2.2PACKING CASE ............................................................................................................................................. 12
3.2.2.1 4-wire micro FIT cable ............................................................................................................ 15
3.2.2.2 2-wire micro FIT cable ............................................................................................................ 16
4 CHARACTERISTICS AND SERVICES ....................................................................................................... 17
5 USING THE MODEM ................................................................................................................................... 19
5.1STARTING WITH THE MODEM ......................................................................................................................... 19
5.1.1 Mounting the modem ..................................................................................................................... 19
5.1. Installation of the modem ................................................................................................................. 19
5.1.3 Checking the communication with the modem .............................................................................. 20
5.1.3.1 Without Library ....................................................................................................................... 20
5.1.3.2 Standard with EGM Library .................................................................................................... 21
5.1.3.3 The application ERCO & GENER EaseLoc-01 ...................................................................... 21
5.1.3.4 The owner application ............................................................................................................ 21
5.1.5 Hardware reset of the modem ....................................................................................................... 22
5.2SPECIFIC RECOMMENDATIONS FOR THE USE OF THE MODEM IN VEHICLES ........................................................ 23
5.2.1 Recommended Connection on the battery of a truck .................................................................... 23
5.2.2 Technical constraints in truck......................................................................................................... 24
5.3.1 GSM led ......................................................................................................................................... 25
5.3.1.1 Without library ......................................................................................................................... 25
5.3.1.2 With EGM standard library ..................................................................................................... 25
5.3.1.3 The application ERCO & GENER EaseLoc-01 ...................................................................... 25
5.3.1.4 The owner application ............................................................................................................ 25
5.3.2 GPS led .......................................................................................................................................... 25
5.4ECHO FUNCTION OF THE DEACTIVATED AT COMMANDS .................................................................................. 25
5.5CHECKING THE QUALITY OF THE GSM RECEPTION SIGNAL .............................................................................. 26
5.6VERIFICATION OF THE PIN CODE ................................................................................................................... 27
5.7VERIFICATION OF THE MODEM REGISTRATION ON THE GSM NETWORK ............................................................ 27
5.8READING A CURRENT POSITION GIVEN BY THE GPS ....................................................................................... 28
5.9MAIN AT COMMANDS (HAYES) .................................................................................................................... 29
5.10TURNING OFF THE MODEM .......................................................................................................................... 30
7.2.2.1 Presentation of internal battery option .................................................................................... 36
7.2.2.2 Specifications of the internal battery option ............................................................................ 36
7.2.2.3 Charge voltage and supply voltage ........................................................................................ 37
7.2.2.4 Indication of presence/absence of the external power supply ............................................... 37
7.2.2.5 Instruction and restrictions of use ........................................................................................... 38
7.2.3 Protections of the power supply ..................................................................................................... 38
7.3RS232 SERIAL LINK ...................................................................................................................................... 38
7.3.1 General Presentation ..................................................................................................................... 38
8.2.1 Power supply ................................................................................................................................. 48
8.2.5 RESET signal ................................................................................................................................. 56
9.2SECURITY IN A VEHICLE ................................................................................................................................ 62
9.3CARE AND MAINTENANCE .............................................................................................................................. 62
11 CLIENT SUPPORT .................................................................................................................................... 63
DECLARATION OF CONFORMITY ............................................................................................................... 64
EG_GenLoc31e_AOB_1003_UG_006_UK Page 5 / 64
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 6 / 64
Presentation
Entirely dedicated to geo-localization and embedded data services, the modem GenLoc 31e AOB combines
both GSM/GPRS and GPS functions in the same robust case.
The GPS data can be transmitted by SMS or data GSM/GPRS communication.
This product includes the GPS function 50 channels Hypersense and its sensitivity ensures the GPS data
collection in difficult environmental conditions.
The modem is Quad-Bands 850/900/1800/1900 MHz and GSM/GPRS Class 10.
The GenLoc 31e AOB has 3 operating modes:
External mode (standard): The driving is made by an external application. The modem is used with
the AT commands set (see EG_EGM_CL_xxx_yy of ERCO & GENER).
Autonomous mode (optional): Once configured, the modem is autonomous; it cyclically registers the
positions and transmits them automatically to the client’s application via different services: SMS,
GSM Data, TCP socket GPRS (see EG_EaseLoc_01_CL_xxx_yy of ERCO & GENER).
Specific development mode: the EGM development tool allows to develop personalized embedded
application. For more information concerning the tools and the training, please contact our sales
department.
The GenLoc 31e AOB provides TOR inputs/outputs allowing the creation of embedded telematic solutions
with high added value.
This document describes the modem and provides the following information:
- General presentation,
- Functional description,
- Available basic services,
- Installation and use of the modem (first level),
- Trouble shooting,
- Recommended accessories for the use of the modem.
For more information concerning this document, ERCO & GENER puts at your disposal the following
elements:
- Commands List
External mode EG_EGM_CL_xxx_yy
Autonomous mode EG_EaseLoc_01_xxx_yy
- Application Note EG_GenLoc31e_1003_AN_xxx_yy
- Release Note EG_GenLoc31e_1003_RL_xxx_yy
- Client support (Hot-Line)
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 7 / 64
Warning
•Erco&Gener advises to read carefully all the documents concerning the GenLoc 31e AOB (User
Guide, Application Notes, Command List).
•ERCO & GENER cannot be held responsible for:
- The problems due to an inappropriate use of the GenLoc 31e AOB.
- The problems due to a wrong configuration
- The problems due to a wrong use of an embedded software application developed or
supplied by a third party.
- The dysfunctions due to the absence or a bad coverage of the GSM, GPRS and GPS
networks.
- The dysfunctions if the product is used for the watching of physical persons where human
life is engaged.
•ERCO & GENER reserves the right to modify the functions of its products "GenLoc 31e AOB" and
"EaseLoc" without previous notice.
- In order to avoid any risk of electrocution, do not open the casing.
- For any functioning, the casing must be closed.
- No internal part can be repaired by the user. The GenLoc 31e AOB must be returned to the factory for any
repair.
- The GenLoc 31e AOB must be placed in a normally ventilated area, out of sources of heat.
- In order to guarantee the electromagnetic compatibility, the length of the serial cable, the supply cable and
the inputs/outputs cable must not exceed 3 meters.
- The GenLoc 31e AOB must not be connected directly to the mains supply; a voltage adapter must be
used.
SCRAP THE WORN BATTERIES ACCORDING TO INSTRUCTIONS;
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 8 / 64
Copyright
The reproduction, transfer, distribution or storage of part or the totality of the contents of this document, in
any form, without the prior written authorization of ERCO & GENER is strictly prohibited.
GenLoc 31e AOB is a trademark of ERCO & GENER.
Hayes is a registered trademark of Hayes Microcomputer Product Inc. The names of products and
companies mentioned in this document may be names or trademarks of their respective holders.
The use of some products or services described in this document may require a paying subscription. The
availability of some products or services described in this document may change, depending on the
configurations and the materials.
In some countries, restrictions of use of the devices may be applied. For more information, thank you to
contact your nearest legally qualified local government representative.
ERCO & GENER follows a method of continuous development. Consequently, ERCO & GENER reserves
the right to change and improve any of its products described in this document, without notice.
The contents of this document are provided “as it is”. Except for the applicable obligatory laws, no guarantee
in any form, explicit or implicit, including but without being limited to it the implicit guarantees of aptitude to
marketing and of appropriateness to a particular use, is granted concerning the precision, the liability or the
contents of this document. ERCO & GENER reserves the right to revise or withdraw this document at any
time and without notice.
ERCO & GENER cannot be held responsible for any loss of data or income, as well as particular damage,
incidental, consecutive or indirect.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 9 / 64
1 References
1.1 Referred documents
Commands List of
Standard library of ERCO & GENER: EG_EGM_CL_xxx_yy
the embedded application EaseLoc of ERCO & GENER: EG_EaseLoc_01_CL_xxx_yy
Application Notes GenLoc 31e AOB of ERCO & GENER :
EG_Genloc31e_1003_AN_xxx_yy
GSM reference documents:
GSM 07.05.
GSM 07.07.
1.2 Abbreviations
Abbreviations Definition
AC
ACM
AMR
AT
BTS
CLK
CMOS
CS
CTS
dB
dBc
dBi
dBm
DC
DCD
DCE
DCS
DSR
DTE
DTMF
DTR
EEPROM
EFR
EGM
E-GSM
EMC
EMI
ESD
ETSI
FIT
FR
FTA
FTP
Alternative Current
Accumulated Call Meter
Adaptive Multi-Rate
Attention (prefix for modem commands)
Base Transceiver Station
ClocK
Complementary Metal Oxide Semiconductor
Coding Scheme
Clear To Send
Decibel
Decibel relative to the Carrier power
Decibel relative to an Isotropic radiator
Decibel relative to one milliwatt
Direct Current
Data Carrier Detect
Data Communication Equipment
Digital Cellular System
Data Set Ready
Data Terminal Equipment
Dual Tone Multi-Frequency
Data Terminal Ready
Electrically Erasable Programmable Read-Only Memory
Enhanced Full Rate
Erco Gener Middleware
Extended GSM
ElectroMagnetic Compatibility
ElectroMagnetic Interference
ElectroStatic Discharges
European Telecommunications Standards Institute
Series of connectors (micro-FIT)
Full Rate
Full Type Approval
File Transfert Protocol
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
GCF
GND
GPIO
GPRS
GPS
GSM
HR
I
IEC
IMEI
I/O
LED
LLC
MAX
ME
MIC
Micro FIT
MIN
MNP
MO
MS
MT
NOM
O
Pa
PBCCH
PC
PCL
PDP
PIN
PLMN
PUK
RF
RFI
RI
RMS
RTS
RX
SIM
SMA
SMB
SMS
SNR
SNTP
SPI
SPL
SPK
SRAM
TCP/IP
TDMA
TU
TUHigh
TX
TYP
UTC
VSWR
Global Certification Forum
GrouND
General Purpose Input Output
General Packet Radio Service
Global Positioning System
Global System for Mobile communications
Half Rate
Input
International Electrotechnical Commission
International Mobile Equipment Identification
Input / Output
Light Emitting Diode
Low Level Command
MAXimum
Mobile Equipment
MICrophone
Family of connectors from Molex
MINimum
Microcom Networking Protocol
Mobile Originated
Mobile Station
Mobile Terminated
NOMinal
Output
Pascal (for speaker sound pressure measurements)
Packet Broadcast Control Channel
Personal Computer
Power Control Level
Packet Data Protocol
Personal Identity Number
Public Land Mobile Network
Personal Unblocking Key
Radio Frequency
Radio Frequency Interference
Ring Indicator
Root Mean Square
Request To Send
Receive
Subscriber Identification Module
SubMiniature version A RF connector
SubMiniature version B RF connector
Short Message Service
Signal-to-Noise Ratio
Simple Network Time Protocol
Serial Peripheral Interface
Sound Pressure Level
SpeaKer
Static RAM
Transmission Control Protocol / Internet Protocol
Time Division Multiple Access
Typical Urban fading profile
Typical Urban, High speed fading profile
Transmit
TYPical
Universal Time Clock
Voltage Stationary Wave Ratio
EG_GenLoc31e_AOB_1003_UG_006_UK Page 10 / 64
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 11 / 64
1.3 Symbols
The following symbols are used to highlight the important information of this userguide.
A symbol for the essential information concerning the module integration and performance.
A warning symbol indicates the actions that could harm or damage the module.
2 Packaging
2.1 Content
The GenLoc 31e AOB is supplied with:
- a GenLoc 31e AOB cardboard packaging,
- a modem GenLoc 31e AOB,
- 2 fixing brackets,
- a 4-wire cable
Red/Black/Orange/Green stripped with 5x20 fuse
or depending on the supplying
Red/Black/Yellow/Brown stripped with mini Blade fuse of 2A/32V.
- a 2-wire stripped cable (Blue/Yellow).
- A technical sheet (Instructions Sheet).
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 12 / 64
2.2 Packing case
The external dimensions of the packing case are:
- Width: 54.5 mm,
- Height: 68 mm,
- Length: 108 mm.
An identification label is put on the top of the packing case. It shows:
- The ERCO & GENER logo,
- The product reference: GenLoc 31e AOB (R30),
- The CE mark,
- The IMEI bar code with 15 digits.
The dimensions of the label are:
- Height: 37 mm,
- Length: 70 mm.
2.3 Modem labels
On the standard casing, there are 2 labels placed on the back part of the modem:
A production label indicating the following information:
- The CE mark,
- The crossed wheelie-bin mark (DEEE standards),
- The direct current mark (VDC),
- The mark AOB (R30),
- The IMEI bar code with 15 digits.
A label of the markings: ROHS (2002/95/CE).
If the internal battery option has been mounted during production, the modem has the
following label: “Lithium-Polymer Battery Inside”.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 13 / 64
3 General Presentation
3.1 Description
Description of the modem GenLoc 31e AOB:
Micro-Fit 4pin/M
connector
Front side
Sub HD 15pin/F
Connector
Micro-Fit 2pin/M
Connector
SMB/M
Connector
SIM card cover GSM LED
2 brackets to fix the modem on a support.
Fixing brackets
Rear side
GPS LED
SMA/F
Connector
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 14 / 64
3.2 External connections
3.2.1 Connections
3.2.1.1 Antenna connectors
GSM antenna connector:
The GSM antenna connector is SMA female with a 50 impedance.
GPS antenna connector:
The GPS antenna connector is SMB male with a 50 impedance.
3.2.1.2 Micro FIT connectors
Female Micro FIT Connector with 4 male pins:
This connector is used for the external DC supply and the GPIOs (the 2 signals Input and Output).
Pin N° Signal
1 +VDC
2 GND
3 INPUT 1(E1)
4 OUTPUT (S1)
The pins 3 and 4 are used for the Input/Output functions. The modem can only be powered
by the pins 1 (+VDC) and 2 (GND).
Female Micro FIT connector with 2 male pins:
This connector is used for the GPIO (2 Input signals).
Pin N°
1 INPUT 3 (E3)
2 INPUT 2 (E2) *
3.2.1.3 15-pin Sub D HD connector
The female 15-pin high density Sub D connector is used for:
- The RS232 serial link connection,
* as an option, E2 can be an analog input (contact us)
Signal
- The audio line connection (microphone and loud-speaker),
- The BOOT and RESET signals.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
1 Signal detection / Buzzer *109 – DS – DCD O
2 Data emission 103 – ED – TXD I
3 Boot BOOT I
4 Microphone + MICP I
5 Microphone - MICN I
6 Data reception 104 – RD – RXD O
7 Data set ready 107 – PDP – DSR NMEA/UBX Frames O
8 Data Terminal Ready 108/2 – TDP – DTR UBX Frames I
9 Signalization ground 102 – TS – GND 10 Loudspeaker + SPKP O
11 Clear to send 106 – PAE – CTS O
12 Request To Send 105 – DPE – RTS I
13 Ring indicator / 3,8V *125 – IA – RI O
14 Reset RESET I
15 Loud Speaker - SPKN O
EG_GenLoc31e_AOB_1003_UG_006_UK Page 15 / 64
(*)Note (by default:
- The pin 1 is the Buzzer output (wiring of the output 109/DCD optional).
3.2.2 Cables
3.2.2.1 4-wire micro FIT cable
One of the two following cables is provided
The 4-wire micro FIT cable allows to power the modem and to use the 2 signals Input and Output.
Molex connector
View from cable side
OUTPUT INPUT 1
- The pin 13 is a fixed tension (to power accessories like GenBlue 15e) of 3,8V 100mA
(wiring of the output 125/RI optional).
Green wire (OUTPUT)
Orange wire (INPUT 1)
Black wire (GND
Red wire (+VDC)
Component Characteristics
4-pin Micro FIT connector
Cable
Wire
Section : 0.75 mm²
Fuse F2.5A L250V
Fuse 2.5A/250V
(5 x 20 mm)
5mm tinned copper wire
Supplier : MOLEX
Length 1.5m
Tinned copper 24 x 0.2 mm
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 16 / 64
Component Characteristics
4-pin Micro FIT connector
Cable Length 1.5m
Wire Tinned copper 24 x 0.2 mm
Surface area : 0.75 mm²
Fuse mini N 2A 32V Fast (Grey)
3.2.2.2 2-wire micro FIT cable
The 2-wire micro FIT cable allows to use the 2 additional inputs.
Molex connector
Blue wire (INPUT 3)
5mm tinned copper wire
View from cable side
INPUT 3
INPUT 2
Descriptions and non-contractual illustrations in this document are given as an indication only.
Yellow wire (INPUT 2)
Component
2-pin Micro FIT connector
Cable
Wire
Supplier : MOLEX
Length 1.5m
Section : 0.5 mm²
ERCO&GENER reserves the right to make any modifications.
Characteristics
EG_GenLoc31e_AOB_1003_UG_006_UK Page 17 / 64
4 Characteristics and Services
The GenLoc 31e AOB is:
A class10 GSM/GPRS modem dedicated to asynchronous binary data transmission, SMS and voice.
A GPS module dedicated to position tracking.
The modem characteristics and the available services are summarized in the table below.
GSM Functions
- Quad-Bands 850/900/1800/1900 MHz
- ETSI GSM Phase 2+ Class 4 (2W @ 850 / 900 MHz)
Class 1 (1W @ 1800 / 1900 MHz)
- SIM Toolkit Release 99
Voice FUNCTIONS
- Voice (GSM mode)
- Telephony, Emergency call 112
- Full Rate, Enhanced Full Rate, Half Rate and AMR (FR/EFR/HF/AMR)
- Echo cancelation and noise reduction
- Full Duplex Free-hand
DATA Functions
- GPRS Class 10 (up to 4Rx / 2Tx)
- PBCCH/PCCCH supported, Coding scheme : CS1 to CS4
- Asynchronous data circuit, transparent and non-transparent 9600 (Standard) at 14400bds (depending on
network)
- SMS Text, PDU, point to point MT/MO and SMS Cell Broadcast
GPS Functions
- Civil frequency L1 (1575,42MHz)
- 50 channel receiver
- Precision : 2.5m CEP (DGPS 2m CEP)
- Sensitivity : -160dB
- Protocols : NMEA-0183, UBX Binary
- A-GPS compatible
Interfaces
- GSM Antenna: SMA-F connector
- GPS Antenna: SMB-M connector
- Management of GPS antenna active 3V
- Power supply : +5.5 to +32 VDC ( micro-FIT connector )
- RS232 (300 to 115200bds) + Audio through the female 15-pin Sub-D
- AT commands: GSM 07.05 and 07.07
- Specific AT commands for GPS (DSR and DTR multiplexing / NMEA Position )
- SIM reader (SIM 3V – 1,8V)
- 3 opto-coupled Inputs and 1 open-collector Output
- External auto-supply via pin RI
- Buzzer output via pin DCD
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
Accessories supplied
- Fixing brackets (x2)
- 4-wire Micro FIT cables (Power supply, Input and Output)
- 2-wire Micro FIT cables (2 Inputs)
Options / Accessories *
- Back-up battery
- Real-Time-Clock backup
- 3-axis accelerometer
- Analog input (instead of opto-coupled input E2)
- Analog input (instead of output SPKN)
- Gen 10400 : Adapter RS232 / Digital Tachograph
- GenBlue 15e : Adapter Bluetooth® / RS232 auto-supplied
- Software development kit : cdrom SDK EGM
- Accessories: Antennas, cables, power supply... (consult our website)
* contact us
EG_GenLoc31e_AOB_1003_UG_006_UK Page 18 / 64
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 19 / 64
5 Using the modem
5.1 Starting with the modem
5.1.1 Mounting the modem
To mount the modem on a support, use the fixing brackets as described below.
Fixing brackets
- Must be fixed on a flat surface.
- Max. height of the screw head: 2 mm.
The aluminum casing of the modem is connected to the 0V (GND) of the power supply and to
the 0V of the RS232 serial link. To avoid any risk of conduction of the ground plane to other
equipments,
the modem must be electrically insulated from its mechanical support.
5.1. Installation of the modem
To install the modem, it is recommended to do the following operations with the modem turned off:
- Remove the SIM card cover on the rear side.
- Carefully insert the SIM card into the reader.
Way of insertion
of the SIM card
- Push the SIM card until hearing a "clic" that ensures its correct positioning.
- Put the SIM cover back.
- Connect the GSM antenna to the SMA connector.
- Connect the GPS antenna to the SMB connector.
- For the connection to the DTE, connect the V24 link via the 15-pin Sub HD cable.
- Connect the supply cable to the continuous and regulated power source (for an automobile
application, see the paragraph 5.2).
- Connect the supply cable to the modem and turn on the external power supply.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
The modem is now ready.
There are different cases depending on the application or library installed inside the
equipment:
- Without library: corresponds to the Boot_Loader.
- With EGM standard library.
- The application ERCO & GENER EaseLoc-01.
- The owner application.
5.1.3 Checking the communication with the modem
5.1.3.1 Without Library
The GenLoc 31e AOB does not contain any library, it will return the menu of the Boot-Loader.
Connect the link RS232 between the DTE (the COM port) and the modem (DCE).
Set the RS232 port of the DTE as follows:
EG_GenLoc31e_AOB_1003_UG_006_UK Page 20 / 64
Bits per second : 115 200 bps,
Data Bits: 8,
Parity: None,
Stop Bits: 1,
▪ Flow control: material.
Use a communication software like HyperTerminal ® of Windows.
Menu by default when there is no library inside the equipment (example of display)
Bootloader V2.27L UE GenLoc 31e AOB (HW0F rev C)
1 - Update application
2 - Erase objects
M - GSM direct access
A - Advanced
E - Exit
With this status, the two leds are off.
In the case where no communication can be established with the modem:
Check the RS232 connection between the DTE and the modem (DCE),
Check the configuration of the COM port of the DTE.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
5.1.3.2 Standard with EGM Library
The GenPro 2xe AOB contains the EGM standard library; it is waiting for a command.
Connect the link RS232 between the DTE (COM port) and the modem (DCE).
Set the RS232 port of the DTE as follows:
Bits per second: 115 200 bps,
Data Bits: 8,
Parity : None,
Stop Bits: 1,
▪ Flow control : material.
Use a communication software like HyperTerminal ® of Windows.
Send the AT command. The modem returns OK. For more precision about the commands, see the
documents "EG_EGM_CL_xxx_yy" of ERCO & GENER.
With this status, the two leds are off.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 21 / 64
In the case where no communication can be established with the modem:
Check the RS232 connection between the DTE and the modem (DCE),
Check the configuration of the COM port of the DTE.
5.1.3.3 The application ERCO & GENER EaseLoc-01
This application is being developed. Contact us.
5.1.3.4 The owner application
The GenLoc 31e AOB contains your application.
Connect the RS232 link between the DTE (the COM port) and the modem (DCE).
Set the RS232 port of the DTE according to your parameters (speed, data bits, parity and stop bit).
Use a communication software like HyperTerminal ® of Windows.
Check the display and the dialogue with the GenLoc 31e AOB according to your our characteristics.
5.1.4 SIM card Extraction
To remove the SIM card from the modem, it is recommended to do the following operations with the modem
turned off:
- Remove the SIM card cover on the rear side.
- Press the SIM card (simple pressure) until hearing a "clic" that ensures its ejection.
- Remove delicately the SIM card from the reader.
- Put the SIM cover back.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
5.1.5 Hardware reset of the modem
To trigger a Hardware reset of the modem, a RESET signal (hardware) is available on the pin 14 of the 15-
pin Sub HD connector (RESET).
The modem Reset is made when the RESET signal (pin 14) is held at a low level during 10ms.
This signal must be considered as a way of reseting the modem in case of emergency only.
For more details concerning the modem RESET, see the paragraph 7.5.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 22 / 64
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 23 / 64
5.2 Specific recommendations for the use of the modem in vehicles
The power supply connector of the modem GenLoc 31e AOB must NOT be connected
directly to the battery of the vehicle.
5.2.1 Recommended Connection on the battery of a truck
All lorries have a Circuit Breaker outside the cabin. The circuit breaker is used for security reasons: for
example, if a fire breaks out in the electric box of the lorry, the driver can cut off the power source and avoid
more damage (explosion).
The circuit breaker is connected to the ground of the lorry, usually connected to the fuse box.
Most of lorry circuit breakers do not cut off the PLUS of the battery, but cut off the ground.
The scheme above shows a recommended power connection where the connection of the modem ground is
not directly connected to the battery, but connected after the circuit breaker (to the ground of the lorry or in
the fuse box).
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
5.2.2 Technical constraints in truck
It is highly recommended NOT to connect the modem supply directly to the battery but to the circuit breaker.
Otherwise the modem can be damaged when the lorry is starting up if the circuit breaker is closed (in this
case, the ground of the lorry and the ground of the battery will be connected via the modem as described in
the scheme below).
EG_GenLoc31e_AOB_1003_UG_006_UK Page 24 / 64
Example of forbidden electrical connection (risk of damage on the modem)
The scheme above shows an example of electrical connection that could damage the modem due to the fact
that the ground connection is directly connected to the battery ground.
In fact in this example, when the circuit breaker is open, the current escapes via the modem and the
electrical circuits of the lorry (the dashboard for example). And when the motor’s starter is used, it will
destroy the cables or the modem.
Moreover, the internal circuits of the modem are not designed to resist to a current about 60 A (when starting
the lorry), or they would be destroyed.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 25 / 64
5.3 Modem leds
5.3.1 GSM led
5.3.1.1 Without library
The GenLoc 31e AOB does not contain any library. The led is off.
5.3.1.2 With EGM standard library
The led remains off.
5.3.1.3 The application ERCO & GENER EaseLoc-01
This application is currently under development. Contact us.
5.3.1.4 The owner application
The GenLoc 31e AOB contains your application. The led status depends on your parameters.
5.3.2 GPS led
The positioning status of the modem is indicated by the GREEN GPS LED located on the rear side of the
modem. It is the green LED situated on the left side and under the SMA connector (see paragraph 3.1).
The table below shows the signification of the different available status of the GPS LED.
GPS LED status LED activity GPS status
Off LED off
On LED flashing
The GPS is not activated or the GPS is searching for
satellites.
The GPS is synchronized with different satellites. It
found its position.
5.4 Echo function of the deactivated AT commands
The modem contains the EGM standard library (see the documents "EG_EGM_CL_xxx_yy" of ERCO &
GENER) in this case, if no echo is returned when entering an AT command, it means that:
- the "local echo " of your communication software (like Hyperterminal) is not activated,
- the echo function of the modem has been deactivated.
The echo function can be set with the command ATE ; it requires a back-up with the command AT&W.
To activate the echo function of the modem, enter the command ATE1.
When sending AT commands to the modem using a communication software, it is recommended to:
- Deactivate the "local echo" parameter in your communication software (like Hyperterminal),
- Activate the echo function of the modem (the command ATE1).
For a communication Machine to Machine with the modem, it is recommended to deactivate the echo
function of the modem (the command ATE0) in order to avoid the CPU receiving redundant responses.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
For more information about the ATE commands, see the document "EG_EGM_CL_xxx_yy" of ERCO &
GENER.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 26 / 64
5.5 Checking the quality of the GSM reception signal
The modem contains the EGM standard library (see the documents "EG_EGM_CL_xxx_yy" of ERCO &
GENER) in this case, the modem will be able to make a call only if the received GSM signal is sufficient.
The command AT+CSQ allows to know the reception level (rssi) of the signal sent by the closest GSM Base
Transceiver Station (BTS), as well as the receive bit error rate (ber).
When the SIM card is inserted and the PIN code entered, the command AT+CSQ allows to measure the
signal from the BTS of the subscribed operator network.
This command can also be used without the SIM card, it indicates in this case the nearest BTS which can be
ORANGE, SFR or BOUYGUES for France (Without SIM card, the current subscription is not recognized).It is
therefore advisable to do the measure when the SIM card is present.
To check the quality of the GSM signal, do the following operations:
Use a communication software like Hyperterminal, enter the command AT+CSQ.
The response is in the following format:
+CSQ : <rssi>, <ber> with:
<rssi> = indicates the reception level,
<ber> = receive bit error rate.
Check the returned value <rssi> with the help of the table below.
<rssi> value Gain in dbm Interpretation <ber> value Interpretation
The GSM modem works normally with a minimum <rssi> between 11 and 15.
Bellow 10, the signal level is insufficient; the modem cannot work depending on the geographical situation or
the vehicle mobility. Above 15, the signal is sufficient.
For more information about AT commands, see the document "EG_EGM_CL_xxx_yy" of ERCO & GENER.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 27 / 64
5.6 Verification of the PIN code
The modem contains the EGM standard library (see the documents "EG_EGM_CL_xxx_yy" of ERCO &
GENER) in this case, the PIN code is essential in order to make a call or to accept a response coming from
the GSM network. This code is held in the SIM card and can be modified by the user.
To check that the PIN code has been entered, use a communication software like Hyperterminal, and enter
the command AT+CPIN?
The table below shows the main responses given by the modem:
Command Response Interpretation
AT+CPIN?
+CPIN : ERROR
The SIM card is absent or not
recognized
+CPIN : READY
+CPIN : SIM PIN
+CPIN : SIM PUK
For more information about AT commands, see the document "EG_EGM_CL_xxx_yy" of ERCO & GENER.
The PIN code is correct
The PIN code is wrong or not entered
yet
The PUK code is required
5.7 Verification of the modem registration on the GSM network
The modem contains the EGM standard library (see the documents "EG_EGM_CL_xxx_yy" of ERCO &
GENER) in this case:
1. Ensure that a valid SIM card has been inserted in the SIM card reader of the modem.
2. Using a communications application like HyperTerminal, enter the following AT commands:
a. AT+CPIN="xxxx" to enter the PIN code. The user has only 3 attempts to enter the PIN code.
After the third attempt, only a second code (code PUK) supplied by the operator, will allow you to chose a
new PIN code.
b. AT+CREG? to check the registration status on the network. The response will be of the
following format: +CREG : <mode>, <stat> with: <Mode> = configuration of the registration message not solicited,
<Stat> = registration status.
3. Check the registration status according to the value returned in the table hereunder.
Command Response Interpretation
AT+CREG?
Descriptions and non-contractual illustrations in this document are given as an indication only.
+CREG : 0,0
+CREG : 0,2 or 0,3
+CREG : 0,1
+CREG : 0,5
The modem is not recognized by the
network
The modem is searching for a network
operator.
The modem is attached in GSM to the
local operator.
The modem is attached in GSM to the
roaming operator.
ERCO&GENER reserves the right to make any modifications.
If the modem is not registered: check the connection between the modem and the antenna or the reception
level of the signal (cf. paragraph 5.5).
For more information about AT commands, see the document "EG_EGM_CL_xxx_yy" of ERCO & GENER.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 28 / 64
5.8 Reading a current position given by the GPS
The modem contains the EGM standard library (see the documents "EG_EGM_CL_xxx_yy" of ERCO &
GENER) in this case, the reading of a GPS position can be done with the command AT+GPSPOS. This
command allows to get the information received of the current position. After powering on the modem, an
acquisition time is necessary (around 45 seconds).
The response is in the following format and the table shows examples of responses:
example: 083205.00 -> 8 hours 32 minutes 05 seconds et 00 hundredth of a second in UTC
<date> : jjmmaa
example: 180406 -> the 18 April 2006
<latitude> : ddmm.mmmmm(N/S)
dd (degrees) 00 to 90
mm.mmmmm (minute) 00,00000 to 59,99999
N/S North or South
example: 4716.81310N -> latitude 47 degrees 16,81310 minutes North
<longitude> : dddmm.mmmmm(E/W)
ddd (degree) 00 to 180
mm.mmmmm (minute) 00,00000 to 59,99999
E/W East or West
example: 00003.51202W -> longitude 0 degree 0 3,51202 minutes West
<altitude> : mmmm.m in meters
<hdop> : mmm.mm horizontal dilution position in meters
<speed> : ssss.s ground speed in km /h
<cap> : dddmm.mmmm
ddd (degree) 000 to 360
mm.mmmm (minute) 00,0000 to 59,9999
<nbre sat> : nn number of satellites seen
The following table shows examples of responses returned by this command.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
Command Response Interpretation
AT+GPSPOS
+GPSPOS:-1,,,,,,,,,0
+GPSPOS:0,083138,180406,,,,,,,6
+GPSPOS:2,083205,180406,4716.81310N,0
0003.51202W,44.9,2.14,0.037,33.43,10
EG_GenLoc31e_AOB_1003_UG_006_UK Page 29 / 64
It is not possible to define a position.
Check the positioning of the GPS antenna
or the GPS configuration (see paragraph
8.2.7.3 Installation of the GPS external
antenna).
It is not yet possible to have a position but
the date and time information are
available.
A complete frame should be obtained
soon or the antenna position is not
optimum (see paragraph 8.2.6.3)
A position is read and all the information is
available.
The frame is considered as complete.
The GPS LED is flashing.
5.9 Main AT commands (HAYES)
The modem contains the EGM standard library (see the documents "EG_EGM_CL_xxx_yy" of ERCO &
GENER) in this case, the table below shows the main AT commands necessary for the control of the
modem.
Other AT commands are available, see the document "EG_EGM_CL_xxx_yy" of ERCO & GENER.
Table: Main AT commands used with the modem.
Description AT Command Response Interpretation
Enter the PIN code
Verification of
registration on the
network
Reception of an
incoming call (2*)
Make a voice call ATD<telephone
Make an emergency
call (112)
Communication lost
AT+CPIN="xxxx"
(xxxx = PIN code)
AT+CREG?
ATA
number>;
( the ; at the end of the
sequence is important; it
allows to make a voice
call )
The modem is attached in GSM to
the local operator.
The modem is attached in GSM to
the roaming operator.
The modem is searching for a
network operator.
The modem is not recognized by the
network.
Reply to the call
Communication established
PIN code not entered
The credit has run out or a
communication has already been
established.
Communication established
Hang-up ATH
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
OK
(1*) with +CMEE=1. The command AT+CMEE=1 allows the display of extended error codes; it is possible to
save it with the command AT&W.
By default, some event codes +EGEVT allow the display of status change of the SIM card (card
present, card ready…) and allows to know some status of the modem (modem ready after a RESET
…), see the Command List of ERCO & GENER.
(2*) with +CRC=1. The command AT+CRC=1 allows in the case of an incoming call to display an extended
message that indicates the canal called. This message corresponds to the type of number called: voice,
data, it is possible to save it with the command AT&W.
Examples:
If the VOICE number is called, the modem replies: +CRING : VOICE
If the DATA number is called, the modem replies: +CRING : REL ASYNC
EG_GenLoc31e_AOB_1003_UG_006_UK Page 30 / 64
5.10 Turning off the modem
The modem contains the EGM standard library (see the documents "EG_EGM_CL_xxx_yy" of ERCO &
GENER) in this case, it is strongly advised to un-register from the network with the command AT+COPS=2.
There is no particular action to do on the GPS part before turning it.
If the battery option is present, a mechanism allows to stop completely the application if the
external power supply is unplugged, and also to prepare the modem for storage or transport, in
order to limit high discharges of the battery.
If the device is not used, it has to be deactivated by sending the following command:
If the modem has an application developed with EGM, send the command
•
AT+GPIOSET=35,0
And cut the external power supply of the modem.
• If the modemdoesnotcontainanyembeddedapplication,via the Boot-Loader menu
Bootloader V2.39 GL31 UB GenLoc31e ENF (HW11 rev H/J)
GSM voltage = 21 mV
1 - Update application
2 - Erase objects
M - GSM direct access
A - Advanced
P - Power off
E – Exit
Enter "P"
And cut the external power supply of the modem.
Important Note : The switching of the battery and its auto-maintain will be automatically
reactivated once the modem will be plugged to its external power supply.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 31 / 64
5.11 Modem updating procedure
To be able to benefit from the latest functions of the GenLoc 31e AOB, an updating procedure can be used
to upgrade the software program in the modem.
This procedure consists in downloading the software into the internal Flash memory of the modem via the
RS232 link available on the 15-pin Sub HD connector.
Contact us for the software updating.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 32 / 64
6 Trouble Shooting
This section of the document describes the problems that may be encountered when using the modem.
6.1 Problem of communication between the modem and the RS232 link (V24)
If the modem does not respond to the AT commands via the RS232 link, refer to the table below to see the
possible causes and the solutions.
Table: Solutions when there is no dialogue between the modem and the RS232 link
If the modem... Check : Action
Returns nothing Is the modem correctly powered? Ensure that the modem is connected to an
external regulated power source and supplies a
tension from 5.5V to 32V (§ 8.2.1).
Is the serial cable connected at
both ends (PC and Modem)?
Is the serial cable correctly cabled
according to the paragraph
3.2.1.3?
Check the connection of the serial cable.
Connect the serial cable according to the table of
paragraph 3.2.1.3.
Returns nothing or
random characters
Is there another application used,
Is the modem without echo and
Is the communications terminal
correctly configured on the PC?
creating a conflict during the
access to the communication
port?
without message reporting?
Ensure that the configuration of the
communication terminal corresponds with the
one of the modem.
Factory configuration of the modem:
Without library (BootLoader)
Speed = 115 200 bps
Data Bits = 8
Parity = none
Stop Bits = 1
Flow Control = material
With standard library
Speed = 115 200 bps
Data Bits = 8
Parity = sans
Stop Bits = 1
Flow Control = material
ERCO&GENER Application – EasePro-01
Contact us.
Owner application
speed, data bits, parity and stop bit according
to your parameters
Close the conflicting application.
Send the command ATE1Q0 followed by AT&W
if a backup is required.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 33 / 64
6.2 "ERROR" message
The modem returns a message "ERROR" (in response to an AT command) in the following cases:
The COM port is not directed to the modem GenLoc 31e AOB but to another modem. Enter ATI1,
and the response must be Enabler_III.... Any other response indicates a dialog with another modem. In this
case, check the COM port used in the Hyperterminal.
The syntax of the AT command is incorrect: check it (see the document "EG_EGM_CL_xxx_yy" of
ERCO & GENER)
The syntax of the AT command is correct, but transmitted with wrong parameters:
- Enter the command AT+CMEE=1 to obtain an error message with its error code instead of a
simple “ERROR” message,
- Enter again the AT command which previously caused the "ERROR" message in order to
obtain the error code.
In case of an error code, the response of the modem may be:
+CME ERROR : < error code >
For more information about the error codes returned by the command AT+CMEE, see the document
"EG_EGM_CL_xxx_yy" of ERCO & GENER.
It is strongly recommended to systematically allow the modem to return the error codes (enter
the command AT+CMEE=1).
6.3 "NO CARRIER" message
If the modem returns the message "NO CARRIER" after an attempted call (voice or data), check the table
below to see the possible causes and the solutions.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
Table: Solutions when a message "NO CARRIER” is returned
If the modem... Check : Action
"NO CARRIER" Is the received GSM signal strong
enough?
EG_GenLoc31e_AOB_1003_UG_006_UK Page 34 / 64
See the paragraph 5.5 to check the quality of the
received signal
Is the modem registered on the
network?
Is the antenna correctly
connected?
"NO CARRIER"
(when attempting a
VOICE call)
"NO CARRIER"
(when attempting a
DATA call)
(1*) For more information about this AT command, see the document "EG_EGM_CL_xxx_yy" of ERCO &
GENER.
If the modem returns the message "NO CARRIER", you can get the extended error code with the command
AT+CEER.
Has the semi-colon (;) been
entered immediately after the
telephone number in the AT
command?
Has the SIM card been configured
for data?
Is the selected modulation type
supported by the called number?
Is the selected modulation type
supported by the network?
See the paragraph 5.7 to check its registration.
See the paragraph 8.2.6.3 for the
recommendations about the GSM antenna
installation.
Ensure that the semi-colon (;) has been entered
immediately after the telephone number in the
AT command.
For example : ATD0123456789;
Ensure that the SIM card is allowed to make data
calls (check with your SIM card supplier).
Ensure that the selected modulation type is
supported by the called number.
Ensure that the selected modulation type is
supported by the network. If not, select a
compatible modulation type with the command
AT+CBST=0,0,1 (1*)
For more information about the error codes returned after having sent the command AT+CEER, see the
document "EG_EGM_CL_xxx_yy" of ERCO & GENER.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 35 / 64
7 Functional Description
7.1 Architecture
7.2 Power supply
7.2.1 General presentation
The modem must be powered by an external DC tension (V+BATTERY) between +5.5V and +32V.
The regulation of the modem power supply is made with a DC/DC internal converter in order to supply all the
necessary internal DC tensions.
For the GPS module, another regulation is made for its internal power supply.
A correct functioning of the modem in communication cannot be guaranteed if the input tension
(V+BATTERY) falls below5.5 V.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
7.2.2 Internal battery option
7.2.2.1 Presentation of internal battery option
The battery is fixed inside the GenLoc 31e AOB. It is connected to an additional charging circuit cabled on
the mother board of the GenLoc 31e AOB.
This battery allows to maintain the GenLoc 31e AOB functioning in the absence of its external power supply
(power supply connected on the Micro-FIT 4-pin female connector).
The internal charging circuit allows to keep permanently the charge of the battery from the external power
supply.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 36 / 64
When the battery is completely discharged, 3 hours are necessary to obtain a new complete charge.
normal that the box gently heated in this case.
The autonomy of the battery essentially depends on the mode of use of the GenLoc 31e AOB (attachment in
GSM/GPRS, Inputs/Outputs, GPS power supply, RS232 connected...).
The internal battery option is not cabled by default and its assembling must be made by us in
our factory (contact us). The option is identified by a label (see paragraph 2.3)
If the battery option is present prepare the modem for storage or transport, in order to limit
high discharges of the battery. For that see 5.10 Turning off the modem.
7.2.2.2 Specifications of the internal battery option
The external power supply of the GenLoc 31e AOB remains unchanged (from +5,5V to 32V DC). The
internal regulator of charge supplies the 4.2V tension necessary for the battery charge.
Table: Characteristics of the polymer lithium battery
Voltage (max.) 4.2V
It is
Capacity 1000 mA/h typical
Exp. Cycle time >300 cycles> 70% of initial capacity
Temperature range Charge : 0°C to +45°C Discharge : -20°C to +45°C
Protection
(Rearmable fuse)
Descriptions and non-contractual illustrations in this document are given as an indication only.
Discharge voltage : 2.30V ±0.058V
Maximum discharge current : 2A to 4A (1.0±0.3s)
ERCO&GENER reserves the right to make any modifications.
7.2.2.3 Charge voltage and supply voltage
The following table shows the consumptions of the modem with GSM and GPS antennas and the SIM card
present.
These values were measured after a complete discharge of the battery.
(2*) The power supply consumption may vary by 5% depending on the temperature range (-20 °C to +55 °C).
7.2.2.4 Indication of presence/absence of the external power supply
EG_GenLoc31e_AOB_1003_UG_006_UK Page 37 / 64
Table: Power consumption (2*) without GSM and GPS
CONDITIONS I Charge Nom.(mA)
T=25°C Sans RS232
The modem contains the EGM standard library (see the documents "EG_EGM_CL_xxx_yy" of ERCO &
GENER) in this case, the command AT+GPIOGET=27 allows to know the status of the external power
supply for the internal battery.
AT+GPIOGET=27<Index>
0 indication of absence of external power supply
1 indication of presence of external power supply
Table: Examples of responses with the internal battery option cabled
Command Response Interpretation
AT+GPIOGET=?
AT+GPIOGET=27
AT+GPIOGET=27
+GPIOGET: (0-27)
OK
+GPIOGET: 27=0
OK
+GPIOGET: 27=1
OK
Syntax
External supply present
External supply absent
For more information concerning this command, see the "EG_EGM_CL_xxx_yy" of ERCO & GENER.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
7.2.2.5 Instruction and restrictions of use
The internal battery option is not cabled by default and its implementation must be made by us in our factory
(contact us).
When the battery is completely discharged, it takes around three hours to obtain a complete charge.
When the battery is connected and charged, it is not possible to do an On/Off of the device. Only putting the
Reset input (pin 14) to the ground or sending the command AT+EGMRST allows a reset of the modem.
The battery cannot be replaced or modified by the user. The device must not be opened, under any
circumstances. For any problem concerning the battery: the device MUST be returned to the factory.
Do not throw the modem and the battery on the fire.
7.2.3 Protections of the power supply
The modem is protected by a F2.5 A / L250 V or 2A / 32V fuse directly assembled on the power supply cable
supplied with the modem.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 38 / 64
The modem is also internally protected against tension peaks of more than 32 V.
Filter guarantees: EMI/RFI protection in input and output and signal smoothing.
7.3 RS232 serial link
7.3.1 General Presentation
The RS232 interface provides an adaptation of the tension levels (V24/CMOS ⇔ V24/V28) between the
GSM/GPRS module (DCE) and the communication port of a PC (DTE).
The RS232 interface is internally protected (ESD protection) against electrostatic peaks coming from the
RS232.
Filter guarantees: EMI/RFI protection in input and output and signal smoothing.
The available signals on the RS232 serial link are:
TX data (CT103/TX) : Data emission,
RX data (CT104/RX) : Data reception,
Request To Send (CT105/RTS) : Request to send,
Clear To Send (CT106/CTS) : Ready to send,
Data Terminal Ready (CT108-2/DTR) : Data terminal ready,
Data Set Ready (CT107/DSR) : Data set ready,
Data Carrier Detect (CT109/DCD) : Signal detection (optional) and Buzzer output (by default),
Ring Indicator (CT125/RI) / 3.8V : Call indicator (optional) and 3.8V power supply for GenBlue 15e
or Gen10400 (by default).
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
The RS232 interface was designed to allow a certain flexibility in the use of the serial interface signals. In
fact, after the setting (see command AT+IFC), the modem can work in 3-wire mode (using only the signals
TX, RX, GND), but the use of the signals TX, RX, GND, CTS, RTS is required for a GPRS application, which
is not the case for the signals DTR, DSR, DCD/Buzzer and RI/3.8V that may not be used.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 39 / 64
Normalized signals of a RS232 serial link
7.3.2 Pins description
Signal Sub HD Connector
Pins numbers
CTXD/CT103 2 I TX Transmit serial data
CRXD/CT104 6 O RX Receive serial data
CRTS/CT105 12 I RTS Request To Send
CCTS/CT106 11 O CTS Clear To Send
CDSR/CT107 7 O DSR Data Set Ready
CDTR/CT108-2 8 I DTR Data Terminal Ready
CDCD/CT109 1 O DCD Buzzer output (1*)
CRI/CT125 13 O RI
CT102/GND 9 Ground
(1*) By default
I/O RS232
Standard
Description Added function
Power supply 3.8V
(1*)
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 40 / 64
7.3.4 Output +3.8V
The tension available on the pin 13 of the 15-pin sub D HD is: see table below
Table: Conditions of use
Parameters Condition Min. Typ. Max. Unit
V
5.5 V +VDC 32V 3.8 Vdc
out
I
Max. 100 mA
out
When the battery option is present, the tension available on the pin 13 of the 15-pin sub D HD is
Parameters Condition Min. Typ. Max. Unit
V
out
I
Max. 100 mA
out
5.5 V +VDC 32V 4.4 4.5 Vdc
* The min. 2.8 V is the limit of auto protection of the battery. From this moment, the battery puts itself in
protection, and the output tension becomes null.
When the battery is not connected, the output tension is 4.4V Vout 4.5 V as long as the power
supply +VDC is present
7.4 Inputs/Outputs functioning
The modem contains the EGM standard library (see the documents "EG_EGM_CL_xxx_yy" of ERCO &
GENER) in this case, the modem GenLoc 31e AOB provides 3 inputs (opto-coupled) and 1 output (open
collector) available for an external use.
These functions can be controlled by AT commands: AT+GPIOSET for a writing access to a GPIO with the GPIO used as an output,
Without power supply * 2.8 4.2 Vdc
AT+GPIOGET for a reading access to the GPIO with the GPIO used as an input.
AT+GPIOSET=10 This command is used to control the output. By default, the output is cabled as an open
collector. To control it:
AT+GPIOSET=<n>,<x> with:
<n> = 10 : Only 1 output available on the GenLoc 31e AOB (so n=10),
<x> = 0 : Output OFF
1 : Output ON
Examples:
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
Command Response Interpretation
AT+GPIOSET=10
AT+GPIOSET=10,0
AT+GPIOGET This command is used to read the inputs. By default the inputs 1 to 3 are opto-coupled. To
read them:
AT+GPIOGET=<n> with:
<n> = 7 : reading the input 1
8 : reading the input 2
9 : reading the input 3
Examples:
Command Response Interpretation
AT+GPIOGET=7
AT+GPIOGET=9
EG_GenLoc31e_AOB_1003_UG_006_UK Page 41 / 64
+GPIOSET: 10=1
OK
OK
+GPIOGET: 7= 1
OK
+GPIOGET: 9= 0
OK
Output 1 OFF, transistor closed
Output 1 goes to ON (transistor open)
Input 1 read at 1, the input 1 is controlled
Input 3 read a 0, the input 3 is not controlled
See table of the paragraph 8.2.3 for the characteristics of use of the Inputs/Outputs.
7.5 BOOT
This signal must NOT be connected, NOT used. Its use is strictly reserved for the manufacturer.
7.6 RESET
7.6.1 General presentation
This signal allows to make a Hardware RESET of the modem. In fact, this pin is used to force a RESET of
the modem, doing a low level during at least 10 ms.
This signal must be used only in case of emergency RESET.
This signal must be driven with an open collector assembly:
pin 14 (RESET) at 0, for the modem Reset,
pin 14 (RESET) at 1, for normal mode.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
Signal Sub HD Connector
Pins number
RESET 14 I/O SCHMITT Reset Modem
• This signal must be used only in case of emergency RESET. A Software RESET is always
preferable to a Hardware RESET. It is strongly unadvised to execute this function whilst in
communication or dialog, without having first detached it from the network operator.
• Using the RESET does not restore the factory parameters.
For more information concerning the Software RESET, see the document
"EG_EGM_CL_xxx_yy" of ERCO & GENER and refer to paragraph 5.10 to turn the device off
and detach correctly the modem from the network operator.
7.6.2 RESET sequence
EG_GenLoc31e_AOB_1003_UG_006_UK Page 42 / 64
Pin description
I/O E/S Type Description
To activate the emergency RESET sequence, the RESET signal must be put to a low level during at least 10
ms.
A soon as the modem has been RESET, if a SIM card is inserted inside the SIM reader, you must wait for
the end of the initialization before accessing it again. Moreover, the acquisition time of a GPS position will
have to be taken into consideration.
Using the RESET does not restore the factory parameters.
7.7 WatchDog
The Hardware WatchDog function allows the surveillance of the modem software activity: the Software
management of the WatchDog is implanted in the embedded application by default. In the case of a
development (EGM) it must be implanted in the embedded application of the final customer.
If the software activity is interrupted, the WatchDog component starts a hardware Reset.
The WatchDog function is active only if the SIM card is present. That’s why, it is imperative to remove the
SIM card during a Firmware updating.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 43 / 64
7.8 Audio
The modem contains the EGM standard library (see the documents "EG_EGM_CL_xxx_yy" of ERCO &
GENER) in this case, the audio interface is standard to connect an equipment like a telephone handset.
The echo cancelation (command AT$MICAEC) and noise reduction features are also available in order to
improve the audio quality in the case of free-hand applications.
The audio interface is standard to connect a telephone handset (the command AT$VSELECT allows the
Handset selection, see the document "EG_EGM_CL_xxx_yy" of ERCO & GENER).
ERCO & GENER advises the use of the cable DATA/AUDIO Sub D 9pts Fem / Sub HD 15pts Male / RJ9
(order code 4404000205) and a telephone handset (order code 3153400000).
(1*) The power supply consumption may vary by 5% depending on the temperature range (-20 °C to +55 °C).
(2*) Idle mode = modem registered on network but not in communication.
72 72 72 72
56 55 51 49
GPS only with passive antenna
CONDITIONS Search Fix
T=25°C I Nom.(mA) I Nom.(mA)
GPS module only @ 5,5V
@ 12V
@ 24V
@ 32V
Descriptions and non-contractual illustrations in this document are given as an indication only.
30 20
17 11
10 7
9 6
ERCO&GENER reserves the right to make any modifications.
T=25°C and SIM card 3V I Nom.(mA) I Nom.(mA) I Nom.(mA) I Nom.(mA)
Idle mode (2*) @ 3.8V 44 44 44 44
In GSM communication
1RX/1TX, Full Power
Power (2W/1W)
In GPRS CL10 communication
2RX/2TX, Full Power
Power (2W/1W)
During TX bursts
Power (2W/1W)
EG_GenLoc31e_AOB_1003_UG_006_UK Page 50 / 64
GPS only with active antenna 20 mA
CONDITIONS Search Fix
T=25°C I Nom.(mA) I Nom.(mA)
47 37
14 11
Table: Consumption
Internal battery mode option
Without external power supply
GPS OFF and with RS232 disconnected
@ 3.8V 258 256 227 218
@ 3.8V 404 406 347 335
@ 3.8V 1423 1423 1147 1061
with GPS (Fixed with antenna 20 mA supply.) and with RS232 connected.
CONDITIONS 850 MHz 900 MHz 1800 MHz 1900 MHz
T=25°C and SIM card 3V I Nom.(mA) I Nom.(mA) I Nom.(mA) I Nom.(mA)
Idle mode (2*) @ 3.8V 87 87 87 87
In GSM communication
1RX/1TX, Full Power
Power (2W/1W)
In GPRS CL10 communication
2RX/2TX, Full Power
Power (2W/1W)
During TX bursts
Power (2W/1W)
(2*) Idle mode = modem registered on network but out of communication.
GPS module only @ 3.8V 35 23
GPS module only @ 3.8V 55 43
@ 3.8V 301 299 270 261
@ 3.8V 447 449 390 378
@ 3.8V 1466 1466 1190 1103
GPS only with passive antenna
CONDITIONS Search Fix
T=25°C I Nom.(mA) I Nom.(mA)
GPS only with active antenna 20 mA
CONDITIONS Search Fix
T=25°C I Nom.(mA) I Nom.(mA)
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
8.2.2 Audio interface
The audio interface is available via the 15-pin Sub HD connector, see the paragraph 3.2.1.3 15-pin Sub HD
connector.
8.2.2.1 Microphone
Mic Input Parameter/Conditions Min Typ Max Units
Maximum Input Range –
Mic(+) to Mic(-)
Nominal Ref. Level –
Mic(+) to Mic(-)
Differential Input Resistance –
Mic(+) to Mic(-)
Microphone Pre-Amplifier Gain Differential MIC 25.6 dB
EG_GenLoc31e_AOB_1003_UG_006_UK Page 51 / 64
Characteristics recommended for the microphone
Inputs 3 dBm0 (Max. digital
sample amplitude when PGA
gain set to 0 dB)
Differential MIC -10 dBm0
Differential MIC,
MICAMP gain = 25.6 dB
32.5 mV
36 k
RMS
8.2.2.2 Loudspeaker
Characteristics of the output for the loudspeaker
Spkr Output Parameter/Conditions Min Typ Max Units
Maximum Differential Resistive
Load
Maximum Differential Capacitive
Load
Common Mode Minimum
Resistive Load
Common Mode Maximum
Capacitive Load
Amplifier Gain
Output Swing 3.9 V
Output Swing 1.5 VPP
100 pF
At Internal Speaker (+) or (-)
At Internal Speaker (+) or (-)
EARG = 1
EARG = 0
PP
120
33
200 k
50 pF
1
-11
dB
dB
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 52 / 64
Parameter Conditions Min Typ Max Units
Earphone output swing at
EARP-EARN
Distortion 2% and 120 , VSP input
level = +3 dBm0, amp gain = -11 dB
Distortion 2% and 33 , VSP input
level = -5.34 dBm0, amp gain = -11 dB
Distortion 2% and 120 , I2S input
level = +3 dBm0, amp gain = -11 dB
Distortion 2% and 120 , VSP input
level = +3 dBm0, amp gain = 1 dB
3.1 3.92
Component Value
C1 CAPACITOR 100 pF
0.98
0.38
0.93
V
P-P
C2, C3 CAPACITOR 47pF
R1, R2 RESISTOR 200 KOhms
8.2.2.3 Buzzer
Characteristics of the output for the Buzzer
Characteristics Symbols Conditions Min. Typ. Max. Unit
collector-base voltage V
collector-emitter voltage V
Emetteur ouvert 48 Vdc
CB0
Open base 40 Vdc
CE0
collector current (DC) IC 600 mAdc
peak collector current ICM 800 mAdc
Collector Cutoff Current I
collector-emitter saturation
voltage
CB0
V
CEsat
transition frequency fT
collector capacitance CC
total power dissipation P
Ttot
IE = 0; VCB = 60 V; Tj = 25 °C 10 nA
IE = 0; VCB = 60 V; Tj = 125 °C 10 µAdc
IC = 150 mA; IB = 15 mA * 300 mV
IC = 500 mA; IB = 50 mA * 1 Vdc
IC = 20 mA; VCE = 20 V; f = 100
MHz
I
= Ie = 0; VCB = 10 V; f = 1
E
MHz
T
25 °C 225 mW
amb
300 MHz
8 pF
dc
dc
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 53 / 64
Example of transducer tested with the GenLoc 31e AOB:
Buzzer characteristics
Values
Type Transducer AT-2720-T-R
Consumption 1-30V peak /3.5mA max.
Resonance frequency 2.048Hz ±500HZ
Acoustic level (SPL) Min.88dBA @10cm
8.2.3 Inputs/Output
By default, the GenLoc 31e AOB provides 3 opto-coupled inputs (E1 to E3) and 1 open-collector output (S1).
As an option, it is possible to have an analog input instead of the opto-coupled input E2.
8.2.3.1 Opto-coupled Inputs
Table: Diode Characteristics of the opto-coupled inputs
Characteristics Symbols Conditions Min. Typ. Max. Unit
max. current I
50 mA
F (rms)
max. inverted tension VR 5 V
Direct tension VF I
Inverted current IR V
= 10 mA 1.0 1.15 1.3 V
F
= 5 V 10 µA
R
Capacity CT V=0, f = 1 MHz --- 30 --- pF
Transfer Ratio IC / IF IF = 5 mA, VCE = 5 V 50 --- 600 %
Saturation of the transfer ratio IC / I
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
IF = 1 mA, VCE = 0.4 V 60 %
F (SAT)
EG_GenLoc31e_AOB_1003_UG_006_UK Page 54 / 64
Internal electric scheme of the 3 inputs
The minimum of voltage command for voltage detection is: 5 V
The maximum voltage command is : 35 V
8.2.3.2 Output
Table: Characteristics of the open-collector output
Characteristics Symbols Conditions Max. Unit
max. tension V
max. tension V
Open transmitter 48 VDC
CE0
V
CES
= 0 V 48 VDC
BE
Collector current IC 0.5 A
Saturation tension V
Dissipation P
I
CEsat
T
Ttot
= 500 mA 1.3 V
C
amb
25 °C, Tj = 110 °C 0.78 W
Electric scheme of the output
No protection is provided. The user must respect the values of the table above.
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
EG_GenLoc31e_AOB_1003_UG_006_UK Page 55 / 64
8.2.3.3 Analog input
As an option, it is possible to have an analog input instead of the opto-coupled input E2.
This analog input allows to do a measure in tension (contact us).
Table: Characteristics of the analog input option
Characteristics Min. value Max. value
Input Voltage -0.3 V DC 10.8 V
DC
Internal electrical scheme of the analog input option
8.2.3.4 Bus One Wire
As an option on the GenLoc 31e AOB, it is possible to have an input Bus One Wire instead of the opto-
coupled input E3.
Table: Characteristics of bus One Wire
Parameters Condition Min. Typ. Max. Unit
VIL Input Voltage – Low -0.3 0.8 Vdc
VIH Input Voltage – High 2 3.3 3.6 Vdc
R
Internal Pull-Up Resistor 100 K
PULLUP
CIN Input Capacitance 14 pF
F
100 KHz
max
Internal Wiring Diagram of One Wire bus
Descriptions and non-contractual illustrations in this document are given as an indication only.
ERCO&GENER reserves the right to make any modifications.
8.2.4 SIM interface
SIM Card 3 V or 1.8 V
8.2.5 RESET signal
EG_GenLoc31e_AOB_1003_UG_006_UK Page 56 / 64
Table: Characteristics of the SIM card supply tension
Cabling Scheme
Table: Conditions of use
Parameters Condition Min. Typ. Max. Unit
VILInput Voltage – Low or float -0.3 0.8 Vdc
VIHInput Voltage – High 2 3.5 Vdc
RIPUInternal Pull-Up Resistor 5K38 Ohms
8.2.6 RF GSM/DCS characteristics
8.2.6.1 RF functioning
The RF functioning complies with the ETSI GSM Standards.
The RF performances for the receiver and the transmitter are described below.
Table: Parameters of the RF receiver and transmitter