ERICO ER Series 7m Stainless Steel Cantilevered Mast User Manual

INSTRUCTION SHEET
®
ERICO INTERCEPTOR SI25i, SI40i or SI60i
Installation Instructions for 7m Stainless Steel Cantilevered Mast - ER Series Terminal Elevation: 5m Above Structure
(ERICO Part # LPC805) Copper Strap
(ERICO Part # A930W004) Drive-in Type Anchor
SI INTERCEPTOR (ERICO Part # SI25i, SI40i or SI60i)
®
Mast Detail
INTCPTSIIER1
(ERICO Part # LPC126R) Copper Cable
Mast Adapter
ER11000SS
(ERICO Part # INTCPTSIIER1)
Stainless Steel Mast (ERICO Part # ER11000SS)
1
-
Bonding Clamp (ERICO Part # LPC570)
2
-
LPC570 Bronze Pipe Bonding Clamp Installing contractor to field adjust and insure a secure bond on highest ER series mast
ER23000SS
ER33000SS
Stainless Steel Mast (ERICO Part # ER23000SS)
LPC126R Copper Cable
Stainless Steel Cable Tie
3
Typical LPC126R Cable Strap
-
Not to Scale
1.57 [39.9mm]
End View
2
Typical ALOF1GS Wall Bracket Base
Not to Scale
2 Holes,
3.54 [89.9mm]
0.43 [10.9mm]
4.72 [119.9mm]
(ERICO Part # CABTIESS) Three every 3.3FT [1M]
1
Not to Scale
-
3.3FT [1M]
3.3FT [1M]
3.3FT [1M]
Stainless Steel Mast (ERICO Part # ER33000SS)
3.3FT [1M]
3.3FT [1M]
3.3FT [1M]
Mast Support Bracket
Detail "A"
(ERICO Part # ALOF1GS)
Two downconductors are required
3
-
Lightning Event Counter Refer to installation manual for alternate locations (ERICO Part # LECIV)
Lightning Event Counter (ERICO Part # LECIV)
Downconductor (ERICO Part # LPC126R)
®
ERICO CADWELD "GR" Connection
®
or mechanical connection (ERICO Part # LPC790)
Ground Inspection Well
2/0 Conductor (3 x20 FT [6.1M] length)
For complete grounding system refer to Detail "A"
Enclosed in ERICO GEM material
Minimum 5/8" X 8' [16mm X 2.4M] long
Bond to the existing building ground system
ground rod in three locations
Suggested triangular grounding system for each downconductor:
The grounding system shown in the detail is a suggested layout. Each radial consists of a trench 20FT [6.1M] in length and approximately 2.5 FT [0.8M] deep. 20FT [6.1M] of 2/0 conductor is laid in the trench and is connected to the ground rod using "GY" CADWELD connection. The conductor in each trench is encased in ERICO GEM material. Ground rods must extend 10FT [3M] below ground level.
Note: This is one of several alternative installation methods. Refer to ERICO installation handbook for more details.
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at
1.
www.erico.com
ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2. All instructions must be
3. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property
4. damage, serious bodily injury and death.
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT
www.erico.com
and from your ERICO customer service representative.
completely
followed to ensure proper and safe installation and performance.
IP79109_B
1 OF 1
© 2006, 2014 ERICO International Corporation.
Loading...