse
2
A fuse rating B mm2 B fuse rating
A mm
2
1.5 mm
2.5 mm
4.0 mm
6.0 mm >6.0 mm >6 mm
* Fuse rating A selection based on maximum current carrying capacity of
conductor. Smaller rating fuse may be selected ir required.
** Short circuit protection selection based on I
16A 1.5 - 6 mm2Nil
2
20A 2.5 - 6 mm2Nil
2
25A 4 - 6 mm
2
32A 6 mm
2
<100A 6 mm
2
>100A 6 mm
2
2
2
2
t rating of cable and fuse.
2
Nil Nil Nil** 100 A**
Page 17
The selection of the 100A HRC fuse is not based on the load carrying capacity of the main circuit but the “T” connection I2t rating. The “T” connection under normal conditions does not carry the load current. Only under surge or fault conditions does this connection carry large currents. Under Australian Standard AS3008.1-1989 it is permissible to rate the protection for these types of circuits by the I2t ratings of the cable. For installation of Surge Suppressor in countries not covered by these regulations it is recommended that this practice be followed, unless it conflicts with the compliance of the local regulations.
12. STATUS INDICATION
A characteristic of all transient and surge protection devices is that they degrade in proportion to the magnitude and number of
incident surges to which they have been subjected. Status indication should be periodically monitored to determine if replacement is required.
2S units
These units are identified by the single Status Indicator provided on the front panel. When power is applied and full surge capacity is available the Status Indicator will be illuminated. Should the indicator fail to illuminate the Surge Suppressor should be replaced, as optimum protection is no longer provided. Note: The Status Indicator will not operate (regardless of surge capacity) if power is not available.
4S units
These units are identified by two Status Indicators which are provided on the front panel. These Status Indicators monitor
PAGE 17
Page 18
DSD INSTALLATION INSTRUCTIONS
separate protection segments. Each Status Indicator is illuminated when power is available and when full surge capacity is available by that segment. The Surge Suppressor should be replaced if either Status Indicator fails to illuminate. Note: The Status Indicators will not operate (regardless of surge capacity) if power is not available.
8S units
These units are identified by four Status Indicators which operate similar to above. The Surge Suppressor should be replaced if any two or more Status Indicators fail to illuminate.
PAGE 18
13. MAINTENANCE & TESTING
Before removing any unit from service ensure that power to the device is isolated. Replacement of any Surge Suppressor should only be undertaken in accordance with all relevant Electricity and Safety Standards by suitably qualified personnel.
TDS-DINLINE units should be inspected periodically, and also following any periods of lightning or transient activity. Check the status indicators and replace if recommended in Section 12 -STATUS INDICATION.
For high transient exposure sites or those of a critical operational nature, it is recommended that the alarm outputs be monitored to provide an additional warning of reduced capacity (refer Section 14 - ALARM RELAY­TDS-AR).
Page 19
TDS-DINLINE Surge Suppressor units are designed for optimum performance under severe transient activity. To provide this performance, electronic components in the unit are encased in a patented proprietary, shock and thermal absorbent compound.
Units cannot be serviced, they must be replaced.
Do not attempt to open or tamper with the units in any way as this may compromise performance and will void warranty.
Do not “Megger” or perform other types of electrical tests that apply voltages greater than the nominal operating voltage of the Surge Suppressor. The Suppressor will attempt to limit these voltages thereby affecting the test result. Where these tests must be performed, remove the Surge Suppressor from circuit first.
14. ALARM RELAY (TDS-AR)
The Surge Suppressor status monitoring circuit which provides the visual status display also provides a low voltage opto­coupler alarm output circuit. This should only be connected to the TDS ALARM RELAY. The TDS-AR voltage free alarm contacts may then provide output to external alarm systems or remote monitoring circuits.
The TDS ALARM RELAY provides fully isolated potential free change-over alarm output contacts. One TDS-AR can be used per Suppressor opto-coupler alarm or Multiple Suppressor opto-coupler alarms can be connected in series to the one TDS-AR to provide a common output.
PAGE 19
Page 20
DSD INSTALLATION INSTRUCTIONS
1 x TDS-AR supports:
20 x TDS140-2S or 10 x TDS 180-4S or 5 x TDS 1160-8S or relative combinations.
It is recommended that the TDS-AR unit be powered from the same power circuit that feeds to the Surge Suppressor being monitored, however it can be powered from other circuits. This allows for example, one TDS-AR unit to be connected to separate Surge Suppressors that are protecting a three phase circuit.
To satisfy Australian wiring regulations the phase supply to the TDS-AR needs to be protected by an overcurrent fuse/circuit breaker. The overcurrent protection should be selected according to the wiring size
PAGE 20
connecting to the TDS-AR Phase and Neutral terminals. For reference a table of values is given on page 24.
Note. Depending upon the usage of the TDS­AR output contacts, failure of power to the TDS-AR may be interpreted as a failure of one or more Surge Suppressors. Visual inspection of all units Status displays would determine this.
Page 21
STATUS
Protection Operational
Protection Alarm
Fault Mode
DISPLAY
EXPLANATION
Normal
16
Fault
12
14
Normal operation
Normal (green) indicator ON Red indicator OFF Relay is energised Power is supplied
Normal
Normal
16
Fault
12
Fault
14
Surge Suppressor in alarm mode or power to Suppressor has been removed
Normal (green) indicator OFF Red indicator ON Relay is de-energised Power is supplied
Power to TDS-AR removed Protection status unknown
Normal (green) indicator OFF Red indicator OFF Relay is de-energised Power is OFF
16
12
14
PAGE 21
Page 22
Ph
DSD INSTALLATION INSTRUCTIONS
SINGLE ALARM CONNECTION EXAMPLE
To transient
N E
protected equipment
TDS140-2S
PAGE 22
T2T1X
NL
TDS-AR
Opto-coupler output
WARNING - Connections are polarity sensitive. Do not reverse.
Voltage free contacts
To remote alarm circuit
Page 23
MULTIPLE ALARM CONNECTION EXAMPLE
T1T
1
T2T2X
X
T
2T1
✽✽
TDS180-4S TDS140-2S
WARNING - Connections are polarity sensitive. Do not reverse.
NL
TDS-AR
Voltage free contacts
To remote alarm circuit
PAGE 23
Page 24
DSD INSTALLATION INSTRUCTIONS
TDS-AR SPECIFICATIONS:
Output Contact Ratings
Nominal switching capacity
Maximum switching power
Maximum switching voltage
Maximum switching current
Input to output isolation
Note: TDS-AR operates on supply voltages
of 100-480V Vrms.
TDS-AR OVERCURRENT PROTECTION
The power supply to the TDS-AR circuit must be provided with upstream overcurrent protection. The fuse rating should be based on
PAGE 24
2A 30VDC
60W 125VA
220VDC, 250VAC
2A
4kV
the wiring size used to connect to the TDS-AR Ph & N terminals.
Australian regulations AS3000-1991, Table B2 specifies the following upstream protection for single phase circuits, unenclosed in air.
Cable Size HRC Fuse or CB Rewirable Fuse
2
1.5mm
2.5mm
4mm
6mm
16A 12A
2
20A 16A
2
25A 20A
2
32A 25A
Where overcurrent protection of the appropriate rating or smaller is already fitted in the upstream circuit, overcurrent protection at the TDS-AR will not be required.
Page 25
ALARM TESTING
Testing of the Alarm Relay which is connected to a fully functional Surge Suppressor unit can be accomplished by removing power to the Surge Suppressor only. The Alarm Relay Status indication and output contacts should alter from the Normal to Fault condition.
Testing of the Alarm Relay unit alone may be accomplished by disconnecting the + / ­connections to the unit. When power is applied the “Fault” Status Indicator should be illuminated. By connecting the + / - terminals together, the “Normal” Status Indicator should be illuminated. The output contacts should alter to the appropriate state.
USE OF OTHER INTERFACES
Only ERICO TDS-AR units are recommended for the interfacing of equipment to the TDS­DINLINE opto-coupler alarm output circuit.
The direct connection of other equipment to the opto-coupler alarm output circuit may not provide sufficient isolation or exceed the opto­coupler specifications. This may damage the Surge Suppressor and/or the connected equipment. Warranty may be voided under such circumstances.
SURGE SUPPRESSOR OPTO-COUPLER ALARM
Opto-coupler
Opto­coupler
Protection diode
Vce = 30V DC
Ic = 150 mA
Note: TDS XXX-4S and TDS XXX-8S have respectively 2 and 4 opto-couples connected internally in series.
PAGE 25
Page 26
DSD INSTALLATION INSTRUCTIONS
15. TDS-SC SURGE COUNTER
The Surge Counter is designed to interface to the TDS DINLINE units via the supplied CT, to record the number of surges and impulses diverted. This is achieved by measuring the transient current diverted by the TDS protection device. It is important that the CT be installed into the circuit where it is measuring the surge current only, and not where mains load current is passed through the core. Method 1 and Method 2 (page 28) detail the correct connection. Page 27 shows an incorrect connection as the equipment load current is passed through the CT core. The magnetic field from the load carrying conductor may cause the CT core to saturate. The surge Counter may fail to record any transients and additionally dangerously high voltages may be present on the TDS-SC & CT terminals.
PAGE 26
WARNINGS
• Do not install CT into load current carrying circuits.
• CT must be installed into surge current path only.
• Only install the CT and Surge Counter after all power and transient sources are removed and isolated from the equipment the Surge Counter is to monitor.
• Do not open circuit or disconnect connections on the secondary of the CT when monitored circuit is powered or connected to possible transient source. Hazardous voltages may exist in the secondary circuit and in the CT/TDS-SC if these instructions are not followed.
Page 27
• Only this CT should be used with the TDS­SC Surge Counter, other suppliers devices may not operate correctly or pose a safety hazard.
• These instructions should only be carried out by qualified personnel in accordance with relevant national electrical and safety codes. Hazardous voltage may exist in the monitored system.
SURGE COUNTER CONNECTION METHODS*
TDS-SC
0586
LOAD
C1C2
CT
Incorrect Method
* Typical connections only
PAGE 27
Page 28
DSD INSTALLATION INSTRUCTIONS
SURGE COUNTER CONNECTION METHODS*
TDS Surge Suppressor
PAGE 28
0586
C1C2
TDS-SC
Surge Current
LOAD
0586
C1C2
TDS-SC
CT
Correct Method 1 Correct Method 2
* Typical connections only
Surge Current
CT
LOAD
Page 29
14. TYPICAL DOMESTIC INSTALLATION (from 80A fused supply)
A
TDS140-2S-277
N
T2T1X
L
L
I
I G H T S
RCD
G
ELCB
H T S
G
G
G
P
P
O
O
G
P
P
O
O
RCD Protected
Neutral Neutral Earth
MEN Link
PAGE 29
Page 30
DSD INSTALLATION INSTRUCTIONS
17. EXTENDED WARRANTY
This product has a limited warranty to be free from defects in materials and workmanship for a period of five (5) years from the date of dispatch from the Manufacturer. The Purchaser acknowledges that lightning is a natural event with statistical variation in behaviour and energy levels which may exceed product ratings, and 100 % protection is not offered and cannot be provided for. Therefore the Manufacturer’s liability is limited to the repair or replacement of the product (at the Manufacturer’s sole option) which in its judgement has not been abused, misused, interfered with by any person not authorised by the Manufacturer, or exposed to energy or transient levels exceeding the Manufacturer’s specifications for the product. The product must be installed and earthed (where applicable) in strict accordance with the Manufacturer’s specifications and all relevant national Electricity and Safety Standards. The Manufacturer and the
PAGE 30
Purchaser mutually acknowledge that the product, by its nature, may be subject to degradation as a consequence of the number and severity of surges and transients that it experiences in normal use, and that this warranty excludes such gradual or sudden degradation. This warranty does not indemnify the Purchaser of the product for any consequential claim for damages or loss of operations or service or profits. Customers should contact their nearest manufacturer’s agent to obtain a Product Repair Authorisation Number prior to making any claim under this warranty. This is only a summary of the warranty given by the Manufacturer. The full text of the warranty is set out in the Manufacturer’s Conditions of Quotation and Sale. The above limited warranty is additional to rights which arise in respect of the sale of industrial and technical products and services to knowledgable buyers under the Australian Trade Practices Act 1974 as amended.
Page 31
18. SIX POINT PLAN
TDS-DINLINE SURGE SUPPRESSORs form an important part of the much larger ERICO lightning, surge and transient protection philosophy (ERICO Lightning Technologies “Six Point Plan”). The level of protection and the degree of attention dedicated to each of the six points will require careful consideration for each site. The degree of protection required is determined by the individual site location/exposure with the aid of risk management principals.
For further advice on your protection needs please contact your local representative.
Capture the lightning strike
Conduct the strike to ground safely
Dissipate the energy through a low impedance earth system
Eliminate earth loops and differentials
Protect equipment from surges on power lines
Protect equipment from transients on telecommunication and signal lines
PAGE 31
Page 32
TDS-DINLINE CONNECTION OPTIONS
Ph-E ProtectionPh-N Protection N-E Protection Ph-Ph Protection
Ph
NPh
E
Ph N
E
NPh
Ph
PhyPh
x
x
Terminals Ph-N Ph-E N-E Ph
www.erico.com
T1 T2 XT1 T2 X
PROTECTION MODE
T1 Ph E E Ph
T2 NPhNPh
X PhNPhPh
T1 T2 X T1 T2 X
x - Phy
x
y
x
Loading...