EPH Controls CP4M Operating Instructions Manual

CP4M Room Thermostat
Hardwired Open Therm®
Contents
1. LCD symbol / button description
2. Resetting the thermostat
3. Setting the date, time and operating mode
4. Factory program settings
5. Adjusting the program settings for 5/2d
6. Copy function
7. Temporary override
8. Permanent override
9. Boost function
10. Holiday function
11. Keypad lock and unlock
12. Backlight mode selection
13. Frost protection
14. Installer Menu (without OpenTherm® connected)
15. Installer Menu (with OpenTherm® connected)
Boiler Plus
Page 1 of 4
Operating Instructions
CAUTION!
Before commencing, disconnect the
device from the mains. There are parts that carry mains voltage behind the cover. Never leave unsupervised when it is open. (Prevent non specialists and especially children from gaining access to it.)
Never remove this product from the electrical baseplate. Disconnect from mains supply in the event of any damage to any buttons. Do not use sharp tools to push any button.
How your programmable thermostat works
When the thermostat is in the AUTO mode, it will operate according to the times and temperatures that have been programmed. The user can select from 6 dierent programs per day - each with a time and a temperature.
There is no OFF time, only a higher and a lower temperature setpoint.
If the user wants the thermostat to be OFF at a certain time, set the temperature for this time to be low. The thermostat will turn ON if the room temperature is lower than the setpoint for the current period.
Example: If P1 is set to be 21˚C at 6am, and if P2 is set to be 10˚C at 8am, the thermostat will look for the temperature to be 21˚C between 6am and 8am.
1. LCD Symbol / button description
1.1 LCD Symbol description
Current program
Day / Month
Current Time
(Boost to time)
1.2 Button description
Day of the week
Operating mode
Temperature
Heating on symbol
Keypad lock symbol
Prior to setting the thermostat, it is neccessary to complete all required settings described in this section.
3. Setting the date, time and operating mode
Press the ‘TIME’ button once, the year will begin ashing.
Press the or buttons to adjust the year. Press the ‘OK’ button.
Press the or buttons to adjust the month. Press the ‘OK’ button.
Press the or buttons to adjust the day. Press the ‘OK’ button.
Press the or buttons to adjust the hour. Press the ‘OK’ button.
Press the or buttons to adjust the minute. Press the ‘OK’ button.
Press the or buttons to adjust from 5/2d to 7d or 24h mode.
Press the or buttons to turn DST (Day Light Saving Time) On or O.
Press the ‘AUTO’ button or wait 5 seconds and the thermostat will return to normal operation.
4. Factory program settings 5/2d
Mon-Fri
Sat-Sun
P1 P2 P3 P4 P5 P6
06:30
21˚C 10˚C 10˚C 10˚C 21˚C 10˚C
08:00 10:00 12:00 14:00 17:30 23:00
21˚C 10˚C 10˚C 10˚C 21˚C 10˚C
08:00
12:00
5/2D
14:00
17:30
22:00
Automatic mode
(Back)
Manual mode
O mode
AUTO MAN OFF PROG
HOL COPY
TIME
BOOST
2. Resetting the thermostat
Press the button on the side of the thermostat.
rst no’ will appear on the screen.
Press the button.
rst yes’ will appear on the screen.
Press the ‘OK’ button to reset the thermostat.
RESET
EPH Controls Ireland
sales@ephcontrols.com www.ephcontrols.com
Set point increase
Set point decrease
Reset button
OK
OK conrm button
Boost mode
Copy function
Holiday mode
Time / date
Mon-Fri
Sat-Sun
Everyday
5. Adjusting the program settings for 5/2d
P1 P2 P3 P4 P5 P6
06:30
21˚C 10˚C 10˚C 10˚C 21˚C 10˚C
08:00 10:00 12:00 14:00 17:30 23:00
21˚C 10˚C 10˚C 10˚C 21˚C 10˚C
P1 P2 P3 P4 P5 P6
06:30
21˚C 10˚C 10˚C 10˚C 21˚C 10˚C
08:00
08:00
12:00
12:00
7D
24H
14:00
14:00
17:30
17:30
22:00
22:00
Press the ‘PROG’ button once.
Programming for Monday to Friday is now selected.
Press the or buttons to adjust the P1 time. Press the ‘OK’ button.
Press the or buttons to adjust the P1 temp. Press the ‘OK’ button.
Repeat this process to adjust P2 to P6 times and temperatures.
Press the ‘OK’ button.
EPH Controls UK
sales@ephcontrols.co.uk www.ephcontrols.co.uk
20190930_CP4M_OpIns_JW
CP4M Room Thermostat
Hardwired Open Therm®
Boiler Plus
Page 2 of 4
Operating Instructions
5. Adjusting the program settings for 5/2d
Programming for Saturday to Sunday is now selected.
Press the or buttons to adjust the P1 time. Press the ‘OK’ button.
Press the or buttons to adjust the P1 temp. Press the ‘OK’ button.
Repeat this process to adjust P2 to P6 times and temperatures.
Press the ‘AUTO’ button to return to automatic mode.
While in PROG Mode pressing the ‘PROG’ button will jump from P1-P2 etc without changing the temperature.
While in PROG Mode pressing the ‘TIME’ button will jump to the next day (block of days).
If 7 D mode is selected, you can program each day of the week with 6 individual times and temperatures.
If 24H mode is selected, you can only program each day of the week with the same 6 times and temperatures.
(Continued)
6. Copy function
Copy function may only be used if the thermostat is in the 7d mode.
Set the times and temperatures for the day that you wish to copy from in PROG Mode.
When still on the day press the ‘COPY’ button.
The day of the week that you have selected will be shown with ‘COPY’ below it.
The next day will begin to ash on the top of the screen.
Press the button to copy the times and temperatures to that day.
Press the button to skip a day.
You can copy to multiple days using the button.
Press the ‘OK’ button when copying has been completed.
7. Temporary override
9. Boost function
The thermostat can be boosted to a specic temperature for 1, 2 or 3 hours while the thermostat is operating in all modes except for holiday mode.
Press the ‘BOOST’ button 1, 2 or 3 times, the time that the boost will be activated to will ash on the screen.
If you do not press any other button the boost will activate to the temperature displayed on the screen after 5 seconds.
If you press the ‘OK’ button the temperature will now ash. You can edit the temperature if you press the or buttons.
Press the ‘OK’ button or wait for 5 seconds to enter BOOST Mode.
BOOST TO’ will now be displayed on the screen with the time that it is activated to displayed above this text.
Press the ‘BOOST’ button again to deactivate the boost.
10. Holiday function
This will switch your heating system o between the start and end times you select .
Press the ‘HOL’ button, ‘HOLIDAY FROM’ will appear on screen.
Press the or buttons to adjust the year. Press the ‘OK’ button.
Press the or buttons to adjust the month. Press the ‘OK’ button.
Press the or buttons to adjust the day. Press the ‘OK’ button.
Press the or buttons to adjust the hour. Press the ‘OK’ button.
HOLIDAY TO’ will appear on screen.
Press the or buttons to adjust the year. Press the ‘OK’ button.
Press the or buttons to adjust the month. Press the ‘OK’ button.
Press the or buttons to adjust the day. Press the ‘OK’ button.
Press the or buttons to adjust the hour. Press the ‘OK’ button.
The thermostat will now return to the mode it was in before the Holiday settings were entered.
To cancel Holiday mode, press the ‘HOL’ button.
When in AUTO mode, press the or buttons to adjust the temperature setpoint.
OvEr’ will appear on the screen.
Press ‘OK’ or after 5 seconds the thermostat will operate in this temporary override, util the next switching time.
To cancel temporary override, press the ‘OFF’ buttton and then press the ‘AUTO’ button to return to the automatic mode.
8. Permanent override
Press the ‘MAN’ button to enter Manual Mode (Permanent Override).
MAN’ will appear on the screen.
Press the or buttons to adjust the temperature setpoint.
Press ‘OK’ to conrm the temperature selection or after 5 seconds the thermostat will operate in this permanent override.
The thermostat will operate in MAN mode until the mode is changed.
To cancel permanent override, press the ‘OFF’ button and then press the
AUTO’ button to return to automatic mode.
11. Keypad lock and unlock
To lock the keypad, press and hold the and buttons for 10 seconds.
will appear on the screen. The keypad is now locked.
To unlock the keypad, press and hold the and buttons for 10 seconds.
will disappear from the screen. The keypad is now unlocked.
12. Backlight mode selection
There are two settings for selection. The factory default setting is AUTO.
OFF The backlight is permanently OFF.
AUTO On pressing any button the backlight stays on for 5 seconds.
ON The backlight is permanently ON.
To adjust the backlight setting, lower the cover on the front of the unit.
Press the ‘OK’ button for 5 seconds.
Press either the or buttons to select the OFF, AUTO or ON mode.
Press the‘OK’ button.
13. Frost protection
Frost protection is built into this thermostat.
It is pre xed at 5°C and is not adjustable.
It will only be activated when the thermostat is in the OFF mode and the room temperature falls below 5°C.
OFF
AUTO
5°C
EPH Controls Ireland
sales@ephcontrols.com www.ephcontrols.com
EPH Controls UK
sales@ephcontrols.co.uk www.ephcontrols.co.uk
20190930_CP4M_OpIns_JW
CP4M Room Thermostat
Hardwired Open Therm®
Boiler Plus
Page 3 of 4
Operating Instructions
14. Installer menu (without OpenTherm® connected)
To access the installer menu, you must hold Prog and OK for 5 seconds.
When in the installer menu, press , and OK to navigate and select. Use AUTO, MAN or OFF to go back a step.
P0 1: Mode (Normal / Optimum Start / TPi) P0 2: Hi Lo (Limiting the thermostat) P0 3: Hysteresis (Dierential) P0 4: Calibration P0 5: Frost Protection Exit
P0 1: Mode (Normal / Optimum Start / TPi)
Normal Mode (Nor)
When the thermostat is in Normal mode, the thermostat will try to reach the target temperature after the program changes.
Example: Program 1 on the thermostat is 21°C for 06:30am and the room temperature is 18°C. The thermostat will start the heating at 06:30am and the room temperature will start to increase then.
Optimum Start Mode (OS)
When the thermostat is in Optimum Start mode, the thermostat will try to reach the target temperature by the start time of the next switching time. This is done by setting the Ti (time interval) on the thermostat in this menu to 10, 15 or 20. This will allow the thermostat 10 mins, 15 mins or 20 mins to increase the room temperature by 1°C.
Ti can be set when OS is selected in the installer menu.
To achieve the target temperature when the program starts, the thermostat will read:
1. The Room Temperature (RT)
2. The Setpoint Temperature (ST)
3. The Target Temperature Dierence (TTD) is the dierence between the setpoint temperature and the room temperature .
The time (in minutes) that it will take to overcome (TTD) is called Optimum Start Time (OST) and its maximum value is 3 hours = 180 mins. This is subtracted from the start time.
As the temperature increases the thermostat will recalculate the OST if the temperature is increasing too quickly.
Optimum Start Control Graph with Ti = 20
0
20
40
60
80
100
120
140
Optimum Start Time (Mins)
160
180
89 7 6 5 4 3 2 1
Target Temperature Dierence ˚C
Example when Ti = 20
Program 1 on the thermostat is 21°C for 06:30am and the room temperature is 18°C. The thermostat will start the heating at 05:30am to reach 21°C for 06:30am @ Ti=20.
Example when Ti = 10
Program 1 on the thermostat is 21°C for 06:30am and the room temperature is 18°C. The thermostat will start the heating at 06:00am to reach 21°C for 06:30am @ Ti=10.
TTD
Boiler Plus
Optimum Start Control Graph with Ti = 15
0
15
30
45
60
75
90
105
Optimum Start Time (Mins)
120
135
89 7 6 5 4 3 2 1
Target Temperature Dierence ˚C
Optimum Start Control Graph with Ti = 10
0
10
20
30
40
50
60
70
Optimum Start Time (Mins)
80
90
89 7 6 5 4 3 2 1
Target Temperature Dierence ˚C
TTD
TTD
20˚C
Time Proportional Integral Mode (TPi)
When the thermostat is in TPi mode and the temperature is rising in the zone and falls into the Proportional Bandwidth section, TPi will start to aect the thermostats operation. The thermostat will turn on and o as it gains heat so that it doesn’t overshoot the setpoint by too much. It will also turn on if the temperature is falling so it doesn’t undershoot the setpoint which will leave the user with a more comfortable level of heat.
There are 2 settings that will aect the thermostats operation:
1. The Number of Heating Cycles Per Hour
2. The Proportional Bandwidth
CyC - Number of Heating Cycles per Hour:
6 Cycles
This value will decide how often the thermostat will cycle the heating on and o when trying to achieve the setpoint temperature. You can select 2/3/6 or 12.
Pb - Proportional Bandwidth:
2˚C
This value refers to the temperature below the setpoint at which the thermostat will start to operate in TPi Control. You can set this temperature from 1.5˚C to 3.0˚C in 0.1˚C increments.
TPi Control
Temp
22˚C
21˚C
20˚C
19˚C
18˚C
17˚C
200 40 60 80 100
Heating On Heating O
Example – Program 1 on the thermostat is 21°C for 06:30am and the room temperature is 18°C. The thermostat will start the heating at 06:30am and the heat will start to increase then but will switch itself o before it reaches temperature and allow the room temperature to increase naturally – this cycle may begin again if the thermostat isn’t reaching temperature.
Setpoint Temperature
Proportional Bandwidth
Time Minutes
P0 2: Hi Lo (Limiting the thermostat)
This menu allows the installer to change the minimum and maximum temperature range that the thermostat can be set at. Defaults are 35°C for Hi and 5°C for Lo.
P0 3: Hysteresis HOn and HOFF
This menu allows the installer to change the switching dierential of the thermostat when the temperature is rising and falling.
HOn is the fall in temperature – Default – 0.4°C. This will allow a fall of 0.4°C from the setpoint before the thermostat turns on again.
HOFF is the rise in temperature – Default – 0.0°C. This will allow the temperature to rise 0°C above its setpoint.
P0 4: Calibration
This menu allows the installer to re-calibrate the thermostat. The current temperature will be displayed on the screen and can be adjusted by pressing the up and down buttons.
P0 5: Frost Protection
ON
This menu allows the installer to activate or de-activate frost protection. When frost protection is activated the thermostat will switch on the boiler when the temperature drops below 5˚C.
Exit
This menu allows the installer to return to the main interface. It is also possible to exit the installer menu by pressing AUTO, MAN or OFF whilst in the installer menu.
EPH Controls Ireland
sales@ephcontrols.com www.ephcontrols.com
EPH Controls UK
sales@ephcontrols.co.uk www.ephcontrols.co.uk
20190930_CP4M_OpIns_JW
CP4M Room Thermostat
Hardwired Open Therm®
15. Installer menu (with OpenTherm® connected)
P0 1 - P0 5 as per CP4M standard
P0 6: Setting DHW temperature P0 7: OpenTherm® Information P0 8: DHOP P0 9: Set OpenTherm® Parameters Exit
P0 6: Setting DHW temperature
This menu allows the installer to change the DHW temperature of the boiler. The temperature can be set in 0.5°C increments by pressing the “+” or “-” buttons.
Press the “OK” button to select the desired temperature.
This menu is only available when the thermostat is connected to OpenTherm® and DHOP is ON (P08 OT installer menu).
P0 7: OpenTherm® Information
Boiler Plus
Page 4 of 4
Operating Instructions
Param Description Range Default
HHCH t-1 Maximum set point heating 45 - 85˚C 85˚C
LLCH t-2
CLI t-3
InFL t-4
HHbO t-5
Minimum set point heating 10 - HHCH˚C 45˚C
This allows user to select dierent climatic curves for weather compensation. This only applies to boilers with an outside sensor connected.
Inuence of room sensor on modulation of the boiler. Recommended value is 10.
This is the target setpoint for your CH ow temperature. Note: This value must be within the range of HHCH and LLCH.
0.2 - 3.0 1.2
0 - 20 10
HHCH Max >=ID57 >=LLCH Min
85˚C
This menu allows the installer to view information received from the OpenTherm® boiler. It may take a few seconds to load information relating to each parameter. The information that can be shown from the boiler is outlined in the table below.
Displayed on
screen
tSEt
tFLO
trEt
tdH
tFLU
tESt
nOdU
FLOr
PrES
Description Remark
Target water temp
Flow water temp
Return water temp
DHW temperature
Flue gas temperature
Outdoor temperature
Modulation percentage
Water ow
Water pressure
This is only visible if DHOP is On (P08 OT Installer menu)
Dependent on boiler
Dependent on boiler
This is only visible if DHOP is On (P08 OT Installer menu)
Dependent on boiler
P0 8: DHOP
This menu allows the installer to activate or deactivate DHW target temperature control from the thermostat. This menu is only available when the thermostat is connected to OpenTherm®
Exit
Press OK button to turn back to main interface.
Climatic Curve
Flow Temperature ˚C
100
80
60
40
20
20 16 12 8 4 0 -4 -8 -12 -16
Outside Temperature ˚C
3 2.5
Exit:
This menu allows the installer to return to the main interface.
It is also possible to exit the installer menu by pressing AUTO, MAN or OFF whilst in the installer menu.
2
1.5
1.2
1
0.8
0.6
0.4
0.2
P0 9: Set OpenTherm® Parameters
This menu allows the installer to congure the OpenTherm® parameters. To access the menu please enter the password “08” with the “+” and “–” buttons.
Press “OK” to conrm.
The parameters that can be set are outlined in the table below.
EPH Controls Ireland
sales@ephcontrols.com www.ephcontrols.com
EPH Controls UK
sales@ephcontrols.co.uk www.ephcontrols.co.uk
20190930_CP4M_OpIns_JW
Loading...