Epcos B 84299 – K 38 Service Manual

www.DataSheet4U.com
4-Line Filters
for Installations and Systems
Power line filters for three-phase systems with additional VHF suppression Rated voltage 440/250 V~, 50/60 Hz Rated current 6 to 75 A
Construction
Four-line filter
Metal case
Screw-type cable fitting for strain relief
on line side, edge protector on load side
Feed-through capacitors
Features
High insertion loss up to the GHz range
Applications
Power supplies for industrial installations
Medical engineering
Packaging machines
Terminals
Safe-to-touch terminal clamps incorporated in case
Marking
Marking on component: Manufacturers logo, ordering code, rated voltage, rated current, date code
Minimum marking on packaging: Manufacturers logo, ordering code
B84299-K33
… B84299-K39
304 03/01
4-Line Filters
for Installations and Systems
Circuit diagram
B84299-K33
… B84299-K39
L1
L2
LINE LOAD
Netz
L3
N
L1
L2
Last
L3
N
SSB0543-U
Typical circuit taking the example of B84299-K35
Technical data
Rated voltage V Rated current I Test voltage V
R
R
P
440/250 V~, 50/60 Hz referred to 40 °C ambient temperature 1414 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
Leakage current l
leak
at 400 V~, 50 Hz
Climatic category in accordance with EN 60068-1
40/085/21 (– 40
°C/+ 85 °C/21 days damp heat test)
Characteristics and ordering codes
I
A
16 25 50 75
R
l
leak
mA
6
< 5 < 5 < 5 < 5 < 10
Terminal cross section
2
mm
4 4
4 16 25
Approx. weight kg
1,8 2,1 3 7,5
11
305 03/01
Ordering code
B84299-K33 B84299-K35 B84299-K36 B84299-K37 B84299-K39
Approvals
×
(for 14 A)
× × (for 20 A) × (for 40 A) × (for 65 A)
4-Line Filters
for Installations and Systems
Dimensional drawings B84299-K33
B84299-K33
… B84299-K39
14
L1
38
L2 L3 N L1
2
Terminal blocks 4 mm
Anschlussklemmen 4 mm
2
50
13,5withedgeprotector
ø13,5 mit Kantenschutz Bohrung im Gehäuse ø15,5±0,4
Hole in case
11,5
15,5 ± 0,4
195±0,3
218
L3 L2
N
LINE
NETZ
38
1)
1,0
50
75
4 x ø6
25,555±0,3
106
Kabeldurchmesser 8-12,59.Kabelverschraubung PG1)
SSB1083-X
SSB1083-X
1) Screw-type cable fitting PG 9, for cable diameter 8 12,5 mm
306 03/01