EPH Controls CRT2 Operating Instructions Manual

Page 1 of 2
CRT2 Room Thermostat Battery Operated
Contents
1. Factory default settings
2. Specication & wiring
3. Mounting
4. Installation
5. Wiring diagram
6. Frost protection
7. Button / symbol description
8. Resetting the thermostat
9. Keypad lock and unlock
10. High and Low temperature limitation
11. Replacing the batteries
Prior to setting the thermostat, it is neccessary to complete all required settings described in this section.
1. Factory default settings
Contacts: Volt Free Temperature indicator: °C Switching dierential: 0.4°C In built frost protection: 5°C High and Low temp. limitation: O
5. Wiring diagram
Operating Instructions
CAUTION!
Before commencing any work on the electrical
connections, you must rst disconnect the thermostat from the mains. None of the 230V connections must be live until the installation has been completed and the housing is closed. Only qualied electricians or authorised service sta are permitted to open the thermostat.
There are parts that may carry mains voltage behind the cover. The thermostat must not be left unsupervised when open. (Prevent non specialists and especially children from gaining access to it.)
Impor tant: Kee p this document
INTERNAL WIRING DIAGRAM CRT2
321
ON OFFCOM
2. Specications & wiring
Power supply: 2xAA Alkaline Battery Power consumption: 2mW Battery replacement: Once per year Temp. control range: 5 ... 35°C Ambient temperature: 0 ... 50°C Contact rating: 8A 250Vac Dimensions: 84 x 84 x 30mm Temperature sensor: NTC 10K Ohm @ 25°C Temperature indication: ˚C Switching dierential: Adjustable from 0.2/0.4/0.6/0.8/1.0˚C Frost protection: Only operational in stand by mode
3. Mounting
The mounting height should be 1.5 meters above the oor level. The thermostat should be wall mounted in the room where the heating is to
be controlled. The place of installation should be chosen so that the sensor can measure the
room temperature as accurately as possible. Choose the mounting location to prevent direct exposure to sunlight or other
heating / cooling sources when mounted. The unit can be tted to: 1. Recessed conduit boxes
2. Surface mounting boxes
3. Directly on walls.
6. Frost protection
Frost protection is built into this thermostat, it is pre xed at 5°C and is not adjustable.
It will only be activated when the thermostat is in the stand by mode and the room temperature reaches 5°C.
5°C
7. Button / Symbol description
Heating ON symbol
Room temperature
Reset button
On / Standby button
Set button
Set point increase Set point decrease
8. Resetting the thermostat
It is necessary to reset the thermostat prior to initial programming.
Press and hold the button for 5 seconds.
dEL will appear on the screen.
Press the button on the side of the thermostat.
Set
RESET
4. Installation
Slacken the fastening screw on the bottom of the thermostat with a philips head screwdriver.
The thermostat is hinged and can be opened 180 degrees.
Mount the unit as described in section 3.
Wire the thermostat according to the wiring diagram. Close the thermostat and tighten the fastening screw.
EPH Controls Ireland
Sitecast Industrial Estate, Pouladu, Cork, T12 W665, Ireland
sales@ephcontrols.com www.ephcontrols.com
9. Keypad lock and unlock
To lock the keypad, press and hold the and buttons for 5 seconds.
will appear on the screen. The keypad is now locked.
To unlock the keypad, press and hold the and buttons for 5 seconds.
will disappear from the screen. The keypad is now unlocked.
OFF
EPH Controls UK
Unit E4, Welland Business Park, Valley Way, Market Harborough, Leicestershire, LE16 7PS, United Kingdom
sales@ephcontrols.co.uk www.ephcontrols.co.uk
20170301_AW1077_CRT2_OpIns_JW
Page 2 of 2
CRT2 Room Thermostat Battery Operated
10. High and Low temperature limitation
An upper and lower temperature limit may be chosen.
Press and hold the and buttons for 10 seconds.
Limit
will appear on the screen.
OFF
Use the button to select .
Press the button to select high limit.
Set
Press the and buttons to select high limit temperature.
Press the button to select low limit.
Press the and buttons to select low limit temperature.
Press the button and the thermostat is ready for operation.
Set
Set
Limit will appear on the screen.
To deactivate High and Low temperature limitation.
Press and hold the and buttons for 10 seconds.
Limit
will appear on the screen.
ON
Use the button to deactivate this function.
Limit
will appear on the screen.
OFF
Press the button and the thermostat is ready for operation.
Set
Set
Limit
ON
Set
OFF
Operating Instructions
11. Replacing the batteries
Slacken the fastening screw on the bottom of the thermostat with a philips head screwdriver.
The thermostat is hinged and can be opened 180 degrees.
Replace the batteries with 2 x AA Alkaline batteries.
Close the thermostat and tighten the fastening screw.