Envision Peripherals Series User Manual

Geothermal/Water Source Outdoor Split Heat Pumps
 • R-410ARefrigerant  • 2,3,4,5,6TonDualCapacity
Installation Information
Water Piping Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
IM1615 10/08
WaterFurnace
NS SPLIT INSTALLATION MANUAL
Table of Contents
Nomenclature 2
PhysicalCharacteristics 2
GeneralInstallationInformation 3-6
ElectricalData 7
WaterPiping 8
AirHandlerNomenclature&CoilData 9
LineSetSizing 9
PhysicalData 10
EnvisionCoilNomenclature 11
RefrigerantCoilCompatability 11
HeatRecoveryUnit 12
WiringSchematics 13
ModesofOperation 14
OperationLogic 15
DIPSwitchSettings 16
Refrigeration 17-19
Pressure/TemperatureConversionChart 20
UnitOperatingParameters 21
PressureDropandRecommendedFlowRates 22
UnitStartup&Troubleshooting 23-26
PreventiveMaintenance 27
ReplacementProcedures 27
PhysicalDimensions 28
1
NS SPLIT INSTALLATION MANUAL
1 2 3 4-6 7 8 9 10 11
N D S 049 A 1 0 A C
Model Type
N = Envision Coax Options
C = Copper Compressor Type N = Cupronickel D = Dual Capacity
Future Option Cabinet Configuration A =
S = Outdoor Split
Hot Water Option Unit Capacity 0 = None
Vintage Voltage
A = Current 1 = 208-230/60/1
Model 026 038 049 064 72
Compressor (1 each)
Factory Charge R410a, oz [kg]
52
[1.47]
56
[1.59]
90
[2.55]
92
[2.61]
104
[2.95]
Coax and Water Piping
Coax & Piping Water Volume - gal [l]
0.7
[2.6]
1.3
[4.9]
1.6
[6.1]
1.6
[6.1]
2.3
[8.7]
Weight - Operating, lb [kg]
189
[186]
236
[107]
250
[113]
271
[123]
290
[132]
Weight - Packaged, lb [kg]
209 [95]
256
[116]
270
[122]
291
[132]
310
[141]
4/9/08
Notes:
All units have TXV expansion devices, and 1/2" [12.2mm] & 3/4" [19.1mm] electrical knockouts.
Dual Capacity Scroll
Model Nomenclature
Physical Characteristics
2
NS SPLIT INSTALLATION MANUAL
General Installation Information
Safety Considerations
WARNING:Beforeperformingserviceormaintenanceoperationsonasystem,turnoffmainpower
switchestobothunits.Turnoffaccessoryheaterpowerswitchifapplicable.Electricalshock couldcausepersonalinjury.Installingandservicingheatingandairconditioningequipmentcan behazardousduetosystempressureandelectricalcomponents.Onlytrainedandqualiedser­vicepersonnelshouldinstall,repairorserviceheatingandairconditioningequipment.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electri-
cal components. Only trained and qualied service personnel should install, repair or service heating and air conditioning
equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing
lters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply, such as the following safety measures:
Follow all safety codes.• Wear safety glasses and work gloves.Use a quenching cloth for brazing operations.• Have a re extinguisher available for all brazing operations.
Moving and Storage
Move units in the normal “up” orientation. Units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the
damage.
Split Unit Location
Locate the split compressor section away from areas that may disturb the customer and in a way that allows easy re-
moval of the access panels and the top of the cabinet. Provide sufcient room to make water, electrical and refrigerant line connections and allow space for service personnel to perform maintenance. The NS split is approved for outdoor installa­tion when properly installed.
Air Coil Location
Refer to the air handler manufacturer’s instructions for the blower coil unit for details on installing the air handling portion
of the system.
Condensate Drain
Follow the blower coil manufacturer’s instructions.
Duct System
All blower coil units/air coils must be installed as specied by the manufacturer’s installation instructions; however, the following recommendations should considered to minimize noise and service problems. An air lter must always be installed upstream of the air coil on the return air side of the air handler or furnace. If there is limited access to the lter rack for normal maintenance, it is suggested that a return air lter grill be installed. Be sure that the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the lter and plugging the air
coil.
In applications using galvanized metal ductwork, a exible duct connector is recommended on both the supply and return air plenums to minimize vibration from the blower. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of 1-inch thick glass ber or be constructed of ductboard. Insulation is usually not installed in the supply branch ducts. Ducts in unconditioned areas should be wrapped with a minimum of 1-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected. If the air handler is connected to existing ductwork, a previous check should have
3
NS SPLIT INSTALLATION MANUAL
General Installation Information (cont.)
been made to assure that the duct system has the capacity to handle the air required for the unit application. If ducting
is too small, as in replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repairs made accordingly. The duct systems and diffusers should be sized to handle the design airow quietly. If air noise or excessive airow is a problem, the blower speed can be changed to a lower speed to reduce airow. This will reduce the performance of the unit slightly in heating; however, it will increase the temperature rise across the air coil. Airow must still meet minimum requirements.
Equipment Selection
The following guidelines should be used when mating an Envision Split to an air handler/coil.
Select R-410A components only. Match the air handler to the air handler coil data table.
Indoor matching adjustable TXV is factory installed on every air handler/coil. Fixed orice or cap tube systems
should not be used.
Utilizing Existing Coil or Air Handler
It is recommended that a new R-410A air handler be installed with an Envision Split considering the long term benets of reliability, warranty, etc. versus the short term installation cost savings. However, the existing air handler may be retained provided the following:
Coil currently is R-410A rated• Coil uses a TXV. No capillary or xed orice systems should be used• A life expectancy of more than 7 years remaining for the air handler and components
4
NS SPLIT INSTALLATION MANUAL
Lineset
To A ir Handler
Insulated
Suction Line
Return
Duct
Low
Voltage Wire
Disconnect
Remote Air Handler
(Maximum Recommended Distance is
60' Between Units)
Condensate Drain (must be trapped)
Supply
Duct
Air
Handler
General Installation Information (cont.)
Connection to Air Coil
Figures 1 and 2 illustrate typical Envision Split installations. The table on page 9 shows typical lineset diameters and maximum length. Linesets over 60 feet are not recommended. If the lineset is kinked or deformed and cannot be reformed, the bad section of pipe should be replaced. A restricted lineset will affect unit performance. As in all R-410A equipment, a reversible liquid line lter drier is required to insure all moisture is removed from the system. This drier should be replaced whenever “breaking into” the system for service. All linesets should be insulated with a minimum of 1/2” closed cell insula­tion. All exterior insulation should be painted with UV resistant paint or covering to insure long insulation life.
Air Handler Installation
Air handlers used with dual capacity units must be capable of operating with a minimum of 2 blower speeds. Refer to the manufacturer’s instructions for the blower coil unit for details on installing the air handling portion of the system. All blower coil units/air coils must be installed as specied by the manufacturer’s installations instructions. However, the following rec-
ommendations should be considered to minimize noise and service problems.
An air lter must always be installed upstream of the air coil on the return air side of the air handler of furnace. If there is limited access to the lter rack for normal maintenance, it is suggested that a return air lter grille be installed. Be sure that the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the lter and plugging the air
coil.
Ensure that the line set size is appropriate to the capacity of the unit (refer to page 9). Line sets should be routed as di-
rectly as possible, avoiding unnecessary bends or turns. All wall penetrations should be sealed properly. Line set should not come into direct contact with water pipes, oor joists, wall studs, duct work, oors, walls and brick. Line set should not be suspended from joists or studs with a rigid wire or strap which comes into direct contact with the tubing. Wide hanger strips which conform to the shape of the tubing are recommended. Isolate hanger straps from line set insulation by using metal sleeves bent to conform to the shape of insulation. Line set insulation should be pliable, and should completely surround the
refrigerant line.
Notes: Improper installation of equipment may result in undesirable noise levels in the living areas.
Figure 1: Typical Split System Application - Remote Blower Coil
5
NS SPLIT INSTALLATION MANUAL
Thermostat
Wire From Furnace
Wire To
Thermostat
Up-Flow
Fossil Fuel
Furnace
Condensate
Drain
(must be trapped)
"A" or
Slab Coil
Supply Duct
Insulated
Suction Line
Return
Duct
Lineset To Air Handler
Disconnect
General Installation Information (cont.)
Dual Fuel Systems
Envision units can be connected to fossil fuel furnaces that include an A-coil or slab coil. Dual fuel installations utilize the Envision heat pump for heating until the point that auxiliary heat is called for on the thermostat. At that point, the furnace will be enabled and the heat pump will be disabled. The Envision heat pump provides air conditioning through the furnace’s
refrigerant coils.
Refer to the furnace manufacturer’s installation manual for the furnace installation, wiring and coil insertion. A WaterFurnace Dual Fuel thermostat, a eld-installed DPST relay or dual capacity auxiliary heat relay is required. See Figure 2 for typical Dual Fuel application.
In add-on Envision Split applications, the coil should be located in the supply side of the furnace to avoid condensation damage to the furnace heat exchanger. A high temperature limit should be installed upstream of the coil to de-energize the compressor whenever the furnace is operating. Without this switch, the Envision Split will trip out on high pressure. A dual fuel thermostat can remove the Y1 and Y2 calls when a W call is energized to allow gas furnace backup on an Envision Split application. Refer to thermostat wiring on page 13 for details.
Figure 2: Typical Split System Heat Pump Coil Add-On Fossil Fuel Furnace
6
NS SPLIT INSTALLATION MANUAL
Rated Voltage
HWA Ext Total Min Max
Model Voltage Min/Max
Pump Loop Unit Circ Fuse/
MCC RLA LRA FLA FLA FLA Amp HACR
026 208-230/60/1 197/253 16.0 10.2 52.0 0.4 5.4 16.0 18.6 25 038 208-230/60/1 197/253 26.0 16.6 82.0 0.4 5.4 22.4 26.6 40 049 208-230/60/1 197/253 33.0 21.1 96.0 0.4 5.4 26.9 32.2 50 064 208-230/60/1 197/253 40.0 25.6 118.0 0.4 5.4 31.4 37.8 60 072 208-230/60/1 197/253 42.5 27.2 150.0 0.4 5.4 33.0 39.8 60
Rated Voltage of 208-230/60/1.
Rev.: 02/20/07
HACR circuit breaker in USA only.
Min/Max Voltage of 197/253.
All fuses Class RK-5.
Compressor
Y1
Y2
O
R
C
C
R
Air Handler
Thermostat
24 VAC
Common Common
24 VAC
Reversing Valve
2nd Stage Compressor
1st Stage Compressor
Y1
Y2
O
R
C
G
G
Fan
W
W
Ty pical EZ Wiring Diagram
P1
Air Handler transformer must be at least 75 VA.
L
Lo
Fault Signal
Envision Split
Y1
Y2
O
R
C
L
C
R
Fossil Fuel
Furnace
Thermostat
24 VAC
Common Common
24 VAC
Fault Signal
Reversing Valve
2nd Stage Compressor
1st Stage Compressor
Y1
Y2
O
R
C
LO
G
G
Fan
W
W
Auxiliary Heat Relay
Note: Field installed DPST dual fuel relay
(Required for dual fuel installation)
Auxiliary Heat Relay
P2
P1
Shut
Down
= chassis
Envision Split
Auxiliary
Heat Relay
Electrical
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable. See unit electri­cal data for fuse or cicuit breaker sizing information.
Electrical Data
Thermostat Wiring
Figure 3a: Thermostat Wiring
Figure 3b: Thermostat Wiring for Dual Fuel Applications
7
NS SPLIT INSTALLATION MANUAL
Loop Supply and Return Piping
Water Piping
Residential NS split units are supplied standard with GeoLink swivel connections with P.T. ports.
CAUTION:Waterpipingexposedtooutsidetemperaturesmaybesubjecttofreezing.
Water Piping
The proper water ow must be provided to each unit whenever the unit operates. To assure proper ow, use pressure/ temperature ports to determine the ow rate. These ports should be located at the supply and return water connections on the unit. The proper ow rate cannot be accurately set without measuring the water pressure drop through the refrigerant­to-water heat exchanger.
Closed Loop - Earth coupled Systems (Outdoor Installations)
Locate unit on an air pad with access hole as shown below. When mounting on an existing concrete pad, holes must
be bored through to accommodate 1 1/4-inch P.E. pipe with 1/2-inch insulation.
Connecting To Earth Loop
The earth loop trench should be continued directly under the unit as shown in Figure 4. Make the connections to op­tional ttings from the loop circulator pump(s) and insure proper backll to support the loop pipe during trench settling. All 1 1/4-inch piping should be insulated with a minimum of 1/2-inch closed cell insulation from below the ground surface to the
loop circulator.
IMPORTANT
pumpiflooptemperaturedropsbelow20°F.Loopfreezesensingshouldalsobemaintainedtothe lowesttemperaturetheinsulatedloopmayencounterinthecaseofpowerfailure.
- Afreezesensingthermostatisinstalledintheunittoautomaticallystartloopcirculator
Flow Center Installation
Flow centers FC1-GL or FC2-GL, as needed, may be internally mounted on the NDS splits, Two stub tubes with barbs are pre connected to the coax. Two tubes with brass ttings, to adapt to the ow center, 2 hoses to connect between the two sets of tubes, and four hose clamps are in­cluded with each NDS unit. The brass adapter ttings have plastic swivel connectors and are also internally threaded to accept 1” NPT ttings.
NOTE: For ease of installation, attach provided hoses to
coax rst and then trim to t to elbows on ow center.
Figure 4: Typical Split System Outdoor Installation Using Closed Loop
8
Envision
Split Model
Matching Air
Handler
Coil Surface
Area (sq ft.)
FPI Rows
Tube
Diameter
022 - 038
042 - 072
NAH060 5.83 12 3 3/8"
NAH036 5.83 12 2 3/8"
Unit Air Factory
Size Handler
Suction Liquid Suction Liquid Suction Liquid
Charge (oz.)
NDS026 NAH026 5/8" OD 3/8" OD 3/4" OD 3/8" OD 3/4" OD 1/2" OD 52
NDS038 NAH036 5/8" OD 3/8" OD 3/4" OD 3/8" OD 3/4" OD 1/2" OD 56
NDS049 NAH048 3/4" OD 3/8" OD 7/8" OD 3/8" OD 7/8" OD 1/2" OD 90
NDS064 NAH060 7/8" OD 1/2" OD 7/8" OD 1/2" OD 1-1/8" OD 1/2" OD 92
NDS072 NAH060 7/8" OD 1/2" OD 7/8" OD 1/2" OD 1-1/8" OD 1/2" OD 104
Notes: Lineset charge for R410A is 0.50 oz. per ft. for 3/8" and 1.0 oz. per ft. for 1/2" tube. Rev.: 4/1/08
Initial Total System Charge = Factory Split charge + lineset charge + 20 oz, then adjust charge by subcooling and superheat measurements.
20 feet 40 feet 60 feet
Air Handler Nomenclature
NAH 036 A 00 0 1 R
Model Type Air Coil
NAH = Envision Air Handler R = Refrigerant
H = Hydronic
Unit Capacity
Refrigerant Models Nom. CFM Motor
022 MBTUH 800 1 = ECM 208-230/60/1 026 MBTUH 925 030 MBTUH 980 036 MBTUH 1225 042 MBTUH 1425 Disconnect 048 MBTUH 1625 0 = No breaker installed (only on 5kW & 10 kW heaters ) 060 MBTUH 1760 1 = Breaker installed (only on 15kW & 20kW heaters)
Hydronic Models
026 MBTUH 925 036 MBTUH 1225 Electric Heat 048 MBTUH 1625 00 = No electric heat 060 MBTUH 1760 05 = 5 kW (available on 022-036)
10 = 10 kW (available on 030-060)
Vintage
Note: Kit NAHBC must be ordered to field convert the NAH042-060 to bottomflow air discharge
15 = 15 kW (available on 042-060)
A = Current 20 = 20 kW (available on 060 only)
NS SPLIT INSTALLATION MANUAL
Air Handler Coil Data
Line Set Sizes
9
NS SPLIT INSTALLATION MANUAL
NAH022 NAH026 NAH030 NAH036 NAH042 NAH048 NAH060
Air Coil Total Face Area, ft2 [m2] Tube outside diameter - in. [mm] Number of rows Fins per inch Suction line connection - in. [mm] sweat Liquid line connection - in. [mm] sweat
Nominal cooling capacity - tons [kW] 1.8 [6.44] 2.1 [7.59] 2.5 [8.79] 3 [10.55] 3.5 [12.30] 4 [14.06] 5 [17.58] Condensate drain connection - (FPT) in. [mm] Blower Wheel Size (Dia x W), in. [mm] Blower motor type/speeds Blower motor output - hp [W] Filter Standard - 1" [51mm] MERV3 disposable, in. [mm] Electrical characteristics (60hz) Shipping weight - lbs. [kg] Operating weight - lbs. [kg]
1/11/08
NAH026 NAH036 NAH048 NAH060
Air Coil Total Face Area, ft2 [m2] Tube outside diameter - in. [mm] Number of rows Fins per inch Water In connection - in. [mm] sweat
Water Out connection - in. [mm] sweat Nominal cooling capacity - tons [kW] 2.1 [7.59] 3 [10.55] 4 [14.06] 5 [17.58] Condensate drain connection - (FPT) in. [mm] Blower Wheel Size (Dia x W), in. [mm] Blower motor type/speeds Blower motor output - hp [W] Filter Standard - 1" [51mm] MERV3 disposable, in. [mm] Electrical characteristics (60hz) Shipping weight - lbs. [kg] Operating weight - lbs. [kg]
3/11/08
220 [99.79]
200 [90.71]
208/230 - 1ph
ECM variable speed
1/2 [373] 1 [746]
20 x 24 [508 x 635]
3/4 [19.05]
11 x 10 [279 x 254]
Air Handler Model Number (Hydronic)
Hydronic
Coil
3
7/8 [22.22]
13
7/8 [22.22]
6.94 [0.64] 3/8 [9.52]
Air Handler Model Number (Refrigerant)
Evaporator
Coil
5.83 [0.54] 3/8 [9.52]
2 3
12
5/8 [15.87] 7/8 [22.22]
3/8 [9.52]
Refrigerant R-410a
3/4 [19.05]
11 x 10 [279 x 254]
ECM variable speed
1/2 [373] 1 [746]
20 x 24 [508 x 635]
208/230 - 1ph
215 [97.52] 220 [99.79]
195 [88.45] 200 [90.71]
NOTE: Water connection dimensions are O.D.
Physical Data
10
NR A C 026 C
Cabinet
Model Type
C = Encased
NR = Envision Refrigerant Coil
U = Uncased
NH = Envision Hydronic Coil
Capacity
Configuration Refrigerant Models
A = "A" Coil 026 MBTUH
036 MBTUH 048 MBTUH
Coil 060 MBTUH
Hydronic Models
060 MBTUH
Note: All Refrigerant Coils include TXV. The encased coil cabinet is designed for upflow applications.
Envision Coil Nomenclature
NS SPLIT INSTALLATION MANUAL
Refrigerant Coil Compatibility
Encased/Uncased Coil
NRAC026* NSZ022 - 800 NRAC026* - NDZ026 NDS026 925
NRAC026* NSZ030 - - 980 NRAC036* NSZ036 - - 1225 NRAC036* - NDZ038 NDS038 1225 NRAC048* NSZ042 - - 1425 NRAC048* NSZ048 - - 1625 NRAC048* - NDZ049 NDS049 1625 NRAC060* NSZ060 - - 1760 NRAC060* - NDZ064 NDS064 1760 NRAC060* NSZ070 - - 1760 NRAC060* - NDZ072 NDS072 1760
Indoor Split Model
(Single)
Indoor Split Model
(Dual Capacity)
11
Outdoor Split Model
(Dual Capacity)
Recommended
Airow (CFM)
7/14/08
NS SPLIT INSTALLATION MANUAL
To
Compressor
Heat Recovery
Unit “In”
From
Heat Recovery
Unit “Out” to
Reversing
Valve
Insulated Line set
With UV Paint To Air handler
Add-on
Hot Water
Generator with
Internal Pump
Cold
Drain Valve
Pipe Tee
Hot
Venting
Waste Valve or
Vent Coupling
Line set
To Hot Water
Generator
P/T Relief
Valve
Heat Recovery Unit for Domestic Hot Water
Service valves have been provided inside the unit for connecting the discharge gas line to a water heating heat recov-
ery unit (see gure 5). To make the connections, close the service valves inside the unit by turning clockwise. Using a recovery canister connect to either of the schrader ports on the DSH service valves and recover the small amount of refrig-
erant trapped inside of the U-tube. PriortobrazingensurethatallrefrigeranthasbeenremovedfromU-tube. Once
the refrigerant is removed, it is recommended that the tube be cut at the “U” to remove any excess oil that may be trapped. (This will also allow for easier removal of the tubing with a torch, since each section can be removed independently). Ser­vicevalvesmustbeprotectedtopreventoverheating. Unbraze the 1/2-inch O.D. U-tube and run tubing from the left
hand service valve to the inlet of the heat recovery unit and from the outlet of the heat recovery unit to the right hand of the
service valve. Typically the one way discharge line length should be limited to 25-30 feet and line size must be increased depending on unit size and length of run. Follow the instructions supplied with the heat recovery unit for mounting location, water piping, and start up. A typical installation is shown below.
IMPORTANT-Reopendischargelineservicevalvesbeforestartingupunit,butonlyafterleakchecking, purging,andevacuatingnewdischargeline.
Figure 5: Service Valves for Heat Recovery Unit Connections
Maximum One-Way Line Length
SIZE 1/2”OD 5/8”OD 3/4”OD
026-038 Up to 9 ft. Up to 25 ft. Up to 30 ft.
049 Up to 5 ft. Up to 13 ft. Up to 30 ft.
064 N/A Up to 9 ft. Up to 25 ft.
072 N/A Up to 6 ft. Up to 20 ft.
Figure 6: Typical Hot Water Piping Layout
12
NS SPLIT INSTALLATION MANUAL
Fused L2
240V L1
HP
240V L2
P6
Microprocessor
Logic Control
(DC Voltage)
P1
Fused L2
R
C
CC-GND
NO
CR2
COM
NO NC
CR4
COM
F1-10A 240V
NO
CR1
COM
1234567
8
123P4123C
P2
Down
C
1234567
Shut
SL1 In
Not
SL1 Out
Used
NOTE 2
Acc Com
Acc NC
Acc NO
123
P3
1 2 3
NO NC
CR3
COM
F1-10A 240V
6
5
487
P5
12
129103
13
14
15
16
11
GWO
R
C
Y1
Y2
LO
On
SW1
1 2 3 4 5 6 7 8 9
10
11
12
On
SW3
On
SW2
1
2 3 4 5 6 7 8 P ulse L / Constant L
Not Used
Not Used
Fan / Comp
Loop / Well
Test / Norm
Outputs / Norm
Inputs / Norm
Dual/ Single Capacity
Normal/Finish on 2
nd
No RPM / RPM
Must be On
Envision / E Series or P remier
ECM2
Air Flow
Settings
1 2 3 4 5
Status LED PCB
SW4
RRRRRGY
R
T
C
NOTE 1
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
NOT USED
NOT USED
CC
CCHI
Fused L1
Black (7)
RV
FP
Field Selection Dips -#1 On, #6 On, #7 On
Not Used
FP thermistor (loop<15°F,well<30°F) Lockout
High Pressure
Low Pressure / Comfort A lert
Not Used
Microprocessor malfunction*
Not Used
Not Used
Drain
Water Flow
High Press
Low Press/ CA
Air Flow
Status
DHW Limit
DHW off
LED No rmal Display Mode
#1 Off, #6 On, #7 On
Not Used
FP thermistor (loop<15°F, well<30°F)
High Pressure
Low Pressure / Comfort Alert
Not Used
Not Used
Not Used
Not Used
Current Fault Status
#6 Off, #7 On
Y1
Y2
O
Not Used
Not Used
SL1
SL2
Input s
#6 On, #7 Off
Lo Capacity Compressor
RV
FAN
Not Used
Loop Pump 1
Output s
#6 Off, #7 Off
Not Used
Output s2
Diagnostic Modes
*Green LED not flashing
Hi Capacity Compressor
Loop Pump 2
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Not UsedNot UsedNot Used
Tan
Orange
Orange
Not Used
Not Used
Yellow
Yellow
LP
Blue
Blue
Black
Black
L
Comfort Alert
NOTE 5
CC
Comfort
Alert
RYC
Y2
C
S
R
Unit Power
208-230/60/1
G
L2 L1
CC
Comfort Alert
Red B lack
Blue
CS
+
-
DC SOL
Run
Capacitor
NOTE 6
Y2
Y
L
R
C
DC
Sol
Data
Port
Comfort Alert
Physical Layout
POWER
ALERT
TRIP
Envision Logic Board -Physical Layout
1 2 3
1
P4
OnOff
SW1
240V - L2
240V - L1
Fused L2
Fused L2
Fused L2
F1
F1
R
R
Microprocessor
Premier 2 Logic Board
CR2- Loop
Pump
N.O.
240V - L2
240V - L1
C
C
1234567
8
9
10111213141516
P6
1234567
8
9
1011121314
P5
Fused L2
Fused L1
CR1- DHW
Pump
N.O.
CC
CC-GND
CCLO
CCHI
1 2 3
P3
2345678
9
101112
1
OnOff
SW2
2345678
1
OnOff
SW3
234
5
P1
1 2 3 4 5 6 7 8
2
3 4 5
P2
6 71
R C Y1 Y2 GOW L
Shut
Down
ACC
NO
ACC
NC
ACC
COM
C C
SL1
IN
SL1
Out
SL2
IN
SL2
Out
N.O.
CR4-
Com
N.O.
CR3-
Com
N.C.
L2
L1
Heat
Recovery
Unit
Pump
Loop Pump(s )
1/2 HP 208-230/60/1
G
Pump
FP
Thermistor
Light Emitt ing Diode - Green
Relay Coil
Capacitor w/ Bleed Resistor
Switch -High Pressure
Switch - Low Pressure
Polarized Connector
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
Field wire lug
Ground
Fuse
CC -
CR1 -
CR2-
CR3 -
CR4 -
F1 and F2 -
FP -
HP -
LP -
RV -
SW1 -
SW2 -
SW3 -
Compressor Contactor
Loop Pump Relay 1
Fuses
Freeze protection sensor
High Pressure Switch
Low Pressure Switch
Reversing Valve Coil
Not Used
DIP Package 8 P osition
DIP Package 5 P osition
Relay Contacts-
N.O., N.C.
G
T
1
3
2
P
L1
Loop Pump Relay 2
Not Used
CS -
Compressor Solenoid
Not Used
Legend
Notes
Yellow (8)
Gray (9)
Violet (10)
Black (1)
Violet (2)
Violet (3)
White (4)
Black (5)
Yellow (6)
Orange (14)
Brown (15)
Tan (16)
Red (11)
Red (12)
Black Black
Green/Yellow
Crankcase Heater
Crankcase Heater
Not Used
Not Used
3
4
9
11
2
10
8
1125
14
13
6
7
CA -
Comfort Alert
Connection of remote unit that does not have a loop pump for slave operation
24V Accessory relay (see SW 2-3 for description of operation)
Field installed DPDT dual fuel relay (Required for dual fuel installation)
DHW pump only in models with hot water generation option
Comfort Alert fault output to Premier Control Board
This switch allows the unit to down stage with the t-stat when OFF and finish on second stage when ON.
Finish second stage reduces stage changing in recip dual capacity compressors and should be ON for
unzoned Dual Cap E-Series or Premier 2 speed units
1 -
2 -
3 -
4 -
5 -
6 -
Wiring Schematics
Envision Series - Dual Capacity Split Wiring Schematic - 208-230/60/1
13
NS SPLIT INSTALLATION MANUAL
Modes of Operation
Heating Operation
Note: At rst power up, a four-minute time delay is employed before the compressor is energized.
Heat,1stStage(Y1)
The compressor and loop pumps are energized 10 seconds after the Y1 input.
Heat,2ndStage(Y1,Y2)DualCapacityUnits
The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum rst stage
compressor run time of 1 minute has expired.
The Comfort Alert will delay the second stage compressor until 5 seconds after it receives “Y2” from the board.
Cooling Operation
In all cooling operations, the reversing valve directly tracks the
reversing valve will be energized.
Cool,1stStage(Y1,O)
The compressor and loop pumps are energized 10 seconds after the Y1 input.
“O”
input. Thus, anytime the
“O”
input is present, the
Cool,2ndStage(Y1,Y2,O)DualCapacityUnits
The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum rst stage
compressor run time of 1 minute has expired.
The Comfort Alert will delay the second stage compressor until 5 seconds after it receives a “Y2” from the board.
Fan Only Operation
The Fan Only mode is controlled directly from the unit thermostat to the unit air handler. No input is given to the micro-
processor to operate the fan function.
Lockout Conditions
During lockout mode, the appropriate thermostat lockout LEDs (if available) will illuminate. The compressor and loop
pumps are de-energized and if the thermostat calls for third stage heating, emergency heat operation will occur.
Lockout modes of any kind can be reset at the thermostat after a 5-second waiting period, which restores normal
operation.
High Pressure
This lockout mode occurs immediately when the normally closed safety switch is momentarily opened.
Low Pressure
This lockout mode occurs when the normally closed switch is opened for 30 continuous seconds.
Freeze Sensing (Water Flow)
This lockout mode occurs when the freeze sensing thermistor temperature (located between the TXV and coax) is at or
below the selected freeze sensing point (well 30°F or loop 15°F) for 30 continuous seconds.
The unit also contains a secondary freeze sensing sensor located on the entering water line of the unit. If the loop reaches a temperature of 20°F the secondary freeze sensing sensor will cycle the loop pumps "on" until the loop tempera­ture rises to or above 25°F.
14
Operation Logic Data
NS SPLIT INSTALLATION MANUAL
OPERATIONLOGIC
DUALCAPACITYUNITS
Compressor-Lo
Compressor-Hi
RevValve
Loop Pumps
Secondary1-Out
Secondary2-Out
EmergLED
T-StatSignal
HE AT ING COOLING
STG1 STG2 STG3 EMERG STG1 STG2
On Off Off Off On Off -
Off On On Off Off On -
Off Off Off Off On On -
On On On Off On On On
On On On Off On On -
Off On On Off Off On -
Off Off Off On Off Off -
Y1 Y1, Y2 Y1, Y2, W W Y1, O Y1, Y2, O -
SL1-INON
15
NS SPLIT INSTALLATION MANUAL
DIP Switch Settings
DIPSWITCH
NUMBER
SW1 N/A NOTUSED N/A N/A
Service/TestMode-Allows control of “NORM” or “TEST” opera-
tional modes. Test mode accelerates most timing functions 16
1
times to allow faster troubleshooting. Test mode also allows view­ing the “CURRENT” status of the fault inputs on the LED display.
FreezeSensingSetting
Allows eld selection of freeze thermistor fault sensing tempera-
2
tures for well water (30°F) or antifreeze-protected (15°F) earth
loops.
AccessoryRelay
3
Allows eld selection of the accessory relay to operate with the
compressor or fan.
SW2
4 NOT USED N/A N/A
5 NOT USED N/A N/A
InputDiagnostics-Allows viewing the inputs from the thermo-
6
stat to the control board such as Y1, Y2, O, G, W, SL1-In on the LED display.
DESCRIPTION OFFPOSITION ONPOSITION
Test Norm
Loop
(Sensing 15° F)
Fan Comp
Diagnostic Inputs
viewed at LEDs
Well
(Sensing 30° F)
Normal Display viewed at LEDs
SW3
OutputDiagnostics-Allows viewing the outputs from the control
7
board such as the compressor, reversing valve, blower, hot water pump, and loop pump on the LED display.
ThermostatSelection
8
Congures the control for a pulsed lockout signal (ComforTalk and FaultFlash thermostats) or continuous 5 VAC lockout signal.
1 Single or Dual Capacity Operation Dual Cap 1 Speed
Zoned/FinishonSecondStage
This switch allows the unit to down stage with the thermostat
2
when off and nish with second stage when on. Finish on second
stage reduces stage changing in reciprocating dual capacity compressors.
3 ECM Fan Monitoring - Set for No PRM on split systems No RPM RPM
4 NOT USED N/A N/A
On dual capacity units this switch allows stage change: on the y
5
when off, and 1 minute delay when on. A delay is required on all
reciprocating dual capacity units.
Diagnostic
Outputs viewed at
LEDs
Pulsed “L”
signal
Normal -
All other systems
Envision
Normal
Display viewed
at LEDs
Continuous “L”
signal
Finish on 2nd
Unzoned Dual
Capacity
E-Series or
Premier 2 speed
E-Series or
Premier
16
NS SPLIT INSTALLATION MANUAL
Replace caps after opening system
Service ports for
attaching refrigerant
gauges
Insulated
Suction Line
Braze
Connection
Liquid
Line
ccw
ccw
Refrigeration
The Envision series comes with a holding charge. The charge must be adjusted in the eld based on performance. Refrigeration piping on the split consists of installing a brazed copper line set between the blower coil unit and the unit’s split compressor section. To select the proper tube diameters for the installation, refer to the table on page 9. Line sets over 60 feet long are not recommended because of oil return and pressure drop problems. The suction line must always be insu­lated. Handle and route the line sets carefully to avoid kinking or bending the tubes. If the line set is kinked or distorted and it cannot be formed back into its original shape, the bad portion of the pipe should be replaced. A restricted line set will affect
the performance of the system.
Connection to Air Coil
Figures 1 and 2 illustrate typical Envision Split installations. The table on page 9 shows typical lineset diameters and maximum length. As in all R-410A equipment, a reversible liquid line lter drier is required to insure all moisture is removed from the system. This drier should be replaced whenever “breaking into” the system for service. All linesets should be insulated with a minimum of 1/2” closed cell insulation. All insulation should be painted with UV resistant paint or covering to
insure long insulation life.
Fasten the copper line set to the blower coil unit as instructed by the coil installation instructions. Nitrogen should be bled through the system at 2 to 3 PSI to prevent oxidation inside the refrigerant tubing. Use a low silver phos-copper braze alloy
on all brazed connections.
Braze line set to the service valve stubs on the inside front of the split cabinet as shown in Figure 7. Nitrogen should be bled through the system at 2 to 3 PSI to prevent oxidation contamination. Use a low
silver phos-copper braze alloy on all brazed connec-
tions. Envision split units are shipped with a factory
charge and service valves are not to be opened
until the line set has been leak tested, purged and
evacuated. Schrader cores should be removed
before brazing. A heat sink should be used on the
service valves and TXV to prevent damage caused
by excessive heat.
Figure 7: Typical Split System Refrigerant Line Connections
17
NS SPLIT INSTALLATION MANUAL
Refrigeration (continued)
Leak Testing
The refrigeration line set must be pressurized and checked for leaks before purging and charging the unit. To pressurize the line set, attach refrigerant gauges to the service ports and add an inert gas (nitrogen or dry carbon dioxide) until pres­sure reaches 60 to 90 PSIG. Never use oxygen or acetylene to pressure test. Use an electronic leak detector or a good quality bubble solution to detect leaks on all connections made in the eld. Check the service valve ports and stem for leaks and all connections made in the eld. If a leak is found, repair it and repeat the above steps. For safety reasons do not pres­surize the system above 150 psi. Purge pressure from line set. The system is now ready for evacuating and charging.
System Evacuation
Ensure that the line set and air coil are evacuated before opening service valves to the split unit. The line set must be evacuated to at least 200 microns to remove the moisture and air that may still be in the line set and coil. Evacuate the sys­tem through both service ports to prevent false readings on the gauge because of pressure drop through service ports.
Initial System Charge Calculation
The Envision unit comes with a factory pre-charge. This volume is not sufcient to run the system. Additional refrigerant
must be added for the lineset. This additional charge added to the factory pre-charge of the Envision unit should be esti-
mated using the following equation:
Addition to Factory Charge = (lineset length x oz. per ft) + (20 oz. for accumulator)
The lineset charge should be calculated by multiplying the length times 0.5 oz./ft for 3/8” liquid line and 1.0 oz/ft for 1/2” liquid line in R-410A systems. The suction line will not hold ‘liquid’ and can be ignored for the calculation. This should result in a slightly under-charged unit exhibiting low subcooling and high superheat. As charge is added, the subcooling should rise and the superheat should fall until 8-16 degrees of superheat is reached when the TXV should be metering the system. See operating details in the startup section of this manual for exact superheat and subcooling values.
Example: 038 with 40 foot of 3/8” liquid line.
Additional to be added = (40 ft x 0.5 oz./ft) + (20 oz. for accumulator)
= 40 oz.
Solution: 40 oz. should be added to the existing 56 oz. of factory charge as an initial charge.
Charging the System
Charge Method – After purging and evacuating the line set, fully open the service valves counterclockwise. Add R-410A (liquid) into the liquid line service port until the pressure in the system reaches approximately 200 PSIG. Never add liquid
refrigerant into the suction side of a compressor. Start the unit and measure superheat and subcooling. Keep adding refrig-
erant until the unit meets the superheat and subcooling values on page 21.
Checking Superheat and Subcooling
Determining Superheat
Measure the temperature of the suction line at the point where the expansion valve bulb is clamped.
1.
Determine the suction pressure in the suction line by attaching refrigeration gauges to the schrader connection on the
2.
suction side of the compressor.
Convert the pressure obtained in Step 2 to the saturation temperature by using the R-410A Pressure/Temperature Con-
3.
version Chart on page 20. Subtract the temperature obtained in Step 3 from Step 1. The difference is the amount of superheat for the unit. Refer to
4.
tables on page 21 for superheat ranges at specic entering water conditions.
Superheat Adjustment
TXV’s are factory set to a specic superheat; however, the superheat should be adjusted for the application. To adjust the TXV to other superheat settings:
Remove the seal cap from the bottom of the valve.
1.
Turn the adjustment screw clockwise to increase superheat and counterclockwise to decrease superheat. One complete
2.
360° turn changes the superheat approximately 3-4°F, regardless of refrigerant type. You may need to allow as much as 30 minutes after the adjustment is made for the system to stabilize.
18
NS SPLIT INSTALLATION MANUAL
Refrigeration (continued)
Once the proper superheat setting has been achieved, replace and tighten the seal cap.
1.
Warning: There are 8 total (360°) turns on the superheat adjustment stem from wide open to fully closed. When adjusting the superheat stem clockwise (superheat increase) and the stop is reached, any further clockwise turning adjustment will
damage the valve.
Determining Subcooling
Measure the temperature of the liquid line on the small refrigerant line (liquid line) just outside the split cabinet. This
1. location will be adequate for measurement in both modes unless a signicant temperature drop in the liquid line is an­ticipated. Measure the liquid line pressure by attaching refrigerant gauges to the schrader connection on the liquid line service
2.
valve.
3. Convert the pressure obtained in Step 2 to the saturation temperature by using the R-410A Pressure/Temperature
Conversion Chart on page 20.
4. Subtract the temperature in Step 1 from the temperature in Step 3. The difference will be the subcooling value for
that unit. Refer to the tables on page 21 for subcooling ranges at specic enter water conditions.
19
NS SPLIT INSTALLATION MANUAL
Pressure/Temperature Coversion Chart for R-410A
PRESSURE
(PSIG)
TEMP °FPRESSURE
(PSIG)
TEMP
°F
PRESSURE
(PSIG)
TEMP °FPRESSURE
(PSIG)
TEMP
°F
PRESSURE
(PSIG)
60 8.5 180 63.5 300 96.3 420 120.6 540 140.0 62 9.9 182 64.2 302 96.8 422 120.9 542 140.3
64 11.2 184 64.8 304 97.2 424 121.3 544 140.6 66 12.5 186 65.5 306 97.7 426 121.6 546 140.9 68 13.8 188 66.1 308 98.1 428 122.0 548 141.2
70 15.1 190 66.8 310 98.6 430 122.3 550 141.4 72 16.3 192 67.4 312 99.0 432 122.7 552 141.7 74 17.5 194 68.0 314 99.5 434 123.0 554 142.0 76 18.7 196 68.7 316 99.9 436 123.4 556 142.3 78 19.8 198 69.3 318 100.4 438 123.7 558 142.6 80 21.0 200 69.9 320 100.8 440 124.1 560 142.9 82 22.1 202 70.5 322 101.2 442 124.4 562 143.2
84 23.2 204 71.1 324 101.7 444 124.8 564 143.5 86 24.3 206 71.7 326 102.1 446 125.1 566 143.7 88 25.4 208 72.3 328 102.5 448 125.4 568 144.0 90 26.5 210 72.9 330 103.0 450 125.8 570 144.3 92 27.5 212 73.5 332 103.4 452 126.1 572 144.6 94 28.6 214 74.1 334 103.8 454 126.5 574 144.9 96 29.6 216 74.7 336 104.2 456 126.8 576 145.1
98 30.6 218 75.3 338 104.7 458 127.1 578 145.4 100 31.6 220 75.8 340 105.1 460 127.5 580 145.7 102 32.6 222 76.4 342 105.5 462 127.8 582 146.0 104 33.5 224 77.0 344 105.9 464 128.1 584 146.2 106 34.5 226 77.5 346 106.3 466 128.5 586 146.5 108 35.4 228 78.1 348 106.7 468 128.8 588 146.8
110 36.4 230 78.7 350 107.2 470 129.1 590 147.1
112 37.3 232 79.2 352 107.6 472 129.4 592 147.3
114 38.2 234 79.8 354 108.0 474 129.8 594 147.6 116 39.1 236 80.3 356 108.4 476 130.1 596 147.9 118 40.0 238 80.9 358 108.8 478 130.4 598 148.2
120 40.9 240 81.4 360 109.2 480 130.7 600 148.4 122 41.7 242 81.9 362 109.6 482 131.1 602 148.7 124 42.6 244 82.5 364 110.0 484 131.4 604 149.0 126 43.4 246 83.0 366 110.4 486 131.7 606 149.2 128 44.3 248 83.5 368 110.8 488 132.0
608 149.5
130 45.1 250 84.1 370 111 .2 490 132.3 132 45.9 252 84.6 372 111 .6 492 132.7 134 46.7 254 85.1
374 112.0 494 133.0 136 47.5 256 85.6 376 112.3 496 133.3 138 48.3 258 86.1 378 112.7 498 133.6 140 49.1 260 86.6 380 113.1 500 133.9 142 49.9 262 87.1 382 113.5 502 134.2
144 50.7 264 87.7 384 113.9 504 134.5 146 51.5 266 88.2 386 114.3 506 134.9 148 52.2 268 88.7 388 114.7 508 135.2 150 53.0 270 89.2 390 115.0 510 135.5 152 53.7 272 89.6 392 115.4 512 135.8 154 54.5 274 90.1 394 115.8 514 136.1 156 55.2 276 90.6 396 116.2 516 136.4 158 55.9 278 91.1 398 116.5 518 136.7 160 56.6 280 91.6 400 116.9 520 137.0
162 57.4 282 92.1 402 117.3 522 137.3
164 58.1 284 92.6 404 117.6 524 137.6 166 58.8 286 93.0 406 118.0 526 137.9 168 59.5 288 93.5 408 118.4 528 138.2
170 60.2 290 94.0 410 118.7 530 138.5 172 60.8 292 94.5 412 119.1 532 138.8 174 61.5 294 94.9 414 119.5 534 139.1 176 62.2 296 95.4 416 119.8 536 139.4 178 62.9 298 95.8 418 120.2 538 139.7
TEMP
°F
20
Unit Operating Parameters
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB. Heating performance based on entering air temperature of 70º F DB.
First Stage Operation
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat Subcooling
Water Temp
Rise °F
Air Temp
Drop °F DB
1.5 125-140 205-225 9-15 3-10 17-21 17-23
3.0 120-135 190-210 9-15 3-10 8-12 17-23
1.5 135-145 260-290 9-18 5-11 16-20 17-23
3.0 126-143 230-250 9-18 5-11 9-13 17-23
1.5 138-150 315-345 8-14 7-14 14-20 17-23
3.0 136-148 300-330 8-14 7-14 8-12 17-23
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat Subcooling
Water Temp
Drop °F
Air Temp
Rise °F DB
1.5 76-89 260-325 7-12 4-16 5-9 12-16
3.0 80-93 265-330 7-12 4-16 3-7 14-18
1.5 105-120 295-355 7-14 4-16 7-11 18-22
3.0 110-125 300-360 7-14 4-16 5-9 20-24
1.5 135-155 330-385 9-14 7-15 8-12 24-28
3.0 140-160 335-390 9-14 7-15 6-10 22-30
Second Stage Operation
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat Subcooling
Water Temp
Rise °F
Air Temp
Drop °F DB
1.5 120-135 215-235 10-16 3-11 17-21 17-23
3.0 115-130 200-220 10-16 3-11 8-12 17-23
1.5 121-136 270-305 9-15 5-12 16-20 17-23
3.0 118-133 255-285 9-15 5-12 9-13 17-23
1.5 126-143 325-360 8-14 7-15 14-20 17-23
3.0 123-140 310-340 8-14 7-15 8-12 17-23
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat Subcooling
Water Temp
Drop °F
Air Temp
Rise °F DB
1.5 72-81 280-330 6-12 10-20 5-9 12-16
3.0 76-85 285-335 6-12 10-20 3-7 14-18
1.5 100-115 305-370 6-12 6-18 7-11 18-22
3.0 105-120 310-375 6-12 6-18 5-9 20-24
1.5 133-147 340-400 7-14 4-15 8-12 24-28
3.0 138-152 345-405 7-14 4-15 6-10 22-30
Heating -- No Desuperheater
30
50
70
70
90
Entering Water
Temp °F
Water Flow
GPM/Ton
Entering Water
Temp °F
Water Flow
GPM/Ton
Cooling -- No Desuperheater
50
Entering Water
Temp °F
Water Flow
GPM/Ton
Cooling -- No Desuperheater
50
70
90
Entering Water
Temp °F
Water Flow
GPM/Ton
Heating -- No Desuperheater
30
50
70
Dual Capacity Models
NS SPLIT INSTALLATION MANUAL
21
NS SPLIT INSTALLATION MANUAL
30°F 50°F 70°F 90°F 110°F
4 1.4 1.3 1.2 1.1 1.0
6 2.8 2.6 2.4 2.3 2.1
8 4.7 4.4 4.1 3.8 3.5
10 7.0 6.6 6.2 5.8 5.3
3 0.8 0.7 0.7 0.7 0.6
5 2.0 1.8 1.7 1.6 1.5
7 3.6 3.4 3.2 3.0 2.8
9 5.8 5.5 5.1 4.8 4.4
5 1.2 1.2 1.1 1.0 1.0
7 2.2 2.1 1.9 1.8 1.7
9 3.4 3.2 3.0 2.8 2.6
11 4.9 4.6 4.3 4 3.7
4 0.9 0.8 0.8 0.7 0.7
6 1.7 1.6 1.5 1.4 1.3
8 2.8 2.6 2.5 2.3 2.1
10 4.2 3.9 3.7 3.4 3.2
6 1.2 1.2 1.1 1.0 1.0
9 2.4 2.2 2.1 2.0 1.8
12 3.9 3.6 3.4 3.2 2.9
15 5.7 5.3 5 4.7 4.3
5 0.9 0.9 0.8 0.8 0.7
8 2.0 1.8 1.7 1.6 1.5
11 3.4 3.1 2.9 2.8 2.5
14 5.0 4.7 4.4 4.1 3.8
8 1.8 1.7 1.6 1.4 1.3
12 3.8 3.5 3.3 3.0 2.8
16 6.5 6.0 5.6 5.2 4.8
20 9.7 9.1 8.5 8.0 7.4
6 1.0 0.9 0.9 0.8 0.8
10 2.6 2.5 2.3 2.1 2.0
14 5.0 4.7 4.4 4.1 3.8
18 8.1 7.6 7.1 6.6 6.1
12 3.2 3.0 2.8 2.6 2.4
15 4.5 4.2 4.0 3.7 3.4
18 6.0 5.7 5.3 4.9 4.6
21 7.8 7.3 6.8 6.4 5.9
10 2.3 2.1 2.0 1.9 1.7
13 3.6 3.3 3.0 2.8 2.6
16 5.0 4.6 4.3 4.0 3.7
19 6.5 6.2 5.8 5.4 5.0
5/30/06
038
full
load
049
part
load
064
full
load
072
part
load
064
part
load
072
full
load
Pressure Drop (psi)
Model GPM
026
part
load
038
part
load
049
full
load
026
full
load
Pressure Drop and Recommended Flow Rates
Dual Capacity
22
NS SPLIT INSTALLATION MANUAL
Unit Startup
Before Powering Unit, Check The Following:
High voltage is correct and matches nameplate.
•
Fuses, breakers and wire size correct.
•
Low voltage wiring complete.
•
Piping completed and water system cleaned and ushed.
•
Air is purged from closed loop system.
•
Isolation valves are open, water control valves or loop pumps wired.
•
Transformer switched to 208V if applicable.
•
DIP switches are set correctly.
•
DHW pump switch is “OFF” unless piping is completed and air has been purged.
•
Blower rotates freely.
•
Blower speed correct.
•
Air lter/cleaner is clean and in position.
•
Service/access panels are in place.
•
Return air temperature is between 50-80ºF heating and 60-95ºF cooling.
•
Check air coil cleanliness to insure optimum performance. Clean as needed according to maintenance guidelines.
•
To obtain maximum performance the air coil should be cleaned before startup. A 10-percent solution of dishwasher detergent and water is recommended for both sides of coil, a thorough water rinse should follow.
Startup Steps
Notes: Complete the Equipment Start-Up/Commissioning Check Sheet during this procedure. Refer to thermostat operat- ing instructions and complete the startup procedure.
1. Initiate a control signal to energize the blower motor. Check blower operation.
2. Initiate a control signal to place the unit in the cooling mode. Cooling setpoint must be set below room temperature.
3. First stage cooling will energize after a time delay.
4. Be sure that the compressor and water control valve or loop pump(s) are activated.
5. Verify that the water ow rate is correct by measuring the pressure drop through the heat exchanger using the P/T plugs and comparing to unit capacity data in specication catalog.
6. Check the temperature of both the supply and discharge water (see page 21).
7. Check for an air temperature drop of 15°F to 25°F across the air coil, depending on the fan speed and entering water
temperature.
8. Decrease the cooling set point several degrees and verify high-speed blower operation.
9. Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or loop pumps
deactivate.
10. Initiate a control signal to place the unit in the heating mode. Heating set point must be set above room temperature.
11. First stage heating will energize after a time delay.
12. Check the temperature of both the supply and discharge water (see page 21).
13. Check for an air temperature rise of 20°F to 35°F across the air coil, depending on the fan speed and entering water
temperature.
14. If auxiliary electric heaters are installed, increase the heating setpoint until the electric heat banks are sequenced on. All stages of the auxiliary heater should be sequenced on when the thermostat is in the Emergency Heat mode. Check amperage of each element.
15. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pumps
deactivate.
23
NS SPLIT INSTALLATION MANUAL
Unit Startup (cont.)
16. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required.
17. Set system to desired normal operating mode and set temperature to maintain desired comfort level.
18. Instruct the owner/operator in the proper operation of the thermostat and system maintenance.
Notes: Be certain to ll out and forward all warranty registration papers.
Final Evaluation
After the initial check of superheat/subcooling values in the heating mode, shut off the unit and allow it to sit 3 to 5 minutes until pressures equalize. Restart the unit in the cooling mode and check the values against those in tables on page 21. If the unit performs satisfactorily, charging is complete. If the unit does not perform to specications, the charge may need to be readjusted until the values are close. Adding refrigerant will increase subcooling. Recovering some of the refrigerant will decrease subcooling and increase superheat. If the superheat/subcooling values are still not close to the specications in tables on page 21, analyze refrigerant circuit operation.
24
Heating Cycle Analysis
COOLING TXV - ACTIVE RIGHT TO LEFT
ClgTXV
Lineset
length
Measure liquid line temperature and pressure here in both heating and cooling modes
COAX
HEATING TXV - ACTIVE LEFT TO RIGHT
HtgTXV
Measure suction temperature here at TXV bulb in heating modes.
Suct PSI____
Suct sat temp____
Volts ____
Amps ____
EWT ____
LWT ____
Suct temp____
Super heat____
Discharge PSI____
Disch. sat temp____
Liquid temp____
Sub cooling____
Bi-flow
filter/drier
Air
Coil
Suction
Discharge
Comp
Desuper­heater
Measure suction temperature here at TXV bulb in cooling modes.
Cooling Cycle Analysis
COOLING TXV - ACTIVE RIGHT TO LEFT
ClgTXV
Measure liquid line temperature and pressure here in both heating and cooling modes
COAX
HEATING TXV-ACTIVE LEFT TO RIGHT
HtgTXV
Measure suction temperature here at TXV bulb in heating modes.
Suct PSI ____
Suct sat temp ____
Volts ____
Amps ____
EWT ____ LWT ____
Suct temp ____
Super heat ____
Discharge PSI ____
Disch. sat temp ____
Liquid temp ____
Sub cooling ____
Bi-flow
filter/drier
Air
Coil
Suction
Discharge
Comp
Desuper­heater
Measure suction temperature here at TXV bulb in cooling modes.
Note: DO NOT hook up pressure gauges unless there appears to be a performance problem.
Lineset
length
Unit Startup/Troubleshooting
NS SPLIT INSTALLATION MANUAL
25
NS SPLIT INSTALLATION MANUAL
Troubleshooting
Standard Microprocessor Controls
To check the unit control board for proper operation:
1. Disconnect thermostat wires at the control board.
2. Jumper the desired test input (Y1, Y2, W, O or G) to the R terminal to simulate a thermostat signal.
3. If control functions properly:
Check for thermostat and eld control wiring (use the diagnostic inputs mode).
4. If control responds improperly:
Ensure that component being controlled is functioning (compressor, blower, reversing valve, etc.).
Ensure that wiring from control to the component is functioning (refer to the LED Denition table below and use the diagnostic outputs mode).
If steps above check properly, replace unit control.
LED Denitions and Diagnostics
Standard Microprocessor
DIAGNOSTIC MODES
INPUTS OUTPUTS 1 OUTPUTS 2
1 NA
6 Off
7 Off
Compressor
(On or Low)
Blower
Low
LED
Drain
NORMAL
DISPLAY MODE
Field Selection DIPS
SW2- 1 On SW2- 1 Off SW2- 1 NA SW2- 1 NA SW2-
SW2- 6 On SW2- 6 On SW2- 6 Off SW2- 6 On SW2-
SW2- 7 On SW2- 7 On SW2- 7 On SW2- 7 Off SW2-
Drain Pan Overflow
Lockout
CURRENT
FAULT STATUS
Drain Pan Overflow Y1
Water Flow
High
Pressure
FP Thermistor (Loop
<15º F, Well<30ºF)
Lockout
High Pressure >600
PSI Lockout
FP Thermistor (Loop
<15º F, Well<30ºF)
High Pressure >600 O Reversing Valve
Y2
Compressor (On or High)
Blower
Medium
Blower
High
Low
Pressure,
Current
Low Pressure <40 Low Pressure/CA <40 G Fan Aux Heat 1
Sensor
Status
DHW Limit
DHW Off
Microprocessor
Malfunction
HWL Thermistor
>130ºF
DHW Pump
Switch Off
Not Used SL1 Loop Pump 1 Aux Heat 3
HWL Thermistor
>130°F
DHW Pump Switch Off
Not Used Loop Pump 2 Aux Heat 4
Refrigerant Systems
To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Compare the change in temperature on the air side as well as the water side to the tables on pages 21. If the unit’s performance is not within the ranges listed, and the airflow and water flow are known to be correct, gauges should then be installed and su­perheat and subcooling numbers calculated. If superheat and subcooling are outside recommended ranges, an adjustment to the refrigerant charge may be necessary.
Notes:
Refrigerant tests must be made with desuperheater turned “OFF”.
proper levels before servicing the refrigerant circuit.
Verify that air and water flow rates are at
26
NS SPLIT INSTALLATION MANUAL
Preventive Maintenance
Water Coil Maintenance
1. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to inltrate the water line. Lines should always be airtight.
2. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be
placed in the discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure.
Notes: On open loop systems, if the installation is in an area with a known high mineral content (125 PPM or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water owing through the unit the less chance for scaling.
Other Maintenance
Filters
Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating con-
ditions and be replaced when necessary. Units should never be operated without a lter.
Condensate Drain
In areas where airborne bacteria produce a slime in the drain pan, it may be necessary to treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty lters. Inspect twice a year to avoid the possibility of overow.
Blower Motors
Blower motors on most air handlers are equipped with sealed ball bearings and require no periodic oiling.
Air Coil
The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum clean. Care must be taken not to damage the aluminum ns while cleaning.
CAUTION:Finedgesaresharp.
Replacement Procedures
Obtaining Parts
When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required.
In-Warranty Material Return
Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return authorization and assistance.
27
NS SPLIT INSTALLATION MANUAL
B
Top View
F
G
D
E
I
H
Suction Line
Connection
Connection Point for Field Installed
Heat Recovery Unit
Liquid Line Connection
Lineset connections are braze type internally mounted
Front View
A
C
Side View
WATER IN
WATER OUT
Rear View
L
K
J
Side View
M
Physical Dimensions
Cabinet Dimensions and Refrigerant Piping Connections
MODEL A B C D E F G H I J K L M
PHYSICALDIMENSIONS
36.0 23.9 25.7 9.3 7.1 9.0 5.6 8.2 10.7 18.9 8.7 14.8 7.0
NS026thruNS072
Notes: Refer to Physical Dimensions and Piping Connections drawings
Inches [cm]
[91.4] [60.7] [65.2] [23.7] [18.0] [22.8] [14.2] [20.9] [27.2] [48.0] [22.1] [37.6] [17.8]
28
IM1615 10/08
Manufactured by
WaterFurnace International, Inc.
9000 Conservation Way
Fort Wayne, IN 46809
WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and reserves the right to change
design and specications without notice. © 2008 WaterFurnace International Inc.
Product: EnvisionSeries-NSOutdoorSplit
Type: Geothermal/Water Source Heat Pumps
Size: 2-6 Tons
Document: Installation Manual
Loading...