ERICO CSBIB User Manual

INSTRUCTION SHEET
INCH
mm
INCH
mm
lbs. (N)
lbs. (N)
lbs. (N)
CSBIB
STRUCTURAL ATTACHMENT FITTING I - BEAM ADAPTER
FM® Load Rating
All Directions
*Part Number
Flange Thickness Flange Width
UL® Load Rating
Across Beam Along Beam Down
lbs. (N) CSBIB075085(XX) 1/4 - 3/4 6 - 19 4 - 8.5 100 - 215 3740 (16635) 3740 (16635) 3740 (16635) 3900 (17345) CSBIB075145(XX) 1/4 - 3/4 6 - 19 4 - 14.5 100 - 365 3740 (16635) 3740 (16635) 3740 (16635) 3900 (17345) CSBIB125180(XX) 3/4 - 1-1/4 19 - 31 4 - 18 100 - 455 3740 (16635) 3740 (16635) 3740 (16635) 3900 (17345)
*(XX) = Finish Specifier
SECTION VIEW FRONT VIEW
ALONG BEAM
DOWN
ACROSS BEAM
Sway Brace assemblies are intended to be installed in accordance with NFPA-13 and the manufacturer's installation instructions.
The required type, number, and size of fasteners used for the structure attachment fitting shall be in accordance with NFPA-13.
WARNING:
ERICO products shall be installed and used only as indicated in ERICO product instruction sheets and training materials. Instruction sheets are available at 1. www.erico.com and from your ERICO customer service representative. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.2. All instructions must be completely followed to ensure proper and safe installation and performance. 3. Improper installation, misuse, misapplication or other failure to completely follow ERICO's instructions and warnings may cause product malfunction, property 4. damage, serious bodily injury and death. Products that are manufactured using spring steel components shall be used only in a non-corrosive indoor environment. 5.
6.
All pipe supports, hangers, intermediate components and structural attachments must ONLY be used as described herein and are NEVER to be used for any other purpose.
NOTE: All load ratings are for static conditions and do not account for dynamic loading such as wind, water or seismic loads, unless otherwise noted. The customer is responsible for:
a. Conformance to all governing codes. b. The integrity of structures to which the products are attached, including their capability of safely accepting the loads imposed, as evaluated by a qualified engineer. c. Using appropriate industry standard hardware as noted above.
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
UL is a registered trademark of Underwriters Laboratory, Inc. NFPA is a registered trademark of National Fire Protection Association.
CADDY, CADWELD, CRITEC, ERICO, ERIFLEX, ERITECH, and LENTON are registered trademarks of ERICO International Corporation.
TECHNICAL SUPPORT:
www.erico.com
CFS389_C
1 OF 2
© 2009 ERICO International Corporation
INSTRUCTION SHEET
CSBIB
STRUCTURAL ATTACHMENT FITTING I - BEAM ADAPTER
#1
B
#3
FLANGE
A
A
#2
B
MIN TORQUE 18 FT-LB (25 N-m)
#4
THICKNESS
FLANGE WIDTH
C
MIN TORQUE 30 FT-LB (41 N-m)
CSBIB is a Structural Attachment Fitting. It is intended to be combined with CSBUNIV, TP225, and SB55N Structural Attachment Fittings, "Bracing Pipe" and a CADDY® brand Sway Brace ("Braced Pipe") Fitting to form a complete bracing assembly.
Sway Brace assemblies are intended to be installed in accordance with NFPA-13 and the manufacturer's assembly instructions.
TECHNICAL SUPPORT:
www.erico.com
CFS389_C
2 OF 2
#6#5
MIN INSTALL TORQUE
55ft-lb (75 N-m)
© 2009 ERICO International Corporation