ERICO 3000 ERITECH SYSTEM User Manual

ERITECH® SYSTEM 3000
Installation, Operation and
Maintenance Manual
ERITECH® SYSTEM 3000 Installation, Operation and Maintenance Manual
EDITION 14
CADDY, CADWELD, CRITEC, ERICO, ERITECH, ERIFLEX and LENTON are registered
First printed 1988
trademarks of ERICO International Corporation.
IP79131_B REVISION 2
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
The ERITECH® SYSTEM 3000
Installation, Operation
and Maintenance Manual
IP79131_B
www.erico.com
1
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Table of Contents
Pre-Installation Requirements ................................................................................ Page 4
Grounding Systems ................................................................................................. Page 5
Downconductors ..................................................................................................... Page 5
Structural Bonding Braid & Conductive Structural Points ...................................... Page 6
Lightning Event Counters ....................................................................................... Page 6
ERITECH
Masts ........................................................................................................................ Page 7
Checking Lightning Protection Components on Receipt ................................. Page 8
ERITECH
Grounding Systems Installation ............................................................................. Page 9
Ground Resistance Lowering Compounds ......................................................... Page 12
Insulation of Grounding Systems Page ............................................................... Page 12
Bonding the Lightning Protection Ground to other Service Grounds .................. Page 12
Labelling ............................................................................................................ Page 13
Downconductors .................................................................................................. Page 14
Downconductor Hauling .................................................................................... Page 14
Penetrations ....................................................................................................... Page 16
Routing ............................................................................................................. Page 16
Securing the Downconductor ............................................................................ Page 18
Use of Mast or Conventional Cable as the Downconductor ............................... Page 19
Labelling ............................................................................................................ Page 20
Structure Bonding Braid .................................................................................... Page 20
Terminating the ERITECH Terminating the ERITECH
Terminals and Masts ............................................................................................. Page 40
Terminals ........................................................................................................... Page 40
Masts ................................................................................................................ Page 40
Mast Bases .........................................................................................................Page 41
Mast Couplings & Guying Points ....................................................................... Page 42
Guying .............................................................................................................. Page 44
Raising of Mast .................................................................................................. Page 45
Lightning Event Counter ................................................................................ Page 48
Long Lengths of ERITECH ERICORE Downconductor ........................................ Page 49
Parallel ERITECH
Series connected ERITECH ERICORE cable sections ............................................. Page 52
Practical Examples for long lengths of ERITECH ERICORE ............................. Page 54
Certification .............................................................................................................. Page 55
Operation & Maintenance ..................................................................................... Page 55
Maintenance Records ........................................................................................... Page 58
Specifications ............................................................................................................ Page 59
Glossary ....................................................................................................................... Page 62
Certificate of Compliance and Warranty Registration .................... Inside Back Cover
®
DYNASPHERE Terminals ......................................................................... Page 6
®
SYSTEM 3000 Installation ...................................................................... Page 9
®
ERICORE Lower End ................................................. Page 24
ERICORE Upper End .................................................. Page 28
®
ERICORE cables ......................................................................... Page 51
2
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
ERITECH® SYSTEM 3000
THE ERITECH® SYSTEM 3000
Installation, Operation
and Maintenance Manual
Due to ongoing research into the phenomena of lightning and lightning
protection technology and product improvement, ERICO reserves the right to alter any information and specifications contained herein at any time without notice. Users should check with ERICO to ensure they have the latest edition.
Warning:
1. ERICO products shall be installed and used only as indicated in ERCIO product instruction sheets and training materials. Instruction sheets are available at www.erico.com and from your ERICO customer service representative.
2. ERICO products must never be used for a purpose other than the purpose for which they were designed or in a manner that exceeds specified load ratings.
3. All instructions must be completely followed to ensure proper and safe installation and performance.
4. Improper installation, misuse, misapplication or other failure to completely follow ERICO’s instructions and warnings may cause product malfunction, property damage, serious bodily injury and death.
SAFETY INSTRUCTIONS: All governing codes and regulations and those required by the job site must be observed. Always use appropriate safety equipment such as eye protection, hard hat, and gloves as appropriate to the application.
®
The ERITECH
International patents on the ERITECH SYSTEM 3000 are existing.
Local Distributors should be the user’s first point of contact with supply, delivery, installation,
limited warranty, and checking of the system for compliance with Manufacturer’s instructions.
www.erico.com
SYSTEM 3000 is manufactured by ERICO.
3
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Pre-Installation Requirements
This manual is a guide to the Installation, Operation and Maintenance of the ERITECH SYSTEM 3000 Lightning Protection System.
It assumes that the system to be installed has been designed by an authorized ERICO representative. The system design will include:
t
Grounding system design - a configuration should be designed as a result of soil resistivity analysis.
®
t Downconductor routes - chosen to
avoid other services, maintain minimum bending radii and minimize downconductor run length.
t Downconductor securing requirements. t Terminal types - operating environment. t CAD analysis design software which
determines terminal placement, mast & height requirements as well as protection level calculation.
All of the above are recommended for a successful installation. If there is any doubt about any of the points mentioned, please contact ERICO or your nearest Distributor for clarification.
Only attempt to install the ERITECH SYSTEM 3000 during storm-free periods.
Figure 1.
4
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
The recommended order of installation is as follows:
1. Full installation of the grounding system.
2. Full installation of the downconductor.
3. Termination of the downconductor to the grounding system.
4. Upper termination of the downconductor (may already have been completed by ERICO) and connection to the ERITECH
5. Termination of bonding cable from upper termination to structure (if required).
6. Raise mast into position and secure.
®
DYNASPHERE air terminal.
Grounding Systems
The grounding system is critical to the integrity of any lightning protection installation and should include consideration of:
t Local Standards compliance
(IEC 61024-1, BS 6551, AS1768-1991,
®
780, C22.1-98, NEC® etc.)
NFPA
t Available space / location. t Natural soil conditions - resistivity of
soil, soil moisture content, soil temperature range, etc.
t Location of underground services -
Power, Communications, Fuel, Gas, Water, etc.
t Corrosive environments, ie: salt
water, acid / alkaline contaminated ground mass.
t Use of suitable grounding rods such
as ERITECH
®
rods.
t Minimization of risk to personnel.
Contact an ERICO office or Distributor if you require further advice on grounding systems.
Downconductors
The ERITECH® ERICORE downconductor or other recommended downconductor should have been selected during the design stage, as should the route, length and any preterminations of the downconductor.
Re-check intended route of downconductor immediately prior to installation to ensure that:
t There are no structural changes or
additions that may effect the initial design.
t Most direct route possible to the
grounding system with minimal number of bends and as flush with the structure as possible.
t Minimum bending radii maintained
(500 mm, 20 in.).
t Parallel routing with other services -
minimum separation = 2 m (80 in.).
t Attachment to the structure is at a
maximum of every 1 m (40 in.) for the top 10% of the downconductor route and 2 m (80 in.) from then on.
t Pipe installations follow the instructions
given on page 17.
www.erico.com
5
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Re-check:
t Securing of downconductor - saddles,
cable ties, beam clamps, cable hangers, etc, are appropriate.
t Method of cable installation, ie. cable
upper terminated on the outside of the drum - to be rolled off from the base of the structure, or cable upper terminated on the inside of the drum - to be rolled off from the top of the structure, (refer Figure 6 on page 15).
t The outer sheath of the downconductor
must be electrically bonded to a conductive structural point within 5 m (17 ft) of the upper termination kit.
Structural Bonding Braid & Conductive Structural Points
When installing the upper end of the downconductor on a masonry
structure (concrete panels, brick, etc), the downconductor should be secured directly to the structural steel work. In addition, the bonding cable (supplied in the termination kit) must be connected via
2
(8 AWG) insulated copper cable to
6 mm the nearest conductive structural point. This point should be where the downconductor first comes into contact with the structure and may be either structural steel work or the reinforcing within concrete panels or slabs.
See Pages 18 to 24, figures 10-17 for more details and diagrams.
Lightning Event Counters
The Lightning Event Counter (LEC IV) is a device for registering and recording the number of strikes that the ERITECH SYSTEM 3000 has intercepted. The design of this counter allows many installation alternatives on the downconductor as discussed in later text. Also, see Specifications on page 60.
The following should be considered prior to installation of the Lightning Event Counter:
®
t It is advisable to locate the LEC IV in
a secure area that is not prone to contact with moving objects, theft, or vandalism.
t If the LEC IV is to be encased in an
additional enclosure, ensure that it is mounted to enable easy access to the display, (see figure 32 on page 48).
ERITECH® DYNASPHERE Terminals
The ERITECH® DYNASPHERE is the air
terminal of the ERITECH SYSTEM 3000.
Ensure that the appropriate air terminal has been provided.
It is recommended that this point be determined prior to the installation to allow for any site work or equipment that may be required prior to the installation.
2
The 6 mm and the length of the cable will need to be determined and obtained before commencing the installation.
(8 AWG) cable is not supplied
Suitable for use in:
t General purpose applications t High temperature environments t Corrosive environments (salt or acid
atmosphere)
6
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Ensure the air terminal is supplied with the finial tip secured in place. The air terminal is supplied with three different finial tip configurations (two separate, and one secured in place), similar to that shown in photo 1. It is important that the
correct finial tip is installed, specific to the application. Photo 2 shows the
three different finial tip sharp to blunt in dimension. (middle), medium tip (left) and rounded tip (right). The application of each of these tips is detailed below:
sizes, ranging from
The sharp tip
Masts
There are three main types of mast configurations:
t Guyed - generally required for mast
t Sharp Tip – Terminal heights less than
20 m (65 ft)
t Medium Tip – Terminal heights less
50 m (165 ft), greater than 20 m
than (65 ft)
t Cantilevered - the lower third of the
t Rounded Tip – Terminal heights greater
than 50 m (165 ft)
Note: heights listed refer to the actual terminal height above ground level
If required, replace the finial tip supplied with the appropriate tip for the application, and tighten firmly.
Warning – Do not install the ERITECH® DYNASPHERE correct finial tip.
without installing the
t Free-standing - base support only.
Ensure that the configurations and heights for your specific installation conform to the design and consultation directives.
Specific advice for each mast configur­ation is provided on pages 40 to 47.
When all of the components for the ERITECH received, they should be checked against the design “Bill of Materials” and for any possible shipping loss or damage.
heights of over 3 m (10 ft) or for climatic conditions where wind gusts may exceed 160 km/h (100 mph). Always consult with a local civil engineer if in doubt. The mast is anchored at the base and then guyed using one or two guy sets, depending on the mast height and configuration, each with 3 lengths of non conductive guying material.
mast is secured to a vertical surface to provide support. These may also require guying depending on mast height.
®
SYSTEM 3000 have been
1 – ERITECH DYNASPHERE with two spare finial tips.
2 – Three (3) ERITECH DYNASPHERE finial tip sizes.
www.erico.com
7
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Checking Lightning Protection Components
on Receipt
Before installation, in particular, check the following:
Terminal(s)
t ERITECH
not been dented in any way.
®
DYNASPHERE terminals have
t The correct finial tip has been installed,
based on the overall height of the air terminal above ground.
®
ERITECH
ERICORE Downconductor(s)
t The cable drum (if supplied) is in a
serviceable condition.
t Correct length(s) t That there is no obvious damage to the
cable.
t Is terminated as required. If the
downconductor has been pretermin­ated before shipment, check that the termination is still intact and in good order. See note on Page 14 on removing protective covers.
t If the Upper Termination Kit has been
supplied separately, check that the Cold-Shrink tube in the kit is in good order, has no tears or cuts and has not collapsed.
This information along with down­conductor lengths and quantities (if more than one length on the one drum), will be printed on a label on the side of the Cable Drum(s).
8
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
ERITECH® SYSTEM 3000 Installation
During the installation of the ERITECH® SYSTEM 3000, all site restrictions
and safety requirements must be followed.
It is important to follow the recommended order of installation:
1. Full installation of the grounding system.
2. Full installation of the downconductor.
3. Termination of the downconductor to the grounding system.
4. Upper termination of the downconductor (may already have been completed by ERICO®) and connection to the ERITECH® DYNASPHERE air terminal with
correctly sized finial tip.
5. Termination of bonding cable from upper termination to structure.
6. Raise mast into position and secure.
Only attempt to install the ERITECH SYSTEM 3000 storm-free periods.
If the terminal must be raised before being connected to the ground system, or cannot be immediately connected, then attempt to connect the lower end of the down-conductor to either the structure steel reinforcing or some other reasonable ground point.
during
Grounding Systems Installation
Prior to the installation of the lightning protection grounding systems, it is important to refer
to site drawings of all underground
www.erico.com
services to ensure that these are avoided and not interrupted during trenching, excavation, boring or driving ground rods, (see figure 4 on page 11).
Care must be taken to follow the ground survey design. Ensure the correct materials have been provided and are used to achieve an acceptable Ground DC resistance (typically <10Ω).
Examples of typical grounding systems that may be used (Note: these may or may not be relevant to the specific ERITECH SYSTEM 3000 design) are shown in figures 2 and 3 on page 10.
9
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Lightning Event Counter - LEC IV
Ground rods clamped or welded to copper ground tape using CADWELD
Each trench is treated with GEM or ERITECH Enhancing Compounds
®
Conductive Saddles
ERITECH
®
ERICORE
Ground Pit
Lower Termination (Bound in Waterproofing Mastic)
Copper Ground Tape Typical lengths, minimum of 5 m (17 ft). (Lengths are dependant upon soil resistivity reading) @ 600 mm (24 in.) depth or greater if required, to ensure that it is below the frost line.
Figure 2: Radial Ground.
Copper ground tape grid 5000 x 5000 mm (17 x 17 ft.) @ 600 mm (24 in.) depth or greater if required to ensure that it is below the frost line.
Figure 3: Grid Ground.
ERITECH ground rods
clamped or welded to
copper ground tape,
using CADWELD.
10
Conductive Saddles
Lightning Event Counter - LEC IV
ERITECH ERICORE
Ground Pit
Lower Termination (Bound in Waterproofing Tape)
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
POWER
GAS
WATER
IRRIGATION
COMMUNICATIONS
SEWERAGE/STORMWATER
Figure 4: Precautions required for ground pit excavation and lower termination corrosion protection.
It is advised that a ground pit is installed where the end of the downconductor
This provides a convenient access point for disconnection and future testing.
terminates to the ground system.
www.erico.com
11
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
When using ground rods it is advisable to:
t Use driving heads to prevent
mushrooming on top of the rod.
t Use driving heads when using
coupled rods.
tUse a post or picket driver.
When bonding the grounding system components, try to use the recommended methods suggested below:
t CADWELD
used to provide permanent electrical bonding, corrosion resistance and mechanical strength between conductors, including most types of copper cable, bar, rod, tape, structural steel work, reinforcing steel and pipe.
t Supplied ground rod clamps should
be used for termination of ERITECH ERICORE downconductors directly to ground rods. This allows later disconnection for maintenance requirements.
®
connections must be
®
t Use of aluminum lugs or couplings is
prohibited.
t Waterproofing mastic tape should be
used for waterproofing corrosion vulnerable connections.
Ground Resistance Lowering Compounds
Ground enhancing compounds, (such as GEM) are recommended and supplied when the existing soil mass has a high resistivity.
These compounds can be used to increase the total surface area of grounding conductors, resistance / impedance.
Compounds may require water and a mixing container.
thereby reducing the ground
When applying these compounds, be sure to take necessary handling precautions as advised by the product instructions, and ensure that the directions for use are followed correctly.
Insulation of Grounding Systems
In some installations, it may be necessary to insulate part of the ground system from an area of the surface, for the purposes of safety or isolation, (pedestrian walkways, proximity to other services, etc.). In this situation, it is recommended that a minimum of 70 mm copper cable is run in PVC conduit to the connection point (start) of the intended ground system. This conduit should be at a depth of at least 600 mm (24 in.), or greater if required, to ensure that it is below the frost line to the start of the intended ground system.
Another possible design method for reducing surface step-potentials may be to insulate the ground system for the first few meters of depth from the surface. This is done by isolating the initial injection point of the downconductor from the surface of the ground mass by running it through PVC conduit to the required depth before exposing it to the ground mass.
2
(2/0 AWG), insulated
Bonding the Lightning Protection Ground to Other Service Grounds
Where separate grounds exist eg: Structure, Power, Communications and Lightning Protection, they should be bonded to form an equipotential ground plane. This will eliminate the possibility of loops and potential differences arising under transient conditions.
together
ground
12
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Surface Area of Isolation
Downconductor Lower Termination
Ground Pit
600 mm (24 in.) or greater to ensure it is below the frost line.
2 m (80 in.)
2
2/0 (AWG)
Insulated Conduit
70 mm Insulated Copper Cable
Start of Grounding System
ERITECH Ground Rod
Figure 5: Various methods of isolating the ground system.
Authorization may be required by the particular service providers before bonding of these grounds takes place.
2
Bonding cable must be 70 mm
(2/0 AWG) minimum depending on local standards. In some circumstances, it may be necessary to use a Transient Earth Clamp (ERICO Part No. TEC100C) which effectively bonds all grounds to the same potential under transient conditions, to satisfy service providers.
For further information, it is advised that local applicable standards are consulted, ie IEC 61024-1, BS 6551, AS1768, NFPA C22.1-98 and NEC
www.erico.com
®
.
®
780,
13
®
Labelling
The labelling of ground pits or grounding systems to local requirements is the responsibility of the customer / installer.
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Downconductors
Depending on site requirements, the downconductor(s) may have their upper terminations completed at a pre-specified end of the cable by ERICO before shipment. These terminations will be protected by a short length of flexible PVC tube.
It is VERY IMPORTANT that when removing these tubes, they are not removed with a knife or cut in any way as this will damage the outer layer of the termination. It is suggested that the tape and cover are best removed by hand. (See figure 6)
All ERITECH® purpose-designed downconductors have a semi-conductive outer sheath which is approximately 2 mm (0.08 in.) thick. Rough or careless handling of the downconductor can damage this sheath and compromise its performance.
Downconductor Hauling
Locate the downconductor cable drum at the appropriate location, (refer to figure 6).
When hauling the downconductor, use the following guide points:
t Ensure that the cable drum, if supplied, is
in a serviceable condition.
t If the downconductor has been upper
terminated on the outside of the drum, then the downconductor must be hauled
off the drum from the ground.
t If the downconductor has been upper
terminated on the inside of the drum, then the drum must be at or near the
of the structure, so that the down-
top conductor drum towards the base, (see figure 6).
can be unwound from the
t When using slings or ropes to haul
downconductors, use MULTIPLE hitches around the cable.
t DO NOT sling from the termination
coupling or cold-shrink section of the terminated downconductor.
t DO NOT use cable stockings over
TERMINATED downconductor ends.
t Protect the downconductor from
abrasion and tearing when hauling over rough surfaces, at all times, especially around corners or through penetrations.
14
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Downconductor pre-terminated on the OUTSIDE end when wound on the cable drum
Figure 6: Cable pre-termination and drum locations.
INCORRECT
Figure 7: Incorrect and correct cable hoisting methods.
www.erico.com
CORRECT
15
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Penetrations
Before routing the downconductor through any penetrations, ensure that:
t If un-terminated, a minimum hole
diameter of 50 mm (2 in.) is provided.
t If terminated, a minimum hole diameter
of 60 mm (2
3
8 in.) is provided.
t Enough physical protection (conduit
or similar) is provided to stop the downconductor from being damaged when being fed through the penetration.
t When feeding the upper termination
of the downconductor through any penetrations, the termination sheds (flanges) should be temporarily wrapped in insulation tape to reduce their diameter and protect them against abrasion. This is very important as the cold-shrink tubes are susceptible to tearing if nicked or scuffed.
If either side of the penetration requires environmental protection ie: waterproofing, air-con pressure seal, etc., use a suitable sealant or deck sealing gland.
Routing
The route taken by the down­conductor is very important and must follow these rules:
t Carefully survey the intended route
of the downconductor immediately prior to the installation to check for any alterations that may effect the original design, ie: structural changes, new antenna or mast installations, air conditioning towers or ducting, etc.
t Use the most direct route practical to
minimize the downconductor length.
t To minimize the risk of side-flash,
DO NOT route the downconductor back beside itself after change of direction, ie: 180º.
t Minimize number of bends. t Minimize strain on the downconductor
during installation.
Radius < 500 mm (20 in.)
INCORRECT
Figure 8: Correct & incorrect cable routing methods.
CORRECT
16
< 2000 mm (80 in.)
INCORRECT
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
t Ensure bend radius maintained >500 mm
(20 in.).
t Parallel routing with other services -
Minimum separation = 2 m (80 in.). Try to isolate as much as possible from other services.
t If the downconductor must cross other
services, ensure that it crosses at right angles to minimize any inductive effect.
t The lower end of the downconductor
must terminate as close as possible to the initial injection point of the grounding system.
INCORRECT
t Allow 500 mm (20 in.) of slack
in the length of downconductor at the upper end of the cable to facilitate mast erection and correct seating of the ERITECH terminal in the top of the FRP mast.
t
Where isolation of the downconductor required, (for physical or proximity safety reasons) install the cable in a insulating conduit with a min thickness of 3 mm (
NOTE: This is the only time that the downconductor should be isolated from the structure and generally only for 2.4 m (8 ft.) maximum. DO NOT route the entire
length of downconductor in insulated conduit.
®
DYNASPHERE
1
imum wall
8 in.).
is
suitable
CORRECT
Figure 9: Correct & incorrect cable routing.
www.erico.com
COMMUNICATIONS / POWER
17
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
t To seat the terminal correctly in the top
of the FRP mast, any cable slack will have to be removed from the mast while also minimizing any stress on the upper termination sheds (flanges) by twisting the FRP mast against the terminal for at least one turn.
If the downconductor is damaged during installation, it must be checked by an ERICO
representative to see if the damage will effect its safe operation.
Securing the Downconductor
Securing of the down­conductor not only provides a mechanical attachment to the
structure, but also an Electro­static connection to the structure via the semiconductive outer sheath of the downconductor cable.
It is important that the down­conductor is both physically and electrically secured to the entire length of the structure to relieve both physical and electrical stresses along the downconductors’ length.
The electrical bonding of the down­conductor is especially important for at least the first 10% of the down­conductor route from the upper termination, and for this reason the downconductor must be secured at least every 1 m (40 in.).
ERITECH® brand of saddles and conductive clamps are
recommended for the purpose of securing the downconductor. These have been specifically designed and manufactured to mechanically secure and electrically bond the ERITECH
®
ERICORE to the structure, while minimizing stress points on the cable.
Use of a brand of saddles other than ERITECH can compromise the outer sheath, creating high stress points which can lead to flashover, (see figure 10).
Use ERITECH clamps only
Figure 10: Detail shows the need to use ERITECH Clamps.
18
www.erico.com
INSTALLATION, OPERATION AND MAINTENANCE MANUAL
t For brick and concrete walls or roofs,
use the ERITECH saddles. These have two 6 mm (
®
brand of stainless steel
1
4 in.) diameter holes on either side and are suitable for use with masonry anchors. These saddles can also be used with other suitable fastenings against wood, fiberglass and metallic surfaces.
t When securing externally to round section
structures such as pipes, tower legs, masts, etc, stainless steel cable ties are recommended. Ensure that these are firmly secured.
t For securing to other structures such as
angle iron, ie: radio towers, structural beams etc., use CADDY clamps and suitable cable clamps from ERICO.
®
brand of beam
t If the downconductor is to be routed
above a false ceiling, ensure that it is fixed to the underside of the concrete floor slab.
t Use of exothermic fastening methods
on ERITECH brand of saddles is NOT recommended.
t Use of CADDY
strut system) is recommended where suitable, (see figure 11).
Use of Mast or Conventional Cable as the Downconducto
In some installations, the mast may be used as the downconductor or alternatively, in short-run installations, conventional cable is sometimes used. In these cases, a Terminal Lug Coupling Adaptor will be supplied to allow a lugged 50 mm
2
(2/0 AWG) (depending on local
70 mm minimum standards) cable termination to the base of the ERITECH (see figure 12).
®
ERISTRUT (or other similar
r
2
(1/0 AWG) or
®
DYNASPHERE,
Use of CADDY® ERISTRUT to anchor downconductor with S/S cable ties
Figure 11: Downconductor anchored to strut.
Lock Screw
Lightning Protection
Lug Coupling
M10 Bolt
Figure 12: Lug Coupling for non-ERITECH ERICORE
downconductors.
Terminal Base
2
50 mm (1/0 AWG)/
2
70 mm (2/0 AWG) minimum downconductor (or as per local standards)
®
www.erico.com
19
Loading...
+ 47 hidden pages