ERICO DAR 275V User Manual

DINLINE ALARM RELAY (DAR)
INSTALLATION INSTRUCTIONS
1. PREPARATION
by qualified personnel. Failure to lockout electrical power during installation or maintenance can result in fatal electrocution or severe burns. Before making any connections be sure that power has been removed from all associated wiring, electrical panels, and other electrical equipment.
CAUTION NOTES:
1. The installation of this device should follow all
applicable electrical codes, such as the National Electrical Code.
2. Check to make sure line voltage does not exceed
DAR275V voltage ratings.
3. Follow all instructions to ensure correct and safe
operation.
4. Do not attempt to open or tamper with the DAR in
any way as this may compromise performance and will void warranty. No user serviceable parts are contained.
2. INTRODUCTION
Selected DSD, TDS & TDF DINLINE Surge Protection Devices include status monitoring circuits which provide visual status display of device capacity. They may also provide a low voltage opto-coupler alarm output circuit that can be connect to the DAR to provide potential free (Form C) change-over contacts. The DAR alarm contacts may be used to provide output to external alarm systems or remote monitoring circuits.
One DAR can be used per DSD/TDS/TDF opto-coupler alarm or up to 16 DSD opto-coupler alarms can be connected in series to the one DAR to provide a common output. It is recommended that the DAR be powered from the same power circuit that feeds the device(s) being monitored, however the DAR can be powered from other circuits. This allows for example, one DAR unit to be connected to separate SPDs that are protecting a three phase circuit.
MODEL NUMBER
DAR 275V
Note. Depending upon the usage of the DAR output contacts, failure of power to the DAR may be interpreted as a failure of one or more of the SPDs being monitored. Visual inspection of the DAR and SPDs status displays would determine this.
3. MOUNTING
The DAR is designed to clip to 35mm (top hat) DIN rails (standard EN50022). Unless otherwise mechanically restrained, use horizontal DIN rails with the DAR module spring clips to the bottom and the label text the correct way up.
NOTE: The DAR must be installed in an enclosure or panel that:
prevents the DAR temperature from exceeding
131°F (55°C)
• provides adequate electrical and safety protection
• prevents the ingress of moisture and water
• allows DAR status indicators to be inspected
4. ELECTRICAL CONNECTION
The interconnecting wiring should:
be of size #10 to #14 AWG (2.5mm² to 6mm²) solid or stranded conductor.
The wire insulation should be stripped back 5/16" (8mm).
NOTE: Do not use greater than 9inlbs (1Nm) of torque
when tightening the terminals.
CONNECTION TO TELECOMMUNICATIONS NETWORKS
The DAR is approved for use in Australia where the alarm contacts may be connected to private lines or building cabling associated with the telecommunications network. NO direct connection to the public switched network should be made.
www.erico.com Page 1 of 2
DINLINE ALARM RELAY
Totransient
Toremotealarmcircui
t
s
LNE
(4-6mm)
Bundle/twisttogether
Keep as short as practical
NL
INSTALLATION INSTRUCTIONS
5. INTERCONNECTION
When connecting the DAR to a single opto-coupler output the + terminal of the SPD should connect to the + terminal on the DAR. The – terminal should connect to the -- terminal.
protected equipment
N EPh
DSD 2S/2T
Opto-coupler output
+/- terminal connections are polarity sensitive. Do not reverse.
When connecting the DAR to multiple opto-couplers the opto ­couplers should be connected in series with + terminal of one connected to the – terminal of the next. The DAR + terminal should connect to + SPD terminal at one end of the series connection and the – DAR terminal connect to the – SPD terminal at the other end of the series connection.
N EPh N EPh
NPh
DAR
Voltage free contacts
NPh
DAR
Voltage free contact
6. FUSING AND ISOLATION
Overcurrent protection must be installed in the upstream circuit of the power supply to the DAR to provide protection to the unit itself and the wiring in case of fault conditions.
The fuse rating should be based on the wiring size used to connect to the DAR Ph & N terminals. Australian regulations AS3000-1991, Table B2 specifies the following upstream protection for single phase circuits, unenclosed in air.
Cable Size HRC Fuse or CB Rewirable Fuse
1.5mm2 16A 12A
2.5mm2 20A 16A
4mm2 25A 20A 6mm2 32A 25A
Where overcurrent protection of the appropriate rating or smaller is already fitted in the upstream circuit, overcurrent protection at the DAR will not be required
6. MAINTENANCE & TESTING
Before removing a DAR unit from service, ensure that the power has been removed. Maintenance, testing and replacement should only be undertaken by qualified personnel.
Testing of a DAR unit which is connected to a fully functional DSD unit can be accomplished by removing power to the DSD only. The DAR Status indication and output contacts should alter from the Normal to Fault condition.
Upto16connections per DARmodule
+/- terminal connections are polarity sensitive. Do not reverse.
5. STATUS INDICATION
Testing of the DAR unit alone may be accomplished by disconnecting the + / -connections to the unit. When power is applied the DAR “Fault” Status Indicator should be illuminated. By connecting the + / - terminals together, the “Normal” Status Indicator should be illuminated. The output contacts should alter to the appropriate state.
7. USE OF OTHER INTERFACES
STATUS
DISPLAY
EXPLANATION
Protection Operational
Normal
8
Fault
6
Normaloperation
Normal(green)indicatorON Red indicatorOFF Relayis energised Power is supplied
4
Protection Alarm Fault Mode
Normal
8
Fault
6
DSDinalarmmodeorpower
toDSDhasbeenremoved
Normal(green)indicatorOFF Red indicator ON Relayisde-energised Power is supplied
Normal
Fault
4
Power to DAR removed Protectionstatusunknown
Normal(green)indicatorOFF Red indicatorOFF Relayis de-energised Power is OFF
8
4
6
www.erico.com Page 2 of 2 Doc: HBCR1681, Rev: 1
Only DAR units are recommended for the interfacing of equipment to the DSD, TDS & TDF opto-coupler alarm output circuit(s). The direct connection of other equipment to these opto-coupler alarm outputs may not provide sufficient isolation or exceed the opto-coupler specifications. This may damage the SPD and/or the connected equipment. Warranty may be voided under such circumstances.
NOTE: In connecting to the SPD opto-coupler alarm output(s), do not reverse the +/- connections as damage may occur
Supply
See section 8for fusing details
Loading...