ERICO EPD240TDFL User Manual

ELE
GRN / YEL
FIG.3
FIG.1FIG.
2
Primary Surge Protectors
Parallel TVSS Filters
EPD120/240TDFL (120/240VAC)
Installation Instructions
TM
R
LINE 1 LINE 2
UNIT OPE RAT ING S TAT US
ELECTRICAL PANEL
LINE2LINE
1
N
G
WIRE UNIT TO AVAILABLE CIRCUIT BREAKER IN ELECTRICAL PANEL KEEP LEAD LEN GTH TO A MINIM UM - TWIST WIRES TOGETHER
BLACK
WHITE
GREEN / YELLOW
EPD
RED
L1
L2
N
G
LID
PREPARATION
DANGER: Electrical shock or burn hazard. Installation of Primary Surge Protector should be
made by qualified personnel. Failure to lockout electrical power during installation or maintenance can result in fatal electrocution or severe burns.
1. Disconnect and lockout power to the breaker box (load
center) or point where the Primary Surge Protector is to be installed. Follow all applicable electrical codes & procedures.
CAUTION: Verify line voltage does not exceed
Surge Protector voltage requirement.
PROTECTOR MOUNTING AND LOCATION
2. The Surge Protector is to be mounted directly to the
breaker box, to keep the wiring as SHORT as possible. The Surge Protector can be mounted on the top, the bottom, or the side of the load center, see FIG. 4. In general, it would mount on the side, immediately adjacent to the two pole breaker which will feed it. If physical obstructions prevent this, then the top or bottom mounting positions can be used.
BASE
MOUNTING
SCREWS
CTRICAL PANEL
LINE2LINE
1
N
G
TWIST WIRES TOGETHER
RED BLACK
WHITE
EPD
L
1
L
2
N
G
5. Remove the screws holding the lid and base of the Surge Protector together.
6. The base (or the complete Surge Protector if step 5 was omitted) can then be butted up against the load center, with the wiring and nipple fed into the load center. Using the provided locknut, fasten the nipple in place inside the load center.
7. Using the holes in the base of the Surge Protector as a template, drill four 3/16 diameter pilot holes in the wall surface.
8. Fix the base to the wall using the (4) #12 x 3/4-lg. screws supplied. See FIG. 2
9. Replace the lid of the Surge Protector back onto the base, and fix in position with the screws previously removed (the screw adjacent to the load center may not be able to be replaced).
10. Pull the wires firmly through into the load center to remove any slack present.
AC ELECTRICAL CONNECTION
11. The Surge Protector is to be installed parallel to the load center bus via a two pole circuit breaker. The circuit breaker rating should be 20A or 30A.
3. Having determined where the Surge Protector is to be mounted, provide a knockout in the load center to receive the ½” nipple provided as part of the Surge Protector.
4. If the load center metalwork is of sufficiently heavy gauge, or the Surge Protector is being mounted to the top of the load center, the Surge Protector may be supported by the nipple alone. If this is the case, DO NOT perform the outlined, shaded steps (steps 5, 7, 8 or 9).
12. Reference FIG. 3 or the front of the Surge Protector for the wiring diagram. Connect the wire leads from the Surge Protector, beginning with:
a) Ground (green/yellow wire) to ground bar b) Neutral (white wire) to neutral bar c) Line wires (black and red wires) to circuit breaker
NOTE: The green wire must be properly and securely connected to system ground.
1999 ERICO Inc, 34600 Solon Rd, Solon, OH 44139 Page 1 of 2 HB-HBCR-133, Rev: 2, Date: 18-MAY-2001
FIG.4
YSURGEPROTECTOR
NINFO
MOUNTING POSITIONS
Primary Surge Protectors
Parallel TVSS Filters
These wires should be TWISTED and kept as SHORT as possible. This will mean trimming these to length. DO NOT coil extra wire length, as this will impede the function of the Surge Protector. Keep bend radii large where applicable (4"-8” recommended).
ENGAGING POWER
13. Tighten and verify all connections, replace the internal cover of the load center, and engage power to the protector. Both Status LEDs should come on indicating correct operation. If not, disconnect power, check wiring, rectify any deficiencies, and repower. If still experiencing difficulties, please contact your supplier, or the manufacturer:
ERICO, Inc. Rail Electrical Products 34600 Solon Rd Solon OH 44139 Ph. (800) 447-7245 Ph. (440) 542-3939
EPD120/240TDFL (120/240VAC)
INDICATORS
14. There is one LED on the front panel for each line protected which, when illuminated, indicates that the protection circuitry is operating correctly for that line. If either LED has extinguished, the Surge Protector has sustained a surge beyond its ratings, and the protection has been compromised. While there may still be some protection provided by the parallel protection stages within the unit, the Surge Protector should be replaced immediately.
PRIMAR
SHOW
UR POSSIBLE
1999 ERICO Inc, 34600 Solon Rd, Solon, OH 44139 Page 2 of 2 HB-HBCR-133, Rev: 2, Date: 18-MAY-2001