Envision Peripherals R-410A User Manual

RESIDENTIAL
• R-410A Refrigerant
• 2, 2.5, 3, 3.5, 4, 5, 6 Ton Single Speed
• 2, 3, 4, 5, 6 Ton Dual Capacity
Installation Information Water Piping Connections Desuperheater Connections Electrical Startup Procedures Troubleshooting Preventive Maintenance
Envision Residential Installation Manual
IM1585 10/07
ENVISION RESIDENTIAL INSTALLATION MANUAL
Model Nomenclature
Model Type
N= Envision
Compressor Type
D= Dual Capacity S= Single Speed
Cabinet Configuration
V= Vertical H= Horizontal
Unit Capacity
Vintage
A= Current
Voltage
1= 208-230/60/1
N D V 049 A 1 1 1 C T L
Return Air Configuration
L= Left R= Right
Discharge Air Configuration
B= Bottom T= Top S= Side E= End
Coax Options
C= Copper N= Cupronickel
Fan Option
0= PSC 1= ECM 2= Oversized ECM Blower Option
(036,038,042,048,049)
3= Oversized PSC Blower Option
(022,030,036,042,048)
Hot Water Option
0= None 1= Hot Water Generation with
factory installed pump
Notes: PSC Motor - Single Speed Only
2
ENVISION RESIDENTIAL INSTALLATION MANUAL
T able of Contents
General Installation Information 4-8 Closed Loop Ground Source Systems 9 Open Loop Ground Water Systems 10 Desuperheater Connection & Startup 11-12 Electrical Connections 13-14 Electronic Thermostat Installation 14 Auxiliary Heat Ratings 14 Electrical Data 15 Fan Performance Table 16-17 Setting Fan Speed 16-17 Vertical Dimensional Data 18 Horizontal Dimensional Data 19 Vertical Bottomfl ow Dimensional Data 20 Physical Data 21-22 Wiring Schematics 23-27 Microprocessor Control 28-32 Unit Startup 33 Operation Logic 34 Unit Operating Parameters 35-36 Pressure Drop & Recommended Flow Rates 37 Troubleshooting 38 Preventive Maintenance 39 Replacement Procedures 39
3
ENVISION RESIDENTIAL INSTALLATION MANUAL
General Installation Information
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main
power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualifi ed service personnel should install, repair or service heating and air conditioning equip- ment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing fi lters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equip­ment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a re extinguisher available.
Moving and Storage
Move units in the normal “up” orientation. Horizontal units may be moved and stored per the information on the packag­ing. Do not stack more than three units in total height. Vertical units may be stored one upon another to a maximum height of two units. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
Unit Location
Locate the unit in an indoor area that allows for easy removal of the fi lter and access panels. Location should have enough space for service personnel to perform maintenance or repair. Provide suffi cient room to make water, electrical and duct connection(s). If the unit is located in a confi ned space, such as a closet, provisions must be made for return air to freely enter the space by means of a louvered door, etc. Any access panel screws that would be diffi cult to remove after the unit is installed should be removed prior to setting the unit. On horizontal units, allow adequate room below the unit for a condensate drain trap and do not locate the unit above supply piping. Care should be taken when units are located in
unconditioned spaces to prevent damage from frozen water lines and excessive heat that could damage electrical components.
Installing Vertical Units
Prior to setting the unit in place, remove and discard the compressor hold down
shipping bolt located at the front of the compressor mounting bracket. Vertical units are available in left or right air return confi gurations. Top air dis- charge vertical units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the fl oor. It is not necessary to anchor the unit to the fl oor (see right). Bottomfl ow units should be mounted level and sealed well to fl oor to prevent air leakage. Bottomfl ow units require the supply air opening to be cut at least 1/2˝ larger than the unit’s air outlet. Protect the edges of combustible fl ooring with sheet metal over-wrap or other non-combustible material.
Figure 1: Vertical Unit Mounting
2” Extruded Polystyrene
4
ENVISION RESIDENTIAL INSTALLATION MANUAL
Installing Horizontal Units
Remove and discard the compressor hold down shipping bolt located at the front of the compressor mounting bracket prior to setting the unit in place. Horizontal units are available with side or end discharge. Horizontal units are normally sus­pended from a ceiling by six 3/8-inch diameter threaded rods. The rods are usually attached to the unit by hanger bracket kits furnished with each unit. Lay out the threaded rods per the dimensions below. Assemble the hangers to the unit as shown. Securely tighten the brackets to the unit using the weld nuts located on the underside of the bottom panel. When attaching the hanger rods to the bracket, a double nut is required since vibration could loosen a single nut. To allow fi lter access, one bracket on the fi lter side should be installed 180° from the position shown in the fi gure below. The unit should be pitched approximately 1/4-inch towards the drain in both directions to facilitate the removal of condensate. Use only the bolts provided in the kit to attach hanger brackets. The use of longer bolts could damage internal parts. Some residential applications require the installation of horizontal units on an attic fl oor. In this case, the unit should be set in a full size secondary drain pan on top of a vibration absorbing pad. The secondary drain pan prevents possible condensate overfl ow or water leakage damage to the ceiling. The secondary drain pan is usually placed on a plywood base isolated from the ceiling joists by additional layers of vibration absorbing material.
CAUTION: Do not use rods smaller than 3/8-inch diameter since they may not be strong enough to support the unit. The rods must be securely anchored to the ceiling.
Figure 2: Horizontal Unit Mounting
O
Threaded Rods
Electrical
Disconnect
To Line
Power
To Thermostat
Line Voltage
Building Water Loop
Flexible Duct Collar
Insulate supply plenum and use at least one 90 elbow to reduce noise
Figure 3: Hanger Location and Assembly
F
A
E
B
Air Coil
Air Coil
D
C
Hanging
Brackets
(Included)
Hose
Kits
Ball Valves
3/8
Threaded Rod
(not supplied)
Bolt and Lockwasher
Model A B C D E F
022 - 030 24.8 036 - 038 72.4 24.1 43.1 042 - 049 77.4 24.1 48.1 060 - 072 82.4 24.1 53.1
Vibration Isolator
27.8
27.8
27.8
Washer
Hex Nuts (not supplied)
63.4 21.1 38.1
25.3
29.3
29.3
29.3
1.1
1.1
1.1
1.1
5
ENVISION RESIDENTIAL INSTALLATION MANUAL
Duct System
An air outlet collar is provided on vertical top air discharge units and all horizontal units to facilitate a duct connection (vertical bottomfl ow units have no collar). A fl exible connector is recommended for discharge and return air duct connec- tions on metal duct systems. Uninsulated duct should be insulated with a minimum of 1-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected.
If the unit is connected to existing ductwork, check the duct system to ensure that it has the capacity to accommodate the air required for the unit application. If the duct is too small, as in the replacement of heating only systems, larger duct­work should be installed. All existing ductwork should be checked for leaks and repaired if necessary. The duct system should be sized to handle the design airfl ow quietly and effi ciently. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of fi berglass or constructed of ductboard for the fi rst few feet. On systems employing a sheet metal duct system, canvas connectors should be used between the unit and the ductwork. If air noise or excessive airfl ow is a problem, the blower speed can be changed.
CAUTION: Be sure to remove the shipping material from the blower discharge before con­necting ductwork.
Water Piping
The proper water fl ow must be provided to each unit whenever the
Figure 4: Swivel Connections (Residential Units)
unit operates. To assure proper fl ow, use pressure/temperature ports to determine the fl ow rate. These ports should be located at the supply and return water connections on the unit. The proper fl ow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger. All source water connections on commercial units are fi ttin g s that accept a male pipe thread (MPT). Insert the connectors by hand, then tighten the fi tting with a wrench to provide a leakproof joint. When con- necting to an open loop (groundwater) system, thread any copper MPT
Stainless Steel Snap Ring
Gasket Material
Locking Ring
Gasket Support Sleeve
tting into the connector and tighten in the same manner as described above. All source water connections on residential units are swivel piping ttings (see Figure 4) that accept a 1-inch male pipe thread (MPT) . The swivel connector has a rubber gasket seal similar to a rubber hose gasket, which when mated to the fl ush end of any 1-inch threaded pipe provides a leak-free seal without the need for thread sealing tape or compound. Check to ensure that the rubber seal is in the swivel con­nector prior to attempting any connection. The rubber seals are shipped attached to the waterline. To make the connection to a ground loop sys­tem, mate the brass connector (supplied in CK4L connector kit) against the rubber gasket in the swivel connector and thread the female locking ring onto the pipe threads, while maintaining the brass connector in the desired direction. Tighten the connectors by hand, then gently snug the tting with pliers to provide a leak-proof joint. When connecting to an open loop (ground water) system, thread any 1-inch MPT fi tting (SCH80 PVC or copper) into the swivel connector and tighten in the same manner as noted above. The open and closed loop piping system should include pressure/temperature taps for serviceability. Never use fl exible hoses smaller than 1-inch inside diameter on the unit. Limit hose length to 10 feet per connection. Check carefully for water leaks.
6
ENVISION RESIDENTIAL INSTALLATION MANUAL
Water Quality
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be pres­ent, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualifi ed service mechanic, as special solutions and pumping equipment are required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional fl ushing.
Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corrosion, along with reduced wear caused by acid cleaning.
7
ENVISION RESIDENTIAL INSTALLATION MANUAL
Freeze Protection
Set the freeze sensing switch SW2-2 on the printed circuit board for applications using a closed loop antifreeze solution
to “LOOP”. On applications using an open loop/ground water system (or closed loop no antifreeze), set this dip switch to “WELL”, the factory default setting. (Refer to the Dip Switch Field Selection table on page 24.)
Condensate Drain
On vertical units, the internal condensate drain assembly consists of a drain tube which is connected to the drain pan, a
3/4-inch PVC female adapter and a fl exible connecting hose. The female adapter may exit either the front or the side of the cabinet. The adapter should be glued to the fi eld-installed PVC condensate piping. On vertical upfl ow units, a condensate hose is inside all cabinets as a trapping loop; therefore, an external trap is not necessary. On horizontal units, a PVC stub is provided for condensate drain piping connection. An external trap is required (see below). If a vent is necessary, an open stand pipe may be applied to a tee in the fi eld-installed condensate piping.
Figure 5: Horizontal Drain Connection
3/4” PVC tube stub
Figure 6: Unit Pitch for Drain
3/4" PVC Coupling
1.5"
Vent (if needed)
3/4" PVC 1/8" per foot
1.5"
1/2'' Pitch
Drain
8
ENVISION RESIDENTIAL INSTALLATION MANUAL
Closed Loop Ground Source Systems
Note: For closed loop systems with antifreeze protection, set SW2-2 to the “loop” position (see table on page 28).
Once piping is completed between the unit, pumps and the ground loop (see fi gure below), fi nal purging and charging of the loop is required. A fl ush cart (or a 1.5 HP pump minimum) is needed to achieve adequate fl ow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter). This is normally adequate for good system operation. Loop static pressure will fl uctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fl uctuation is normal and should be considered when initially charging the system.
After pressurization, be sure to open the plug 1 turn in the end of the loop pump motor(s) (if applicable) to allow trapped air to be discharged and to ensure that the motor housing has been fl ooded. Ensure that the loop pumps provide adequate ow through the unit(s) by checking the pressure drop across the heat exchanger and comparing it to the unit capacity data in the specifi cation catalog. 2.5 to 3 GPM of fl ow per ton of cooling capacity is recommended in earth loop applications.
Figure 7: Closed Loop Ground Source Application
Auxiliary Heat
Disconnects
(If Applicable)
Unit Supply
Thermostat
Supply
Low
Voltage to
Vibration Absorbing Pad
Polyethylene w/
P/T Plugs
Multiple Units on One Flow Center
When two units are connected to one loop pumping system, pump control is automatically achieved by connecting the SL terminals on connector P2 in both units with 2-wire thermostat wire. These terminals are polarity dependant (see Figure 8). The loop pump(s) may be powered from either unit, whichever is more convenient. If either unit calls, the loop pump(s) will automati­cally start. The use of two units on one fl ow center is generally limited to a total of 20 GPM capacity.
®
GeoLink
®
Armaflex Insulation
Flexible Duct Collar
Auxiliary Heater Knockout
Unit Power
Desuperheater Connections
Drain
P/T
Envision to Envision
Microprocessor Units
Dual Capacity Envision Unit #1
Shut
CC
Down
With pump wired to Unit 1
With pump wired to Unit 2
Shut
CC
Down
Envision Unit #2 Dual Capacity
Link
o
Ge
Flow
nt
e
C
Insulated piping or hose kit
SL1InSL1
Out
SL1InSL1
Out
TO
LOOP
®
r
e
Note: Additional information can be found in Flow Center installation manual (IM1961) and Flush Cart manual (WFS302).
Figure 8: Primary/Secondary Hook-up
Envision to Envision
Microprocessor Units
Single Speed Envision Unit #1
Shut
Down
Shut
Down
Envision Unit #2 Single Speed
CC
CC
SL1InSL1
Out
SL1InSL1
Out
With pump wired to Unit 1
With pump wired to Unit 2
Envision to
Electromechanical Units
Envision Unit #1
Shut
Down
To Electromechanical Unit
CC
C
SL1InSL1
S
Out
9
ENVISION RESIDENTIAL INSTALLATION MANUAL
)
)
)
Open Loop Ground Water Systems
Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure proper water fl ow through the unit by checking pressure drop across the heat exchanger and comparing it to the fi gures in unit capacity data tables in the specifi cation catalog. 1.5-2 GPM of fl ow per ton of cooling capacity is recommended in open loop applications. Due to only minor differences in fl ow rate from low to high, only one solenoid valve should be used. The valve should be sized for full fl ow .
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, i.e. recharge well, storm sewer, drain fi eld, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.
Note: For open loop/groundwater systems or systems that do not contain an antifreeze solution, set SW2-Switch #2 to the “WELL ” position. (Refer to the table on page 28.) Slow opening/closing solenoid valves ( type VM) are recommended to eliminate water hammer.
Figure 9a: Open Loop Solenoid Valve Connection Option
Typical quick operating external 24V water solenoid valve (type PPV100 or BPV100) wiring.
C
P1
R
SV
Acc Com Acc NC Acc NO
1 2
P3
3
Solenoid
Valve
Note:
SW2-3 should be in the Comp “ON” position.
Figure 10: Open System - Groundwater Application
Unit Supply
Aux. HeatSupply
Figure 9b: Open Loop Solenoid Valve Connection Option
Typical slow operating external 24V water solenoid valve (type VM) wiring.
CC
CC-GND
CCHI
Logic Board
Comfort
Alert
Flexible Duct Collar
Violet(2
VM valve
CC
Blk(1
Violet(3
Y1 Y2
Wht(4)
Rubber Bladder Expansion Tank
Auxiliary
Disconnects
(IfApplicable)
Compressor Line Voltage
Low Voltage
to Thermostat
and Valve
P/T Plugs
Vibration
Absorbing Pad
Heater Knockout
Desuperheater
Connections
Drain
Strainer
Solenoid
Valve
valve whileacid flushing)
Boiler Drains
For HXFlushing
(to isolatesolenoid
Flow Control
(on outletof
Solenoid Valve)
Water Out
Shut OffValves
Shut OffValves
Valve
Water In
10
ENVISION RESIDENTIAL INSTALLATION MANUAL
Desuperheater Connections
To m a x i m i ze t h e b e n e fi ts of the desuperheater a minimum 50- gallon water heater is recommended. For higher demand applications, use an 80 -gallon water heater or two 50 -gallon water heaters connec ted in a series as shown below. Electric water heaters are recommended. Make sure all local electrical and plumbing codes are met for installing a desuperheater.
Note: Under certain conditions, Envision dual capacity units operate with very low refrigerant discharge temperatures, producing little or no water heating capability. This scenario occurs when the unit is operating with cold entering source water (loop or well). Allowing the desuperheater pump to operate during these conditions actually removes heat from the DHW circulating through the unit. To overcome this, En vision unit microprocessors have been programmed to disengage the desuperheater pump during such conditions. (Dur ing low capac ity c ooling oper ation, the pump will operate only if the DHW temperature entering the unit is less than the liquid line temperature plus 35º F. During high capacity cooling operation, the pump will operate only if the DHW temperature is less than the l i quid line t emperature plus 60º F.) Using a preheat tank, as shown in Figure 12, will maximize desuperheater capabilities.
Water Tank Preparation
To install a unit with desuperheater, follow these installation guidelines.
Turn off the power to the water heater.
1. Attach a water hose to the water tank drain connection and run the other end of the hose to an open drain or
2. outdoors. Close the cold water inlet valve to the water heater tank.
3. Drain the tank by opening the valve on the bottom of the tank, then open the pressure relief valve or hot water
4. faucet. Flush the tank by opening the cold water inlet valve to the water heater to free the tank of sediments. Close when
5. draining water is clear. Disconnect the garden hose and remove the drain valve from the water heater.
6. Refer to Plumbing Installation and Desuperheater Startup on page 12.
7.
Residential units with desuperheaters contain an internal circulator and fi ttings.
CAUTION: Elements will burn out if energized dry.
Figure 11: Typical Desuperheater Installation
3/4 x 3/4 x 1/2 tee
Venting Waste
Valve or Vent
Coupling
DHW
Water In
DHW
Water Out
Cold
Water In
P/T Relief
Drain Valve
Valve
Water Out
In
Hot
Figure 12: Desuperheater Installation In Preheat Tank
Venting Waste Valve or Vent Coupling
Note: This con guration maximizes desuperheater capability.
3/4" x 3/4" x 1/2" tee
DHW
Water In
DHW
Water Out
Cold
Water In
P/T Relief
Valve
In
Drain ValveDrain Valve
Hot
Water Out
P/T Relief
Valve
11
ENVISION RESIDENTIAL INSTALLATION MANUAL
Plumbing Installation
1. Inspect the dip tube in the water heater cold inlet for a check valve. If a check valve is present it must be removed or damage to the desuperheater circulator will occur.
2. Remove drain valve and fi tti n g .
3. Thread the 3/4-inch NPT x 3-1/2-inch brass nipple into the water heater drain port.
4. Attach the center port of the 3/4-inch FPT tee to the opposite end of the brass nipple.
5. Attach the 1/2-inch copper to 3/4-inch NPT adaptor to the side of the tee closest to the unit.
6. Install the drain valve on the tee opposite the adaptor.
7. Run interconnecting tubing from the tee to DHW water out.
8. Cut the cold water “IN” line going to the water heater.
9. Insert the reducing solder tee in line with cold water “IN” line as shown.
10. Run interconnecting copper tubing between the unit DHW water “IN” and the tee (1/2-inch nominal). The recommended maximum distance is 50 feet.
11. To prevent air entrapment in the system, install a vent coupling at the highest point of the interconnecting lines.
12. Insulate all exposed surfaces of both connecting water lines with 3/8-inch wall closed cell insulation. Note: All plumbing and piping connections must comply with local plumbing codes
.
Desuperheater Startup
1. Close the drain valve to the water heater.
2. Open the cold water supply to the tank.
3. Open a hot water faucet in the building to bleed air from the system. Close when full.
4. Open the pressure relief valve to bleed any remaining air from the tank, then close.
5. If so equipped, unscrew the indicator plug 1 turn on the motor end of the pump until all air is purged from the pump, then tighten the plug. Use vent couplings to bleed air from the lines.
6. Carefully inspect all plumbing for water leaks and correct as required.
7. Before restoring electrical supply to the water heater, adjust the temperature setting on the tank.
On tanks with both upper and lower elements, the lower element should be turned down to the lowest setting, approximately 100°F. The upper element should be adjusted to 120°F to 130°F. Depending upon the specifi c needs of the customer, you may want to adjust the upper element differently.
On tanks with a single element, lower the thermostat setting to 120°F.
8. After the thermostat(s) is adjusted, replace the access cover and restore electrical supply to the water heater.
9. Make sure that any valves in the desuperheater water circulating circuit are open.
10. Turn on the unit to fi rst stage heating.
11. The DHW pump should be running. When the pump is fi rst started, open the inspection port 1 turn (if equipped) until water dribbles out, then replace. Allow the pump to run for at least fi ve minutes to ensure that water has fi lled the circulator properly. Be sure the switch for the DHW pump (SW4) is “ON”. The DHW “OFF” LED on the unit should not be illuminated.
12. The temperature difference between the water entering and leaving the desuperheater should be 5°F to 15°F. The water fl ow should be approximately 0.4 GPM per ton of nominal cooling.
13. Allow the unit to heat water for 15 to 20 minutes to be sure operation is normal.
CAUTION: Never operate the DHW circulating pump while dry. If the unit is placed in operation before the desuperheater piping is connected, be sure that the pump switch is set to the OFF position.
12
ENVISION RESIDENTIAL INSTALLATION MANUAL
Electrical Connections
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
Unit Power Connection
Connect the incoming line voltage wires to L1 and L2 of the contactor as shown in Figure 13C for single-phase unit. Consult the Unit Electrical Data in the Specifi cation Catalog for correct fuse sizes.
Open lower front access panel. Remove ground fastener from bottom of control box (Figure 13B). Swing open control box (Figure 13A). Insert power wires through knockouts on lower left side of cabinet. Route wires through left side of control box and connect to contactor and ground (Figure 13C). Close control box and replace grounding fastener before unit start-up.
Figure 13A:
Wire access (control box open)
Location
Figure 13B:
Wire access (control box closed)
Ground FastenerWire Insert
Figure 13C:
Line Voltage 208-230/60/1 control box
L2 L1
Accessory Relay
A set of “dry” contacts has been provided to control accessory devices, such as water solenoid valves on open loop instal­lations, electronic air cleaners, humidifi ers, etc. This relay contact should be used only with 24 volt signals and not line voltage power. The relay has both normally open and normally closed contacts and can operate with either the fan or the compressor. Use DIP switch SW2-3 to cycle the relay with fan or compressor. The relay contacts are available on terminals #2 and #3 of P3.
208 Volt Operation
All Envision 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red and blue transformer wires must be switched on terminal strip PS.
13
ENVISION RESIDENTIAL INSTALLATION MANUAL
Electrical Connections (cont.)
Pump Wiring
Figure 14: Pump Wiring 208-230/60/1
See Figure 14 for electrical connections from control box to pumps.
Electronic Thermostat
Position the thermostat subbase against the wall so that it is level and the thermostat wires protrude through the middle of the subbase. Mark the position of the subbase mounting holes and drill holes with a 3/16-inch bit. Install supplied anchors and secure base to the wall. Thermostat wire must be 8-conductor, 18­AWG wire. Strip the wires back 1/4-inch (longer strip lengths may cause shorts) and insert the thermostat wires into the connector as shown. Tighten the screws to insure secure connections. The thermostat has the same type connectors, requiring the same wiring. See instructions enclosed in the thermostat for detailed installation and operation information.
Figure 15: Thermostat Wiring
Microprocessor Controlle
r
R
C Y1 Y2
W
O
G
24VAC (Hot) 24VAC (Common)
Compressor (1st Stage) Compressor (2nd Stage) Aux. Heat Reversing Valve
Blower Relay
L
System Monitor
Thermostat Connection
Note: DIP switch SW2-8 is required to be in the “OFF” position for the control to operate with FaultFlash or ComforTalk thermostats. SW2-8 in the “ON” position confi gures the control to operate with typical thermostats (continuous lockout signal). There must be a wire connecting Y2 on the microprocessor controller to 2nd stage compressor on the thermostat for proper operation.
Auxiliary Heat Ratings
KW BTU/HR Min Envision Series Compatibility
Model 208V 230V Stages 208V 230V CFM 022 026 - 030 036 - 049 060 - 072
EAM(H)5 3.6 4.8 1 12,300 16,300 450 EAM(H)8 5.7 7.6 2 19,400 25,900 550 EAM(H)10 7.2 9.6 2 24,600 32,700 650 EAL(H)10 7.2 9.6 2 24,600 32,700 1100 EAL(H)15 10.8 14.4 3 36,900 49,100 1250 EAL(H)15-3 10.8 14.4 3 36,900 49,100 1250 EAL(H)20 14.4 19.2 4 49,200 65,500 1500
14
••
••
••
••
••
Unit Electrical Data
Single speed with ECM motor
Model
022 030 036 036* 042 042* 048 048* 060 070
*With optional 1 HP ECM2 motor
Rated
Voltage
208-230/60/1 197/253
Voltage
MIN/MAX
Single speed with PSC Motor
Model
022 022* 030 030* 036 036* 042 042* 048 048* 060 070
*With optional over-sized blower
Rated Voltage
Voltage Min/Max
208-230/60/1 197/253
Compressor
MCC RLA LRA FLA FLA FLA FLA Amp HACR
14.0 9.0 48.0 0.4 5.4 4.0 18.8 21.0 30
20.0 12.8 58.3 0.4 5.4 4.0 22.6 25.8 35
22.0 14.1 73.0 0.4 5.4 4.0 23.9 27.4 40
22.0 14.1 73.0 0.4 5.4 7.0 26.9 30.4 40
26.0 16.6 79.0 0.4 5.4 4.0 26.4 30.6 45
26.0 16.6 79.0 0.4 5.4 7.0 29.4 33.6 50
31.0 19.8 109.0 0.4 5.4 4.0 29.6 34.6 50
31.0 19.8 109.0 0.4 5.4 7.0 32.6 37.6 50
41.2 26.4 134.0 0.4 5.4 7.0 39.2 45.8 70
47.0 30.1 158.0 0.4 5.4 7.0 42.9 50.4 80
Compressor
MCC RLA LRA FLA FLA FLA FLA Amp HACR
14.0 9.0 48.0 0.4 5.4 1.2 16.0 18.2 25
14.0 9.0 48.0 0.4 5.4 1.5 16.3 18.5 25
20.0 12.8 58.3 0.4 5.4 1.5 20.1 23.3 35
20.0 12.8 58.3 0.4 5.4 2.2 20.8 24.0 35
22.0 14.1 73.0 0.4 5.4 2.8 22.7 26.2 40
22.0 14.1 73.0 0.4 5.4 3.5 23.4 26.9 40
26.0 16.6 79.0 0.4 5.4 3.5 25.9 30.1 45
26.0 16.6 79.0 0.4 5.4 4.6 27.0 31.2 45
31.0 19.8 109.0 0.4 5.4 3.5 29.1 34.1 50
31.0 19.8 109.0 0.4 5.4 4.6 30.2 35.2 50
41.2 26.4 134.0 0.4 5.4 5.9 38.1 44.7 70
47.0 30.1 158.0 0.4 5.4 5.9 41.8 49.3 70
ENVISION RESIDENTIAL INSTALLATION MANUAL
HWG Ext Fan Total Min Max
Pump Loop Motor Unit Circ Fuse/
HWG Ext Fan Total Min Max
Pump Loop Motor Unit Circ Fuse/
2/20/07
Dual Capacity
Model
026 038 038* 049 049* 064 072
*With optional 1 HP ECM2 motor NOTE: HACR circuit breaker in USA only. All fuses Class RK-5
Rated
Voltage
208-230/60/1 197/253
Voltage
MIN/MAX
Compressor
MCC RLA LRA FLA FLA FLA FLA Amp HACR
16.0 10.2 52.0 0.4 5.4 4.0 20.0 22.6 30
26.0 16.6 82.0 0.4 5.4 4.0 26.4 30.6 45
26.0 16.6 82.0 0.4 5.4 7.0 29.4 33.6 50
33.0 21.1 96.0 0.4 5.4 4.0 30.9 36.2 50
33.0 21.1 96.0 0.4 5.4 7.0 33.9 39.2 60
40.0 25.6 118.0 0.4 5.4 7.0 38.4 44.8 70
42.5 27.2 150.0 0.4 5.4 7.0 40.0 46.8 70
HWG Ext Fan Total Min Max
Pump Loop Motor Unit Circ Fuse/
5/30/06
15
ENVISION RESIDENTIAL INSTALLATION MANUAL
Fan Blower Motor Airflow (cfm) at External Static Pressure (in. wg)
Model Spd Size HP 0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
H 1110 1095 1080 1065 1045 1020 995 970 945 915 880 810 ---­M 9 x 71/5850845835825815805795775755735715----­L 750745740735725715700685670650630----­H 1290 1270 1245 1220 1190 1160 1125 1090 1055 1020 985 880 760 - - ­M 9 x 7 1/3 1100 1090 1075 1060 1045 1020 995 970 940 910 875 785 625 - - ­L 910 905 900 895 885 875 865 850 835 810 780 710 560 - - ­H 1665 1640 1610 1580 1550 1515 1480 1450 1415 1315 1215 1090 980 - - ­M 9 x 7 1/2 1465 1445 1425 1400 1375 1350 1325 1260 1190 1140 1090 990 890 - - ­L 1130 1115 1100 1090 1075 1035 995 965 930 895 860 795 730 - - ­H 2010 1975 1940 1905 1870 1825 1780 1735 1690 1640 1590 1470 1210 - - ­M 10 x 10 1/2 1670 1650 1630 1610 1590 1560 1530 1495 1460 1425 1390 1190 1080 - - ­L 1220 1215 1210 1295 1200 1180 1160 1130 1100 1060 1020 930 ---­H 2010 1975 1940 1905 1870 1825 1780 1735 1690 1640 1590 1470 1210 - ­M 10 x 10 1/2 1670 1650 1630 1610 1590 1560 1530 1495 1460 1425 1390 1190 1080 - - ­L 1220 1215 1210 1295 1200 1180 1160 1130 1100 1060 1020 930 ---­H 2430 2400 2365 2330 2290 2255 2215 2180 2140 2095 2045 1945 1835 1715 1510 1330 M 11 x 10 1 2265 2235 2205 2175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1260 L 2075 2050 2020 1995 1965 1940 1915 1885 1850 1820 1785 1720 1610 1505 1335 1175 H 2430 2400 2365 2330 2290 2255 2215 2180 2140 2095 2045 1945 1835 1715 1510 1330 M 11 x 10 1 2265 2235 2205 2175 2145 2110 2070 2035 2000 1960 1915 1825 1730 1605 1440 1260 L 2075 2050 2020 1995 1965 1940 1915 1885 1850 1820 1785 1720 1610 1505 1335 1175
Fan Blower Motor Airflow (cfm) at External Static Pressure (in. wg)
Model Spd Size HP 0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.50 0.60 0.70 0.80 0.90 1.00
H 1290 1270 1245 1220 1190 1160 1125 1090 1055 1020 985 880 760 - - ­M 9 x 7 1/3 1100 1090 1075 1060 1045 1020 995 970 940 910 875 785 625 - - ­L 910 905 900 895 885 875 865 850 835 810 780 710 560 - - ­H 1365 1340 1325 1305 1280 1250 1215 1180 1140 1100 1055 960 850 - - ­M 9 x 7 1/2 1040 1040 1035 1030 1020 1005 990 970 945 915 885 810 735 - - ­L 880 880 880 880 875 870 860 840 820 800 775 730 480 - - ­H 1930 1905 1875 1840 1805 1765 1725 1680 1635 1530 1425 1270 1150 1025 - ­M 9 x 7 1/2 1635 1620 1600 1580 1555 1530 1505 1465 1425 1335 1240 1135 1035 775 - ­L 1230 1230 1225 1215 1200 1165 1130 1095 1060 1035 1005 935 795 675 - ­H 2115 2075 2035 1980 1920 1900 1880 1840 1795 1730 1660 1390 1225 1070
1070
-­M 10 x 10 3/4 2005 1980 1950 1910 1865 1815 1765 1725 1685 1585 1485 1315 1140 1025 - ­L 1860 1835 1805 1780 1750 1715 1675 1635 1590 1540 1490 1260 1115 980 - ­H 2115 2075 2035 1980 1920 1900 1880 1840 1795 1730 1660 1390 1225 - ­M 10 x 10 3/4 2005 1980 1950 1910 1865 1815 1765 1725 1685 1585 1485 1315 1140 1025 - ­L 1860 1835 1805 1780 1750 1715 1675 1635 1590 1540 1490 1260 1115 980 - -
Factory settings are in Bold High-Static option not available for 060 and 070
Air flow values are with dry coil and standard filter For wet coil performance first calculate the face velocity of the air coil (Face Velocity [fpm] = Airflow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by 0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg.
022
030
036
042
048
060
070
022
030
036
042
048
Fan Performance Data - PSC
Standard PSC Motor
Optional High Static PSC Motor
Setting Fan Speed - PSC
CAUTION: Disconnect all power before performing this operation.
16
HIGH
E
R
I
W
D
E
E
P
S
N
A
F
PSC FAN MOTOR BODY
LOWMEDIUM
ENVISION RESIDENTIAL INSTALLATION MANUAL
Fan Performance Data - ECM
ECM2
Single Speed
MODEL
022 0.50
030 0.50
036 0.50 036
w/1hp*
042 0.50 042
w/1hp* L M
048 0.50 048
w/1hp*
060 0.75
070 0.75
Factory settings are at recommended L-M-H DIP switch locations CFM is controlled within ±5% up to the maximum ESP M-H settings MUST be located within boldface CFM range Max ESP includes allowance for wet coil and standard filter Lowest and Highest DIP switch settings are assumed to be L and H respectively
MAX AIR FLOW DIP SWITCH SETTINGS ESP123456789101112
650 750 850 1000 1100 1200
0.75
0.75
0.75
800 1000 1100 1300 1500 1600
650
800
650
800
800
800
400 500 600 700 400 500 600 700
L MH
800 900 1050 1150 1250 1350 1450 1550 900 1000 1200 1400 1600 1700 1850 2000 2200 2300 2400 800 900 1050 1150 1250 1350 1450 1550 900 1000 1200 1400 1600 1700 1850 2000 2200 2300 2400 950 1100 1300 1500 1750 1950 2100 2300 950 1100 1300 1500 1750 1950 2100 2300
L M L M
L
L
L
L MH
L L
MH
MH
H
MH
800 900 1000 1100 1200
H
800 900 1000 1100 1200
MH
H
1300 1400 1500
1800
MH
5/30/06
Dual Capacity
MODEL
026 0.50
038 0.50 038
w/1hp*
049 0.50 049
w/1hp*
064 0.75
072 0.75
Factory settings are at recommended L-M-H DIP switch locations CFM is controlled within ±5% up to the maximum ESP M-H settings MUST be located within boldface CFM range Max ESP includes allowance for wet coil and standard filter Lowest and Highest DIP switch settings are assumed to be L and H respectively
A 12-position DIP switch package on the control allows the airfl ow levels to be set for low, medium, and high
speed when using the ECM2 blower motor. Only three of the DIP switches can be in the "on" position.
The example to the right shows SW1 on the control board confi gured for the following NS042 airfl ow settings.
MAX AIR FLOW DIP SWITCH SETTINGS ESP123456789101112
650 750 850 1000 1100 1200
0.75
0.75
The fi rst "on" switch (the lowest position number) determines the low speed fan setting.
• The second "on" switch determines the medium speed fan setting.
• The third "on" switch determines the high speed fan setting.
Low Speed Fan: 900 CFM
• Medium Speed Fan: 1150 CFM
• High Speed Fan: 1450 CFM
800 1000 1100 1300 1500 1600
L MH
650
800
L
800
800
400 500 600 700
L
800 900 1050 1150 1250 1350 1450 1550
L
900 1000 1200 1400 1600 1700 1850 2000 2200 2300 2400 950 1100 1300 1500 1750 1950 2100 2300
L M
950 1100 1300 1500 1750 1950 2100 2300
L M
MH
MH
L
800 900 1000 1100 1200
MH
H
1300 1400 1500
1800
MH
H
5/30/06
SW1
OnOff
1 2 3 4 5 6 7 8
9 10 11 12
Setting Fan Speed - ECM
ECM2 fan motors have a 12-speed selector dip switch on the logic board (SW1) and are factory set for optimum perfor­mance. To change speeds, select the appropriate speeds on dip switch SW1. Consult the ECM2 fan performance table below for specifi c airfl ow and switch information.
CAUTION: Disconnect all power before performing this operation.
17
ENVISION RESIDENTIAL INSTALLATION MANUAL
LEFT RETURN RIGHT RETURN
FRONT
TOP
2ft [61cm ]
Primary Service Access
TOP
A
DEHFKJ I G
1.9in
[4.8cm]
1.9in
[4.8cm]
M
R
Q
N
O
L
R
N
O
L
P
Q
RIGHT SIDE
B
C
B
LEFT SIDE
STS
T
C
Vertical Dimensional Data
T op Air Discharge
Overall Cabinet
Vertical Models
in. 22.5 26.5 48.5 2.0 7.0 13.5 16.5 10.2
022-030
cm. 57.2 67.2 123.2 5.0 17.7 34.2 41.8 26.0 21.6 26.4 29.8 15.5 2.1 35.6 35.6 11.1 4.2 56.3 66.0 4.4
in. 25.6 31.6 50.4 2.3 7.3 15.9 18.9 10.6
036-038
cm. 65.0 80.2 128.0 5.7 18.4 40.3 47.9 26.8 20.3 28.6 32.4 17.5 2.8 45.7 45.7 9.6 4.4 71.2 66.0 4.3
in. 25.6 31.6 54.4 2.3 7.3 15.9 18.9 10.6
042-049
cm. 65.0 80.2 138.2 5.7 18.4 40.3 47.9 26.8 20.3 28.6 32.4 17.5 2.8 45.7 45.7 9.6 4.4 71.2 76.2 4.3
in. 25.6 31.6 58.4 2.3 7.3 15.9 18.9 10.6
060-072
cm. 65.0 80.2 148.3 5.7 18.4 40.3 47.9 26.8 20.3 28.6 32.4 17.5 2.8 45.7 45.7 9.6 4.4 71.2 86.4 4.3
Condensate is 3/4" PVC female glue socket and is switchable from side to front Vertical unit shipped with deluxe 2" (field adjustable to 1") duct collar/filter rack extending from unit 3.25" and is suitable for duct connection. Discharge flange is field installed and extends 1" [25.4 mm] from cabinet Decorative molding and water connections extend 1.2" [30.5mm] beyond front of cabinet.
IJK
AB CDE F G H
Width Depth Height* In Out HWG In
Water Connections Electrical Knockouts
HWG
Out
Cond-
ensate
Loop
Water FPT HWG FPT
1" Swivel 1" Swivel
1" Swivel 1" Swivel
1" Swivel 1" Swivel
1" Swivel 1" Swivel
1/2" cond 1/2" cond 3/4" cond LMNOPQRST
Low
Voltage
8.5 10.4 11.8 6.1 0.8 14.0 14.0 4.4 1.7 22.2 26.0 1.7
8.0 11.3 12.8 6.9 1.1 18.0 18.0 3.8 1.7 28.1 26.0 1.7
8.0 11.3 12.8 6.9 1.1 18.0 18.0 3.8 1.7 28.1 30.0 1.7
8.0 11.3 12.8 6.9 1.1 18.0 18.0 3.8 1.7 28.1 34.0 1.7
Ext Pump
Discharge Connection
duct flange installed (±0.10 in)
Power Supply
Supply
Width
Supply
Depth
Return Connection
using std deluxe filter rack (±0.10 in)
Return
Return
Depth
Height
Rev.: 07/19/06 B
18
ENVISION RESIDENTIAL INSTALLATION MANUAL
S
S
Horizontal Dimensional Data
TOP VIEW
2ft [61cm ]
Primary Service Access
Q
P
2.1in [5.4cm ]
MOUNT (2) HANGER BRACKET AS SHOWN TO ALLOW ACCES TO FILTER
SIDE DISHCARGE VIEW
B
END VIEW
L
L
O
N
M
C
H
1.9in
[4.8cm]
KJ I
FRONT VIEW
A
S
DE F G
AS SHOWN LR UNIT (RR UNIT ON OPPOSITE SIDE—SAME DIMENSIONS)
Overall Cabinet
Horizontal
Models
in. 22.5 63.0 19.3 2.0 7.0 13.5 16.5 0.8
022-030
cm. 57.2 160.0 49.0 5.0 17.7 34.2 41.8 2.1 22.2 24.0 30.0 5.8 26.5 23.8 14.7 7.0 77.3 42.9 3.3
in. 25.6 72.0 21.3 2.3 7.3 15.9 18.9 0.8
036-038
cm. 65.0 182.9 54.1 5.7 18.4 40.3 47.9 2.1 22.2 24.0 30.0 34.6 33.5 7.0 90.0 47.9 3.3
in. 25.6 77.0 21.3 2.3 7.3 15.9 18.9 0.8
042-049
cm. 65.0 195.6 54.1 5.7 18.4 40.3 47.9 2.1 22.2 24.0 30.0 34.6 33.5 7.0 102.5 47.9 3.3
in. 25.6 82.0 21.3 2.3 7.3 15.9 18.9 0.8
060-072
cm. 65.0 208.3 54.1 5.7 18.4 40.3 47.9 2.1 22.2 24.0 30.0 34.6 33.5 7.0 115.2 47.9 3.3
Right Return End Discharge
Right Return Side Discharge
Left Return End Discharge
Left Return Side Discharge
AB C
Width Depth Height* In Out HWG In
DE F G H
LUnits Not Shown Above O
in. 2.8 4.6
cm. 7.1 11.8
in. 4.9 6.9
cm. 12.4 17.5
in. 4.9 7.6
cm. 12.4 19.4
in. 2.8 6.9
cm. 7.1 17.5
Water Connections Electrical Knockouts
IJK
HWG
Out
Cond-
ensate
Loop
Water FPT HWG FPT
1" Swivel 1" Swivel
1" Swivel 1" Swivel
1" Swivel 1" Swivel
1" Swivel 1" Swivel
1/2" cond 1/2" cond 3/4" cond LMNOPQRS
Low
Ext Pump
Voltage
8.8 9.4 11.8 2.3 10.5 9.4 5.8 2.8 30.5 16.9 1.3
8.8 9.4 11.8
8.8 9.4 11.8 13.6 13.2 2.8 40.4 18.9 1.3
8.8 9.4 11.8 13.6 13.2 2.8 45.4 18.9 1.3
Power
Supply
Discharge Connection
duct flange installed (±0.10 in)
Supply
Supply
Height
Depth
13.6 13.2 2.8 35.5 18.9 1.3
SEE
CHART
SEE
CHART
SEE
CHART
SEE
CHART
SEE
CHART
SEE
CHART
using std deluxe filter rack (±0.10 in)
Return Connection
Return Depth
Return Height
O
Rev.: 07/18/06 B
S
R
Condensate is 3/4" PVC female glue socket and is switchable from side to front Horizontal unit shipped with deluxe 2" (field adjustable to 1") duct collar/filter rack extending from unit 2.88" and is suitable for duct connection. Discharge flange is field installed and extends 1" [25.4 mm] from cabinet Decorative molding and water connections extend 1.2" [30.5mm] beyond front of cabinet.
19
ENVISION RESIDENTIAL INSTALLATION MANUAL
Vertical Dimensional Data
Bottomfl ow
LEFT RETURN
RIGHT RETURN
1.70
4
(4.3 cm)
C
S
S
T
T
B
LEFT SIDE
R
L
2ft [61cm]
Primary Service Access
Bottomflow
Models
022-030 .66.81.546.349.146.37.947.642.043.535.255.625.22.ni 0 9.3 10.5 1.0 2.2 22.2 26.0 5.6
036-072 .41.92.258.059.846.30.060.754.844.345.265.135.52.ni 8 13.4 13.6 1.5 1.8 28.1 34.0 5.6
Condensateis 3/4" PVC femaleglue socketand is switchable from side tofront Verticalbottomflow unitshippedwithdeluxe 2" (fieldadjustableto1") duct collar/filter r ack extendingfromunit3.25" and issuitable for ductconnection. Decorative moldingand w ater connectionsex tend 1.2" (30.5mm)beyond frontofcabinet.
ABCDEFG H
Width Depth Height In Out HWG In HWG Out Condensate Water FPT
O
M
LEFT BOTTOM DISCHARGE
2017.984.3313.762.75.mc
N
FLOOR FOOT PRINT
4321
19.2212.0118.8510.088.46.mc 2.6 23.1 12.2 34.0 34.5 3.8 4.6 71.4 86.4 14.2
snoitcennoCretaWtenibaCllarevO 5
1" Swivel
.92.6216.8111.
1
1" Swivel 1" Swiv el
Loop
Q
RIGHT BOTTOM DISCHARGE
HWG
FPT
1" Swiv el
B
RIGHT SIDE
RQ
O
FLOOR FOOT PRINT
Electrical Knockouts
I
J
1/2" cond 1/2" cond 3/4" cond
Low
Voltage
ExtPump
Power Supply
C
K
J
I
LN
P
DischargeConnection
K
.6 21.8 15.2 23.6 26.7 2.5 5.6 56.4 66.0 14.2
4117.0114.601
310.9212.4211.94.2518.44
duct flange installed (±0.10 in)
LMNOPQRST
Supply
Width
Supply
Depth
3
2 1
1.90 (4.7 cm)
5
A
FRONT
using std deluxe filter rack (± 0.10 in)
D
H
Return Connection
Return
Return Height
Depth
E
Rev.: 09/27/07
G
F
20
ENVISION RESIDENTIAL INSTALLATION MANUAL
Physical Data (Single Speed)
Model
Compressor (1 each) Factory Charge R410a, oz [kg] Vertical 62 [1.76] 62 [1.76] 82 [2.32] 82 [2.32] 98 [2.78] 110 [3.12] 146 [4.14] Factory Charge R410a, oz [kg] Horizontal 60 [1.70] 66 [1.87] 82 [2.32] 82 [2.32] 98 [2.78] 94 [2.67] 122 [3.46]
022 030 036 042 048 060 070
Copeland Scroll
Fan Motor & Blower
SINGLE SPEED
Fan Motor Type/Speeds
Fan Motor- hp [W]
Blower Wheel Size (Dia x W), in. [mm]
ECM
PSC
ECM 1/2 [373] 1/2 [373] 1/2 [373] 1/2 [373] 1/2 [373] 1 [746] 1 [746]
PSC 1/5 [149] 1/3 [249] 1/2 [373] 1/2 [373] 1/2 [373] 1 [746] 1 [746]
ECM
PSC
9 x 7
[229 x 178]
9 x 7
[229 x 178]
9 x 7
[229 x 178]
9 x 7
[229 x 178]
ECM Variable Speed
PSC 3 Speeds
11 x 10
[279 x 254]
10 x 10
[254 x 254]
[279 x 254]
[254 x 254]
11 x 10
10 x 10
11 x 10
[279 x 254]
10 x 10
[254 x 254]
11 x 10
[279 x 254]
11 x 10
[279 x 254]
Coax and Water Piping
Water Connections Size - Swivel - in [mm] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] HWG Connection Size - Swivel - in [mm] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] Coax & Piping Water Volume - gal [l] 0.7 [2.6] 1.0 [3.8] 1.3 [4.9] 1.3 [4.9] 1.6 [6.1] 1.6 [6.1] 2.3 [8.7]
Vertical
Air Coil Dimensions (H x W), in. [mm]
Air Coil Total Face Area, ft2 [m2] 3.9 [0.362] 3.9 [0.362] 4.9 [0.451] 5.6 [0.570] 5.6 [0.570] 6.3 [0.641] 6.3 [0.641] Air Coil Tube Size, in [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] Air Coil Number of rows 3 3 3 3 3 4 4
Filter Standard - 2" [51mm] Pleated MERV11 Throwaway, in [mm]
Weight - Operating, lb [kg] 305 [138] 320 [145] 365 [166] 380 [172] 420 [190] 455 [206] 480 [218] Weight - Packaged, lb [kg] 315 [143] 330 [150] 375 [170] 390 [177] 430 [195] 465 [211] 490 [222]
28 x 20
[711 x 542]
28 x 24
[712 x 610]
28 x 20
[711 x 542]
28 x 24
[712 x 610]
28 x 25
[711 x 635]
28 x 30
[712 x 762]
32 x 25
[813 x 635]
32 x 30
[813 x 762]
32 x 25
[813 x 635]
32 x 30
[813 x 762]
36 x 25
[914 x 635]
36 x 30
[914 x 762]
Horizontal
Air Coil Dimensions (H x W), in. [mm]
Air Coil Total Face Area, ft2 [m2] 3.9 [0.362] 3.9 [0.362] 4.9 [0.451] 5.6 [0.570] 5.6 [0.570] 6.3 [0.641] 6.3 [0.641] Air Coil Tube Size, in [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] Air Coil Number of rows 3 3 3 3 3 3 3
Filter Standard - 2" [51mm] Pleated MERV11 Throwaway, in [mm]
Weight - Operating, lb [kg] 307 [139] 322 [146] 370 [168] 385 [175] 425 [193] 460 [209] 485 [220] Weight - Packaged, lb [kg] 322 [146] 337 [153] 385 [175] 400 [181] 440 [200] 475 [215] 500 [227]
18 x 30
[457 x 762]
1 - 18 x 32
[457 x 813]
18 x 30
[457 x 762]
1 - 18 x 32 [457 x 813]
20 x 35
[508 x 889]
1 - 20 x 37
[686 x 940]
20 x 40
[508 x 1016]
1 - 20 x 20 [508 x 508] 1 - 20 x 22 [508 x 559]
20 x 40
[508 x 1016]
1 - 20 x 20 [508 x 508] 1 - 20 x 22 [508 x 559]
20 x 45
[508 x 1143]
1 - 20 x 25 [508 x 635] 1 - 20 x 22 [508 x 559]
Notes: Sizes 036, 042, 048 available with 1HP blower motor. (ICM only)
11 x 10
[279 x 254]
11 x 10
[279 x 254]
36 x 25
[914 x 635]
36 x 30
[914 x 762]
20 x 45
[508 x 1143]
1 - 20 x 25 [508 x 635] 1 - 20 x 22
[508 x 559]
4/9/07
21
ENVISION RESIDENTIAL INSTALLATION MANUAL
Physical Data (Dual Capacity)
Model
Compressor (1 each) Copeland 2-speed Scroll, UltraTech Factory Charge R410a, oz [kg] Vertical 62 [1.76] 78 [2.21] 89 [2.52] 122 [3.46] 140 [3.97] Factory Charge R410a, oz [kg] Horizontal 60 [1.70] 76 [2.16] 89 [2.52] 124 [3.52] 160 [4.54]
026 038 049 064 072
DUAL CAPACITY
ECM Fan Motor & Blower
Fan Motor Type/Speeds ECM Variable Speed Fan Motor- hp [W] 1/2 [373] 1/2 [373] 1/2 [373] 1 [746] 1 [746]
Blower Wheel Size (Dia x W), in. [mm]
9 x 7
[229 x 178]
11 x 10
[279 x 254]
11 x 10
[279 x 254]
11 x 10
[279 x 254]
11 x 10
[279 x 254]
Coax and Water Piping
Water Connections Size - Swivel - in [mm] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] HWG Connection Size - Swivel - in [mm] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] 1" [25.4] Coax & Piping Water Volume - gal [l] 0.7 [2.6] 1.3 [4.9] 1.6 [6.1] 1.6 [6.1] 2.3 [8.7]
Vertical
Air Coil Dimensions (H x W), in. [mm] Air Coil Total Face Area, ft2 [m2] 3.9 [0.362] 4.9 [0.451] 5.6 [0.570] 6.3 [0.641] 6.3 [0.641]
Air Coil Tube Size, in [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] Air Coil Number of rows 3 3344
Filter Standard - 2" [51mm] Pleated MERV11 Throwaway, in [mm]
Weight - Operating, lb [kg] 305 [138] 370 [168] 420 [190] 465 [211] 480 [218] Weight - Packaged, lb [kg] 315 [143] 380 [172] 430 [195] 475 [215] 490 [222]
28 x 20
[711 x 542]
28 x 24
[712 x 610]
28 x 25
[711 x 635]
28 x 30
[712 x 762]
32 x 25
[813 x 635]
32 x 30
[813 x 762]
36 x 25
[914 x 635]
36 x 30
[914 x 762]
36 x 25
[914 x 635]
36 x 30
[914 x 762]
Horizontal
Air Coil Dimensions (H x W), in. [mm] Air Coil Total Face Area, ft2 [m2] 3.9 [0.362] 4.9 [0.451] 5.6 [0.570] 6.3 [0.641] 6.3 [0.641]
Air Coil Tube Size, in [mm] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] 3/8 [9.5] Air Coil Number of rows 3 3344
Filter Standard - 2" [51mm] Pleated MERV11 Throwaway, in [mm]
Weight - Operating, lb [kg] 307 [139] 375 [170] 425 [193] 470 [213] 485 [220] Weight - Packaged, lb [kg] 322 [146] 390 [177] 440 [200] 485 [220] 500 [227]
18 x 30
[457 x 762]
1 - 18 x 32
[457 x 813]
20 x 35
[508 x 889]
1 - 20 x 37
[686 x 940]
20 x 40
[508 x 1016]
1 - 20 x 20
[508 x 508]
1 - 20 x 22
[508 x 559]
20 x 45
[508 x 1143]
1 - 20 x 25 [508 x 635] 1 - 20 x 22 [508 x 559]
20 x 45
[508 x 1143]
1 - 20 x 25
[508 x 635]
1 - 20 x 22 [508 x 559]
4/9/07
Notes: Sizes 038, 049 available with 1HP blower motor (ICM only).
22
ENVISION RESIDENTIAL INSTALLATION MANUAL
C
HWL
HP
Thermostat
CO
R
CY1O
L1
Y2
NOTE4
G
LP
PS
FP
W
Brn(15)
Org(14)
123
P10
4
5
Envision - SingleSpeed Wiring Schematic - 208-230/60/1
97P774-06 9/27/06
PB2
Auxiliary Electric Heat Power
208-230/60/1
With optional ' EA' Series
Auxiliary ElectricHeat
Typical schematic shown
2
3
HE1 TS1
HE2 TS2
HE3 TS3
HE4 TS4
P7
L4 L2
L2 NOTE5
Pink
Yel
Blk
Gray
Pink
Yel
Blk
Gray
Gray
Blk
Yel
Pink
Gray
Pink
Blk
Yel
Pink
Yel
Blk
Gray
Pink
Yel
Blk
Gray
Grn
F2
P9
ER1
ER2
ER3
ER4
L1
L1 L3
NO
NO
NO
NO
Org
Brn
Brn
Org
Brn
Or
5
4
Pink
Orange
White
Tan
Blue
NOTE2
Red
6
EASeries PCB
Blk/Wht(11)
Gry/Wht(10)
SL1 In
SL1Out
Optional
RemoteUnit
Without
LoopPump
Foldandmatearrows
Foldand mate arrows
Foldand mate arrows
Foldand mate arrows
L1 L2
Single Disconnect Power
208-230/60/1
AuxElect Power
208-230/60/1
L1 L2 L1 L2
Unit Power
208-230/60/1
CSAinstalled units only
Localcodes may require asingle
sourceof power supply
Breakerbox
furnishedby
installer
E-SeriesLogic Board - Physical Layout
NOTE9
1
123
P10
456
P2
1
StatusLED PCB
SW4
RRRRR
GYR
T
T
G G
432
1
P8
123
4
123
1
P4
OnOff
SW1
240V- L2
240V- L1
Fused L2
Fused L2
Fused L2
F1
F1
R
R
Microprocessor
Premier2LogicBoard
CR2- Loop
Pump
N.O.
240V- L2
240V- L1
C
C
1
2345678
9
10111213141516
P6
1234567
8
9
1011121314
P5
Fused L2
Fused L1
CR1- DHW
Pump
N.O.
CC
CC-GND
CCLO
CCHI
123
P3
234
5
678
9
101112
1
OnOff
SW2
2
3
4
5
678
1
OnOff
SW3
234
5
P1
1234567 8
2
345
P2
671
RCY1Y2 GOWL
Shut
Down
ACC
NO
ACC
NC
ACC
COM
CC
SL1
IN
SL1
Out
SL2
IN
SL2
Out
CircuitBreakers
CC
Blk(1)
Transformer
NOTE1
24V
Red
208V
Blu
240V
Blk
Blk/WhYel
Gry(9)
N.O.
CR4-
Com
N.O.
CR3-
Com
N.C.
Unit Power
208-230/60/1
G
L2 L1
CC
NOTE6
DHW
Pump
Blu
3A
Fuse
Optional
Electronic
Air-Filter
NOTE10
240V L2
240VL1
240VL 2
P6
Premier 2
Microprocessor
Logic Control
(DC Voltage)
P1
Fused L2
R
C
CC-GND
NO
CR2
COM
F1-10A240 V
Fused L2
NO
CR1
COM
Pink
1234567
8
123
P4
Pink
Black
Violet
Yellow
Black
Blue
Blue
Orange
Orange
Pink
Yellow
Yellow
Pink
Orange
White
Tan
Blue
NotUsed
123C
P2
Down
C
1234567
Shut
SL1 In
Not
SL1Out
Used
NOTE3
AccCom
AccNC
AccNO
123
P3
NotUsed
NotUsed
Brown
Gray
123
MainLogic PCB
F1-10A
240V
Tan
NotUsed
Red
6
5
487
P5
12
129
10
349
11
2
10
8
1125
3
13
14
15
16
11
GWO
R
C
Y1
Y2
LO
On
SW1
123456789
101112
ECM2
AirFlow
Settings
Black
Blue
14
13
6
7
CC
NO
NC
CR4
COM
NO
NC
CR3
COM
Blk(7)
Blu(17)
Violet(2)
RV
Ext Pump
1/2 hp Total
208-230/60/1
Pump Pump
G
2
1
PB1
1
2
Yel(8)
Comfort
Alert
R
Y
C
CCHI
NotUsed
NotUsed
Violet(3)
Blk(5)
Yel(6)
L
ComfortAlert
15
10
16
3
P12
P11
2
345
1
8
Pink(13)
FieldSelection Dips - #1 On, #6On, #7 On
Drainpan overflow Lockout
FPthermistor (loop<15 °F,well<30°F) Lockout
HighPressure > 600 PSI Lockout
Low Pressure < 40 PSI Lockout
ECM2RPM < 100 rpm Lockout
Microprocessormalf unction*
HWLthermi stor> 130°F
DHWpump switch off
Drain
WaterFlow
HighPress
LowPress / Comp
AirFlow
Status
DHWLim it
DHWoff
LED Normal Display Mode
#1Off, #6 On,#7 On
Drainpan overflow
FPthermistor (loop< 15°F,well<30° F)
HighPressure > 600 PSI
Low Pressure < 40 PSI
ECM2RPM < 100 rpm
NotUsed
HWLthermistor > 130°F
DHWpump switch off
Current Fault Status
#6Off, #7 On
Y1
Y2
OGW
SL1
SL2
--
Inputs
#6On, #7 Off
CompressorLo
CompressorHi
RV
FAN
DHWPump
LoopPump 1
LoopPump 2
--
Outputs
#6Of f,#7 Off
BlowerLo
BlowerMed
BlowerHi
AuxHeat #1
AuxHeat #2
AuxHeat #3
AuxHeat #4
--
Outputs2
Diagnostic Modes
*GreenLED not flashing
NOTE11
C
S
R
Run
Capacitor
132
Red Black
Blue
Tan
(16)
Comfort Alert
LED Flash Code Description
Green Solid Module Has Power
Red Solid Y1 Present But Compressor Not Running
Code 1 Long Run Time
Code2 System PressureTrip
Code 3 S hort Cycling
Code 4 Loc ked Rotor
Code 5 Open Circ uit
Code 6 Open S tart Circuit
Code 7 Open Run Circ uit
Code 8 W elded Contactor
Code 9 Low V oltage
Yellow
Comfort Alert Status
Notes:
1– Switch Blueand Redwires for 208V operation.
2- Connection ofremote unitthat does nothave aloop pumpfor slaveoperation .
3- 24VAccessory relay(see SW2 -3 fordescription ofoperation )
4- The blk/whand gray/wh wiresar eremoved whenAux Heat isinstalled .
6- DHW pumponly in models withhot water generationoption .
5- Buss lugsL1 and L2can be removedand dualpow erwire setsconnected directlyto boxlugs L 1,L2 ,
andL3, L4.
10- When optionalelectronic air-filter is installed, powerfor the electronicair-f ilteris provided byP2-2 and
24VAC.
8– SW3-4 shouldbe in theOFF positionwhen using the 17P501A01 electricheat board and
shouldbe ON whenusing the 17P514A01 electricheat board .
11-Comfort Alert faultoutput toPremier Control Board
9– SW2-8 mustb ein theO FFposition for pulsed“L” lockout signaland inthe ON positionfor constant
“L”lockout signal.
7– This Sw itchallows theunit todown stagewith thet -stat whenOFF andfinish on secondstagewhen
ON. Finish second stagered ucesstage changing inrecip dualcapacity compressors andshould
beON for unzonedDual CapE -Series orPremier 2 speedunits.
On
SW3
On
SW2
1
2345678
NoHtg 3/ Htg3
Dehum /Norm
Fan/ Comp
Loop/ Well
Test/ Norm
Outputs/ Norm
Inputs / Norm
2Speed / 1 Speed
Normal /Finish on 2
nd
(Note 7)
NoRPM / RPM
ElectricHeat / Normal (Note 8)
Envision /E Series or Premier
1
234
5
PulseL / Constant L (NOTE 9)
Y
L
R
C
DC
Sol
Data
Port
ComfortAl ert
PhysicalLayout
POWER
ALERT
TRIP
Brn
Wht
Grn
P13
H M L
PSC
FanMotor
Cap
Blk
Wht
Thermistor
Light emitting diode - Green
Relaycoil
Capacitorw /bleed resistor
Switch -Condensate overflow
Switch -High pressure
Switch -Low pressure
Switch-Hot Water On/Off
Polarizedconnector
FactoryLow voltage wiring
FactoryLine voltage wiring
Fieldlow voltage wiring
Fieldline voltage wiring
Optionalblock
DCVoltage PCB traces
Internaljunction
Quickconnect terminal
Wirenut
Fieldwirelug
Ground
Fuse
CC-
CO-
CR1-
CR2-
CR3-
CR4-
F1and F2 -
FP-
HE-
HP-
LP-
PB1, PB2-
PS-
RV-
SW1 -
SW2 -
SW3 -
SW4 -
TS-
CompressorContactor
Condensateoverflow sensor
DHWpump relay
Looppump relay
Fuses
Freezeprotection sensor
Heaterelement
Highpressure switch
Low pressure switch
Powerblocks
Powerstrip
ReversingValve coil
DIPpackage 12 position
DIPpackage 8 position
DIPpackage 5 position
Hotwater pump enable switch
Thermallimit switch
Legend
RelayContacts -
N.O., N.C.
G
T
132
P
L1
PSCFan Speed Relay
PSCFan Power Relay
ER1to ER4 - Aux heatstage relays
HWL-
Hotwater limit sensor
SC-
StartContactor
StartRelay
SR-
CS- Compressor Solenoid
CA-
ComfortAl ert
Wiring Schematics
Envision - Single Speed Wiring Schematic - 208-230/60/1 - PSC
23
C
HWL
HP
Thermostat
CO
R C
Y1
O
L1
Y2
NOTE 4
G
LP
PS
FP
W
Brn(15)
Org(14)
1 2 3
P10
4 5
97P774-01 6/29/06
Org
Brn
NOTE 2
6
Blk/Wht(11)
Gry/Wht(10)
SL1 In SL1 Out Optional
Remote Unit
Without
Loop Pump
StatusLED PCB
SW4
R R R R R G Y R
T
T
CC
Blk(1)
Transformer
NOTE 1
24V
Red 208V
Blu
240V
Blk
Blk/WhYel
Gry(9)
Unit Power
208-230/60/1
G
L2 L1
CC
NOTE 6
DHW Pump
Blu
3A
Fuse
Optional
Electronic
Air-Filter
NOTE 10
240V L2
240V L1
240V L2
P6
Premier 2
Microprocessor
Logic Control (DC Voltage)
P1
Fused L2
R
C
CC-GND
NO
CR2
COM
F1-10A 240V
Fused L2
NO
CR1
COM
Pink
1 2 3 4 5 6 7 8
1 2 3
P4
Pink
Black
Violet
Yellow
Black
Blue
Blue
Orange Orange
Pink Yellow Yellow
Pink
Orange
White
Tan
Blue
Not Used
1 2 3C
P2
DownC1
2 3 4 5 6 7
Shut
SL1 In
Not
SL1 Out
Used
NOTE 3
Acc Com Acc NC Acc NO
1 2 3
P3
Not Used
Not Used
Brown
Gray
123
F1-10A
240V
Tan
Not Used
Red
6
5
4
8
7
P5
12
1
2
9
10
3
4 9
11
2 10
8 1 12 5
3
13
14
15
16
11
G
W
O
R
C Y1 Y2
LO
On
SW1
1 2 3 4 5 6 7 8
9 10 11 12
On
SW2
1 2 3 4 5 6 7 8
No Htg3 / Htg3
Dehum / Norm
Fan / Comp
Loop / Well
Test / Norm
Outputs / Norm
Inputs / Norm
ECM2 Air Flow Settings
NOTE 7
Black
Blue
14
13 6 7
CC
NO
NC
CR4 COM
NO
NC
CR3 COM
Fused L1
Blk(7)
Blu(17)
Violet(2)
RV
Ext Pump
1/2 hp Total
208-230/60/1
Pump Pump
G
2
1
PB1
1
2
Yel(8)
Comfort
Alert
R
Y
C
CCHI
Not Used Not Used
Violet(3)
Blk(5)
Yel(6)
L
Comfort Alert
Pulse L / Constant L (See Note 9)
ECM2
Fan Motor
Grn
15 10163
On/Off
PWM
RPM
C2
RPMgrnd
P12
P112 3 4 51
8
Pink(13)
NOTE11
C
S
R
Run
Capacitor
1
3
2
Red Black
Blue
Tan (16)
Comfort Alert
Field Selection Dips - #1 On, #6 On, #7 On Drain pan overflow Lockout FP thermistor (loop<15°F,well<30°F) Lockout High Pressure > 600 PSI Lockout Low Pressure < 40 PSI Lockout / CA ECM2 RPM < 100 rpm Lockout Microprocessor malfunction* HWL thermistor > 130°F DHW pump switch off
Drain WaterFlow High Press Low Press/Comp Air Flow Status DHW Limit DHW off
LED Normal Display Mode
#1Off, #6 On,#7 On Drain pan overflow FP thermistor (loop<15°F, well<30°F) High Pressure > 600 PSI Low Pressure < 40 PSI / CA ECM2 RPM < 100 rpm Not Used HWL thermistor > 130°F DHW pump switch off
Current Fault Status
#6 Off, #7 On
Y1 Y2
O G W
SL1
--
--
Inputs
#6On, #7 Off Compressor Lo Compressor Hi
RV
FAN DHW Pump Loop Pump(s)
--
--
Outputs
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi Aux Heat #1 Aux Heat #2
AuxHeat #3
Aux Heat #4
--
Outputs2
Diagnostic Modes
*Green LED not flashing
LED Flash Code Description
Green Solid Module Has Power
Red Solid Compressor Overload Trip
Code 1 Long Run Time Code 2 System Pressure Trip Code 3 Short Cycling Code 4 Locked Rotor Code 5 Open Circuit Code 6 Open Start Circuit Code 7 Open Run Circuit Code 8 Welded Contactor Code 9 Low Voltage
Yellow
Comfort Alert Status
PN - 17P513-07
On
SW3
2 Speed / 1 Speed
Normal / Finish on 2
nd
(Note 12) No RPM / RPM OldEH& ECM/ Normal(Note8) Envision / E Series or Premier
1 2 3 4 5
ENVISION RESIDENTIAL INSTALLATION MANUAL
Wiring Schematics
Envision - Single Speed Wiring Schematic - 208-230/60/1 - ECM
24
ENVISION RESIDENTIAL INSTALLATION MANUAL
PB2
Auxiliary Electric Heat Power
208-230/60/1
Violet
Blu
With optional ' EA' Series Auxiliary ElectricHeat Typical schematic shown
2 3
HE1 TS1
HE2 TS2
HE3 TS3
HE4 TS4
P7
L4 L2
L2 NOTE 5
Pink
Yel Blk
Gray
Pink
Yel
Blk
Gray
Gray
Blk Yel
Pink
Gray
Pink
Blk
Yel
Pink
Yel
Blk
Gray
Pink Yel Blk Gray
Grn
F2
P9
ER1
ER2
ER3
ER4
L1
L1 L3
NO
NO
NO
NO
Brn
Org
Brn Or
5 4
Pink
Orange
White
Tan
Blue
Violet
Blue
Yellow
Black
Gray
Red
EA Series PCB
E-Series Logic Board - Physical Layout
1
123
P10
456
P2
1
G G
4 3 2 1
P8
1 2 3 4
123
1
P4
OnOff
SW1
240V- L2
240V- L1
Fused L2
Fused L2
Fused L2
F1
F1
R R
Microprocessor
E-SeriesLogic Board
CR2- Loop Pump
N.O.
240V- L2
240V- L1
C C
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16
P6
1 2 3 4 5 6 7
8
9 10 11 12 13 14
P5
Fused L2
Fused L1
CR1- DHW
Pump
N.O.
CC
CC-GND
CCLO CCHI
123
P3
2 3 4 5 6 7 8
9 10 11 12
1
OnOff
SW2
2 3 4 5 6 7 8
1
OnOff
SW3
2 3 4 5
P1
1234567 8
2
345P2671
RCY1Y2 GOWL
Shut
Down
ACCNOACC
NC
ACC COM
CC
SL1INSL1
Out
SL2INSL2
Out
L1 L2
Single Disconnect Power
208-230/60/1
Aux Elect Power
208-230/60/1
L1 L2 L1 L2
Unit Power
208-230/60/1
CSA installed units only
Local codes may require a single
source of power supply
Breaker box furnished by
installer
Circuit Breakers
N.O.
CR4-
Com
N.O.
CR3-
Com
N.C.
ECM2
Fan Motor
Grn
15 10163
On/Off
PWM
RPM
C2
RPMgrnd
P12
P112 3 4 51
8
1. Switch Blue and Red wires for 208V operation.
2. Connection of remote unitthat does not have a loop pump for slave operation.
3. 24V Accessory relay (see SW2 -3 for description of operation).
4. The blk/wh and gray/wh wires are removed when Aux Heat is installed.
5. Buss lugs L1 and L2 canbe removedand dual power wire sets connecteddirectly to boxlugs L1, L2, andL3, L4.
6. DHW pump only in models with hot water generation option.
7. Air Flow Configuration Example: SW1 configured for dip 1 as low, dip 3 as medium, and dip5 as high speed ECM2 fan.
8. SW3-4 should be in the OFF position when using ECM motor and 17P501A01 electric heat board and should be ON when
using ECM2 with 17P514A01 electric heat board.
9. SW2-8 must be in the OFF position for pulsed “L” lockout signal and in the ON position for constant “L” lockoutsignal.
10. When optional electroni c air-filter is installed, power for the electronic air-filter is provided by P2-2and 24 VAC.
11. Comfort Alert fault output to Premier Control Board.
12. This switch allows the unit to down stage with the t-stat when off and finish with second stage when on. Finish on second stage reduces stage changing in recip dual capacity compressors and should be ON for unzoned Dual Cap E Series or Premier 2 Speed.
NOTES
Thermistor Light emitting diode - Green Relay coil Capacitor w/ bleed resistor Switch - Condensate overflow Switch - High pressure Switch - Low pressure
Switch -Hot WaterOn/Off Polarized connector
Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Fieldlinevoltagewiring Optional block DC Voltage PCB traces Internal junction Quick connect terminal
Wire nut Field wire lug Ground
Fuse
CC ­CO ­CR1 ­CR2­CR3 ­CR4 ­F1 and F2 ­FP ­HE ­HP -
LP ­PB1, PB2 ­PS ­RV ­SW1 ­SW2 ­SW3 ­SW4 ­TS -
Compressor Contactor Condensate overflow sensor DHW pump relay
Loop pump relay
Fuses Freeze protection sensor Heater element High pressure switch
Low pressure switch Power blocks Power strip Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Thermal limit switch
Legend
Relay Contacts­N.O., N.C.
G
T
132
P
L1
PSC Fan Speed Relay PSC Fan Power Relay
ER1 to ER4 - Aux heat stage relays
HWL -
Hot water limit sensor
SC -
Start Contactor Start Relay
SR -
CS - Compressor Solenoid
CA -
Comfort Alert
97P774-01 6/29/06
Y
L
R C
DC Sol
Data Port
Comfort Alert PhysicalLayout
POWER
ALERT
TRIP
25
ENVISION RESIDENTIAL INSTALLATION MANUAL
Wiring Schematics
Envision - Dual Capacity Wiring Schematic - 208-230/60/1- ECM
S
C
R
Comfort
Alert
CC
Thermostat
R
C Y1 Y2
W
O
G
L1
NOTE 2
C
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
NOTE 10
Optional Electronic
Air-Filter
Ext Pump
1/2 hp Total
208-230/60/1
Pump Pump
R C
Y2
Y
Violet(3)
Violet(2)
Blk(1)
G
Yel(6)
Blk(5)
Wht(4)
Shut
DownC1
SL1 In
SL1 Out
Used
NOTE 3
Acc Com Acc NC Acc NO
123
StatusLED PCB
SW4
CCHI
CC-GND
P1
R
C Y1 Y2
W O G
LO
P2
Not
P3
Fuse
CR1
CC
R R R R R G Y R
PB1
2
2
1
1
Blu
DHW
Pump
3A
Pink
Pink(13)
Blu(17)
NO
COM
1 2 3 4 5 6 7 8
1
1 2
2
2 3
3C
3 4 5 6 7
1 2 3
P4
NOTE 6
Fused L2
CR2
ECM2 Air Flow Settings
NOTE 7 SW1
Gry(9)
Yel(8)
NO
COM
SW2
On
1 2 3 4 5 6 7 8
9 10 11 12
LED Normal Display Mode
Drain WaterFlow High Press Low Press/Comp Air Flow Status DHW Limit DHW off
*Green LED not flashing
Field Selection Dips - #1 On, #6 On, #7 On Drain pan overflow Lockout FP thermistor (loop<15°F,well<30°F) Lockout High Pressure > 600 PSI Lockout Low Pressure < 40 PSI Lockout / CA ECM2 RPM < 100 rpm Lockout Microprocessor malfunction* HWL thermistor > 130°F DHW pump switch off
Fused L2
On
NO
CR3
1
Test / Norm Loop / Well
2 3
Fan / Comp
4
Dehum / Norm
5
No Htg3 / Htg3
6
Inputs / Norm
7
Outputs / Norm
8
Pulse L / Constant L (See Note 9)
PN - 17P513-07
Unit Power
208-230/60/1
G
240V L2
NC
NO
COM
Premier 2
Microprocessor
Logic Control
(DC Voltage)
SW3
On
1 2 3 4 5
Blue
Run
Capacitor
NC
CR4 COM
Blk(7)
2 Speed / 1 Speed
nd
Normal / Finish on 2 No RPM / RPM OldEH& ECM/ Normal(Note8) Envision / E Series or Premier
Current Fault Status
#1Off, #6 On,#7 On Drain pan overflow FP thermistor (loop<15°F, well<30°F) High Pressure > 600 PSI Low Pressure < 40 PSI / CA ECM2 RPM < 100 rpm Not Used HWL thermistor > 130°F DHW pump switch off
Comfort Alert
Tan (16)
240V L2
F1-10A 240V
(Note 12)
Red Black
L2 L1
Org(14)
Fused L1
CC
Gry/Wht(10)
Brn(15)
240V L1
F1-10A
8 13 7 4 5 14 12 6 15 10 9 2 1 3 11 16
P5 11 4 9
2 10 3
8 1 12 5 13 6 7 14
Diagnostic Modes
DC SOL
+
-
Blk/Wht(11)
240V
R
C
P6
Inputs
#6 Off, #7 On
Y1 Y2
O G W
SL1
--
--
CS
NOTE 4
NOTE 1
Not Used
Black
Violet
Yellow
Blue Gray
Brown Not Used Not Used
Orange
Blue Pink
White
Tan Red
Not Used
NOTE 11
L
Tan
Orange
Orange
Not Used
Not Used
Pink
Pink Yellow Yellow
Blue
Blue
Black Black
Outputs
#6On, #7 Off
Compressor Lo Compressor Hi
DHW Pump Loop Pump(s)
FAN
RV
Comfort Alert
--
--
2
1
3
PS
Blk
RV
T
T
Outputs2
#6 Off, #7 Off
Blower Lo
Blower Med
Blower Hi Aux Heat #1 Aux Heat #2
AuxHeat #3
Aux Heat #4
--
Brn
Org
Red
Blu
208V
240V
Transformer
24V
Blk/WhYel
CO
HWL
FP
LP
HP
LED Flash Code Description
Green Solid Module Has Power
Red Solid Compressor Overload Trip
Code 1 Long Run Time Code 2 System Pressure Trip Code 3 Short Cycling Code 4 Locked Rotor
Yellow
Code 5 Open Circuit Code 6 Open Start Circuit Code 7 Open Run Circuit Code 8 Welded Contactor Code 9 Low Voltage
Grn
Comfort Alert Status
ECM2
Fan Motor
C2
On/Off
RPM
15 10163
97P774-02 6/29/06
P112 3 4 51
PWM
RPMgrnd
P12
8
P10
1 2 3 4 5 6
26
ENVISION RESIDENTIAL INSTALLATION MANUAL
With optional ' EA' Series Auxiliary ElectricHeat Typical schematic shown
Yellow
Black
Violet
Blue Gray
Orange
White
Brn
Org
Grn
Blue Pink
Tan Red
C2
ECM2
Fan Motor
On/Off
15 10163
Blu
Violet
P112 3 4 51
PWM
RPM
RPMgrnd
P12
8
Legend
240V- L1
Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Internal junction Quick connect terminal
Wire nut Field wire lug
L1
Ground Relay Contacts-
N.O., N.C. Fuse
Comfort Alert
CA ­CC -
Compressor Contactor
CO -
Condensate overflow sensor
CR1 -
DHW pump relay Loop pump relay
CR2-
PSC Fan Speed Relay
CR3 -
PSC Fan Power Relay
CR4 ­F1 and F2 -
Fuses
FP -
Freeze protection sensor
HE -
Heater element
HP -
High pressure switch ER1 to ER4 - Aux heat stage relays CS - Compressor Solenoid
NOTES
1. Switch Blue and Red wires for 208V operation.
2. Connection of remote unit that does not have a loop pump for slave operation.
3. 24V Accessory relay (see SW2 -3 for description of operation).
4. The blk/wh and gray/wh wires are removed when Aux Heat is installed.
5. Buss lugs L1 and L2 can be removed and dual power wire sets connected directly to box lugs L1, L2,and L3, L4.
6. DHW pump only in modelswith hot water generation option.
7. Air Flow Configuration Example: SW1 configured for dip 1 as low, dip 3 as medium, and dip 5 as high speed ECM2 fan.
8. SW3-4 should be in the OFF position when usingECM motor and 17P501A01 electric heat board and should beON when
using ECM2 with 17P514A01 electric heat board.
P
T
G
LP ­PB1, PB2 ­PS ­RV ­SW1 ­SW2 ­SW3 ­SW4 ­TS ­HWL ­SC ­SR -
132
Thermistor Light emitting diode - Green Relay coil Capacitor w/ bleed resistor Switch - Condensate overflow Switch - High pressure Switch - Low pressure
Switch -Hot Water On/Off Polarized connector
Low pressure switch Power blocks Power strip Reversing Valve coil DIP package 12 position DIP package 8 position DIP package 5 position Hot water pump enable switch Thermal limit switch
Hot water limit sensor
Start Contactor
Start Relay
240V- L1
N.O.
CR1- DHW
Pump
CC-GND
CC
CCLO CCHI
C C R R
P4
1234567 8
123
RCY1Y2 GOWL
E-Series Logic Board - Physical Layout
F1
N.O.
CR2- Loop
Pump
SW1
OnOff
1 2 3 4 5 6 7 8
9 10 11 12
P1
Auxiliary Electric Heat Power
208-230/60/1
L2 NOTE 5
L1
L4 L2
Brn
Blk
456
Fused L2
1 2 3 4 5
SL2INSL2
L1 L3
F2
Or
PB2
ER1
Gray
NO
ER2
NO
ER3
ER4
1
EA Series PCB
240V- L2
F1
N.O.
Com
CR4-
9
1
10
2
11
3
12
4
13
5
14
6
15
7
16
8
8
1
9
2
10
3
11
4
12
5
13
6
14
7
P3
123
ACCNOACC
ACC COM
NC
Out
NO
NO
240V- L2
P8
Pink
4
Yel
3
Blk
2
Gray
1
Gray
P7
Blk
1 2 3
Yel
4
Pink
Comfort Alert Physical Layout
P6
P5
POWER
ALERT
Gray
Pink
Data Port
DC Sol
TRIP
Pink
Yel Blk
Gray
Blk Yel
Y2 Y
L
R C
Gray
HE1 TS1
Blk
HE2 TS2
Yel
HE3 TS3
Pink
HE4 TS4
Local codes may require a single
Single Disconnect Power
Breaker box furnished by
installer
L1 L2 L1 L2
Aux Elect Power
208-230/60/1
CSA installed units only
source of power supply
208-230/60/1
L1 L2
Circuit Breakers
208-230/60/1
Unit Power
G G
P9
1 2
Grn
3 5 4
Pink
Yel
P2
123
P10
Fused L1
Fused L2
Fused L2
Fused L2
N.C. N.O.
Com
CR3-
E-SeriesLogic Board
Microprocessor
SW2
SW3
OnOff
OnOff
1 2 3 4 5 6 7 8
2
345P2671
Shut
SL1INSL1
CC
Down
10. When optional electronic air-filter is installed, power for the electronic air-filter is providedby P2-2 and 24 VAC.
11. Comfort Alert fault output to Premier Control Board.
12. This switch allows the unit to down stage with the t-stat when off and finish with second stage when on. Finish on second stage reduces stage changing in recip dual capacity compressors and should be ON for unzoned Dual Cap E Series or Premier 2 Speed.
Out
9. SW2-8 must be in the OFF positionfor pulsed “L” lockoutsignalandin the ON positionforconstant“L” lockoutsignal.
97P774-02 6/29/06
27
ENVISION RESIDENTIAL INSTALLATION MANUAL
Microprocessor Control
Startup
The unit will not operate until all the inputs and safety controls are checked for normal conditions. At fi rst power-up, a four-minute delay is employed before the compressor is energized.
Component Sequencing Delays
Components are sequenced and delayed for optimum space conditioning performance.
Accessory Relay
An accessory relay on the control board allows for fi eld connection of solenoid valves, electronic air cleaners, etc. The accessory relay has a normally open output and a normally closed output.
Short Cycle Protection
The control employs a minimum "off" time of four minutes to provide for short cycle protection of the compressor.
Condensate Overfl ow Protection
The Envision control board incorporates an impedance sensing liquid sensor at the top of the drain pan. Upon a continuous 30-second sensing of the condensate, compressor operation is suspended (see Fault Retry), and the condensate overfl ow lockout LED begins fl ashing.
Shutdown Mode
A 24VAC common signal to the “shutdown” input on the control board puts the unit into shutdown mode. Compressor, hot water pump and fan operation are suspended.
Safety Controls
The Envision control receives separate signals for a high pressure switch for safety, a low pressure switch to prevent loss of charge damage, and a low suction temperature thermistor for freeze sensing. Upon a continuous 30-second measurement of the fault (immediate for high pressure), compressor operation is suspended, the appropriate lockout LED begins fl ashing. (Refer to the "Fault Retry" section below.)
Testing
The Envision control allows service personnel to shorten most timing delays for faster diagnostics. (Refer to the Field Selection DIP switch SW2-1 on page 24.)
Fault Retry
All faults (except for low RPM faults with the ECM2 fan motor) are retried twice before fi nally locking the unit out. An output signal is made available for a fault LED at the thermostat. The “fault retry” feature is designed to prevent nuisance service calls.
Diagnostics
The Envision control board allows all inputs and outputs to be displayed on the LEDs for fast and simple control board diagnosis. (Refer to the Field Selection DIP Switch SW2-1 on page 24.)
Resistance Heat Control (208-230 Units)
The electric heat control module contains the appropriate high-voltage control relays. Control signals energize the relays in the proper sequence, and the LED display board indicates which stages are energized.
Hot Water High Limit (Domestic Hot Water Option)
This mode occurs when the hot water input temperature is at or above 130°F for 30 continuous seconds. The DHW limit status LED on the unit illuminates and the hot water pump de-energizes. Hot water pump operations resume on the next compressor cycle or after 15 minutes of continuous compressor operation during the current thermostat demand cycle.
Hot Water Justifi ca tion
Since compressor hot gas temperature is dependant on loop temperature in cooling mode, loop temperatures may be too low to allow proper heating of water. The control will monitor water and refrigerant temperatures to determine if conditions are satisfactory for heating water. The DHW limit status LED on the unit illuminates when conditions are not favorable for heating water.
Heating Operation
Heat, 1st Stage (Y1)
The fan motor is started on low speed immediately (PSC ON), the loop pump is energized 5 seconds after the “Y1” input is received, and the compressor is energized on low capacity 10 seconds after the “Y1” input. The fan is switched to medium speed 15 seconds after “Y1” input (ECM only). The hot water pump is cycled 30 seconds after the "Y1" input.
Heat, 2nd Stage (Y1,Y2) Single-Speed Units
The hot water pump is de-energized, which directs all heat to satisfying the thermostat, and the fan changes to high speed 15 seconds after the "Y2" input (ECM only).
eat, 2nd Stage (Y1,Y2) Dual Capacity Units
H
The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum fi rst stage compressor run time of 1 minute has expired. The ECM blower changes from medium to high speed 15 seconds after the “Y2” input.
The Comfort Alert will delay the second stage compressor until 5 seconds after it receives a “Y2” from the board.
Heat, 3rd Stage (Y1,Y2,W) Single-Speed Units
The fi rst stage of resistance heat is energized 10 seconds after “W” input, and with continuous 3rd stage demand, the additional stages of resistance heat engage sequentially every 5 minutes.
28
ENVISION RESIDENTIAL INSTALLATION MANUAL
Microprocessor Control (cont.)
Heat, 3rd Stage (Y1,Y2,W) Dual Capacity Units
The hot water pump is de-energized which directs all heat to satisfy the thermostat. The 1st stage of resistance heat is energized 10 seconds after “W” input, and with continuous 3rd stage demand, the additional stages of resistance heat engage sequentially every 5 minutes.
Emergency Heat (W only)
The fan is started on high speed, and the fi rst stage of resistance heat is energized 10 seconds after the "W" input. Continuing demand will engage the additional stages of resistance heat sequentially every 2 minutes.
Cooling Operation
In all cooling operations, the reversing valve directly tracks the “O” input. Thus, anytime the “O” input is present, the reversing valve will be energized.
Cool, 1st Stage (Y1,O)
The blower motor and hot water pump are started immediately, the loop pump(s) is energized 5 seconds after the “Y1” input is received. The compressor will be energized (on low capacity for Dual Capacity units) 10 seconds after the “Y1” input. The ECM blower will shift from low to medium speed 15 seconds after the “Y1” input (85% of medium speed if in dehumidifi cation mode).
Cool, 2nd Stage (Y1, Y2, O) Single Speed Units
The fan changes to high speed (85% of high speed if in dehumidifi cation mode) 15 seconds after the “Y2” input (ECM only).
Cool, 2nd Stage (Y1, Y2, O) Dual Capacity Units
The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum fi rst stage compressor run time of 1 minute has expired. The ECM blower changes to high speed 15 seconds after the “Y2” input (85% of high speed if in dehumidifi cation mode). The Comfort Alert will delay the second stage compressor until 5 seconds after it receives a “Y2” from the board.
Lockout Conditions
During lockout mode, the appropriate unit and thermostat lockout LEDs will illuminate. The compressor, loop pump, hot water pump, and accessory outputs are de-energized. Unless the lockout is caused by an ECM2 low RPM fault, the fan will continue to run on low speed. If the thermostat calls for heating, emergency heat operation will occur. Comfort Alert lockouts cannot be reset at the thermostat. All other lockout modes can be reset at the thermostat after turning the unit off, then on, which restores normal operation but keeps the unit lockout LED illuminated. Interruption of power to the unit will reset a lockout without a waiting period and clear all lockout LEDs.
High Pressure
This lockout mode occurs when the normally closed safety switch is opened momentarily (set at 600 PSI).
Low Pressure This lockout mode occurs when the normally closed low
pressure switch is opened for 30 continuous seconds (set at 40 PSI). A low pressure fault may also be indicated when a Comfort Alert lockout has occurred.
Freeze Sensing (Water Flow)
This lockout mode occurs when the freeze thermistor temperature is at or below the selected freeze sensing point (well 30°F or loop 15°F) for 30 continuous seconds.
Condensate Overfl ow This lockout mode occurs when the condensate over ow
level has been reached for 30 continuous seconds.
Fan RPM The control board monitors fan RPM to sense operation.
This lockout mode occurs if the fan RPM falls below the low RPM limit (100 RPM) for 30 continuous seconds (ICM only).
Fan (G only)
The fan starts on low speed (PSC ON). Regardless of fan input “G” from thermostat, the fan will remain on low speed for 30 seconds at the end of each heating, cooling or emergency heat cycle.
A DIP switch on the Envision control allows fi eld selection of 15% reduced fan speeds for cooling in the dehumidifi cation mode or medium and high fan speeds for cooling in the normal mode.
Note: Fan speed can change automatically only with an ECM Motor.
ECM2 Airfl ow Selection DIP Switches (SW1)
A 12-position DIP switch package on the Envision control allows the airfl ow levels to be set for low, medium and high speed. (Refer to the ECM Blower Table on page 15.)
Only three of the DIP switches can be in the “on” position. The fi rst “on” switch (the lowest position number) determines the “low speed fan” setting. The second “on” switch determines the “medium speed fan” setting, and the third “on” switch determines the “high speed fan” setting, (see page 15).
29
ENVISION RESIDENTIAL INSTALLATION MANUAL
Microprocessor Control (cont.)
Compressor Monitoring/Comfort Alert
The comfort Alert displays abnormal compressor conditions through a unique fl ash code and communicates the conditions to the heat pump microprocessor control. The heat pump microprocessor will determine which fault to act on and ignore. Fault codes 2 (sys­tem pressure), 4 (locked rotor), 6 (open start circuit), and 7 (open run circuit) will result in a lockout. All other fault codes are passive. All compressor alerts are displayed on the module by fl ashing the yellow Alert LED a specifi c number of times consecutively followed by a pause, and then repeated. The number of consecutive fl ashes or “Flash Code” correlates to a specifi c abnormal condition. The red “TRIP” LED means there is a thermostat demand signal “Y” present but the compressor is not running. The green “POWER” LED means the module has power.
Green "POWER" LED - module has power Red "TRIP" LED - Thermostat "Y" demand signal is present, but the compressor is not running.
Comfort Alert Flash Codes
Yellow "ALERT" LED LED Description Cause
Flash Code 1 Long Run Time Eighteen consecutive hours of compressor run time Flash Code 2 System Pressure Trip Not applicable Flash Code 3 Short Cycling Compressor run time of less than 3 minutes on 4 consecutive cycles Flash Code 4 Locked Rotor Four consecutive compressor protector trips indicating compressor won't start Flash Code 5 Open Circuit "Y" thermostat demand signal with no compressor current Flash Code 6 Open Start Circuit "Y" thermostat demand signal with no current in the start circuit Flash Code 7 Open Run Circuit "Y" thermostat demand signal with no current in the run circuit Flash Code 8 Welded Contactor Current detected with no "Y" thermostat demand signal present Flash Code 9 Low Voltage Less than 17 VAC detected in control circuit
* Flash code number corresponds to a number of LED flashes, followed by a pause and then repeated. * TRIP and ALERT LEDs flashing at the same time indicates control circuit voltage is too low for operation. * Reset ALERT flash code by removing 24 VAC power from module. * Last ALERT flash code is displayed for 1 minute after module is powered on.
Resetting Comfort Alert Codes
Alert codes can be reset manually by cycling power off and on to the Comfort Alert module. Alert codes will reset automatically if conditions return to normal.
Flash Code Number LED Description Automatic Reset of Alert Codes
Flash Code 1 Long Run Time Thirty "alert free" on and off cycles to reset automatically Flash Code 2 System Pressure Trip Not applicable Flash Code 3 Short Cycling Four "alert free" on and off cycles to reset automatically Flash Code 4 Locked Rotor Four "alert free" on and off cycles to reset automatically Flash Code 5 Open Circuit One "alert free" on and off cycles to reset automatically Flash Code 6 Open Start Circuit One "alert free" on and off cycles to reset automatically Flash Code 7 Open Run Circuit One "alert free" on and off cycles to reset automatically Flash Code 8 Welded Contactor One "alert free" on and off cycles to reset automatically Flash Code 9 Low Voltage Resets when voltage rises above 19 VAC
* Reset ALERT flash code by removing 24 VAC power from module.
30
ENVISION RESIDENTIAL INSTALLATION MANUAL
Microprocessor Control (cont.)
Thermostat Displays
Fault Flash
When using a TA32W01 or TP32W02 thermostat and SW2-8 is in the pulsing “L” position, FaultFlash will enable a user to view the
thermostat and count the fault indicator fl ashes to determine the lockout condition the unit is experiencing.
ComforT alk
When using a TP32U03, 04 or 05 thermostat and SW2-8 is in the pulsing “L” position, ComforTalk will enable the user to view the
thermostat and determine the fault. The thermostat can be confi gured to show either lockout text or lockout codes.
The LED board on the front of the unit will display all lockouts. The Low Pressure LED will fl ash for a low pressure condition or a Comfort Alert fault. If the low pressure lockout was caused by Comfort Alert codes 4, 6 or 7, then the Comfort Alert will be fl ashing. If no Comfort Alert code is visible, then it is a low pressure lockout.
The following tables show the codes that will be displayed on the different ComforTalk and FaultFlash thermostats.
FaultFlash Thermostats ComforTalk Thermostats
TA32W01 and TP32W02 Thermostats TP32U03, TP32U04 and TP32U05 Thermostats
Thermostat Display
Lockout Code
2 Flashes High Pressure Fault "High Pressure" or "E2" High Pressure Fault 3 Flashes Low Pressure Fault "Low Pressure" or "E3" Low Pressure Fault 4 Flashes Not Applicable "E4" Not Applicable 5 Flashes Water Flow Fault "Water Flow" or "E5" Water Flow Fault 6 Flashes Not Applicable "E6" Not Applicable 7 Flashes Condensate Fault "Condensate" or "E7" Condensate Fault 8 Flashes Voltage out of Range "Voltage Range" or "E8" Voltage out of Range 9 Flashes RPM Fault "RPM" or "E9" RPM Fault
10 Flashes
Lockout code 10 - see Comfort Alert module to determine the specific flash code for compressor abnormalities.
Lockout Description Lockout Description
Comfort Alert Compressor Module Fault
Thermostat Display
Lockout Code
"Comfort Alert" or "E10"
These thermostats can be configured to display the lockout condition "text" or error number. * A slow flash of 1 second on and off means the heat pump microprocessor SW2-1 is configured for "Test Mode" or thermostat is miswired.
Lockout code 10 - see Comfort Alert module to determine the specific flash code for compressor abnormalities.
Comfort Alert Compressor Module Fault
31
ENVISION RESIDENTIAL INSTALLATION MANUAL
Microprocessor Control (cont.)
DIP Switch Settings
Prior to powering unit, ensure that all DIP switches on SW2 & SW3 are set properly according to the tables below.
FACTORY SETUP DIP SWITCHES (SW3)
DIP
SWITCH
NUMBER
SW 3- 1
SW 3- 2
Dual Capacity/Single-Speed
Confi gures the control for single-speed compressor operation or dual capacity opera- tion.
Zoned/Finish on Second Stage
This switch allows the unit to down stage with the thermostat when off and fi nish with second stage when on. Finish on second stage reduces stage changing in recipro­cating dual capacity compressors.
DESCRIPTION OFF POSITION ON POSITION
Dual Capacity Opera­tion
Normal - All Other Systems
Single-Speed Operation
Finish on 2nd - Unzoned Dual Capacity E Series or Premier 2 Speed
]
NEW
SW 3- 3
SW 3- 4
SW 3- 5
DIP
SWITCH
NUMBER
SW 2- 1
SW 2- 2
SW 2- 3
No RPM/RPM
Confi gures the control to monitor the RPM output of an ECM/ECM2 blower motor. When using IntelliZone or a PSC fan motor, the control should be confi gured for “NO RPM” sensing.
Electric heat and ECM2
Allows backward compatibility with older Premier Series. In the Off position this switch allows older electric heat board (17P501A01) and older ECM (square end) compatibility. On is for all newer EH board (17P514A01) and ECM2 (round end).
On dual capacity units this switch allows stage change: on the fl y when off, and 1 minute delay when on. A delay is required on all reciprocating dual capacity units.
FIELD SELECTION DIP SWITCHES (SW2)
DESCRIPTION OFF POSITION ON POSITION
Service Test Mode
On the control, allows fi eld selection of “NORMAL” or “TEST” operational modes. Test mode accelerates most timing functions 16 times to allow faster troubleshooting. Test mode also allows viewing the “CURRENT” status of the fault inputs on the LED display.
Freeze Sensing Setting
Allows fi eld selection of freeze thermistor fault sensing temperatures for well water (30°F) or antifreeze-protected (15°F) earth loops.
Accessory Relay
Allows fi eld selection of the accessory relay to operate with the compressor or fan.
PSC Fan/RPM Moni­toring Disabled
Old EH & Old ECM Normal
Envision E-Series or Premier
Test Mode Normal Speed Operation
Loop Water Freeze Protection 15° F
Acc Relay Tracks Fan
ECM-ECM2 Fan/RPM Monitoring Enabled
Well Water Freeze Protec­tion 30° F
Acc Relay Tracks Compres­sor
SW 2- 4
SW 2- 5
SW 2- 6
SW 2- 7
SW 2- 8
Fan Speed Control
Allows fi eld selection of reduced fan speed (85% of selected medium and high speed – ECM only) for cooling in the dehumidifi cation mode.
Auxiliary Off
Disables 3rd-stage Heating. Full emergency heat would still be available if needed.
Diagnostics Inputs
Allows viewing the inputs from the thermostat to the control board such as Y1, Y2, O, G, W, SL1-In on the LED display.
Diagnostics Outputs
Allows viewing the outputs from the control board such as compressor, reversing valve, blower, hot water pump, and loop pump on the LED display.
Thermostat Selection
Confi gures the control for a pulsed lockout signal (ComforTalk and FaultFlash ther- mostats) or continuous 5 VAC lockout signal.
32
Dehumidifi cation Fan Speeds
Disable Heating Stage 3
Diagnostic Inputs Viewed at LEDs
Diagnostic Outputs Viewed at LEDs
Pulsed “L” signal Continuous “L” signal
Normal Fan Speeds
Enable Heating Stage 3
Normal Display Viewed at LEDs
Normal Display Viewed at LEDs
]
NEW
ENVISION RESIDENTIAL INSTALLATION MANUAL
Unit Startup
Before Powering Unit, Check The Following:
Note: Remove and discard the two compressor hold down shipping bolts located at the front and rear of the compressor mounting bracket. The bolts can then be discarded.
High voltage is correct and matches nameplate.
Fuses, breakers and wire size correct.
Low voltage wiring complete.
Piping completed and water system cleaned and fl ushed.
Air is purged from closed loop system.
Isolation valves are open, water control valves or loop pumps wired.
Condensate line open and correctly pitched.
Transformer switched to 208V if applicable.
Black/white and gray/white wires in unit control box have been removed if auxiliary heat has been installed.
Dip switches are set correctly.
DHW pump switch is “OFF” unless piping is completed and air has been purged.
Blower rotates freely – foam shipping support has been removed.
Blower speed correct (dip switch is set correctly).
Air fi lter/cleaner is clean and in position.
Service/access panels are in place.
Return air temperature is between 50-80ºF heating and 60-95ºF cooling.
Check air coil cleanliness to insure optimum performance. Clean as needed according to maintenance guidelines.
To obtain maximum performance the air coil should be cleaned before startup. A 10-percent solution of dishwasher detergent and water is recommended for both sides of coil, a thorough water rinse should follow.
Startup Steps
Note: Complete the Equipment Start-Up/Commissioning Check Sheet during this procedure. Refer to thermostat operating instructions and complete the startup procedure.
1. Initiate a control signal to energize the blower motor. Check blower operation.
2. Initiate a control signal to place the unit in the cooling mode. Cooling setpoint must be set below room temperature.
3. First stage cooling will energize after a time delay.
4. Be sure that the compressor and water control valve or loop pump(s) are activated.
5. Verify that the water fl ow rate is correct by measuring the pressure drop through the heat exchanger using the P/T plugs and comparing to unit capacity data in specifi cation cata lo g .
6. Check the temperature of both the supply and discharge water (see pages 35-36).
7. Check for an air temperature drop of 15°F to 25°F across the air coil, depending on the fan speed and entering water temperature.
8. Decrease the cooling set point several degrees and verify high-speed blower operation.
9. Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or loop pumps deactivate.
10. Initiate a control signal to place the unit in the heating mode. Heating set point must be set above room temperature.
11. First stage heating will energize after a time delay.
12. Check the temperature of both the supply and discharge water (see pages 35-36).
13. Check for an air temperature rise of 20°F to 35°F across the air coil, depending on the fan speed and entering water temperature.
14. If auxiliary electric heaters are installed, increase the heating setpoint until the electric heat banks are sequenced on. All stages of the auxiliary heater should be sequenced on when the thermostat is in the Emergency Heat mode. Check amperage of each element.
15. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pumps deactivate.
16. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required.
17. Set system to desired normal operating mode and set temperature to maintain desired comfort level.
18. Instruct the owner/operator in the proper operation of the thermostat and system maintenance.
Note: Be certain to ll out and forward all warranty registration papers.
33
ENVISION RESIDENTIAL INSTALLATION MANUAL
Operation Logic Data
OPERATION LOGIC
SINGLE SPEED UNITS
Compressor ECM2 Normal ECM2 Dehumidify PSC Rev Valve Loop Pump DHW Pump Aux Heater Secondary 1- Out Emerg LED T-Stat Signal
DUAL CAPACITY UNITS
Compressor-Lo Compressor-Hi ECM2 Normal ECM2 Dehumidify Rev Valve Loop Pumps DHW Pump Aux Heater Secondary 1- Out Secondary 2- Out Emerg LED T-Stat Signal
HEATING COOLING
STG1 STG2 STG3 EMERG STG1 STG2
On On On Off On On - ­Med High High High Med High Low ­Med High High High 85% Med 85% High Low -
On On On On On On On -
Off Off Off Off On On - -
On On On Off On On - On
On Off Off Off On On - -
Off Off Staged Staged Off Off - -
On On On Off On On - -
Off Off Off On Off Off Off -
Y1 Y1, Y2 Y1, Y2, W W Y1, O Y1, Y2, O G -
On Off Off Off On Off - -
Off On On Off Off On - ­Med High High High Med High Low ­Med High High High 85% Med 85% High Low -
Off Off Off Off On On - -
On On On Off On On - On
On On Off Off On On - -
Off Off Staged Staged Off Off - -
On On On Off On On - -
Off On On Off Off On - -
Off Off Off On Off Off - -
Y1 Y1, Y2 Y1, Y2, W W Y1, O Y1, Y2, O G -
FAN ON SL1 - IN ON
34
Unit Operating Parameters
Single Speed Models
ENVISION RESIDENTIAL INSTALLATION MANUAL
Entering Water
Temp °F
50
70
90
Entering Water
Temp °F
30
50
70
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB. Heating performance based on entering air temperature of 70º F DB.
Water Flow
GPM/Ton
1.5 133 - 148 205 - 225 17 - 26 10 - 14 18 - 22 18 - 22
3.0 129 - 144 185 - 205 20 - 29 7 - 11 8 - 10 18 - 22
1.5 139 - 154 280 - 300 8 - 11 8 -12 18 - 22 18 - 22
3.0 137 - 152 250 - 270 9 - 12 7 - 11 8 - 10 18 - 22
1.5 143 - 158 360 - 380 8 - 11 9 - 13 18 - 22 16 - 20
3.0 141 - 156 330 - 350 9 - 12 8 - 12 8 - 10 16 - 20
Water Flow
GPM/Ton
1.5 73 - 79 279 - 304 7 - 13 2 - 6 11 - 15 4 - 8 7 -10 18 - 24
3.0 79 - 85 285 - 310 8 - 14 2 - 6 11 - 15 4 - 8 3 - 6 20 - 26
1.5 103 - 109 308 - 333 8 - 12 4 - 8 13 - 17 6 - 10 8 - 11 20 - 26
3.0 110 - 116 315 - 340 9 - 13 4 - 8 13 - 17 6 - 10 4 - 7 22 - 28
1.5 140 - 146 330 - 365 10 - 14 7 - 11 14 - 18 9 - 13 11 - 14 26 - 32
3.0 146 - 153 340 - 375 10 - 14 7 - 11 14 - 18 9 - 13 7 - 10 28 - 34
Suction
Pressure
PSIG
Suction Pressure
PSIG
Discharge
Pressure
PSIG
Discharge
Pressure
PSIG
022-070
Superheat
Cooling -- No Desuperheater 022-070
Superheat
Heating -- No Desuperheater
022-040
Subcooling
022-070
Subcooling
048
Subcooling
060-070
Subcooling
Water Temp
Rise °F
Water Temp
Drop °F
Air Temp Drop
°F DB
Air Temp Rise
°F DB
35
ENVISION RESIDENTIAL INSTALLATION MANUAL
p
g
p
g
p
p
g
p
g
Unit Operating Parameters
Dual Capacity Models
FIRST STAGE OPERATION
Coolin
-- No Desuperheater
Entering Water
Tem
°F
50 70 90
Entering Water
Tem
°F
30 50 70
Water Flow
GPM/Ton
1.5 125-140 205-225 12-20 8-14 17-21 17-23
3.0 120-135 190-210 12-20 8-14 8-12 17-23
1.5 135-145 280-290 10-16 8-14 16-20 17-23
3.0 133-143 250-260 10-16 8-14 9-13 17-23
1.5 142-152 345-355 8-12 8-14 14-20 17-23
3.0 140-150 330-340 8-12 8-14 8-12 17-23
Water Flow
GPM/Ton
1.5 76-84 280-295 8-12 3-10 5-9 12-16
3.0 80-88 285-300 8-12 3-10 3-7 14-18
1.5 100-115 310-330 10-14 3-10 7-11 18-22
3.0 105-120 315-335 10-14 3-10 5-9 20-24
1.5 135-150 325-350 12-16 3-10 8-12 24-28
3.0 140-155 330-355 12-16 3-10 6-10 22-30
Suction
Pressure PSIG
Suction
Pressure PSIG
SECOND STAGE OPERATION
Entering Water
Temp °F
50 70 90
Water Flow
GPM/Ton
1.5 130-140 215-235 12-20 8-14 16-22 17-23
3.0 128-138 190-210 12-20 8-14 8-12 17-23
1.5 138-148 280-310 10-16 10-16 15-21 17-23
3.0 136-146 250-280 10-16 8-14 7-13 17-23
1.5 145-155 350-380 9-14 10-16 14-20 17-23
3.0 143-153 320-350 9-14 8-14 6-10 17-23
Suction
Pressure PSIG
Discharge
Pressure PSIG Su
Discharge
Pressure PSIG Su
Discharge
Pressure PSIG Superheat Subcooling
erheat Subcoolin
Heatin
Cooling -- No Desuperheater
-- No Desuperheater
erheat Subcoolin
Water Temp
Rise °F
Water Temp
Dro
°F
Water Temp
Rise °F
Air Temp Drop
°F DB
Air Temp Rise
°F DB
Air Temp Drop
°F DB
Entering Water
Temp °F
30 50 70
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB. Heating performance based on entering air temperature of 70º F DB.
Water Flow
GPM/Ton
1.5 73-85 270-305 8-14 3-10 6-10 15-21
3.0 77-90 280-315 8-14 3-10 4-8 17-23
1.5 97-110 290-325 10-16 3-10 9-13 22-28
3.0 102-115 300-335 10-16 3-10 7-11 24-30
1.5 130-145 320-355 13-19 3-10 10-14 30-36
3.0 135-150 325-360 13-19 3-10 8-12 32-38
Suction
Pressure PSIG
Discharge
Pressure PSIG Superheat Subcooling
Heating -- No Desuperheater
36
Water Temp
Drop °F
Air Temp Rise
°F DB
ENVISION RESIDENTIAL INSTALLATION MANUAL
Pressure Drop
Single Speed Models Dual Capacity Models
Model GPM
3.0 0.9 0.9 0.8 0.7 0.7
022
030
036
042
048
060
070
4.5 1.7 1.6 1.5 1.4 1.3
6.0 2.8 2.7 2.5 2.3 2.2
8.0 4.7 4.4 4.1 3.9 3.6
4.0 1.5 1.4 1.3 1.2 1.1
6.0 3.0 2.8 2.7 2.5 2.3
8.0 5.1 4.8 4.5 4.2 3.9
10.0 7.7 7.2 6.8 6.3 5.8
5.0 1.0 1.0 0.9 0.8 0.8
7.0 2.1 1.9 1.8 1.7 1.6
9.0 3.6 3.3 3.0 2.8 2.6
12.0 6.3 5.9 5.5 5.1 4.8
5.0 0.8 0.7 0.7 0.7 0.6
8.0 2.1 2.1 1.9 1.8 1.7
11.0 4.2 4.1 3.8 3.5 3.3
14.0 7.6 6.7 6.3 5.8 5.4
6.0 1.1 1.0 1.0 0.9 0.8
9.0 2.3 2.1 2.0 1.9 1.7
12.0 3.9 3.7 3.4 3.2 3.0
16.0 6.7 6.3 5.9 5.5 5.1
9.0 2.4 2.2 2.1 2.0 1.8
12.0 3.9 3.6 3.4 3.2 2.9
15.0 5.7 5.3 5.0 4.7 4.3
20.0 9.5 8.9 8.3 7.8 7.2
12.0 3.0 2.8 2.6 2.4 2.2
15.0 4.4 4.0 3.8 3.5 3.3
18.0 6.0 5.5 5.1 4.8 4.4
24.0 9.7 9.1 8.5 7.9 7.3
Pressure Drop (psi)
30°F 50°F 70°F 90°F 110°F
Model GPM
026 full
load
10.0 7.0 6.6 6.2 5.8 5.3
026 part
load
038 full
load
11.0 4.9 4.6 4.3 4.0 3.7
038 part
load
10.0 4.2 3.9 3.7 3.4 3.2
049 full
load
049 part
load
064 full
load
064 part
load
072 full
load
072 part
load
12.0 3.9 3.6 3.4 3.2 2.9
15.0 5.7 5.3 5.0 4.7 4.3
11.0 3.4 3.1 2.9 2.8 2.5
14.0 5.0 4.7 4.4 4.1 3.8
12.0 3.8 3.5 3.3 3.0 2.8
16.0 6.5 6.0 5.6 5.2 4.8
20.0 9.7 9.1 8.5 8.0 7.4
10.0 2.6 2.5 2.3 2.1 2.0
14.0 5.0 4.7 4.4 4.1 3.8
18.0 8.1 7.6 7.1 6.6 6.1
12.0 3.2 3.0 2.8 2.6 2.4
15.0 4.5 4.2 4.0 3.7 3.4
18.0 6.0 5.7 5.3 4.9 4.6
21.0 7.8 7.3 6.8 6.4 5.9
10.0 2.3 2.1 2.0 1.9 1.7
13.0 3.6 3.3 3.0 2.8 2.6
16.0 5.0 4.6 4.3 4.0 3.7
19.0 6.5 6.2 5.8 5.4 5.0
Pressure Drop (psi)
30°F 50°F 70°F 90°F 110°F
4.0 1.4 1.3 1.2 1.1 1.0
6.0 2.8 2.6 2.4 2.3 2.1
8.0 4.7 4.4 4.1 3.8 3.5
3.0 0.8 0.7 0.7 0.7 0.6
5.0 2.0 1.8 1.7 1.6 1.5
7.0 3.6 3.4 3.2 3.0 2.8
9.0 5.8 5.5 5.1 4.8 4.4
5.0 1.2 1.2 1.1 1.0 1.0
7.0 2.2 2.1 1.9 1.8 1.7
9.0 3.4 3.2 3.0 2.8 2.6
4.0 0.9 0.8 0.8 0.7 0.7
6.0 1.7 1.6 1.5 1.4 1.3
8.0 2.8 2.6 2.5 2.3 2.1
6.0 1.2 1.2 1.1 1.0 1.0
9.0 2.4 2.2 2.1 2.0 1.8
5.0 0.9 0.9 0.8 0.8 0.7
8.0 2.0 1.8 1.7 1.6 1.5
8.0 1.8 1.7 1.6 1.4 1.3
6.0 1.0 0.9 0.9 0.8 0.8
37
ENVISION RESIDENTIAL INSTALLATION MANUAL
Troubleshooting
Standard Microprocessor Controls
To check the unit control board for proper operation:
1) Disconnect thermostat wires at the control board.
2) Jumper the desired test input (Y1, Y2, W, O or G) to the R terminal to simulate a thermostat signal.
3) If control functions properly:
Check for thermostat and fi eld control wiring (use the diagnostic inputs mode).
4) If control responds improperly:
Ensure that component being controlled is functioning (compressor, blower, reversing valve, etc.).
Ensure that wiring from control to the component is functioning (refer to the LED Defi nition table below and use the diagnostic outputs mode).
If steps above check properly, replace unit control.
LED Defi nitions and Diagnostics
Standard Microprocessor
DIAGNOSTIC MODES
INPUTS OUTPUTS 1 OUTPUTS 2
Compressor
(On or Low)
Y2
G Fan Aux Heat 1
W DHW Pump Aux Heat 2
Not Used Aux Heat 4
–––
Compressor (On or High)
Blower
Low
Blower
Medium
Blower
High
LED
Drain
Water Flow
High
Pressure
Low
Pressure/
Compressor
Airfl ow
Status
DHW Limit
DHW Off
NORMAL
DISPLAY MODE
Field Selection DIPS
SW2- 1 On SW2- 1 Off SW2- 1 NA SW2- 1 NA SW2- 1 NA SW2- 6 On SW2- 6 On SW2- 6 Off SW2- 6 On SW2- 6 Off SW2- 7 On SW2- 7 On SW2- 7 On SW2- 7 Off SW2- 7 Off
Drain Pan Overfl ow
Lockout
FP Thermistor (Loop
<15º F, Well<30ºF)
Lockout
High Pressure >600
PSI Lockout
Low Pressure <40
PSI Lockout or
Comfort Alert
ECM2 RPM <100
RPM
Microprocessor
Malfunction
HWL Thermistor
>130º
DHW Pump
Switch Off
CURRENT
FAULT STATUS
Drain Pan Overfl ow Y1
FP Thermistor (Loop
<15º F, Well<30ºF)
High Pressure >600 O Reversing Valve
Low Pressure <40
or Comfort Alert
ECM2 RPM
<100 RPM
Not Used SL1 Loop Pump(s) Aux Heat 3
HWL Thermistor
>130°F
DHW Pump
Switch Off
Refrigerant Systems
To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Compare the change in temperature on the air side as well as the water side to the tables on pages 35-36. If the unit’s performance is not within the ranges listed, and the airfl ow and water fl ow are known to be correct, gauges should then be installed and super- heat and subcooling numbers calculated. If superheat and subcooling are outside recommended ranges, an adjustment to the refrigerant charge may be necessary.
Note:
Refrigerant tests must be made with desuperheater turned “OFF”.
Verify that air and water fl ow rates are at proper
levels before servicing the refrigerant circuit.
38
ENVISION RESIDENTIAL INSTALLATION MANUAL
Preventive Maintenance
Water Coil Maintenance
1. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infi ltrate the water line. Lines should always be airtight.
2. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure.
Note: On open loop systems, if the installation is in an area with a known high mineral content (125 PPM or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water fl owing through the unit the less chance for scaling.
Other Maintenance
Filters
Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating condi-
tions and be replaced when necessary. Units should never be operated without a fi lter.
Condensate Drain
In areas where airborne bacteria produce a slime in the drain pan, it may be necessary to treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty fi lters. Inspect twice a year to avoid the possibility of overfl ow.
Blower Motors
ECM blower motors are equipped with sealed ball bearings and require no periodic oiling.
PSC blower motors should only be lubricated if dry operation is suspected.
Desuperheater Coil
See Water Coil Maintenance section above.
Air Coil
The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum (with a brush attachment) clean. Care must be taken not to damage the aluminum fi ns while cleaning.
CAUTION: Fin edges are sharp.
Replacement Procedures
Obtaining Parts
When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required.
In-Warranty Material Return
Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return authorization and assistance.
39
Manufactured by WFI 9000 Conservation Way Fort Wayne, IN 46809
WaterFurnace has a policy of continuous product research and development and reserves the right to change design and specifi cations without notice. ©2007 WFI.
Product: Envision Type: Geothermal/Water Source Heat Pumps Size: 2 thru 6 Ton Single Speed 2 thru 6 Ton Dual Capacity
Document Type: Installation Manual Part Number: IM1585 Release Date: 10/07 Supercedes: 04/07
Loading...