Envision NSKW 06, NSKW 08, NSKW 12, NSKW 17 Installation Manual

Geothermal Hydronic Heat Pump - 50 Hz
Installation Information
Water Piping Connections
Electrical Data
Startup Procedures
Preventive Maintenance
NSKW Installation Manual
IM1066WN 05/15
Table of Contents
Model Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
BS EN 14511-2 Performance Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Legend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
NSKW INSTALLATION MANUAL
Water Quality
Field Connected Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
Potable Water Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-12
Hydronic Section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-14
Accessories and Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-17
Wiring Schematics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-21
Heat Pump Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
External Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23-24
Converting to a Dedicated Cooling Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Unit Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Standard Board - Control Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27-28
Standard Control - Panel Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-30
Optional Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-35
Reference Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Pressure Drop. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Flow Rates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Thermistor Resistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Operating Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Antifreeze Correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Troubleshooting Guideline for Refrigerant Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Heating and Cooling Cycle Analysis. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Startup and Troubleshooting Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43-44
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Service Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
NSKW INSTALLATION MANUAL
Model Nomenclature
1-4
NSKW
Model
NSKW = Envision Series 50Hz Hydronic Heat Pump
Capacity (kW Output)
06 08 12 17
Operation
H = Heating Only R = Reversible
Voltage
6 = 220-240/50/1 7 = 380-420/50/3
Hot Water Option
0 = No Hot Water Generation, No IntelliStart 2 = Hot Water Generation, No IntelliStart (12-17) 3 = No Hot Water Generation, IntelliStart 5 = Hot Water Generation, IntelliStart (12-17)
7R869010211C12C13-14SS15
5-6
08
A
Vintage
A = 08-17 B = 06
Future Option
SS = Standard Option
Load Coax C = Copper N = Cupronickel
Source Coax
C = Copper N = Cupronickel
Controls Option
2 = Standard Board 4 = FX10 without communication 5 = FX10 with Open N2 Com Card 6 = FX10 with LonWorks card Com Card 7 = FX10 with BACnet Com card 8 = FX10 without communication, with User Interface 9 = FX10 with Open N2 Com Card, with User Interface 0 = FX10 with Lonworks Com card, with User Interface 3 = FX10 with BACnet Com card, with User Interface
1
NOTES: Hot Water Generation (HWG) only available on NSKW12-17 and requires a field installed external pump
1
- 06 heating only models are available only with copper double wall vented load coax.
All Envision Series NSKW product is safety tested to CE standards and performance tested in accordance with standard BS EN 14511-2.
4
BS EN 14511-2 Performance Ratings
Heating Performance
B0/W35 W10/W35 B0/W45 B5/W35 W10/W45
Capacity
Model
All ratings based upon 220V operation All ratings based on new heat pump with clean heat exchangers
Output
06
5.80 3.80 1.53 7.30 4.80 1.52 5.50 2.90 1.90 6.60 4.30 1.54 7.10 3.70 1.92
08
8.30 4.20 1.98 10.6 5.30 2.00 8.00 3.20 2.50 9.50 4.80 1.98 10.2 4.10 2.49
12
17
COP
kW
11.6 4.20 2.80 14.4 5.30 2.72 11.3 3.20 3.53 13.3 4.80 2.77 14.2 4.10 3.46
16.6 3.70 4.49 21.4 4.70 4.55 15.9 2.90 5.50 19.0 4.30 4.42 20.4 3.70 5.51
Cooling Performance
Model
All ratings based upon 220V operation All ratings based on new heat pump with clean heat exchangers
06
08
12
17
Capacity
Output kW
4.00 2.80 1.43 5.90 4.10 1.44 8.10 5.60 1.45
6.10 3.00 2.03 9.00 4.40 2.05 12.4 6.00 2.07
8.20 2.90 2.82 12.0 4.30 2.80 16.6 5.80 2.86
11.2 2.60 4.30 16.4 3.80 4.32 22.7 5.20 4.37
Power
Capacity
Input
W30/B0 W30/W12 W30/W23
EER (W/W)
kW
Output
COP
kW
Power Input kW Capacity
Power
Capacity
Input
kW
Output kW
Output
kW
COP
EER (W/W)
Power
Capacity
Input
Output
kW
Power Input kW Capacity
COP
kW
Output kW
NSKW INSTALLATION MANUAL
Power
Input
kW
Capacity
Output
kW
EER (W/W)
COP
Power
Input
kW
9/26/11
Power Input
kW
9/26/11
Legend
ABBREVIATIONS AND DEFINITIONS:
COP = coefficient of performance EER = cooling energy efficiency (TC/kW) ELT = entering load fluid temperature EST = entering source fluid temperature to heat pump FLA = full load amps FtHd = pressure drop in feet of head gpm = US gallon per minute HC = heating capacity in kW HE = heat of extraction in kW HR = heat rejected in kW kPa = kilopascal kW = kilowatt
CONVERSIONS:
x°F = (x - 32)/1.8°C 1 bar = 100 kPa 1 gpm = 0.0631 L/s
L/s = liters per second LLT = leaving load fluid temperature from heat pump LRA = locked rotor amps (starting current) LST = leaving source fluid temperature from heat pump LWPD = load heat exchanger water pressure drop MCC = maximum continuous current PD = pressure drop psi = pressure drop in pounds per square inch P/T = Pressure/Temperature RLA = run load amps TC = total cooling capacity in kW W = Watt
1 US Gallon = 3.785412 L 1 Btu/h = 0.29037 W
5
NSKW INSTALLATION MANUAL
General Installation Information
Safety Considerations
Installing and servicing air conditioning and heating equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for brazing operations. Have fire extinguisher available for all brazing operations.
NOTE: Before installing, check voltage of unit(s) to ensure proper voltage.
WARNING: Before performing service or maintenance operations on the system, turn off main power switches to the unit. Electrical shock could cause serious personal injury.
Process Water Applications
For process water applications, it is recommended that a secondary load heat exchanger be installed to prevent corrosion to the unit’s primary coaxial coil. In situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. Over a period of time, ground water unit heat exchanger coils may lose heat exchange capability due to a buildup of mineral deposits. These can be cleaned only by a qualified service mechanic as special pumping equipment and solutions are required.
WARNING: To avoid equipment damage, do not leave the system filled in a building without heat during cold weather, unless adequate freeze protection levels of antifreeze are used. Heat exchangers do not fully drain and will freeze unless protected, causing permanent damage.
Unit Location
Provide sufficient room to make water and electrical connections. If the unit is located in a confined space, provisions must be made for unit servicing. Locate the unit in an indoor area that allows easy removal of the access panels and has enough space for service personnel to perform maintenance or repair. These units are not approved for outdoor installation and, therefore, must be installed inside the structure being conditioned. Do not locate units in areas subject to freezing conditions.
WARNING: Do not store or install units in corrosive environments or in locations subject to temperature or humidity extremes (e.g. attics, garages, rooftops, etc.). Corrosive conditions and high temperature or humidity can significantly reduce performance, reliability, and service life.
Mounting Units
Units should be mounted level on a vibration absorbing pad slightly larger than the base to provide isolation between the unit and the floor. It is not necessary to anchor the unit to the floor. Allow access to the front, back, and side access panels for servicing.
Moving and Storage
Move units in the normal “Up” orientation as indicated by the labels on the unit packaging. When the equipment is received, all items should be carefully checked against the bill of lading to ensure that all crates and cartons have been received in good condition. Examine units for shipping damage, removing unit packaging if necessary to properly inspect unit. Units in question should also be internally inspected. If any damage is observed, the carrier should make the proper notation on delivery receipt acknowledging the damage. Units are to be stored in a location that provides adequate protection from dirt, debris and moisture.
DWP`ObW]\>OR;]c\bW\U
6
Dimensional Data
NSKW INSTALLATION MANUAL
A
C
B
Z
Y
NOTE: Plastic front panel extends 3.56 cm beyond front of cabinet.
Overall Cabinet Water Connections
Model
06 08
12 17
Model
06 08
12 17
NOTE: Plastic front panel extends 3.56 cm beyond front of cabinet.
ABCDE FGH I
Depth Height Width
cm. 59.7 66.3 49.5 25.4 56.4 25.4 56.4 - - 25.4 mm 25.4 mm - 4 0.6 3 6.1 36 .1 cm. 78.7 66.5 55.9 5.3 49.8 5.3 49.8 60.7 60.7 25.4 mm 25.4 mm 12.7 mm 43.4 37.6 43.4 cm. 78.7 66.5 55.9 5.6 52.3 5.6 52.3 60.7 60.7 31.8 mm 31.8 mm 12.7 mm 43.4 37.6 43.4 cm. 78.7 66.5 55.9 6.1 58.4 6.1 58.4 52.3 52.3 31.8 mm 31.8 mm 12.7 mm 43.4 37.6 43.4
MNOP QR S T UVWXYZ
Load
Liquid In
cm. 6.1 6.1 6.1 6.1 - - 8.9 7.4 37.8 6.6 5.3 4.4 7.4 10.4 cm. 4.1 7.0 7.0 4.1 5.1 4.6 12.2 12.2 43.4 7.0 37.8 12.2 12.2 43.4 cm. 4.6 9.1 9.1 4.6 5.3 4.6 12.2 12.2 43.4 7.1 37.8 12.2 12.2 43.4 cm. 4.6 10.2 10.2 4.6 10.7 3.6 12.2 12.2 43.4 7.1 37.8 12.2 12.2 43.4
Load
Liquid
Out
X
Source
Liquid In
W
Load
Liquid
In
Source Liquid
Load
Liquid
Out
Water Connections Electrical Knockouts
HWG In
Out
Source
Liquid
In
HWG
Out
Source
Liquid
Out
Power
Supply
HWG In
Voltage
V
Low
U
HWG
Out
Load
Water
Side
Power
Supply
I
FPT
E
L
Side
Power
Supply
N
R
D
Source
Water
FPT
S
Pump
M
HWG
Water
FPT
Ext
T
Q
P
H
G
J
K
F
O
8/09/13NOTE: Plastic front panel extends 1.4" (3.56 cm) beyond front of cabinet.
Electrical Knockouts
JKL
1/2 in.
cond
Low
Voltage
Ext
Pump
3/4 in.
Power
Supply
cond
Ext
Pump
3/4 in.
cond
Power
Supply
Power
Supply
8/6/10
Physical Data
Model 06 08 12 17
Compressor (1 each) Scroll
Factory Charge R410A, oz [kg] 58 [1.64] 70 [1.98] 68 [1.93] 110 [3.12] Coax & Piping Water Volume - gal [l]* 0.89 [3.38] 1.0 [3.94] 1.4 [5.25] 1.6 [6.13] Weight - Operating, lb [kg] 225 [102.1] 290 [131.5] 325 [147.4] 345 [156.5] Weight - Packaged, lb [kg] 247 [112.0] 305 [138.3] 340 [154.2] 360 [163.3]
Note: * Source or load side only 3/25/15
7
NSKW INSTALLATION MANUAL
Water Quality
General
NSKW heat pumps may be successfully applied in a wide range of residential and light commercial applications. It is the responsibility of the system designer and installing contractor to ensure that acceptable water quality is present and that all applicable codes have been met in these installations. Failure to adhere to the guidelines in the
building’s piping system that the designer may need to take into consideration when deciding the parameters of the water quality.
If an antifreeze or water treatment solution is to be used, the designer should confirm it does not have a detrimental effect on the materials in the system.
water quality table could result in loss of warranty.
Contaminated Water
Water Treatment
Do not use untreated or improperly treated water. Equipment damage may occur. The use of improperly treated or untreated water in this equipment may result in scaling, erosion, corrosion, algae or slime. The services of a qualified water treatment specialist should be engaged to determine what treatment, if any, is required. The product warranty specifically excludes liability for corrosion, erosion or deterioration of equipment.
The heat exchangers and water lines in the units are copper or cupronickel tube. There may be other materials in the
Water Quality Guidelines
Material Copper 90/10 Cupronickel 316 Stainless Steel
pH Acidity/Alkalinity
Scaling
Corrosion
Iron Fouling
(Biological Growth)
Erosion
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm
Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm Chlorine Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Chlorides Less than 20 ppm Less than 125 ppm Less than 300 ppm
Carbon Dioxide Less than 50 ppm 10 - 50 ppm 10 - 50 ppm
Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm
Ammonia Chloride Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Nitrate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Hydroxide Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Sulfate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Total Dissolved Solids (TDS) Less than 1000 ppm 1000 - 1500 ppm 1000 - 1500 ppm
LSI Index +0.5 to -0.5 +0.5 to -0.5 +0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
2
+ (Ferrous)
Less than 0.5 ppm (rotten egg
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
7 - 9 7 - 9 7 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm < 0.2 ppm < 0.2 ppm
< 1.8 m/sec < 1.8 m/sec < 1.8 m/sec
In applications where the water quality cannot be held to prescribed limits, the use of a secondary or intermediate heat exchanger is recommended to separate the unit from the contaminated water.
The following table outlines the water quality guidelines for unit heat exchangers. If these conditions are exceeded, a secondary heat exchanger is required. Failure to supply a secondary heat exchanger where needed will result in a warranty exclusion for primary heat exchanger corrosion or failure.
(Total Hardness)
less than 350 ppm
10 - 50 ppm Less than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12
8
Field Connected Water Piping
NSKW INSTALLATION MANUAL
General
Each unit is equipped with captive female pipe thread (FPT) water connections to eliminate ‘egg-shaping’ from use of a backup wrench. For making the water connections to the unit, a Teflon tape thread sealant is recommended to minimize internal fouling of the piping. Do not over tighten connections. All supply and return water piping should be insulated to prevent excess condensation from forming on the water lines.
NOTES: 1) WaterFurnace recommends a male national pipe thread (NPT) to British standard pipe fitting (BSPF) to adapt to NSKW water connections. 2) Units are factory run­tested using propylene glycol. Prior to connecting piping to unit, thoroughly flush heat exchangers.
The piping installation should provide service personnel with the ability to measure water temperatures and pressures. The water lines should be routed so as not to interfere with access to the unit. The use of a short length of high pressure hose with a swivel type fitting may simplify the connections and prevent vibration. Optional stainless steel hose kits are available as an accessory item.
Before final connection to the unit, the supply and return hose kits must be connected, and the system flushed to remove dirt, piping chips and other foreign material. Normally, a combination balancing and close-off (ball) valve is installed at the return, and a rated gate or ball valve is installed at the supply. The return valve can be adjusted to obtain the proper water flow. The valves allow the unit to be removed for servicing.
The proper water flow must be delivered to each unit whenever the unit heats or cools. To assure proper flow, the use of pressure/temperature ports is recommended
to determine the flow rate. These ports should be located adjacent to the supply and return connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant­to-water heat exchanger (See Pressure Drop Table for water flow and pressure drop information). Normally about 0.054 L/s per kW flow rate of cooling capacity (0.040 L/s per kW minimum) is needed. Both source as well as load fluid piping must be at least as large as the unit connections on the heat pump (larger on long runs).
Never use flexible hoses of a smaller inside diameter than that of the water connection on the unit and limit hose length to
3.05 m per connection. Check carefully for water leaks.
CAUTION: Water piping exposed to outside temperature may be subject to freezing.
Open Loop Well Water Systems
Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit. Use a closed bladder type expansion tank to minimize mineral deposits. Ensure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in the pressure drop table. Normally, about 0.038 L/s per kW flow rate of cooling capacity is needed in open loop systems, 0.029 L/s per kW minimum if entering source temperature is above 10°C.
Some water control valves draw their power directly from the unit’s 24V transformer and can overload and possibly burn out the transformer. Check total VA draw of the water valve(s) and ensure it is under 40 VA.
Discharge water from a heat pump can be disposed of in various ways depending on local building codes (i.e. recharge
Typical Open Loop Installation
Line Voltage Disconnect
Load Liquid
Connections
Shut-off Valve
(to isolate solenoid
valve while acid
flushing)
Rubber Bladder
Expansion Tank
Flow Regulator Valve
Solenoid
Valve
Boiler Drains for HX Flushing
P/T Plugs
Vibration Absorbing Mesh or Air Pad
Water Out
Water In
Shut-off Valve
NOTE: Valves and boiler drains must be installed so the heat exchanger can be acid flushed.
9
NSKW INSTALLATION MANUAL
Field Connected Water Piping cont.
well, storm sewer, drain field, adjacent stream or pond, etc.). Most local codes restrict the use of sanitary sewer for disposal. Consult your local building and zoning departments to ensure compliance in your area.
Earth Coupled Systems with Flow Center
Once piping is completed between the unit, flow center and the earth loop, final purging and charging of the loop is needed. A pump capable of 14 m
3
/hr @ 25 meters of head is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Maintain the pH in the 7.6-8.2 range for final charging.
Flush the system adequately to remove as much air as possible. Then, pressurize the loop to a static pressure of 345-517 kPa. This is normally adequate for good system operation. Ensure that the flow center provides adequate flow through the unit by checking pressure drop across the heat exchanger and by comparing it to the figures shown in the Pressure Drop tables. Usually, 0.054 L/s per kW or minimum 0.040 L/s per kW of cooling capacity is needed in closed loop earth-coupled applications.
Ground Loop Design and Installation
This instruction manual does not cover the design and installation of the ground loop system. WaterFurnace recommends that all ground loops are designed using
Typical Closed Loop Earth Coupled Installation
Earth Coupled Loop
Piping with Insulation
Line Voltage Disconnect
Unit Connector Kits
with Insulation
P/T Plugs
Vibration Absorbing Mesh or Air Pad
GeoLink
Load Liquid
Connections
TM
Design Studio (GDS) or another commercial software package. Installers shall follow the guidelines detailed in Microgeneration Certification Scheme (MCS) Installation Standard MIS 3005 for designing ground loop collectors. Additional guidance on ground collectors is provided by International Ground-Source Heat Pump Association (IGSHPA).
Potable Water Systems
NSKW06-17 kW heat pumps can be equipped with a double-wall vented coaxial heat exchanger capable of hot water generation (HWG). An optional factory-installed hot water generator coil may be provided with NSKW08-17. The temperature of the hot water produced by the heat pump cannot be adjusted and will vary with the inlet temperature. WaterFurnace recommends the use of a properly sized buffer tank equipped with supplemental electric immersion heaters in conjunction with all NSKW models used in an HWG application. Immersion heaters must be capable of heating the water to 60°C at a regular time interval to prevent the build-up of bacteria such as Legionella. Installations must meet minimum requirements outlined in UK Domestic Heating Compliance Guide.
CAUTION: Hot water in excess of 60°C can cause scalding.
Hot Water Generator Connections
The heat reclaiming hot water generator coil is vented double-
wall copper construction and is suitable for potable water. To maximize the benefits of the hot water generator a minimum 50-gallon water heater is recommended. For higher demand applications, use an 80-gallon water heater as shown below or two 50-gallon water heaters connected in a series. A geo storage tank should not be used in this application unless it is plumbed in a series with an electric water heater. The geo storage tank is equipped with a single 4500 Watt element and will not be able to provide adequate water heating if used as a standalone water heater. Electric water heaters are recommended. Make sure all local electrical and plumbing codes are met for installing a hot water generator. The Envision NSKW is not supplied with an internal circulator.
10
Potable Water Systems cont.
Suggested Domestic Water Heater Hookup
207 kPa
RELIEF VALVE
Back Flow Preventer /
Pressure Relief Valve
Pressure
Gauge
Vent
Expansion
Tank
Air
Air
Separator
LOAD PUMP
NSKW INSTALLATION MANUAL
HYDRONIC
LOAD
Vent Valve or
P/T Port**
Dielectric
Unions
GEO
STORAGE
TANK
Dip Tube
Dielectric
Unions
Ball Valve
NOTES: * A 207 kPa pressure relief valve (Part No: SRV30) should be used in
hydronic applications. ** Vent valve or Pressure/Temperature port at highest point in return line prior to ball valve.
NOTES:
1) Unions and valves must be installed so that acid flushing of the heat exchanger is possible.
2) Route thermistor wires to NSKW. Remove yellow thermistor wires on TB 3 and 4 from control box and connect thermistor wires from geothermal storage tank. Set the pump sampling (PS) in the set up of the control board to continuously (C) sampling (reference Note 5 in the Wiring Schematic).
P/T
Ports
Ball Valve
FROM
HWG
HWG
WaterFurnace
NSKW Series
TO
PUMP
Source OUT
P/T Ports
Source IN
HOT
(Piped in
series to
an electric
water heater)
COLD
DOMESTIC
11
NSKW INSTALLATION MANUAL
Potable Water Systems cont.
Alternate Hot Water Installation with Direct Coupling to a Double Wall Unit
Dielectric
Unions
HOT
COLD
LOOP FIELD
FLOW CENTER
Dielectric
Unions
Ball Valve
WaterFurnace
GEOTANK
NOTES:
1) Unions and valves must be installed so that acid flushing of the heat exchanger is possible.
2) Make sure there is not a check valve in the diptube of the tank.
3) Route thermistor wires to NSKW. Remove yellow thermistor wires on TB 3 and 4 from control box and connect thermistor wires from geothermal storage tank. Set the pump sampling (PS) in the set up of the control board to continuously (C) sampling (reference Note 5 in the Wiring Schematic).
P/T
Ports
Ball Valve
WaterFurnace
NSKW06 (Heating Only)
with Double Wall Load Coax
P/T Ports
12
Hydronic Section
NSKW INSTALLATION MANUAL
General guidelines are shown below for component selection and design/installation criteria for the piping system. Local codes supersede any recommendations in this manual.
Shut Off/Flow Regulation Valves
Use full port ball valves or gate valves for component isolation. If valves are going to be used frequently, ball valves are recommended. Globe valves are designed for flow regulation. Always install globe valves in the correct direction (fluid should enter through the lower body chamber).
Check valves
Swing check valves must be installed in the horizontal position with the bonnet of the valve upright. Spring check valves can be mounted in any position. A flow check valve is required to prevent thermo-siphoning (or gravity flow) when the circulator pump is off or when there are two circulators on the same system.
Storage (Buffer) Tank
A buffer tank is required for all hydronic heating systems
using Envision NSKW heat pumps. The tank should be sized to provide 2 gallons [7.6 L] of storage capacity for every
300W of nominal heat pump capacity.
Pressure Relief Valve
Most codes require the use of a pressure relief valve if a closed loop heat source can be isolated by valves. Even if local code does not require this device, WaterFurnace recommends its installation. If the pressure relief valve in the buffer tank is not already rated at 207 kPa maximum pressure, one must be installed. The pressure relief valve should be tested at start up for operation. Note that the waste pipe must be at least the same diameter as the valve outlet (never reduce), and valves may not be added to this pipe. The bottom of the pipe must terminate at least 15 cm above the floor. If the piping is connected to a drain, there must be an air gap.
Pressure Reducing Valves or Feed Water Valves
This valve lowers the pressure from the make-up water line
to the system. Most are adjustable and directional. A “fast fill” valve is required for initial filling of the system. Some have screens, which must be cleaned after the initial filling. If there is a restriction in the screen, the system could go to 0 kPa, potentially causing pumps(s) failure. A valve should be installed on each side of the pressure reducing valve for servicing. Both valves should have tags reading “Do not shut this valve under normal operation – service valve only.”
Expansion Tanks
Expansion tanks are required on hydronic systems to help absorb the pressure swings as the temperature in the system fluctuates.
Elbows/Tees
Long radius elbows or two 45° elbows will lower pressure drop. Standard tees have a greater restriction on the “T” portion than tees designed with angled outlet ports.
Antifreeze
Antifreeze is required if any of the piping system is located
in areas subject to freezing.
Dielectric Unions
Dielectric unions are recommended whenever connecting two dissimilar metals to one and other to prevent electro­galvanic corrosion.
When using the various types of hydronic heat distribution
systems, the temperature limits of the geothermal system must be a major consideration. In new construction, the distribution system can easily be designed with the temperature limits in mind. In retrofits, care must be taken to address the operating temperature limits of the existing distribution system. The maximum storage tank temperature for the Envision NSKW is 54.4°C. Typical in floor radiant systems require much lower temperatures, typically 37.8°-46.1°C, which is ideal for the Envision NSKW.
Backflow Prevention Check Valves
Most codes require backflow prevention check valves. Note that a single check valve is not equal to a backflow prevention check valve. Even if local code does not require this device, WaterFurnace recommends its installation. This is particularly important if the system will use antifreeze.
13
NSKW INSTALLATION MANUAL
Hydronic Section cont.
Open the screw 2 turns only in the end of the pump motor (if Grundfos
®
pumps are used) to allow trapped air to be discharged and to ensure the motor housing has been flooded.
Route thermistor wires to NSKW. Remove yellow thermistor wires on TB 3 and 4 from control box and connect thermistor wires from geothermal storage tank. Set the pump sampling (PS) in the set up of the control board to continuously (C) sampling (reference Note 5 in the Wiring Schematic).
Adequate rate of flow is very important to system performance and long term reliability. Follow the guidelines for recommended flow and pipe sizing in the NSKW recommendations table.
207 kPa
RELIEF VALVE
Back Flow Preventer /
Pressure Relief Valve
Pressure
Gauge
Air
Vent
Expansion
Tank
WaterFurnace Geothermal Storage Tank Thermostat and Thermistor
NSKW
Yellow Thermistor Wires Connected to TB (3 and 4) on NSKW Control Board
LOAD PUMP
Air
Separator
HYDRONIC
LOAD
Vent Valve or
P/T Port**
Dielectric
Unions
GEO
STORAGE
TANK
Dip Tube
Dielectric
Unions
Ball Valve
NOTES: * A 207 kPa pressure relief valve (Part No: SRV30) should be used in
hydronic applications. ** Vent valve or Pressure/Temperature port at highest point in return line prior to ball valve.
Ball Valve
14
P/T
Ports
FROM
HWG
HWG
WaterFurnace
NSKW Series
TO
PUMP
Source OUT
P/T Ports
Source IN
HOT
(Piped in
series to
an electric
water heater)
COLD
DOMESTIC
Accessories and Options
Geo Storage Tank Dimensions
NSKW INSTALLATION MANUAL
°
3
0
0
3
°
From Geo
PRIMARY ANODE 99 cm - 80 Gallon
106.7 cm - 119 Gallon
HOT OUTLET
w/35.6 cm SECONDARY ANODE
Approx. 2.54 cm
T & P
VALVE
HEIGHT
90.8 cm
To Geo 150 cm Dip Tube
20.3 cm
COLD INLET
132.0 cm DIP TUBE
Yellow Wire attached to Thermistor or Thermostat for Top Exit
Element Location
Lower Sensor Thermistor (12P541-01) to be used by Water to Water Units
Optional “From Geo” Connection
13.3 cm
Model
Number
GEO-STORAGE-80
GEO-STORAGE-120
DRAIN VALVE
Gallon [Liter]
Capacity
80 [303] 4500 1 16 160.6 61.0 92.5
119 [450] 4500 1 16 160.6 71.1 141.1
Element
Wattage
(240 Volt)
DIAMETER
Number
of
Elements
R
Value
Lower Thermostat
Dimensions in cm
Height Diameter
Approx Shipping
Weight kg
15
NSKW INSTALLATION MANUAL
Electrical Data
Model
06
08
12
17
Notes:
* - With optional IntelliStart, Type D MCB recommended
NSKW Control Box
Optional IntelliStart
(Single Phase Only)
Rated
Voltage
220-240/50/1 198/264 17.5 11.2 60.0 24.0 1.5 4.5 17.2 20.0 30
380-420/50/3 342/462 6.5 4.2 28.0 16.8 - - 4.2 5.3 6
220-240/50/1 198/264 27.0 17.3 97.0 34.0 1.5 4.5 23.3 27.6 40
380-420/50/3 342/462 10.0 6.4 45.0 27.0 - - 6.4 8.0 10
220-240/50/1 198/264 31.5 20.2 126.0 44.0 1.5 4.5 26.2 31.2 50
380-420/50/3 342/462 12.1 7.8 51.5 31.0 - - 7.8 9.8 15
220-240/50/1 198/264 45.0 29.0 130.0 46.0 1.5 4.5 35.0 42.3 70
380-420/50/3 342/462 19.0 12.2 87.0 52.0 - - 12.2 15.3 25
®
Voltage
Min/Max
MCC RLA LRA LRA*
Compressor
Load
Pump
FLA
Source
Pump
FLA
Total
Unit FLA
Terminal Board
Terminal Power Strip
Min
Circ
Amp
Max Fuse/ HACR
1/15/15
Power Block
(IntelliStart Only)
Compressor Contactor
Run Capacitor
(Single Phase Only)
Ground Lug
Transformer
Load Pump Relay
Power Block
Reversing Valve Relay (Reversible Units Only)
Source Pump Relay
16
Loading...
+ 32 hidden pages