Epcos B 84143 – AFE 1 Service Manual

www.DataSheet4U.com
Customer-Specific Filters B84143-AFE1
for AFE Converters
Power line filters for three-phase systems Rated voltage 440/250 V~, 50/60 Hz Rated current 65 A
Three-line filter
Metal case
Features
Extremely saturation-proof chokes
Optimized for operation under full load
with motor cables of up to 500 m total length
Reduction of voltage ripple between phases
Up to 12 actuators
Applications
AFE frequency converters for motor drives, e.g.
textile machinesconveyor systemsmachine tools
For suppliers and energy recovery
For further information refer to chapter Application notes”, page 92
Terminals
Safe-to-touch terminal blocks
Marking
Marking on component: Manufacturers logo, ordering code, rated current, rated voltage, rated temperature, date code, terminal assignment, safety approvals
Minimum marking on packaging: Manufacturers logo, ordering code
324 03/01
www.DataSheet4U.com
Customer-Specific Filters B84143-AFE1
for AFE Converters
Circuit diagram
LINE LOAD
L1
U
L2
L3
PE PE
SSB1641-P
Technical data
Rated voltage V Rated current I Test voltage V
R
R
P
440/250 V~, 50/60 Hz referred to 40 °C ambient temperature
930 V–, 2 s (line/line)
2700 V–, 2 s (lines/case)
Overload capability 1,5 · I
Leakage current I
leak
Climatic category 25/085/21 (– 25
for 3 min per hour or
R
für 30 s per hour
2,5 · I
R
at 400 V~, 50 Hz
°C/+ 85 °C/21 days damp heat test)
in accordance with EN 60068-1
Characteristics and ordering codes
I
R
Terminal cross section
A
mm
65 50
I
leak
2
mA
R
m
typ
Approx. weight kg
< 300 8,5 30 upon request
Ordering code
V
W
325 03/01
Loading...