Envision Series Geothermal Indoor Split Heat Pumps
• R-410A Refrigerant
• 2 - 6 Ton Single Speed
• 2 - 6 Ton Dual Capacity
Installation Information
Water Piping Connections
Desuperheater Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
Envision Split Installation Manual
IM1592 06/07
ENVISION SERIES INSTALLATION MANUAL
NDZ049A11AC
Coax Options
Model TypeC= Copper
N= EnvisionN= Cupronickel
Compressor TypeOpen Option
D= Dual CapacityA= Standard
S= Single Speed
Hot Water Option
Cabinet Configuration0=None
Z= Indoor Split1=Hot Water Gerneration with
factory installed pump
Unit Capacity
Voltage
Vintage1=208-230/60/1
A= Current
Model022030036042048060070026038049064072
Compressor (1 each)
Factory Charge R410a, oz [kg]
56
[1.59]56[1.59]56[1.59]74[2.1]90[2.55]92[2.61]
108
[3.06]52[1.47]56[1.59]90[2.55]92[2.61]
104
[2.95]
Coax and Water Piping
Water Connections Size - Swivel- in [mm]
1 [25.4]
HWG Connection Size - Swivel - in [mm]
1 [25.4]
Coax & Piping Water Volume - gal [l]
0.7
[2.6]
1.0
[3.8]
1.3
[4.9]
1.3
[4.9]
1.6
[6.1]
1.6
[6.1]
2.3
[8.7]
0.7
[2.6]
1.3
[4.9]
1.6
[6.1]
1.6
[6.1]
2.3
[8.7]
Weight - Operating, lb [kg]
164
[74]
174
[79]
212
[96]
213
[97]
246
[112]
251
[114]
292
[132]
189
[186]
236
[107]
250
[113]
271
[123]
290
[132]
Weight - Packaged, lb [kg]
184
[83]
194
[88]
232
[105]
233
[106]
266
[121]
271
[123]
312
[142]
209
[95]
256
[116]
270
[122]
291
[132]
310
[141]
Notes:
All units have TXV expansion devices, and 1/2" [12.2mm] & 3/4" [19.1mm] electrical knockouts.
Rev.:6/7/07
1 [25.4]
Single Speed ScrollDual Capacity Scroll
1 [25.4]
Model Nomenclature
Physical Characteristics
2
ENVISION SERIES INSTALLATION MANUAL
Table of Contents
Model Nomenclature 2
Physical Characteristics 2
General Installation Information 4-8
Air Handler Coil Data 9
Line Set Sizes 9
Open Loop Well Water Systems 10-11
Closed Loop Ground Source Systems 12
Desuperheater 13-14
Electical Data 14
Thermostat Wiring 15
Wiring Schematics 16-17
Microprocessor Control Features and Operation 18-19
Operation Logic Data 20
DIP Switch Settings 21
Refrigeration 22-25
Unit Operating Parameters 26-27
Unit Startup 28-30
Pressure Drop & Recommended Flow Rates 31
Troubleshooting 32
Preventive Maintenance 33
Replacement Procedures 33
Physical Dimensions 34
3
ENVISION SERIES INSTALLATION MANUAL
General Installation Information
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main power switches
to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause
personal injury.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electri-
cal components. Only trained and qualied service personnel should install, repair or service heating and air conditioning
equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing
lters. All other operations should be performed by trained service personnel. When working on heating and air conditioning
equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may
apply, such as the following safety measures:
Follow all safety codes.
•
Wear safety glasses and work gloves.
•
Use a quenching cloth for brazing operations.
•
Have a re extinguisher available for all brazing operations.
•
Moving and Storage
Move units in the normal “up” orientation. Units may be moved and stored per the information on the packaging. Do not
stack more than three units in total height. Do not attempt to move units while stacked. When the equipment is received, all
items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine
units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally
inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the
damage.
Unit Location
Locate the unit in an indoor area that allows for easy removal of the access panels. Location should have enough space
for service personnel to perform maintenance or repair. Provide sufcient room to make water, electrical and refrigerant line
connections. Any access panel screws that would be difcult to remove after the unit is installed should be removed prior to
setting the unit. Care should be taken when units are located in unconditioned spaces to prevent damage from frozen water
lines and excessive heat that could damage electrical components.
Air Coil Location
Refer to the air handler manufacturer’s instructions for the blower coil unit for details on installing the air handling portion
of the system.
Condensate Drain
Follow the blower coil manufacturer’s instructions.
Duct System
All blower coil units/air coils must be installed as specied by the manufacturer’s installation instructions; however, the
following recommendations should considered to minimize noise and service problems.
An air lter must always be installed upstream of the air coil on the return air side of the air handler or furnace. If there
is limited access to the lter rack for normal maintenance, it is suggested that a return air lter grill be installed. Be sure that
the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the lter and plugging the air
coil.
In applications using galvanized metal ductwork, a exible duct connector is recommended on both the supply and
return air plenums to minimize vibration from the blower. To maximize sound attenuation of the unit blower, the supply and
return plenums should include an internal duct liner of 1-inch thick glass ber or be constructed of ductboard. Insulation is
usually not installed in the supply branch ducts. Ducts in unconditioned areas should be wrapped with a minimum of 1-inch
duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s
performance will be adversely affected. If the air handler is connected to existing ductwork, a previous check should have
been made to assure that the duct system has the capacity to handle the air required for the unit application. If ducting is too
4
ENVISION SERIES INSTALLATION MANUAL
General Installation Information (continued)
small, as in replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be
checked for leaks and repairs made accordingly. The duct systems and diffusers should be sized to handle the design
airow quietly. If air noise or excessive airow is a problem, the blower speed can be changed to a lower speed to
reduce airow. This will reduce the performance of the unit slightly in heating; however, it will increase the temperature
rise across the air coil. Airow must still meet minimum requirements.
Equipment Selection
The following guidelines should be used when mating an Envision Split to an air handler/coil.
Select R-410A components only.
•
Select 12 SEER or higher air handler/coil.
•
Match the air handler to the air handler coil data table on page 9.
•
Indoor matching adjustable TXV should be used with any air handler/coil. Fixed orice or cap tube systems
•
should not be used.
Utilizing Existing Coil or Air Handler
It is recommended that a new R-410A air handler be installed with an Envision Split considering the long term benets of reliability, warranty, etc. versus the short term installation cost savings. However, the existing air handler may be
retained provided the following:
Coil currently is R-410A rated
•
Coil uses a TXV. No capillary or xed orice systems should be used
•
A life expectancy of more than 7 years remaining for the air handler and components
•
5
ENVISION SERIES INSTALLATION MANUAL
Disconnect
Thermostat Wire
From Air Handler
Vibration Absorbing Pad or Air Pad
P/T Plugs
Water Out
Water In
Lineset To Air Handler
Insulated Suction Line
Supply
Duct
Wire To
Thermostat
Return
Duct
Condensate Drain
(must be trapped)
To Drain
Remote Air Handler
(Maximum Recommended Distance is
50' Between Units)
DHW In
DHW Out
Connection to Air Coil
Figures 1 and 2 illustrate typical Envision Split installations. The table on page 9 shows typical lineset diameters and
maximum length. Linesets over 60 feet are not recommended. If the lineset is kinked or deformed and cannot be reformed,
the bad section of pipe should be replaced. A restricted lineset will affect unit performance. As in all R-410A equipment, a
reversible liquid line lter drier is required to insure all moisture is removed from the system. This drier should be replaced
whenever “breaking into” the system for service. All linesets should be insulated with a minimum of 1/2” closed cell insulation. All exterior insulation should be painted with UV resistant paint or covering to insure long insulation life.
Air Handler Installation
Air handlers used with dual capacity units must be capable of operating with a minimum of 2 blower speeds. Refer to the
manufacturer’s instructions for the blower coil unit for details on installing the air handling portion of the system. All blower
coil units/air coils must be installed as specied by the manufacturer’s installations instructions. However, the following rec-
ommendations should be considered to minimize noise and service problems.
An air lter must always be installed upstream of the air coil on the return air side of the air handler of furnace. If there is
limited access to the lter rack for normal maintenance, it is suggested that a return air lter grille be installed. Be sure that
the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the lter and plugging the air
coil.
Ensure that the line set size is appropriate to the capacity of the unit (refer to page 9). Line sets should be routed as di-
rectly as possible, avoiding unnecessary bends or turns. All wall penetrations should be sealed properly. Line set should not
come into direct contact with water pipes, oor joists, wall studs, duct work, oors, walls and brick. Line set should not be
suspended from joists or studs with a rigid wire or strap which comes into direct contact with the tubing. Wide hanger strips
which conform to the shape of the tubing are recommended. Isolate hanger straps from line set insulation by using metal
sleeves bent to conform to the shape of insulation. Line set insulation should be pliable, and should completely surround the
refrigerant line.
Notes: Improper installation of equipment may result in undesirable noise levels in the living areas.
Figure 1: Typical Split System Application with Remote Blower Coil
6
ENVISION SERIES INSTALLATION MANUAL
Disconnect
Thermostat
Wire From Furnace
Vibration Absorbing Pad or Air Pad
P/T Plugs
Wire To
Thermostat
Up-Flow
Fossil Fuel
Furnace
Condensate
Drain
(must be trapped)
"A" or
Slab Coil
Supply Duct
Air Temperature Limit Switch to prevent compressor operation
when entering air is greater than
90°F.
Water Out
Water In
Lineset To Air Handler
Insulated
Suction Line
DHW In
Return
Duct
DHW Out
Dual Fuel Systems
Envision units can be connected to fossil fuel furnaces that include an A-coil or slab coil. Dual fuel installations utilize the
Envision heat pump for heating until the point that auxiliary heat is called for on the thermostat. At that point, the furnace
will be enabled and the heat pump will be disabled. The Envision heat pump provides air conditioning through the furnace’s
refrigerant coils.
Refer to the furnace manufacturer’s installation manual for the furnace installation, wiring and coil insertion. A
WaterFurnace Dual Fuel thermostat, a eld-installed DPST relay or dual capacity auxiliary heat relay is required. See Figure
2 for typical Dual Fuel application.
In add-on Envision Split applications, the coil should be located in the supply side of the furnace to avoid condensation
damage to the furnace heat exchanger. A high temperature limit should be installed upstream of the coil to de-energize the
compressor whenever the furnace is operating. Without this switch, the Envision Split will trip out on high pressure. A dual
fuel thermostat can remove the Y1 and Y2 calls when a W call is energized to allow gas furnace backup on an Envision Split
application. Refer to thermostat wiring on page 15 for details.
The proper water ow must be provided to each unit whenever the unit
Figure 3: Swivel Connections
(Residential Units)
operates. To assure proper ow, use pressure/temperature ports to determine the ow rate. These ports should be located at the supply and return
water connections on the unit. The proper ow rate cannot be accurately set
without measuring the water pressure drop through the refrigerant-to-water
heat exchanger.
All source water connections on residential units are swivel piping ttings
(see Figure 3) that accept 1-inch male pipe threads (MPT) . The swivel connector has a rubber gasket seal similar to a rubber hose gasket, which when
mated to the ush end of any 1-inch threaded pipe provides a leak-free seal
without the need for thread sealing tape or compound. Check to ensure that
the rubber seal is in the swivel connector prior to attempting any connection.
The rubber seals are shipped attached to the waterline. To make the connection to a ground loop system, mate the brass connector (supplied in CK4L
connector kit) against the rubber gasket in the swivel connector and thread
the female locking ring onto the pipe threads, while maintaining the brass
connector in the desired direction. Tighten the connectors by hand, then gently snug the tting with pliers to provide a leak-proof joint. When connecting
to an open loop (ground water) system, thread the 1-inch MPT tting (SCH80
PVC or copper) into the swivel connector and tighten in the same manner as
noted above. The open and closed loop piping system should include pressure/temperature taps for serviceability.
Never use exible hoses smaller than 1-inch inside diameter on the unit. Limit hose length to 10 feet per connection.
Check carefully for water leaks.
Notes: Lineset charge for R410A is 0.50 oz. per ft. for 3/8" and 1.0 oz. per ft. for 1/2" tube.
Rev.: 6/8/07
Initial Total System Charge = Factory Envision Split charge + lineset charge + 20 oz, then adjust charge by subcooling and superheat measurements.
20 feet40 feet60 feet
Notes: * Variable speed air handler required for all dual capacity units.
Line Set Sizes
ENVISION SERIES INSTALLATION MANUAL
9
ENVISION SERIES INSTALLATION MANUAL
Disconnect
Thermostat Wire
From Air Handler
Vibration Absorbing Pad or Air Pad
P/T Plugs
Boiler Drains for
System Flushing
Water Solenoid
Control Valve
Rubber Bladder
Pressure Tank
Lineset
To Air Handler
Flow
Regulator
Shut-Off Valves
Water Out
Water In
From W ell
Acc Com
Acc NC
Acc NO
1
2
3
C
R
P1
P3
SV
Solenoid
Valve
CC-GND
CC
CCHI
Comfort
Alert
Y1
Y2
Logic Board
Violet(3)
Blk(1)
Wht(4)
VM valve
Violet(2)
CC
Open Loop - Well Water Systems
Typical open loop piping is shown below. Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed bladder type expansion tank to minimize
mineral formation due to air exposure. Ensure proper water ow through the unit by checking pressure drop across the heat
exchanger and comparing it to the gures in the unit capacity data tables in the specication catalog. Usually 1.5-2 GPM of
ow per ton of cooling capacity is recommended in open loop applications. In dual capacity units, stage 1 is 70% of the total
tonnage. Therefore, due to only minor differences in ow rate from low to high, only one solenoid valve should be used. The
valve should be sized for full ow.
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways depending
on local building codes (i.e.
recharge well, storm sewer,
drain eld, adjacent stream or
pond, etc.). Most local codes
forbid the use of sanitary sewer
for disposal. Consult your local
building and zoning departments to ensure compliance in
your area.
Notes: For open loop/ground-
water systems or sytems that
do not contain an antifreeze
solution, set SW2-Switch #2
to the “WELL” position (Refer
to the table on page 21.) Slow
opening/closing solenoid valves
(type VM) are recommended to
eliminate water hammer.
Figure 4: Typical Split System Application Open Loop - Well Water
Figure 5: Open Loop Solenoid Valve Connection Option
Typical quick operating external 24V water solenoid valve
(type PPV100 or BPV100) wiring.
Figure 9b: Open Loop Solenoid Valve Connection Option
Water control valves draw their power directly from a unit’s 24V transformer and can overload and possibly burn out the
transformer. Check total VA draw of the water valve and ensure that it is under 15 VA.
Water Quality
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time,
lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualied
service mechanic, as special solutions and pumping equipment are required. Desuperheater coils can likewise become
scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger
may require occasional ushing.
11
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.