ERICO ER Series 7m Stainless Steel Guyed Mast User Manual

INSTRUCTION SHEET
®
ERICO INTERCEPTOR SI25i, SI40i or SI60i
Installation Instructions for 7m Stainless Steel Guyed Mast - ER Series
Mast Detail
1
-
Stainless Steel Cable Tie (ERICO Part # CABTIESS) Three every 3.3FT [1M]
For complete grounding system refer to Detail "A"
SI INTERCEPTOR
®
(ERICO Part # SI25i, SI40i or SI60i
Mast Adapter (ERICO Part # INTCPTSIIER2)
Bonding Clamp (ERICO Part # LPC570)
Guy Kits (ERICO Part # GUYKIT7M/GRIP) (ERICO Part # GUYKIT4M/GRIP) Do not over-tension guy wires (Slightly sagging)
Stainless Steel Mast Base (ERICO Part # ER3BASESS) Refer to Detail "B"
Preferred Angle 45° - 60°
1
-
INTCPTSIIER1
ER11000SS
ER23000SS
ER33000SS
ER3BASESS
LPC570 Bronze Pipe Bonding Clamp Installing contractor to field adjust and insure a secure bond on highest ER series mast
LPC126R Copper Cable
Not to Scale
Detail "A"
2
-
Suggested triangular grounding system for each downconductor:
Two downconductors are required
Lightning Event Counter Refer to installation manual for alternate locations (ERICO Part # LECIV)
2/0 Conductor (3 x 20FT [6.1M] length) Enclosed in ERICO GEM material
Minimum 5/8" X 8' [16mm X 2.4M] long ground rod in three locations
(ERICO Part # LPC805) Copper Strap
(ERICO Part # A930W004) Drive-in Type Anchor
(ERICO Part # LPC126R) Copper Cable
2
Typical LPC126R Cable Strap
-
Not to Scale
Detail "B"
4 HOLES, Ø1/2 [12.5mm]
Lightning Event Counter (ERICO Part # LECIV)
Downconductor (ERICO Part # LPC126R)
®
ERICO CADWELD "GR" Connection or mechanical connection (ERICO Part # LPC790)
Ground Inspection Well
Bond to the existing building ground system
®
7 [178mm]
9 [229mm]
The grounding system shown in the detail is a suggested layout. Each radial consists of a trench 20FT [6.1M] in length and approximately 2.5FT [0.8M] deep. 20FT [6.1M] of 2/0 conductor is laid in the trench and is connected to the ground rod using "GY" CADWELD connection. The conductor in each trench is encased in ERICO GEM material. Ground rods must extend 10FT [3M] below ground level.
Note: This is one of several alternative installation methods. Refer to ERICO installation handbook for more details.
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2. All instructions must be
3. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4. damage, serious bodily injury and death.
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT
www.erico.com
and from your ERICO customer service representative.
completely
followed to ensure proper and safe installation and performance.
IP79121_B
1 OF 1