INSTRUCTION SHEET
INSTRUCTION SHEET
SBF3C1000AL
SBF3C1000AL
561176
561176
Top
Bottom
6.93
176.0
IEC 60947-7-1
1000 VAC / 1500 VDC
Uimp = 12kV; Ipk = 75 kA
Icw kA rms 1s = 72
4.40
111.8
1200 A
2.73 69.4
UL 1953
1260 A
1000 V AC/DC
SCCR up to 100kA*
AL or CU Conductor
IP20
95% Fill Ratio
Halogen Free
UL 94 V-0
.90
22.8
No. Terminals
2 (TOP)
1 (BOTTOM)
No. Terminals
2 (TOP)
1 (BOTTOM)
1.88 47.7
measurement only.
6-32 UNC-2B
9 in-lbs [1.0 N-m]
4 mm² /12 AWG max
IEC 60947-7-1
For voltage
Conductor
1
1
ERIFLEX FLEXIBAR**
Conductor
ERIFLEX FLEXIBAR**
Size
2X20X1 to
10X50X1
35 mm² to
300 mm²
UL 1953
Size
2X20X1 to
10X50X1
2/0 AWG to
600 kcmil
DIA
N/A
23.5 mm
DIA
N/A
0.92 in
Torque
42.4 N-m
Torque
375 in-lbs
Strip Length
50 mm
39 mm
73 mm
Strip Length
1.97 in
1.53 in
2.88 in
Hex
10 mm
32 - 50 mm wide FLEXIBAR
Hex
3/8 in
20 - 32 mm wide FLEXIBAR
NOTE:
*Refer to UL file E497276.
1.
**Includes ERIFLEX FLEXIBAR Advanced.
2.
For multiple phase assemblies, join blocks together before installing onto DIN profile.
3.
When mounted on DIN profile, end stops should be used on both ends of gangable blocks.
4.
For IEC, the cable must be secured within 15 cm of the terminal.
5.
WARNING:
nVent products shall be installed and used only as indicated in nVent product instruction sheets and training materials. Instruction sheets are available at
1.
www.nVent.com
nVent products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
2.
All instructions must be
3.
Improper installation, misuse, misapplication or other failure to completely follow nVent's instructions and warnings may cause product malfunction, property
4.
damage, serious bodily injury and/or death, and void your warranty.
SAFETY INSTRUCTIONS:
All governing codes and regulations and those required by the job site must be observed.
Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
nVent, CADDY, ERICO CADWELD, ERICO CRITEC, ERICO, ERIFLEX, and LENTON are owned by nVent or its global affiliates. All other
trademarks are the property of their respective owners. nVent reserves the right to change specifications without prior notice.
TECHNICAL SUPPORT
www.nVent.com
and from your nVent customer service representative.
completely
followed to ensure proper and safe installation and performance.
IP8393_A
1 OF 1
© 2018 nVent All Rights Reserved