ViewStar AU series solar charge controller
1. Overview
Thank you for selecting the ViewStar AU series common positive solar charge
controller. The VS-A controller is a PWM charge controller with built in LCD display that
adopts the most advanced digital technique. The multiple load control modes enable it can
be widely used on solar home system, traffic signal, solar street light, solar garden lamp,
etc. The features are listed below:
Adopt high quality components of ST,IR and Infineon, make sure product using lifespan
Terminals have UL and VDE certification, the product is more safer and more reliable
Controller can work continuously at full load within the environment temperature range
from -25 to 55 ℃
3-Stage intelligent PWM charging:Bulk, Boost/Equalize, Float
Support 3 charging options: Sealed, Gel, and Flooded
LCD display design, dynamically displaying device’s operating data a nd worki ng
condition
Double USB design, the power supply charge for electronic equipment
With humanized button settings, operation will be more comfortable and convenient
Multiple load control modes
Energy statistics function
Battery temperature compensation function
Extensive Electronic protection
2. Product Features
※ USB output ports provide the power supply of 5VDC/2.4A and have the short
circuit protection.
NOTE: Unplug the RTS, the temperature of battery will be set to a fixed
value 25ºC.
3. Wiring
(1) Connect components to the charge controller in the sequence as shown above and pay
much attention to the “+” and “-”. Please don’t insert the fuse or turn on the breaker during
the installation. When disconnecting the system, the order will be reserved.
(2)After power on the controller, check the LCD on. Otherwise please refer to chapter
6.Always connect the battery first, in order to allow the controller to recognize the system
voltage.
(3)The battery fuse should be installed as close to battery as possible. The suggested
distance is within 150mm.
(4) The VS AU series is a positive ground controller. Any positive connection of solar, load
or battery can be earth grounded as required.
NOTE: Please connect the inverter or other load that it has the large start
current to the battery rather than to the controller, if the inverter or other
load is necessary.
4. Operation
4.1 Button Function
Browse interface
Setting parameter
Load ON/OFF
Clear error
Enter into Set Mode
Save data
4.2 LCD Display
Status Description
PV Voltage, Current ,Power
Battery capacity, In Charging
Battery voltage. current, temperature
Load Voltage, Current, Load mode
Browse interface
NOTE:
1) When no operation, the interface will be automatic cycle, but the follow two interfaces
not be display.
2) Accumulative power zero clearing: Under PV power interface, press SET button and
hold on 5s then the value blink, press SET button again to clear the value.
3) Setting temperature unit: Under battery temperature interface, press SET button and
hold on 5s to switch.
Fault Indication
Battery level shows empty, battery frame blink,
fault icon blink
Battery level shows full, battery frame blink, fault
icon blink
Figure 2 Connection diagram
Optional Accessory:
Name: Remote Temperature Sensor
Model: RTS300R47K3.81A
Acquisition of battery temperature for undertaking
temperature compensation of control parameters, the
standard length of the cable is 3m (length can be
customized). The RTS300R47K3.81A connects to the port
③ on the controller.
※ Thank you for selecting ViewStar AU series solar charge
controller. Please read this manual carefully before using the
product.

BEIJING EPSOLAR TECHNOLOGY CO., LTD. Tel:+86-10-82894112 / 82894962 Website:www.epsolarpv.com/www.epever.com
3 4
Battery level shows current value, battery frame
blink, fault icon blink
Load overload① ,Load short circuit
①When load current reaches1.02-1.05 times 1.05-1.25 times, 1.25-1.35 times and
1.35-1.5 times more than nominal value, controller will automatically turn off loads in 50s,
30s,10s and 2s respectively
4.3 Load mode setting
Operating Steps:
Under load mode setting interface, press SET button and hold on 5s till the number begin
flashing, then press MENU button to set the parameter, press SET button to confirm.
Load will be on for 1 hour
since sunset
Load will be on for 1 hour
before sunrise
Load will be on for 2 hours
since sunset
Load will be on for 2 hours
before sunrise
Load will be on for 3~13
hours since sunset
Load will be on for 3~13
hours before sunrise
Load will be on for 14 hours
since sunset
Load will be on for 14
hours before sunrise
Load will be on for 15 hours
since sunset
Load will be on for 15
hours before sunrise
Manual mode(Default load
ON)
NOTE: Please set Light ON/OFF, Test mode and Manual mode via Timer1. Timer2
will be disabled and display "2 n".
4.4 Battery Type
Operating Steps
Under Battery Voltage interface, press SET button and hold on 5s then enter into the
interface of Battery type setting. After choosing the battery type by pressing MENU button,
waiting for 5s or pressing SET button again to modify successfully.
Battery Type
①Sealed (Default) ②Gel ③Flooded
NOTE: Please refer to the battery voltage parameters table for the different battery
type.
5. Protections
When the battery is correct connecting, the
PV can be reversed.
The controller is not
damage
When the PV is not connecting, the battery
can be reversed.
The battery voltage reaches to the OVD
The battery voltage reaches to the LVD
The battery voltage reaches to the LVD
Temperature sensor is higher than 65℃
Temperature sensor is less than 55℃
Temperature sensor is higher than 85℃
Temperature sensor is less than 75℃
Load current ≥2.5 times rated current
One short circuit, the output is OFF 5s;
Two short circuit, the output is OFF 10s;
Three short circuit, the output is OFF 15s;
Four short circuit, the output is OFF 20s;
Five short circuit, the output is OFF 25s;
Six short circuit, the output is OFF
Output is OFF
Clear the fault:
Restart the controller
or wait for one
night-day cycle
(night time>3 hours).
Load current ≥2.5 times rated current
1.02-1.05 times, 50s,
1.05-1.25 times, 30s
1.25-1.35 times,10s
1.35-1.5 times 2s
Output is OFF
Clear the fault:
Restart the controller
or wait for one
night-day cycle
(night time>3 hours).
The RTS is short-circuited or damaged
Charging or
discharging at 25℃
The LCD is off
during daytime when
sunshine falls on PV
modules properly
Confirm that PV wire connections
are correct and tight
Wire connection is
correct, LCD not
display
1) Battery voltage is
lower than 9V
2) PV voltage is less
than battery voltage
1) Please check the voltage of
battery. At least 9V voltage to
activate the controller
2) Check the PV input voltage
which should be higher than
battery’s
Check if the battery voltage is
higher than OVD point (over
voltage disconnect voltage), and
disconnect the PV.
When the battery voltage is
restored to or above LVR point
(low voltage reconnect voltage),
the load will recover
The controller will automatically
turn the system off. But while the
temperature decline to be below
50 ºC, the controller will resume.
Over load or Short
circuit
Please reduce the number of
electric equipments or check
carefully loads connection.
8. Disclaimer
This warranty does not apply under the following conditions:
1) Damage from improper use or use in an unsuitable environment.
2) PV or load current, voltage or power exceeding the rated value of controller.
3) User disassembly or attempted repair the controller without permission.
4) The controller is damaged due to natural elements such as lighting.
5) The controller is damaged during transportation and shipment.
7.Technical Specifications
Battery input voltage range
Rated charge/discharge current
Max. PV open circuit voltage
Sealed(Default) / Gel / Flooded /User
Equalize Charging Voltage※
Sealed:14.6V/ Gel: No/ Flooded:14.8V/User:9-17V
Sealed:14.4V/ Gel:14.2V/ Flooded:14.6V/User:9-17V
Sealed/Gel/Flooded:13.8V/User:9-17V
Low Voltage Reconnect
Voltage※
Sealed/Gel/Flooded:12.6V/User:9-17V
Low Volt. Disconnect
Voltage※
Sealed/Gel/Flooded:11.1V/User:9-17V
Temperature compensation
coefficient
Charge circuit voltage drop
Discharge circuit voltage drop
Working environment
temperature
-25℃~+55℃(Product can work continuously at full load)
※Above the parameters are in 12V system at 25℃, twice in 24Vsystem