IBS/IBSB Advanced Insulated Braided Conductor, Halogen Free is the ideal ready-to-install flexible wire replacement solution that
is specifically designed for connections to all molded case circuit breakers, including the most compact breakers on the market.
IBS/IBSB Advanced connects to the front access terminals of the breakers without any additional accessories, such as angular
connectors, spreaders, ring terminal connectors or extenders. IBS/IBSB Advanced is available in cross sections of 25 to 240 mm²
(49.34 to 273.65 kcmil), lengths from 230 to 1,030 mm (9.06" to 40.55"), and 80 to 700 A.
Manufactured in an ISO 9001 certified automated facility, IBS/IBSB Advanced is formed by weaving high-quality electrolytic copper
wire to form a durable low voltage connector with maximum flexibility which allows for more compact power connections to
circuit breakers. The IBS/IBSB Advanced allows users to reduce the total size and weight of the installation, improving both design
flexibility and assembly aesthetics.
The unique manufacturing process of integral pre-punched palms make IBS/IBSB Advanced ready to connect out of the box. There
are no lugs to purchase or install, making connections simpler and faster and eliminates faulty connections due to vibration or
fatigue.
IBS/IBSB Advanced is compatible with all major brand molded case circuit breakers.
The advanced technology insulation is a high-resistance low smoke, halogen-free and flame retardant thermoplastic.
IBS/IBSB Advanced does not generate corrosive gases and produces a relatively low smoke opacity in accordance with IEC 61034-2
and UL 2885. The low smoke characteristic improves visibility conditions for people to be able to easily locate the emergency exit
and also allows rescue workers to better assess an emergency situation. IBS/IBSB Advanced means greater safety for individuals,
less damage for your electrical equipment and less environmental impact.
The halogen–free feature enables a reduction in the quantity of toxic smoke. IBS/IBSB Advanced does not contain any halogens,
according to IEC 60754-1 and UL 2885, minimizing toxicity and making it the ideal product for use in enclosed spaces such as
data centers, rail, and public facilities such as hospitals and schools. This also facilitates the use of IBS/IBSB Advanced in specific
applications such as submarines, switchboards and other enclosed environments that require a low emissions solution.
In addition to the above features, IBS/IBSB Advanced is compliant with the UL 94-V0 testing standard and glow wire test 960 °C.
The flame retardant portion of the test illustrates the self-extinguish feature. This superior feature of IBS/IBSB Advanced is also
shown by the Limiting Oxygen Index (LOI) at 30%. In case of fire, IBS/IBSB Advanced generates a limited quantity of smoke that is
less damaging to your electrical equipment.
Page 2
• Suitable for all main molded case circuit breakers
A
L
B
HS1
HS2
C
D
• Resistant to vibration, improving reliability and performance
• Insulated by high-resistance, halogen free, flame retardant and low smoke material
• Tinned copper provides superior corrosion resistance
• Improves assembly flexibility and aesthetics
• Quick and easy installation
• No additional cutting, stripping, crimping and punching needed
• Integral palm without lugs or terminals reduces material and assembly weight
• Conforms to NF EN 45545 obtaining an HL2 classification for chapters R22 and R23
• DNV GL® and Bureau Veritas certified for marine and offshore applications
• Small wire diameter provides maximum flexibility
• Dramatically smaller and more flexible than comparable cable based on ampacity
• Better power density than cable with lower skin effect ratio
• Reduces total installation cost
• RoHS compliant
• Tinned copper allows for copper or aluminum conductor connections
Part NumberIBSBADV70-330
Article Number534415
Typical Application Current Rating300 A
Peak Short Circuit Current (Ipk)30 kA
FinishTinned
MaterialCopper
Dielectric Strength20 kV/mm
Flammability RatingUL® 94V-0
Halogen Free RatingUL® 2885
Low Smoke RatingIEC® 61034-2
UV Resistance RatingUL® 854
Insulation Elongation500 %
Insulation Thickness0.07"
Max Working Voltage, IEC/UL 7581,000 VAC
Max Working Voltage, UL 67600 VAC/DC
Working Temperature-58 to 239 °F
Wire Diameter0.006"
Certification DetailsUL® 67
Complies WithIEC® 60439.1
Cross Section138.15 kcmil
Conductor Width0.79"
Thermoplastic Elastomer
IEC® 60754-1
IEC® 62821-1
ISO 5659-2
UL® 2885
UL® 2556
1,500 VDC
UL® 758
IEC® 60695-2-11 (Glow Wire Test 960 °C)
IEC® 61439.1
IEC® 61439.1 Class II
Page 3
Part NumberIBSBADV70-330
Conductor Thickness0.17"
Length (L)12.99"
A0.35"
B0.43"
C1.06"
D0.43"
Hole Size 1 (HS1)0.33"
Hole Size 2 (HS2)0.41"
CertificationsABS INSULATED BRAIDS
Standard Packaging Quantity10 pc
UPC78285696080
EAN-130782856960805
Bureau Veritas 41939 BV
CE
CSA 70173298
CSA 90005
cURus
DNV GL IBS/IBSB Advanced, TAE00003B8
EN 45545-2 IBS/IBSB Advanced
IEC 60695-2-12 CC11418_FADV
IEC 61439-1 Class II IBSB_ADV
IEC 61439-1 IBSB_ADV
ISO 5659-2 CC11518_FADV
RoHS
UL
UL (IEC) AVLV2.E316390
Maximum Ampacity Ratings
Cross Section
(mm²/kcmil)
25/49.341161341421501571641771.62
50/98.682132462602742883013251.62
70/138.152262612772913063193451.62
100/197.352983443653854044224561.62
120/236.823634194444684915135541.62
185/365.14164805095375635886351.62
240/473.655566426817187537868491.62
Circuit
Breaker
Current Rating
Part NumberIBSBADV25xIBSADV25xIBSBADV50xIBSADV50xIBSBADV70xIBSBADV100xIBSBADV120xIBSBADV185xIBSBADV240x
Schneider
Electric®
Compact®
(IEC)
Square D®
PowerPact®
(UL)
ABB®
Tmax® (IEC)
ABB®
Tmax® (UL)
ΔT 30° C (A)ΔT 40° C (A)ΔT 45° C (A)ΔT 50° C (A)ΔT 55° C (A)ΔT 60° C (A)ΔT 70° C (A)
∆T = Temperature of conductors – Internal temperature of panel.
This table indicates the temperature rise produced by chosen current in the given section. This calculation does not take into account the heat dissipation from the switch gear.
IBSB Advanced Insulated Braided Conductor with a cross section of 240 mm² (473.65 kcmil) is constructed of red copper strands with tinned palms.
Distance between supports must not exceed 630 mm (17.8") according to IEC 61439-1.
ABB is a registered trademark of ABB Asea Brown Boveri Ltd. ABS is a registered certification mark of American Bureau of Shipping. CSA, CSA-US and C-CSA-US are registered
trademarks of Canadian Standards Association. DNV GL and the Horizon Graphic are trademarks of DNV GL AS. GE and Record Plus are registered trademark of General Electric
Company. Hager is a registered trademark of the Hager Group. IEC is a registered trademark of the International Electrotechnical Commission. Legrand is a registered trademark
of Legrand North America, Inc. Moeller, xEnergy, and Cutler Hammer are registered trademarks of Eaton Corporation. Schneider Electric and Compact are registered trademarks of
Schneider Electric SA. Siemens and Sentron are registered trademarks of Siemens Aktiengesellschaft. Square D and PowerPact are registered trademarks of SNA Holdings Inc. Tmax
is a registered trademark of ABB SACE Spa. UL, UR, cUL, cUR, cULus and cURus are registered certification marks of UL LLC.