Envision NDS026 Series, NDS064 Series, NDS072 Series, NDS038 Series, NDS049 Series Installation Manual

Page 1
Installation Information
Water Piping Connections
Electrical Data
Startup Procedures
Troubleshooting
Preventive Maintenance
NDS Installation Manual
IM1004SN 03/11
Page 2
Page 3
Table of Contents
Model Nomenclature........................................................... 4
General Installation Information ................................................5-8
Water Quality ................................................................. 8
Water Piping.................................................................. 9
Electrical Data ................................................................10
Thermostat Wiring ............................................................10
Dimensional Data..............................................................11
Physical Data .................................................................11
Model Nomenclature - Air Handler ...............................................12
Coil Data - Air Handler .........................................................12
Physical Data - Air Handler .....................................................13
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Model Nomenclature - Coil .....................................................13
Refrigerant Coil Compatibility...................................................13
Wiring Schematics..........................................................14-17
Microprocessor Control .....................................................18-21
Operation Logic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
DIP Switch Settings........................................................... 22
Refrigeration ............................................................. 23-24
Line Set Sizes ................................................................ 24
Pressure/Temperature Conversion Chart for R-410A............................... 25
Operating Parameters......................................................... 26
Pressure Drop................................................................ 27
Compressor and Thermistor Resistance ......................................... 27
Refrigerant Circuit Guideline ................................................... 28
Heat of Extraction/Rejection Data .............................................. 28
Reference Calculations........................................................ 29
Legend ..................................................................... 29
Operating Limits .............................................................29
Startup and Troubleshooting................................................ 30-32
Preventative Maintenance ..................................................... 33
Replacement Procedures ......................................................33
Service Parts List ............................................................. 34
Page 4
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Model Nomenclature
1 2 3
D S
N
Model Type
N = Envision
Compressor Type
D = Dual Capacity
Cabinet Configuration
S = Outdoor Split
Unit Capacity 026
038 049 064 072
NOTE: *026-049 uses the FC1-GL and 060-072 uses the FC2-GL, the flow center is factory installed. If these flow centers do not meet the flow requirements, select A = None for digit 10.
4-6
0497A819010A11C
Coax Options
C = Copper N = Cupronickel
Flow Center
A = None B = Flow Center*
IntelliStart Options
0 = No IntelliStart 3 = IntelliStart
Voltage
1 = 208-230/60/1
Vintage
A = Current
4
Page 5
General Installation Information
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to both units. Turn off accessory heater power switch if applicable. Electrical shock could cause personal injury. Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply, such as the following safety measures:
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use a quenching cloth for brazing operations.
• Have a fire extinguisher available for all brazing operations.
Moving and Storage
Move units in the normal “up” orientation. Units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
Condensate Drain
Follow the blower coil manufacturer’s instructions.
Duct System
All blower coil units/air coils must be installed as specified by the manufacturer’s installation instructions; however, the following recommendations should considered to minimize noise and service problems.
An air filter must always be installed upstream of the air coil on the return air side of the air handler or furnace. If there is limited access to the filter rack for normal maintenance, it is suggested that a return air filter grill be installed. Be sure that the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the filter and plugging the air coil.
In applications using galvanized metal ductwork, a flexible duct connector is recommended on both the supply and return air plenums to minimize vibration from the blower. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of 1-inch thick glass fiber or be constructed of ductboard. Insulation is usually not installed in the supply branch ducts. Ducts in unconditioned areas should be wrapped with a minimum of 1-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected. If the air handler is connected to existing ductwork, a previous check should have been made to assure that the duct system has the capacity to handle the air required for the unit application. If ducting is too small, as in replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repairs made accordingly. The duct systems and diffusers should be sized to handle the design airflow quietly. If air noise or excessive airflow is a problem, the blower speed can be changed to a lower speed to reduce airflow. This will reduce the performance of the unit slightly in heating; however, it will increase the temperature rise across the air coil. Airflow must still meet minimum requirements.
Split Unit Location
Locate the split compressor section away from areas that may disturb the customer and in a way that allows easy removal of the access panels and the top of the cabinet. Provide sufficient room to make water, electrical and refrigerant line connections and allow space for service personnel to perform maintenance. The NDS split is approved for outdoor installation when properly installed.
Air Coil Location
Refer to the air handler manufacturer’s instructions for the blower coil unit for details on installing the air handling portion of the system.
Equipment Selection
The following guidelines should be used when mating an Envision Split to an air handler/coil.
• Select R-410A components only.
• Match the air handler to the air handler coil data table.
• Indoor matching adjustable TXV is factory installed on every NAH air handler/coil. Fixed orifice or cap tube systems should not be used.
• Minimum of two (2) blower speeds
Utilizing Existing Coil or Air Handler
It is recommended that a new R-410A air handler be installed with an Envision Split considering the long term
5
Page 6
NDS OUTDOOR SPLIT INSTALLATION MANUAL
General Installation Information cont.
benefits of reliability, warranty, etc. versus the short term installation cost savings. However, the existing air handler may be retained provided the following:
Coil currently is R-410A rated
Coil uses a TXV. No capillary or fixed orifice systems should be used
A life expectancy of more than 7 years remaining for the air handler and components
Flush air coil and line set
When utilizing the existing air coil or line set, only flushing compounds that vaporize should be used; which means they are packaged in a pressurized disposable cylinder. It is preferable to use a flushing agent that removes oil, water, and acid, plus, is biodegradeable and non-toxic. The flushing agent should be safe to use with both HCFC and HFC refrigerants. Once a flushing agent has been selected, follow the instructions provided with the product.
The first step should be purging the lines or air coil with nitrogen. Purging with nitrogen first will remove some of the particulate and residual oil which will allow the flushing agent to work better. Never blow the flushing agent through a compressor, filter drier, or txv as it will cause the components to fail.
When flushing is complete and the final system is assembled, an acid check should be preformed on the system. Acid test kits are available from most HVACR distributors.
An air filter must always be installed upstream of the air coil on the return air side of the air handler or furnace. If there is limited access to the filter rack for normal maintenance, it is suggested that a return air filter grille be installed. Be sure that the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the filter and plugging the air coil.
Ensure that the line set size is appropriate to the capacity of the unit (refer to Line Set Sizes table). Line sets should be routed as directly as possible, avoiding unnecessary bends or turns. All wall penetrations should be sealed properly. Line set should not come into direct contact with water pipes, floor joists, wall studs, duct work, floors, walls and brick. Line set should not be suspended from joists or studs with a rigid wire or strap which comes into direct contact with the tubing. Wide hanger strips which conform to the shape of the tubing are recommended. Isolate hanger straps from line set insulation by using metal sleeves bent to conform to the shape of insulation. Line set insulation should be pliable, and should completely surround the refrigerant line.
NOTE: Improper installation of equipment may result in undesirable noise levels in the living areas.
Typical Split System Application ­Remote Blower Coil
Connection to Air Coil
Typical Split System Application - Remote Blower Coil and Typical Split System Heat Pump Coil Add-on Fossil Fuel Furnace illustrations show typical Envision Split installations. The Line Set Sizes table shows typical line set diameters and maximum length. Line sets over 60 feet are not recommended. If the line set is kinked or deformed and cannot be reformed, the bad section of pipe should be replaced. A restricted line set will affect unit performance. As in all R-410A equipment, a reversible liquid line filter drier is required to ensure all moisture is removed from the system. This drier should be replaced whenever “breaking into” the system for service. All line sets should be insulated with a minimum of 1/2” closed cell insulation. All exterior insulation should be painted with UV resistant paint or covering to ensure long insulation life.
Air Handler Installation
Air handlers used with dual capacity units must be capable of operating with a minimum of 2 blower speeds. Refer to the manufacturer’s instructions for the blower coil unit for details on installing the air handling portion of the system. All blower coil units/air coils must be installed as specified by the manufacturer’s installations instructions. However, the following recommendations should be considered to minimize noise and service problems.
Insulated
Suction Line
Lineset
To Air Handler
Condensate Drain (must be trapped)
Disconnect
Low
Voltage Wire
Remote Air Handler
(Maximum Recommended Distance is
60' Between Units)
Supply
Duct
Air
Handler
Return
Duct
6
Page 7
General Installation Information cont.
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Dual Fuel Systems
Envision units can be connected to fossil fuel furnaces that include an A-coil or slab coil. Dual fuel installations utilize the Envision heat pump for heating until the point that auxiliary heat is called for on the thermostat. At that point, the furnace will be enabled and the heat pump will be disabled. The Envision heat pump provides air conditioning through the furnace’s refrigerant coils.
Refer to the furnace manufacturer’s installation manual for the furnace installation, wiring and coil insertion. A WaterFurnace Dual Fuel thermostat or a field-installed DPST relay is required. See the Typical Split System Heat Pump Coil Add-on Fossil Fuel Furnace illustration for typical Dual Fuel application.
Typical Split System Heat Pump Coil Add-on Fossil Fuel Furnace
Disconnect
Insulated
Suction Line
In add-on Envision Split applications, the coil should be located in the supply side of the furnace to avoid condensation damage to the furnace heat exchanger. A high temperature limit should be installed upstream of the coil to de-energize the compressor whenever the furnace is operating. Without this switch, the Envision Split will trip out on high pressure. A dual fuel thermostat can remove the Y1 and Y2 calls when a W call is energized to allow gas furnace backup on an Envision Split application. Refer to the Thermostat Wiring section for details.
Supply Duct
"A" or
Slab Coil
Lineset To Air Handler
Wire From Furnace
Thermostat
Wire To
Thermostat
Return
Duct
Condensate
Drain
(must be trapped)
Up-Flow
Fossil Fuel
Furnace
7
Page 8
NDS OUTDOOR SPLIT INSTALLATION MANUAL
mpp 02 naht sseLmpp 2 naht sseLmpp 2 naht sseLainommA
mpp 5. naht sseLmpp 5. naht sseLmpp 5. naht sseLetafluS ainommA
Water Quality
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period
with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing. Failure to adhere to the guidelines in the water quality table
could result in loss of warranty. of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils can likewise become scaled and possibly plugged. In areas
pH Acidity/Alkalinity 9 - 7 9 - 7 9 -7
Scaling Calcium and Magnesium Carbonate (Total Hardness) less than 350 ppm (Total Hardness) less than 350 ppm (Total Hardness) less than 350 ppm
Hydrogen Sulfide
Corrosion mpp 5. naht sseLmpp 5. naht sseLmpp 5. naht sseLedirolhC ainommA
LSI Index
Iron Fouling
(Biological Growth) Iron Oxide
Erosion Suspended Solids
Note:
Grains = PPM divided by 17 mg/l is equivalent to PPM
Bacterial Iron Potential
Less than .5 ppm (rotten egg smell
appears at 0.5 PPM)
+
0.5 to -.05
Less than 1 ppm. Above this level
deposition will occur.
Less than 10 ppm and filtered for max of
600 micron size
Units with cupronickel heat exchangers are recommended
for open loop applications due to the increased resistance
to build-up and corrosion, along with reduced wear caused
by acid cleaning.
+
0.5 to -.05
Less than 1 ppm. Above this level
deposition will occur.
Less than 10 ppm and filtered for max of
600 micron size
Less than 1 ppm. Above this level
Less than 10 ppm and filtered for max of
+
0.5 to -.05
deposition will occur.
600 micron size
leetS sselniatS 613lekciN-orpuC 01/09reppoClairetaM
mpp 1 naht sseLmpp 05 - 01
mpp 002 naht sseLmpp 521 naht sseLmpp 521 naht sseLsetafluS
mpp 5. naht sseLmpp 5. naht sseLmpp 5. naht sseLenirolhC
mpp 003 naht sseLmpp 521naht sseLmpp 02 naht sseLsedirolhC
mpp 05 -01mpp 05 - 01mpp 05 naht sseLedixoiD nobraC
mpp 5. naht sseLmpp 5. naht sseLmpp 5. naht sseLetartiN ainommA mpp 5. naht sseLmpp 5. naht sseLmpp 5. naht sseLedixordyH ainommA
mpp 0051-0001mpp 0051-0001mpp 0001 naht sseL)SDT( sdiloS devlossiD latoT
mpp 2. < mpp 2. < mpp2. <
ces/tf 6<ces/tf 6 <ces/tf 6 < )retaW hserF( yticoleV dlohserhT
8
Page 9
Water Piping
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Residential NDS split units are supplied standard with GeoLink swivel connections with P.T. ports.
CAUTION: Water piping exposed to outside temperatures may be subject to freezing.
Water Piping
The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger.
Closed Loop - Earth coupled Systems (Outdoor Installations)
Locate unit on an air pad with access hole as shown below. When mounting on an existing concrete pad, holes must be bored through to accommodate 1 1/4-inch P.E. pipe with 1/2-inch insulation.
Connecting To Earth Loop
The earth loop trench should be continued directly under the unit as shown in the Typical Split System Outdoor Installation Using Closed Loop. Make the connections to optional fittings from the loop circulator pump(s) and ensure proper backfill to support the loop pipe during trench settling. All 1 1/4-inch piping should be insulated with a minimum of 1/2-inch closed cell insulation from below the ground surface to the loop circulator.
Flow Center Installation
Flow centers FC1-GL or FC2-GL, as needed, may be internally mounted on the NDS splits, Two stub tubes with barbs are pre connected to the coax. Two tubes with brass fittings, to adapt to the flow center, 2 hoses to connect between the two sets of tubes, and four hose clamps are included with each NDS unit. The brass adapter fittings have plastic swivel connectors that also accept 1 in. O.D. copper pipe (sweat).
NOTE: For ease of installation, attach provided hoses to coax first and then trim to fit to elbows on flow center.
Typical Split System Outdoor Installation Using Closed Loop
IMPORTANT: A freeze detection thermostat is installed in the unit to automatically start loop circulator pump if loop temperature drops below 20°F. Loop freeze detection should also be maintained to the lowest temperature the insulated loop may encounter in the case of power failure.
Open Loop (Indoor Installations)
NDS Splits can be installed on an open loop system, but only indoors. All NDS Splits are supplied with GeoLink swivel connectors. The swivel connectors will also accept a 1 in. O.D. copper pipe (sweat) which can be connected in an open loop system.
Loop Supply and Return Piping
9
Page 10
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Typical EZ Wiring Diagram
Electrical Data
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable. See unit electrical data for fuse or cicuit breaker sizing information.
Model
026
038
049
064
072
Rated
Voltage
208-230/60/1 197/253 16.0 10.2 52.0 18.0 5.4 15.6 17.0 25
208-230/60/1 197/253 26.0 16.6 82.0 29.0 5.4 22.0 23.4 40
208-230/60/1 197/253 33.0 21.1 96.0 34.0 5.4 26.5 2 7. 9 50
208-230/60/1 197/253 40.0 25.6 118.0 41.0 5.4 31.0 32.4 60
208-230/60/1 197/253 42.5 2 7.2 150.0 53.0 5.4 32.6 34.0 60
Rated voltage of 208-230/60/1. HACR circuit breaker in USA only. Min/Max voltage of 197/253. All fuses Class RK-5 * With optional IntelliStart
Thermostat Wiring
Thermostat Wiring
Air Handler
C
R
W
G
Common Common
24 VAC
Fan
Thermostat
Y1
Y2
O
L
C
R
W
G
Voltage
Min/Max
1st Stage Compressor
2nd Stage Compressor
Reversing Valve
Fault Signal
24 VAC
Compressor Ext
MCC RLA LRA LRA*
Thermostat Wiring for Dual Fuel Applications
Envision Split
Y1
Y2
O
P1
Lo
C
R
Fossil Fuel
Furnace
C
R
W
G
Auxiliary Heat Relay
Loop
FLA
Thermostat
Y1
Y2
O
L
Common Common
24 VAC
Fan
C
R
G
W
Unit FLA
1st Stage Compressor
2nd Stage Compressor
Reversing Valve
Fault Signal
24 VAC
Total
Auxiliary
Heat Relay
Min
Circ
Amp
Max Fuse/ HACR
Envision Split
Y1
Y2
O
LO
C
R
Shut
Down
1/17/11
P1
P2
Air Handler transformer must be at least 75 VA.
Note: Field installed DPST dual fuel relay
(Required for dual fuel installation) or use TP32U03 or TP32U04
10
Auxiliary Heat Relay
= chassis
Page 11
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Dimensional Data
Cabinet Dimensions and Refrigerant Piping Connections
Top View
B
Rear View
J
K
L
WATER OUT
WATER IN
Suction Line
Connection
Liquid Line
Connection
Front View
D
E
F
H
I
G
Lineset connections are braze type internally mounted
Side View
Side View
M
Model A B C D E F G H I J K L M
in
026 thru 072
Refer to Physical Dimensions and Piping Connections drawings
36.0 23.9 26.7 9.3 7.1 9.0 5.6 8.2 10.7 18.9 8.7 14.8 7.0
[cm] [91.4] [60.7] [67.8] [23.7] [18.0] [22.8] [14.2] [20.9] [27.2] [48.0] [22.1] [37.6] [17.8]
A
C
Physical Data
Model 026 038 049 064 072
Compressor (1 each) Dual Capacity Scroll Factory Charge R-410A, oz [kg] 52 [1.47] 56 [1.59] 90 [2.55] 92 [2.61] 104 [2.95]
Coax and Water Piping
Water Connections Size - Swivel- in [mm] GeoLink Swivel Connectors Brass Service Valve - Liquid Line - in [mm] 3/8 [9.525] 1/2 [12.7] Brass Service Valve - Suction Line - in [mm] 5/8 [15.875] 3/4 [19.05] 7/8 [22.2 25] Coax and Piping Water Volume - gal [l] 0.7 [2.6] 1.3 [4.9] 1.6 [6.1] 1 .6 [6.1] 1.6 [6.1] Weight - Operating, lb [kg] 189 [86] 236 [107] 250 [ 113] 271 [123] 290 [132] Weight - Packaged, lb [kg] 209 [95] 256 [116] 270 [122] 291 [132] 3 10 [141]
All units have TXV expansion devices, and 1/2 in. [12.2 mm] and 3/4 in. [19.1 mm] electrical knockouts. Brass service valves are sweat type valves.
10/29/08
11
Page 12
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Model Nomenclature - Air Handler
1-3 4-6 7 8-9 10 11 12
NAH 036 A 00 0 1 R
Model Type Air Coil
NAH = Envision Series Air Handler R = Refrigerant
Unit Capacity
Refrigerant Models Nom. CFM Motor
022 MBTUH 800 1 = ECM 208-230/60/1 026 MBTUH 925 030 MBTUH 980 036 MBTUH 1225 042 MBTUH 1425 048 MBTUH 1625 060 MBTUH 1760
Hydronic Models
026 MBTUH 925 036 MBTUH 1225 Electric Heat 048 MBTUH 1625 00 = No electric heat 060 MBTUH 1760 05 = 5 kW (available on 022-036 only)
Vintage 15 = 15 kW (available on 042-060 only) A = Current 20 = 20 kW (available on 060 only)
H = Hydronic
Disconnect
0 = No breaker installed (only on 5kW & 10kW heaters) 1 = Breaker installed (only on 15kW & 20kW heaters)
10 = 10 kW (available on 030-060 only)
NOTE: Kit NAHBC must be ordered to field convert the NAH042-060 to bottomflow air discharge.
Coil Data - Air Handler
Envision Split Model Matching Air Handler Coil Surface Area (ft2) FPI Rows Tube Diameter
022 - 038
042 - 072
NAH036 5.83 12 2 3/8 in.
NAH060 5.83 12 3 3/8 in.
Compatibilty Table - Air Handler
Air Handler
NAH022A***1R
NAH026A***1R
NAH030A***1R
NAH036A***1R
NAH036A***1R
NAH042A***1R
NAH048A***1R
NAH048A***1R
NAH060A***1R
NAH060A***1R
NAH060A***1R
NAH060A***1R
Indoor Split Model
(Single)
NSZ022 - 800 5
- NDZ026 NDS026 925 5
NSZ030 - - 980 5, 10
NSZ036 - - 1225 5, 10
- NDZ038 NDS038 1225 5, 10
NSZ042 - - 1425 10, 15
NSZ048 - - 1625 10, 15
- NDZ049 NDS049 1625 10, 15
NSZ060 - - 1760 10, 15, 20
- NDZ064 NDS064 1760 10, 15, 20
NSZ070 - - 1760 10, 15, 20
- NDZ072 NDS072 1760 10, 15, 20
Indoor Split Model
(Dual Capacity)
Outdoor Split Model
(Dual Capacity)
Airflow(CFM) Electric Heat (kW)
6/9/08
12
Page 13
Physical Data - Air Handler
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Air Handler Model Number (Refrigerant)
Air Coil Total Face Area, ft2 [m2] Tube outside diameter - in. [mm]
Evaporator
Coil
Refrigerant R-410a Nominal cooling capacity - tons [kW] 1.8 [6.44] 2.1 [7.59] 2.5 [8.79] 3 [10.55] 3.5 [12.30] 4 [14.06] 5 [17.58] Condensate drain connection - (FPT) in. [mm] Blower Wheel Size (Dia x W), in. [mm] Blower motor type/speeds Blower motor output - hp [W] Filter Standard - 1" [51mm] MERV3 disposable, in. [mm] Electrical characteristics (60hz) Shipping weight - lbs. [kg] Operating weight - lbs. [kg]
Number of rows Fins per inch Suction line connection - in. [mm] sweat Liquid line connection - in. [mm] sweat
NAH022 NAH026 NAH030 NAH036 NAH042 NAH048 NAH060
5.83 [0.54] 3/8 [9.52]
2 3
12
5/8 [15.87] 7/8 [22.22]
3/8 [9.52]
3/4 [19.05]
11 x 10 [279 x 254]
ECM variable speed
1/2 [373] 1 [746]
20 x 24 [508 x 635]
208/230 - 1ph
215 [97.52] 220 [99.79]
195 [88.45] 200 [90.71]
Model Nomenclature - Coil
1-2 3
NR
A
Model Type
NR = Envision Refrigerant Coil NH = Envision Hydronic Coil
Configuration Refrigerant Models
A = "A" Coil 026 MBTUH
Coil
4
C
5-7
026
8
C
Cabinet
C = Encased U = Uncased
Capacity
036 MBTUH 048 MBTUH 060 MBTUH
Hydronic Models
060 MBTUH
1/11/08
NOTE: All Refrigerant Coils include TXV.
Refrigerant Coil Compatibility
Encased/Uncased Coil
NRAC026* NSZ022 - 800 NRAC026* - NDZ026 NDS026 925 NRAC026* NSZ030 - - 980 NRAC036* NSZ036 - - 1225 NRAC036* - NDZ038 NDS038 1225 NRAC048* NSZ042 - - 1425 NRAC048* NSZ048 - - 1625 NRAC048* - NDZ049 NDS049 1625 NRAC060* NSZ060 - - 1760 NRAC060* - NDZ064 NDS064 1760 NRAC060* NSZ070 - - 1760 NRAC060* - NDZ072 NDS072 1760
Indoor Split Model
(Single)
Indoor Split Model
(Dual Capacity)
13
Outdoor Split Model
(Dual Capacity)
Recommended Airflow
(CFM)
7/14/08
Page 14
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Thermistor
Light Emitting Diode - Green
Relay Coil
Capacitor w/ Bleed Resistor
Switch-High Pressure
Switch-Low Pressure
Polarized Connector
Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Internal junction Quick connect terminal
Wire nut
Field wire lug
Ground
Fuse
CC - CR1 - CR2- CR3 - CR4 - F1 and F2 - FD - HP - LP - RV - SW1 - SW2 - SW3 -
Compressor Contactor
Loop Pump Relay1
Fuses Freeze Detection sensor High Pressure Switch Low Pressure Switch Reversing Valve Coil Not Used DIP Package 8 Position DIP Package 5 Position
Relay Contacts - N.O., N.C.
G
T
132
P
L1
Loop Pump Relay2 Not Used
CS -
Compressor Solenoid
Not Used
Legend
1 - Connection of remote unit that does not have a loop pump for slave operation. 2 - 24V Accessory relay (see SW2 -3 for description of operation) 3 - Field installed DPDT dual fuel relay. (Required for dual fuel installation) 4 - DHW pump only in models with hot water generation option. 5 - Comfort Alert fault output to Premier Control Board 6 - This Switch allows the unit to down stage with the t-stat when OFF and finish on second stage when ON. Finish second stage reduces stage changing in recip dual capacity compressors and should be ON for unzoned Dual Cap E-Series or Premier 2 speed units.
Notes
Crankcase Heater
CA -
Comfort Alert
LED Flash Code Desc ription
Green S olid Module Has Power
Red Solid Y1 Present But Compressor Not Running
Code 1 Long Run Time Code 2 Sy stem Pressure Trip Code 3 Short Cyc ling Code 4 Locked Rotor Code 5 Open Circuit Code 6 Open Start Circuit Code 7 Open Run Circuit Code 8 W elded Contactor Code 9 Low Voltage
Yellow
Comfort Alert Status
Wiring Schematics
Dual Capacity Split - 208-230/60/1
Loop Pump(s)
Comfort
Alert
R C
Y2
Y
1/2 HP 208-230/60/1
Pump
Recovery
Violet (3)
CC
Heat
Unit
Pump
G
NOTE 1
C
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
L2
L1
Yellow (6)
Black (5)
White (4)
Violet (2)
Black (1)
CR1
CCHI
CC-GND P1
R
C
Y1
Y2
W
O
G
LO
P2 Shut Down
C
SL1 In
SL1 Out
Not
Used
NOTE 2
P3
Acc Com
Acc NC
Acc NO
1 2 3
Gray(9)
Yellow(8)
NO
COM
CR2
CC
1
2
3
4
5
6
7
8
1
1
1 2
2
2 3
3
3C 4
5
6
7
1
2
3
ECM2 Air Flow Settings
SW1
P4
S
C
R
Blue
Unit Power
208-230/60/1
G
FP
Red (11)
Crankcase Heater
Black Black
Fused L2
NO
COM
Fused L2
NO NC
COM
CR3
NO NC
CR4
Black (7)
Comfort Alert
Run
Capacitor
Red (12)
Green/Yellow
F1-10A 240V
COM
Fused L1
Microprocessor
Logic Control (DC Voltage)
SW2
On
On
1 2 3 4 5 6 7 8 9
10
NOT USED
11 12
1
Test / Norm
2
Loop / Well
3
Fan / Comp
4
Not Used
5
Not Used
6
Inputs / Norm
7
Outputs / Norm
8 Pulse L / Constant L
SW3
On
Dual/ Single Capacity
1 2
3 4 5
nd
Normal/Finish on 2 No RPM / RPM Must be On Envision / E Series or Premier
NOTE 6
Tan (16)
240V L2
Orange (14)
Red Black
CC
L2 L1
Brown (15)
240V L1
P6
8
13
7
4
5
14
12
6
15
10
9
2
1
3
11
16
P5
11
4
9
2
10
3 8
1
12
5
13
6
7
14
DC SOL
CS
+
-
Comfort A lert
RV
T
LP
HP
FD
F1-10A 240V
R
C
Tan
Orange
Orange
Not Used
Not Used
Not Used
Not Used
Yellow
Yellow
Blue
Blue
Black
Black
NOTE 5
L
NOT USED
R
R
R
R
R
G
Status LED PCB
Y
R
SW4
LED Normal Display Mode
Field Selection Dips - #1 On, #6 On, #7 On Not Used
Drain
FD thermistor (loop<15°F,well<30°F) Lockout
Water Flow
High Pressure
High Press
Low Pressure / Comfort Alert
Low Press/CA
Not Used
Air Flow
Microprocessor malfunction*
Status
Not Used
DHW Limit
Not Used
DHW off
*Green LED not flashing
14
Current Fault Status
#1 Off, #6 On, #7 On Not Used FD thermistor (loop<15°F, well<30°F) High Pressure Low Pressure / Comfort Alert Not Used Not Used Not Used Not Used
Diagnostic Modes
Inputs
#6 Off, #7 On
Y1 Y2
O Not Used Not Used
SL1 SL2
Outputs
#6 On, #7 Off Lo Capacity Compressor Hi Capacity Compressor
RV FAN
Not Used Loop Pump 1 Loop Pump 2
Outpu ts2
#6 Off, #7 Off
Not Used Not Used Not Used Not Used Not Used Not Used Not Used
Not UsedNot UsedNot Used
Page 15
Wiring Schematics cont.
Dual Capacity Split - 208-230/60/1 cont.
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Notes
1 - Connection of remote unit that does not have a loop pump for slave operation. 2 - 24V Accessory relay (see SW2 -3 for description of operation) 3 - Field installed DPDT dual fuel relay. (Required for dual fuel installation) 4 - DHW pump only in models with hot water generation option. 5 - Comfort Alert fault output to Premier Control Board 6 - This Switch allows the unit to down stage with the t-stat when OFF and finish on second stage when ON. Finish second stage reduces stage changing in recip dual capacity compressors and should be ON for unzoned Dual Cap E-Series or Premier 2 speed units.
Legend
Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Internal junction Quick connect terminal
Wire nut
Field wire lug
L1
Ground
Relay Contacts ­N.O., N.C.
Fuse
CA ­CS ­CC ­CR1 ­CR2­CR3 ­CR4 ­F1 and F2 ­FD ­HP ­LP ­RV ­SW1 ­SW2 ­SW3 -
P
Comfort Alert Compressor Solenoid Compressor Contactor Not Used Loop Pump Relay1 Loop Pump Relay2 Not Used Fuses Freeze Detection sensor High Pressure Switch Low Pressure Switch Reversing Valve Coil Not Used DIP Package 8 Position DIP Package 5 Position
Crankcase Heater
Thermistor
T
Light Emitting Diode - Green
G
Relay Coil
Capacitor w/ Bleed Resistor
Switch-High Pressure
Switch-Low Pressure
132
Polarized Connector
240V - L1
CR1- DHW
Pump
CC-GND
CC
CCLO CCHI
P4
1 2 3 4 5 6 7 8
1 2 3
R C Y1 Y2 GOW L
Logic Board - Physical Layout
240V - L1
N.O.
Fused L1
F1
N.O.
CR2- Loop Pump
Fused L2
CR3-
N.C. N.O.
Microprocessor
SW1
SW2
OnOff
C C R R
P1
LED Flash Code Desc ription
Green S olid Module Has Power
Red Solid Y1 Present But Compressor Not Running
Yellow
OnOff
1 2 3 4 5 6 7 8 9 10 11 12
Code 1 Long Run Time Code 2 Sy stem Pressure Trip Code 3 Short Cyc ling Code 4 Locked Rotor Code 5 Open Circuit Code 6 Open Start Circuit Code 7 Open Run Circuit Code 8 W elded Contactor Code 9 Low Voltage
1 2 3 4 5 6 7 8
2
3 4 5P26 71
Shut
C C
Down
Comfort Alert
Physical Layout
POWER
Y2
Y
Data Port
L
R
C
DC Sol
ALERT
TRIP
Comfort Alert Status
Fused L2
Com
SL1INSL1
SW3
Fused L2
Fused L2
240V - L2
240V - L2
F1
N.O.
Com
CR4-
9
1
10
2
11
3
12
4
P6
13
5
14
6
15
7
16
Out
8 9
10 11 12 13 14
P3
1 2 3
ACCNOACCNCACC
8
1 2
3
P5
4 5 6
7
COM
OnOff
1 2 3 4 5
SL2INSL2
Out
97P788-01 4/19/10
15
Page 16
NDS OUTDOOR SPLIT INSTALLATION MANUAL
1 2 3
P4
Thermistor
Light Emitting Diode-Green
Relay Coil
Capacitor w/ Bleed Resistor
Switch - High Pressure
Switch - Low Pressure
Polarized Connector
Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Internal junction Quick connect terminal
Wire nut
Field wire lug
Ground
Fuse
CC - CR1 - CR2- CR3 - CR4 - F1 and F2 - FP -
HP - LP - RV - SW1 - SW2 - SW3 -
Compressor Contactor
Loop Pump Relay 1
Fuses Freeze Detection sensor High Pressure Switch Low Pressure Switch Reversing Valve Coil Not Used DIP Package 8 Position DIP Package 5 Position
Relay Contacts - N.O., N.C.
G
T
132
P
L1
Loop Pump Relay 2 Not Used
CS -
Compressor Solenoid
Not Used
Legend
Crankcase Heater
CA - Comfort Alert
1 - Connection of remote unit that does not have a loop pump for slave operation. 2 - 24V Accessory relay (see SW2 -3 for description of operation) 3 - Field installed DPDT dual fuel relay. (Required for dual fuel installation) 4 - DHW pump only in models with hot water generation option. 5 - Comfort Alert fault output to Premier Control Board 6 - This Switch allows the unit to down stage with the t-stat when OFF and finish on second stage when ON. Finish second stage reduces stage changing in recip dual capacity compressors and should be ON for unzoned Dual Cap E Series or Premier 2 speed units.
Notes
Run Winding
Active
Start
Common
IntelliStart
2
1
PB2
Red
Blue
Pink
Black
LED Flash Code Desc ription
Green Solid Module Has Power
Red Solid Y1 Present But Compressor Not Running
Code 1 Long Run Time Code 2 Sys tem Pressure Trip Code 3 Short Cyc ling Code 4 Locked Rotor Code 5 Open Circuit Code 6 Open Start Circuit Code 7 Open Run Circuit Code 8 Welded Contactor Code 9 Low Voltage
Yellow
Comfort Alert Status
Wiring Schematics cont.
Dual Capacity Split with IntelliStart - 208-230/60/1
Loop Pump(s)
Comfort
Alert
R C
Y2
Y
Violet (3)
CC
1/2 HP 208-230/60/1
Pump
G
Heat
Recovery
Unit
Yellow (6)
NOTE
1
C
SL1 In
SL1 Out
Optional
Remote Unit
Without
Loop Pump
Pump
L2
L1
Black (5)
White (4)
Violet (2)
Black (1)
CR1
CCHI
CC-GND P1
R
C
Y1
Y2
W
O
G
LO
P2 Shut Down
C
SL1 In
SL1 Out
Not
Used
NOTE 2
P3
Acc Com
Acc NC
Acc NO
1 2 3
Gray(9)
Yellow(8)
SW1
CR2
ECM 2 Air Flow Settings
NO
COM
SW2
On
1 2 3 4 5 6 7 8 9
10
NOT USED
11 12
NO
COM
CC
1
2
3
4
5
6
7
8
1
1
1 2
2
2 3
3
3C 4
5
6
7
1
2
3
P4
Fused L2
NO NC
CR3
On
1
Red (11)
Fused L2
COM
Microprocessor
Logic Control (DC Voltage)
Test / Norm
2
Loop / Well
3
Fan / Comp
4
Not Used
5
Not Used
6
Inputs / Norm
7
Outputs / Norm
8 Pulse L / Constant L
Unit Power
208-230/60/1
G
FP
Crankcase Heater
Black B lack
NO NC
CR4
Black (7)
SW3
On
Dual/ Single Capacity
1
Normal/Finish on 2
2
No RPM / RPM
3
Must be On
4
Envision / E Series or Premier
5
Blue
Comfort Alert
Run
Capacitor
Red (12)
Green/Yellow
F1-10A 240V
COM
nd
NOTE 6
240V L2
Fused L1
Tan (16)
Orange (14)
S
R
CC
T2
L2 L1
C
Brown (15)
240V L1
P6
8
13
7
4
5
14
12
6
15
10
9
2
1
3
11
16
P5
11
4
9
2
10
3 8
1
12
5
13
6
7
14
Black
DC SOL
CS
+
-
Red
T1
F1-10A 240V
R
C
NOT USED
NOTE 5
Tan
Orange
Orange
Not Used
Not Used
Not Used
Not Used
Yellow
Yellow
Blue
Blue
Black
Black
Comfort A lert
L
RV
T
LP
HP
FD
Status LED PCB
SW4
R
R
R
R
R
G
Y
R
LED Normal Display Mode
Field Selection Dips -#1 On, #6 On, #7 On
Drain
Not Used
Water Flow
FD thermistor (loop<15°F,well<30°F) Lockout
High Press
High Pressure
Low Press/CA
Low Pressure / Comfort Alert
Air Flow
Not Used
Status
Microprocessor malfunction*
DHW Limit
Not Used
DHW off
Not Used
*Green LED not flashing
Current Fault Status
#1 Off, #6 On, #7 On Not Used FD thermistor (loop<15°F, well<30°F) High Pressure Low Pressure / Comfort Alert Not Used Not Used Not Used Not Used
16
Diagnostic Modes
Inpu ts
#6 Off, #7 On
Y1 Y2
O Not Used Not Used
SL1 SL2
Outpu ts
#6 On, #7 Off
Lo Capacity Compressor
Hi Capacity Compressor
RV
FAN
Not Used Loop Pump 1 Loop Pump 2
Outpu ts2
#6 Off, #7 Off
Not Used Not Used
Not Used Not Used Not Used Not Used Not Used
Not UsedNot UsedNot Used
Page 17
Wiring Schematics cont.
Dual Capacity Split with IntelliStart - 208-230/60/1 cont.
NDS OUTDOOR SPLIT INSTALLATION MANUAL
PB2
2
1
Pink
Blue
Black
Red
Run Winding
Active
Start
Common
Legend
Factory Low voltage wiring Factory Line voltage wiring Field low voltage wiring Field line voltage wiring Optional block DC Voltage PCB traces Internal junction Quick connect terminal
Wire nut
L1
Field wire lug
Ground
Relay Contacts ­N.O., N.C.
Fuse
CA - Comfort Alert CS ­CC ­CR1 ­CR2­CR3 ­CR4 ­F1 and F2 ­FP -
HP ­LP ­RV ­SW1 ­SW2 ­SW3 -
P
Compressor Solenoid Compressor Contactor Not Used Loop Pump Relay 1
Loop Pump Relay 2 Not Used Fuses Freeze Detection sensor High Pressure Switch Low Pressure Switch Reversing Valve Coil Not Used DIP Package 8 Position DIP Package 5 Position
Crankcase Heater
Thermistor
T
Light Emitting Diode-Green
G
Relay Coil
Capacitor w/ Bleed Resistor
Switch - High Pressure
Switch - Low Pressure
132
Polarized Connector
IntelliStart
240V - L1
CR1- DHW
Pump
CC-GND
CC
CCLO CCHI
P4
1 2 3 4 5 6 7 8
1 2 3
R C Y1 Y2 GOW L
Logic Board - Physical Layout
240V - L1
N.O.
Fused L1
F1
N.O.
CR2- Loop Pump
Fused L2
CR3-
N.C. N.O.
Microprocessor
SW1
SW2
OnOff
C C R R
P1
LED Flash Code Desc ription
Green Solid Module Has Power
Red Solid Y1 Present But Compressor Not Running
Yellow
OnOff
1 2 3 4 5 6 7 8 9 10 11 12
Code 1 Long Run Time Code 2 Sys tem Pressure Trip Code 3 Short Cyc ling Code 4 Locked Rotor Code 5 Open Circuit Code 6 Open Start Circuit Code 7 Open Run Circuit Code 8 Welded Contactor Code 9 Low Voltage
1 2 3 4 5 6 7 8
2
3 4 5P26 71
Shut
SL1INSL1
C C
Down
Comfort Alert
Physical Layout
POWER
Y2
Y
Data Port
L
R
C
DC Sol
ALERT
TRIP
Comfort Alert Status
240V - L2
Fused L2
Fused L2
Fused L2
240V - L2
F1
N.O.
Com
Com
CR4-
9
1
10
2
11
3
12
4
P6
13
5
14
6
15
Out
16
8 9
10 11 12 13 14
P3
1 2 3
ACCNOACCNCACC
7
8
1 2
3
P5
4 5 6
7
COM
SW3
OnOff
1 2 3 4 5
SL2INSL2
Out
Notes
1 - Connection of remote unit that does not have a loop pump for slave operation. 2 - 24V Accessory relay (see SW2 -3 for description of operation) 3 - Field installed DPDT dual fuel relay. (Required for dual fuel installation) 4 - DHW pump only in models with hot water generation option. 5 - Comfort Alert fault output to Premier Control Board 6 - This Switch allows the unit to down stage with the t-stat when OFF and finish on second stage when ON. Finish second stage reduces stage changing in recip dual capacity compressors and should be ON for unzoned Dual Cap E Series or Premier 2 speed units.
97P788-02 4/19/10
17
Page 18
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Microprocessor Control
Startup
The unit will not operate until all the inputs and safety controls are checked for normal conditions. At first power­up, a four-minute delay is employed before the compressor is energized.
Component Sequencing Delays
Components are sequenced and delayed for optimum space conditioning performance.
Accessory Relay
An accessory relay on the control board allows for field connection of solenoid valves, electronic air cleaners, etc. The accessory relay has a normally open output and a normally closed output.
Short Cycle Protection
The control employs a minimum “off” time of four minutes to provide for short cycle protection of the compressor.
Shutdown Mode
A 24VAC common signal to the “shutdown” input on the control board puts the unit into shutdown mode. Compressor and blower operation are suspended.
Heating Operation
Heat, 1st Stage (Y1)
The blower motor is started on low speed immediately (PSC ON), the loop pump is energized 5 seconds after the “Y1” input is received, and the compressor is energized on low capacity 10 seconds after the “Y1” input. The blower is switched to medium speed 15 seconds after “Y1” input (ECM only).
Heat, 2nd Stage (Y1,Y2) Dual Capacity Units
The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum first stage compressor run time of 1 minute has expired. The ECM blower changes from medium to high speed 15 seconds after the “Y2” input.
The Comfort Alert will delay the second stage compressor until 5 seconds after it receives a “Y2” from the board.
Heat, 3rd Stage (Y1,Y2,W) Dual Capacity Units
The 1st stage of resistance heat is energized 10 seconds after “W” input, and with continuous 3rd stage demand, the additional stages of resistance heat engage 90 seconds after the first stage.
Safety Controls
The Envision control receives separate signals for a high pressure switch for safety, a low pressure switch to prevent loss of charge damage, and a low suction temperature thermistor for freeze detection. Upon a continuous 30-second measurement of the fault (immediate for high pressure), compressor operation is suspended, the appropriate lockout LED begins flashing. (Refer to the “Fault Retry” section below.)
Testing
The Envision control allows service personnel to shorten most timing delays for faster diagnostics. (Refer to the Field Selection DIP switch table.)
Fault Retry
All faults are retried twice before finally locking the unit out. An output signal is made available for a fault LED at the thermostat. The “fault retry” feature is designed to prevent nuisance service calls.
Diagnostics
The Envision control board allows all inputs and outputs to be displayed on the LEDs for fast and simple control board diagnosis. (Refer to the Field Selection DIP Switch SW2-1 table.)
Emergency Heat (W only)
The blower is started on high speed, and the first stage of resistance heat is energized 10 seconds after the “W” input. Continuing demand will engage the additional stages of resistance heat 90 seconds after the first stage.
Cooling Operation
In all cooling operations, the reversing valve directly tracks the “O” input. Thus, anytime the “O” input is present, the reversing valve will be energized.
Cool, 1st Stage (Y1,O)
The blower motor is started immediately, the loop pump(s) is energized 5 seconds after the “Y1” input is received. The compressor will be energized (on low capacity for Dual Capacity units) 10 seconds after the “Y1” input. The ECM blower will shift from low to medium speed 15 seconds after the “Y1” input (85% of medium speed if in dehumidification mode).
Cool, 2nd Stage (Y1, Y2, O) Single Speed Units
The blower changes to high speed (85% of high speed if in dehumidification mode) 15 seconds after the “Y2” input (ECM only).
18
Page 19
Microprocessor Control cont.
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Cool, 2nd Stage (Y1, Y2, O) Dual Capacity Units
The second stage compressor will be activated 5 seconds after receiving a “Y2” input as long as the minimum first stage compressor run time of 1 minute has expired. The ECM blower changes to high speed 15 seconds after the “Y2” input (85% of high speed if in dehumidification mode). The Comfort Alert will delay the second stage compressor until 5 seconds after it receives a “Y2” from the board.
Blower (G only)
The blower starts on low speed (PSC ON). Regardless of blower input “G” from thermostat, the blower will remain on low speed for 30 seconds at the end of each heating, cooling or emergency heat cycle.
Lockout Conditions
During lockout mode, the appropriate unit and thermostat lockout LEDs will illuminate. The compressor, loop pump, and accessory outputs are de-energized. The blower will continue to run on low speed. If the thermostat calls for heating, emergency heat operation will occur.
Comfort Alert lockouts cannot be reset at the thermostat. All other lockout modes can be reset at the thermostat after turning the unit off, then on, which restores normal operation but keeps the unit lockout LED illuminated. Interruption of power to the unit will reset a lockout without a waiting period and clear all lockout LEDs.
High Pressure
This lockout mode occurs when the normally closed safety switch is opened momentarily (set at 600 PSI).
Low Pressure
This lockout mode occurs when the normally closed low pressure switch is opened for 30 continuous seconds (set at 40 PSI). A low pressure fault may also be indicated when a Comfort Alert lockout has occurred.
Freeze Detection (Water Flow)
This lockout mode occurs when the freeze detection thermistor temperature is at or below the selected point (well 30°F or loop 15°F) for 30 continuous seconds.
19
Page 20
NDS OUTDOOR SPLIT INSTALLATION MANUAL
* Reset ALERT flash code by removing 24 VAC power from module.
Microprocessor Control cont.
Compressor Monitoring/Comfort Alert
The Comfort Alert displays abnormal compressor conditions through a unique flash code and communicates the conditions to the heat pump microprocessor control. The heat pump microprocessor will determine which fault to act on and ignore. Fault codes 2 (system pressure), 4 (locked rotor), 6 (open start circuit), and 7 (open run circuit) will result in a lockout. All other fault codes are
passive. All compressor alerts are displayed on the module by flashing the yellow Alert LED a specific number of times consecutively followed by a pause, and then repeated. The number of consecutive flashes or “Flash Code” correlates to a specific abnormal condition. The red “TRIP” LED means there is a thermostat demand signal “Y” present but the compressor is not running. The green “POWER” LED means the module has power.
Green "POWER" LED - module has power Red "TRIP" LED - Thermostat "Y" demand signal is present, but the compressor is not running.
Comfort Alert Flash Codes
Yellow "ALERT" LED LED Description Cause
Flash Code 1 Long Run Time Not applicable Flash Code 2 System Pressure Trip Not applicable Flash Code 3 Short Cycling Compressor run time of less than 3 minutes on 4 consecutive cycles Flash Code 4 Locked Rotor Four consecutive compressor protector trips indicating compressor won't start Flash Code 5 Open Circuit "Y" thermostat demand signal with no compressor current Flash Code 6 Open Start Circuit "Y" thermostat demand signal with no current in the start circuit Flash Code 7 Open Run Circuit "Y" thermostat demand signal with no current in the run circuit Flash Code 8 Welded Contactor Current detected with no "Y" thermostat demand signal present Flash Code 9 Low Voltage Less than 17 VAC detected in control circuit
* Flash code number corresponds to a number of LED flashes, followed by a pause and then repeated.
* TRIP and ALERT LEDs flashing at the same time indicates control circuit voltage is too low for operation.
* Reset ALERT flash code by removing 24 VAC power from module.
* Last ALERT flash code is displayed for 1 minute after module is powered on.
Resetting Comfort Alert Codes
Alert codes can be reset manually by cycling power off and on to the Comfort Alert module. Alert codes will reset automatically if conditions return to normal.
Flash Code Number LED Description Automatic Reset of Alert Codes
Flash Code 1 Long Run Time Not applicable Flash Code 2 System Pressure Trip Not applicable Flash Code 3 Short Cycling Four "alert free" on and off cycles to reset automatically Flash Code 4 Locked Rotor Four "alert free" on and off cycles to reset automatically Flash Code 5 Open Circuit One "alert free" on and off cycles to reset automatically Flash Code 6 Open Start Circuit One "alert free" on and off cycles to reset automatically Flash Code 7 Open Run Circuit One "alert free" on and off cycles to reset automatically Flash Code 8 Welded Contactor One "alert free" on and off cycles to reset automatically Flash Code 9 Low Voltage Resets when voltage rises above 19 VAC
20
Page 21
Microprocessor Control cont.
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Thermostat Displays
Fault Flash
When using a TA32W02 or TP32W03 thermostat and SW2-8 is in the pulsing “L” position, FaultFlash will enable a user to view the thermostat and count the fault indicator flashes to determine the lockout condition the unit is experiencing.
user to view the thermostat and determine the fault. The thermostat can be configured to show either lockout text or lockout codes.
The LED board on the front of the unit will display all lockouts. The Low Pressure LED will flash for a low pressure condition or a Comfort Alert fault. If the low pressure lockout was caused by Comfort Alert codes 4, 6 or 7, then the Comfort Alert will be flashing. If no Comfort Alert code
ComforTalk
is visible, then it is a low pressure lockout. When using a TP32U03, 04 or 05 thermostat and SW2-8 is in the pulsing “L” position, ComforTalk will enable the
The following tables show the codes that will be displayed on the different ComforTalk and FaultFlash thermostats.
FaultFlash Thermostats ComforTalk Thermostats
TA32W02 and TP32W03 Thermostats TP32U03, TP32U04 and TP32U05 Thermostats
Thermostat Display
Lockout Code
Lockout Description Lockout Description
2 Flashes High Pressure Fault "High Pressure" or "E2" High Pressure Fault 3 Flashes Low Pressure Fault "Low Pressure" or "E3" Low Pressure Fault 4 Flashes Not Applicable "E4" Not Applicable 5 Flashes Water Flow Fault "Water Flow" or "E5" Water Flow Fault 6 Flashes Not Applicable "E6" Not Applicable 7 Flashes Condensate Fault "Condensate" or "E7" Condensate Fault 8 Flashes Voltage out of Range "Voltage Range" or "E8" Voltage out of Range 9 Flashes RPM Fault "RPM" or "E9" RPM Fault
10 Flashes
Lockout code 10 - see Comfort Alert module to determine the specific flash code for compressor abnormalities.
Comfort Alert Compressor Module Fault
Thermostat Display
Lockout Code
"Comfort Alert" or "E10"
These thermostats can be configured to display the lockout condition "text" or error number. * A slow flash of 1 second on and off means the heat pump microprocessor SW2-1 is configured for "Test Mode" or thermostat is miswired.
Lockout code 10 - see Comfort Alert module to determine the specific flash code for compressor abnormalities.
Comfort Alert Compressor Module Fault
21
Page 22
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Operation Logic Data
OPER ATION LOGIC
Compressor-Lo
Compressor-Hi
Rev Valve
Loop Pu mps
Secondary 1 - Out
Secondary 2- Out
Emerg LED
T-Stat Signal
STG1 STG2 STG3 EMERG STG1 STG2
On Off Off Off On Off -
Off On On Off Off On -
Off Off Off Off On On -
On On On Off On On On
On On On Off On On -
Off On On Off Off On -
Off Off Off On Off Off -
Y1 Y 1, Y2 Y1, Y2, W W Y1, O Y1 , Y2, O -
HE ATIN G COOLING
DUAL CAPACIT Y UNITS
DIP Switch Settings
DIP SWITCH
NUMBER
SW1 N /A NOT USE D N/A N/A
Service/Test Mode - Allows control of “NORM” or “TEST” operational
modes. Test mode accelerates most timing functions 16 times to allow
1
faster troubleshooting. Test mode also allows viewing the “CURRENT” status of the fault inputs on the LED display.
Freeze Detection Setting
2
This DIP allows field selection of freeze detection fault sensing for well water (30°F) or anti-freeze protected earth loops (15°F).
Accessory Relay
3
Allows field selection of the accessory relay to operate with the compressor
SW2
SW3
or blower.
4 NOT USED N/A N /A
5 NOT USED N /A N /A
Input Diagnostics - Allows viewing the inputs from the thermostat to the
6
control board such as Y1, Y2, O, G, W, SL1-In on the LED display.
Output Diagnostics - Allows viewing the outputs from the control board
7
such as the compressor, reversing valve, blower, and loop pump on the LED display.
Thermostat Selection
Configures the control for a pulsed lockout signal (ComforTalk and
8
FaultFlash thermostats) or continuous 5 VAC lockout signal.
1 Single or Dual Capacity Operation Dual Cap 1 Speed
Zoned/Finish on Second Stage
This switch allows the unit to down stage with the thermostat when off and
2
finish with second stage when on. Finish on second stage reduces stage changing in reciprocating dual capacity compressors.
3 ECM Blower Monitoring - Set for No PRM on split systems No RPM RPM
4 NOT USED N/A N/A
On dual capacity units this switch allows stage change: on the fly when off,
5
and 1 minute delay when on. A delay is required on all reciprocating dual capacity units.
DESCRIPTION OFF POSITION ON POSITION
Te s t Norm
Loop
(Sensing 15° F)
Blower Comp
Diagnostic Inputs
viewed at LEDs
Diagnostic
Outputs viewed at
LEDs
Pulsed “L”
signal
Normal -
All other systems
Envision E-Series or Premier
Normal Display viewed at LEDs
Display viewed
SL1 - IN ON
Well
(Sensing 30° F)
Normal
at LEDs
Continuous “L”
signal
Finish on 2nd
Unzoned Dual
Capacity
E-Series or
Premier 2 speed
22
Page 23
Refrigeration
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Leak Testing
The refrigeration line set must be pressurized and checked for leaks before purging and charging the unit. To pressurize the line set, attach refrigerant gauges to the service ports and add an inert gas (nitrogen or dry carbon dioxide) until pressure reaches 60 to 90 PSIG. Never use oxygen or acetylene to pressure test. Use an electronic leak detector or a good quality bubble solution to detect leaks on all connections made in the field. Check the service valve ports and stem for leaks and all connections made in the field. If a leak is found, repair it and repeat the above steps. For safety reasons do not pressurize the system above 150 psi. Purge pressure from line set. The system is now ready for evacuating and charging.
System Evacuation
Ensure that the line set and air coil are evacuated before opening service valves to the split unit. The line set must be evacuated to at least 200 microns to remove the moisture and air that may still be in the line set and coil. Evacuate the system through both service ports to prevent false readings on the gauge because of pressure drop through service ports.
Charge Amount When Using NAH Air Handler
The Envision Split is shipped with a facotry pre-charge. This volume of refrigerant is not sufficient to run the system and additional refrigerant must be added. If using an NAH Air Handler please refer to the table in this section for charge amounts to be added. The “Factory Charge” column is the charge amount the compressor section/split is shipped with from the factory. The “Charge Amount with NAH Air Handler” column is the total amount of charge for the NAH Air Handler + Compressor section/split. This column does not factor in additional refrigerant needed for the line set. The installer of the system must add charge appropriately for the specific length of the line set. A 3/8 in. liquid line is calculated at 0.50 oz. of charge per linear foot, and a 1/2 in. liquid line is calculated at 1.0 oz. of charge per linear foot using R-410A refrigerant. The suction line will not hold “liquid” and should be ignored for the charge calculation.
Example: NDS036/NAH036 with 20 ft. of 3/8 in. liquid line. Remember that when using the NAH Air Handler, the column “Charge Amount with NAH Air Handler” will be used. Now calculate for the additional 20 ft. ineset. Additional refrigerant to be added = (20 ft. x 0.5 oz.) = 10 oz. Solution: 10 oz. should be added to the recommended charge of 86 oz. found in the “Charge Amount with NAH Air Handler” column for a total charge of 96 oz.
After initial charge, the system should be operated and
the system subcooling and superheat verified to the Unit
Operating Parameters table.
If an air handler manufactured by others is used then
refrigerant should be added to the Envision Split factory
pre-charge. Refrigerant should be added for liquid line
length. This should result in a slightly under-charged
system exhibiting low subcooling and high superheat.
As charge is added, the subcooling should rise and the
superheat should fall.
Charging the System
Charge Method – After purging and evacuating the line set,
fully open the service valves counterclockwise. Add R-410A
(liquid) into the liquid line service port until the pressure
in the system reaches approximately 200 PSIG. Never add
liquid refrigerant into the suction side of a compressor.
Start the unit and measure superheat and subcooling. Keep
adding refrigerant until the unit meets the superheat and
subcooling values in the Operating Parameters tables.
Checking Superheat and Subcooling
Determining Superheat
1. Measure the temperature of the suction line at the point where the expansion valve bulb is clamped.
2. Determine the suction pressure in the suction line by attaching refrigeration gauges to the schrader connection on the suction side of the compressor.
3. Convert the pressure obtained in Step 2 to the saturation temperature by using the Pressure Temperature Conversion Chart for R-410A.
4. Subtract the temperature obtained in Step 3 from Step 1. The difference is the amount of superheat for the unit. Refer to the Operating Parameters tables for superheat ranges at specific entering water conditions.
Superheat Adjustment
TXVs are factory set to a specific superheat; however, the superheat should be adjusted for the application. To adjust the TXV to other superheat settings:
1. Remove the seal cap from the bottom of the valve.
2. Turn the adjustment screw clockwise to increase superheat and counterclockwise to decrease superheat. One complete 360° turn changes the superheat approximately 3-4°F, regardless of refrigerant type. You may need to allow as much as 30 minutes after the adjustment is made for the system to stabilize.
3. Once the proper superheat setting has been achieved, replace and tighten the seal cap.
WARNING: There are 8 total (360°) turns on the superheat adjustment stem from wide open to fully closed. When
23
Page 24
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Refrigeration cont.
adjusting the superheat stem clockwise (superheat increase) and the stop is reached, any further clockwise turning adjustment will damage the valve.
Determining Subcooling
1. Measure the temperature of the liquid line on the small refrigerant line (liquid line) just outside the split cabinet. This location will be adequate for measurement in both modes unless a significant temperature drop in the liquid line is anticipated.
2. Measure the liquid line pressure by attaching refrigerant gauges to the schrader connection on the liquid line service valve.
3. Convert the pressure obtained in Step 2 to the saturation temperature by using the Pressure Temperature Conversion Chart for R-410A.
4. Subtract the temperature in Step 1 from the temperature in Step 3. The difference will be the subcooling value for that unit. Refer to the Operating Parameters tables for subcooling ranges at specific enter water conditions.
Line Set Sizes
20 feet 40 feet 60 feet
Unit Size
026 NAH026 5/8” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 52 74 038 NAH036 3/4” OD 3/8” OD 3/4” OD 3/8” OD 3/4” OD 1/2” OD 56 86 049 NAH048 3/4” OD 3/8” OD 7/8” OD 3/8” OD 7/8” OD 1/2” OD 90 115 064 NAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 92 112 072 NAH060 7/8” OD 1/2” OD 7/8” OD 1/2” OD 1-1/8” OD 1/2” OD 104 132
NOTES: * The “Charge Amount with NAH Air Handler” column is based on the charge amount for an NAH Air Handler + Compressor Section Split. Additional charge will have to be added accordingly for line set length. After charge is added, adjustments can be made to get appropriate subcooling and superheat. Additional charge for R-410A is 0.50 oz. per ft. for 3/8 in. and 1.0 oz. per ft. for 1/2 in. tube.
Air
Handler
Suction Liquid Suction Liquid Suction Liquid
Factory
Charge (oz.)
*Charge Amount
with NAH
Air Handler
(oz.)
4/16/10
24
Page 25
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Pressure/Temperature Coversion Chart for R-410A
PRESSURE
(PSIG)
60 8.5 180 63.5 300 96.3 420 120.6 540 140.0
62 9.9 182 64.2 302 96.8 422 120.9 542 140.3 64 11.2 184 64.8 304 97. 2 424 121.3 544 140.6 66 12.5 186 65.5 306 97. 7 426 121.6 546 140.9
68 13.8 188 66.1 308 98.1 428 122.0 548 141.2 70 15.1 190 66.8 310 98.6 430 122.3 550 141.4
72 16.3 192 6 7. 4 312 99.0 432 122.7 552 141.7
74 17.5 194 68.0 314 99.5 434 123.0 554 142.0
76 18.7 196 68.7 316 99.9 436 123.4 556 142.3
78 19.8 198 69.3 318 100.4 438 123.7 558 142.6 80 21.0 200 69.9 320 100.8 440 124.1 560 142.9
82 22.1 202 70.5 322 101.2 442 124.4 562 143.2 84 23.2 204 71.1 324 101.7 444 124.8 564 143.5 86 24.3 206 71.7 326 102.1 446 125.1 566 143.7
88 25.4 208 72.3 328 102.5 448 125.4 568 144.0 90 26.5 210 72.9 330 103.0 450 125.8 570 144.3
92 2 7.5 212 73.5 332 103.4 452 126.1 572 144.6 94 28.6 214 74. 1 334 103.8 454 126.5 574 144.9 96 29.6 216 74 .7 336 104.2 456 126.8 576 145.1 98 30.6 218 75.3 338 104.7 458 127.1 578 145.4
100 31.6 220 75.8 340 105.1 460 127.5 580 145.7 102 32.6 222 76.4 342 105.5 462 127.8 582 146.0 104 33.5 224 77. 0 344 105.9 464 128.1 584 146.2 106 34.5 226 77.5 346 106.3 466 128.5 586 146.5 108 35.4 228 78 .1 348 106.7 468 128.8 588 146.8
110 36.4 230 78.7 350 107.2 470 129.1 590 1 47.1 112 37. 3 232 79.2 352 107.6 472 129.4 592 147.3 114 38.2 234 79.8 354 108.0 474 129.8 594 147.6 116 39 .1 236 80.3 356 108.4 476 130.1 596 147.9 118 40.0 238 80.9 358 108.8 478 130.4 598 148.2
120 40.9 240 81.4 360 109.2 480 130.7 600 148.4
122 41.7 242 81.9 362 109.6 482 131.1 602 148.7
124 42.6 244 82.5 364 110.0 484 131.4 604 149.0 126 43.4 246 83.0 366 110.4 486 131.7 606 149.2 128 44.3 248 83.5 368 110.8 488 132.0 130 45.1 250 84.1 370 111.2 490 132.3
132 45.9 252 84.6 372 111.6 492 132.7
134 46.7 254 85.1 136 4 7.5 256 85.6 376 112.3 496 133.3
138 48.3 258 86.1 378 112.7 498 133.6
140 49.1 260 86.6 380 113.1 500 133.9 142 49.9 262 8 7.1 382 113.5 502 134.2 144 50.7 264 87.7 384 113.9 504 134.5 146 51.5 266 88.2 386 114.3 506 134.9 148 52.2 268 88.7 388 114.7 508 135.2 150 53.0 270 89.2 390 115.0 510 135.5
152 53.7 272 89.6 392 115.4 512 135.8
154 54.5 274 90.1 394 115.8 514 136.1 156 55.2 276 90.6 396 116.2 516 136.4
158 55.9 278 91.1 398 116.5 518 136.7
160 56.6 280 91.6 400 116.9 520 13 7.0
162 5 7. 4 282 9 2.1 402 117.3 522 137.3
164 58.1 284 92.6 404 117.6 524 137.6 166 58.8 286 93.0 406 118.0 526 137.9 168 59.5 288 93.5 408 118.4 528 138.2 170 60.2 290 94.0 410 118.7 530 138.5
172 60.8 292 94.5 412 119.1 532 138.8 174 61.5 294 94.9 414 119.5 534 139.1 176 62.2 296 95.4 416 119.8 536 139.4 178 62.9 298 95.8 418 120.2 538 139.7
TEMP
°F
PRESSURE
(PSIG)
TEMP
°F
PRESSURE
(PSIG)
374 112.0 494 133.0
TEMP
°F
PRESSURE
(PSIG)
TEMP
°F
PRESSURE
(PSIG)
608 149.5
TEMP
°F
25
Page 26
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Operating Parameters
First Stage Operation
Entering
Water Temp
°F
50
70
90
Entering
Water Temp
°F
30
50
70
Water Flow
GPM/Ton
1.5 130-150 193-230 130-150 200-245 8-16 7-14 15-21 18-24
3.0 128-153 190-230 125-140 205-240 8-16 3-10 9-14 18-25
1.5 130-150 238-282 135-150 240-280 6-16 4-16 12-18 18-25
3.0 130-155 238-262 125-145 245-270 6-18 5-11 5-10 18-24
1.5 133-148 308-340 130-155 300-365 7-16 6-18 10-16 19-25
3.0 138-153 303-333 130-165 305-350 7-18 7-14 5-10 17-22
Water Flow
GPM/Ton
1.5 78-100 275-325 85-105 325-385 6-11 4-16 5-9 20-29
3.0 78-110 285-325 90-120 335-375 6-11 4-16 3-7 20-32
1.5 105-120 305-350 100-130 340-400 5-12 4-16 5-12 24-32
3.0 110-125 305-355 110-125 345-395 9-15 2-14 4-9 20-34
1.5 140-155 305-355 130-165 370-430 5-12 2-14 8-12 24-39
3.0 145-160 330-360 140-160 375-425 7-17 7-15 4-10 24-39
NDS026 thru NDS064 NDS072 NDS026 thru NDS072 Suction
Pressure
PSIG
NDS026 thru NDS064 NDS072 NDS026 thru NDS072 Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Discharge
Pressure
PSIG
Cooling -- No Desuperheater
Suction
Pressure
PSIG
Heating -- No Desuperheater
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat Subcooling
Superheat Subcooling
Water Temp
Rise °F
Water Temp
Drop °F
Air Temp
Drop °F DB
Air Temp
Rise °F DB
Second Stage Operation
Cooling -- No Desuperheater
Entering
Water Temp
°F
50
70
90
Entering
Water Temp
°F
30
50
70
Cooling performance based on entering air temperatures of 80°F DB, 67°F WB. Heating performance based on entering air temperature of 70°F DB.
Water Flow
GPM/Ton
1.5 120-140 200-245 105-150 210-270 7-17 6-14 15-21 19-26
3.0 115-140 195-290 110-130 215-260 7-15 4-11 9-14 20-24
1.5 121-136 265-310 105-150 280-350 9-15 6-18 12-18 19-25
3.0 123-139 265-310 110-140 285-320 10-16 8-16 5-10 18-24
1.5 122-140 310-360 115-140 325-385 8-14 6-18 10-16 18-24
3.0 123-139 310-350 120-135 330-355 8-14 7-15 5-10 17-23
Water Flow
GPM/Ton
1.5 72-89 295-350 70-100 320-370 7-18 10-20 5-9 18-24
3.0 73-87 305-330 75-90 315-365 7-18 10-20 3-7 18-27
1.5 100-120 320-365 95-130 375-430 6-14 6-18 5-12 23-34
3.0 105-120 355-365 100-125 370-420 6-14 6-18 4-9 20-37
1.5 142-158 360-380 130-165 400-470 6-12 4-15 8-12 28-38
3.0 138-152 365-390 135-160 405-465 7-14 4-15 4-10 24-42
NDS026 thru NDS064 NDS072 NDS026 thru NDS072 Suction
Pressure
PSIG
NDS026 thru NDS064 NDS072 NDS026 thru NDS072 Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Discharge
Pressure
PSIG
Suction
Pressure
PSIG
Heating -- No Desuperheater
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
Discharge
Pressure
PSIG
Superheat Subcooling
S u p e r h e a t Subcooling
Water Temp
Rise °F
Water Temp
Drop °F
Air Temp
Drop °F DB
Air Temp
Rise °F DB
26
Page 27
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Pressure Drop
Dual Capacity
Model GPM
026
full
load
026 part
load
038
full
load
038 part
load
049
full
load
049 part
load
064
full
load
064 part load
072
full
load
072 part load
10 7.0 6.6 6.2 5.8 5.3
10 4.2 3.9 3.7 3.4 3.2
12 3.9 3.6 3.4 3.2 2.9 15 5.7 5.3 5 4.7 4.3
14 5.0 4.7 4.4 4 .1 3.8
12 3.8 3.5 3.3 3.0 2.8 16 6.5 6.0 5.6 5.2 4.8
20 9.7 9.1 8.5 8.0 7. 4
10 2.6 2.5 2.3 2.1 2.0 14 5.0 4.7 4.4 4 .1 3.8 18 8.1 7.6 7. 1 6.6 6.1 12 3.2 3.0 2.8 2.6 2.4 15 4.5 4.2 4.0 3.7 3.4 18 6.0 5.7 5.3 4.9 4.6 21 7. 8 7.3 6.8 6.4 5.9 10 2.3 2 .1 2.0 1.9 1.7 13 3.6 3.3 3.0 2.8 2.6 16 5.0 4.6 4.3 4.0 3.7 19 6.5 6.2 5.8 5.4 5.0
30°F 50°F 70°F 90°F 110°F
4 1.4 1.3 1.2 1 .1 1.0 6 2.8 2.6 2.4 2.3 2.1 8 4.7 4.4 4 .1 3.8 3.5
3 0.8 0.7 0.7 0.7 0.6 5 2.0 1.8 1.7 1.6 1.5 7 3.6 3.4 3.2 3.0 2.8 9 5.8 5.5 5 .1 4.8 4.4 5 1.2 1.2 1.1 1.0 1.0 7 2.2 2.1 1.9 1.8 1.7 9 3.4 3.2 3.0 2.8 2.6 11 4.9 4.6 4.3 4 3.7 4 0.9 0.8 0.8 0.7 0.7 6 1.7 1.6 1.5 1.4 1.3 8 2.8 2.6 2.5 2.3 2.1
6 1.2 1.2 1.1 1.0 1.0 9 2.4 2.2 2.1 2.0 1.8
5 0.9 0.9 0.8 0.8 0.7 8 2.0 1.8 1.7 1.6 1.5 11 3.4 3 .1 2.9 2.8 2.5
8 1.8 1.7 1.6 1.4 1.3
6 1.0 0.9 0.9 0.8 0.8
Pressure Drop (psi)
5/30/06
Compressor Resistance
Compressor Resistance Chart (Ohms)
Model
026 038 049 064 072
1.23-1.30 1.41-1.50 .829-.954 1.19-1.38 .590-.679 1.41-1.62 .455-.524 .558-.643 .344-.395 .495-.570
208-230/60/1
Run Start
Thermistor Resistance
Thermistor Resistance Chart
Thermistor
Temperature (°F)
5 75757-70117
14 57392-53234 23 43865-40771 32 33809-31487
41 26269-24513 50 20570-19230 59 16226-15196 68 12889-12093 77 10310-9688 86 8300-7812 95 6723-6337
104 5480-5172
113 4490-4246
122 3700-3504
131 3067-2907
140 2554-2424 149 2149-2019
Microprocessor
Resistance (Ohms)
1/13/11
7/6/ 1 0
27
Page 28
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Refrigerant Circuit Guideline
Symptom
Under Charged System (Possible Leak) Low Low Low High Low Low Low Over Charged System High High High Normal High Normal/Low Normal Low Air Flow Heating High High High High/Normal Low High Low Low Air Flow Cooling Low Low Low Low/Normal High High Low Low Water Flow Heating Low/Normal Low/Normal Low Low High Low High Low Water Flow Cooling High High High High Low Low High High Air Flow Heating Low Low Low Low High Low Low High Air Flow Cooling Low High Normal High Low Low Normal High Water Flow Heating Normal Low Normal High Normal Normal Low High Water Flow Cooling Low Low Low Low High Normal Low Low Indoor Air Temperature Heating Low Low Low Normal High Normal Normal/High Low Indoor Air Temperature Cooling Low Low Low Normal/Low High Low Low High Indoor Air Temperature Heating High High High Normal/High Normal/Low Low Normal High Indoor Air Temperature Cooling High High High High Low Low High Restricted TXV (Check Service Advisory) High Low Normal/Low High High Low Low Insufficient Compressor (Possible Bad Valves) Low High Low High Normal/High Low Low TXV - Bulb Loss of Charge Low Low Low High High Low Low Scaled Coaxial Heat Exchanger Heating Low Low Low Normal/Low High Low Low Scaled Coaxial Heat Exchanger Cooling High High High Normal/Low Low Low Low Restricted Filter Drier Check temperature difference (delta T) across filter drier.
Head
Pressure
Suction
Pressure
Compressor
Amp Draw
Superheat Subcooling
Air Temp.
Differential
Water Temp.
Differential
7/6/ 1 0
Heat of Extraction/Rejection Data
Model GPM
Part
Load
026
Full
Load
Part
Load
038
Full
Load
Part
Load
049
Full
Load
Part
Load
064
Full
Load
Part
Load
072
Full
Load
Heat of Extraction (kBtuh) Heat of Rejection (kBtuh)
30°F 50°F 70°F 90°F 30°F 50°F 70°F 90°F 110°F
3.0 13.1 17.6 21.5 23.5 22.9 21.8
5.0 9.4 13.8 18.6 22.6 21.7 23.6 23.0 21.7 20.2
7.0 9.6 14.1 18.9 23.0 21.9 23.7 23.1 21.7 20.2
4.0 17.8 23.4 28.5 31.0 31.2 30.0
6.0 13.4 18.8 24.7 29.9 29.9 31.1 31.3 29.9 28.1
8.0 13.6 19.3 25.1 30.5 30.1 31.2 31.3 29.9 28.1
4.0 17.9 23.3 28.1 32.5 31.8 30.0
6.0 12.8 18.7 24.5 29.8 29.8 32.7 32.0 30.1 28.2
8.0 13.9 19.7 25.2 29.8 30.3 33.1 32.4 30.4 28.5
5.0 25.1 31..5 36.1 44.8 45.1 42.8
7.0 18.7 26.2 33.2 38.6 41.8 45.2 45.7 43.6 41.0
9.0 19.1 26.9 34.3 40.0 42.0 45.5 46.0 43.8 41.1
5.0 24.0 29.5 33.7 44.9 46.1 44.0
8.0 19.2 26.4 32.6 37.5 40.6 45.0 45.8 43.4 40.5
11.0 19.8 27. 5 34.3 39.9 40.0 44.9 46.1 44.3 41.5
6.0 33.3 40.6 46.1 60.2 60.2 56.4
9.0 26.0 34.7 42.8 49.1 56.0 60.2 60.8 57. 4 52.9
12.0 26.5 35.7 44.2 50.9 56.1 60.4 61 .1 57.6 53.2
6.0 31.0 39.2 46.1 56.3 55.4 52.1
10.0 21.6 31.4 40.9 49.7 52.4 56.2 55.5 52.4 49.4
14.0 22.6 32.6 41.7 49.8 52.2 56.2 55.6 52.6 49.7
8.0 40.8 52.7 64.7 73.7 75.7 70.3
12.0 31.9 43.8 55.1 65.8 66.8 74 .1 76.1 70.5 66.2
16.0 32.2 44.7 56.8 68.6 6 7. 2 74.5 76.5 70.9 66.3
10.0 36.4 46.5 54.7 63.4 63.0 58.9
13.0 25.2 36.7 48.5 59.1 57. 7 63.2 63.0 59.2 55.1
16.0 26.7 38.2 49.4 59.1 57.3 63.2 63.3 59.5 55.4
12.0 48.3 62.7 69.0 81.8 83.0 77.8
15.0 37. 2 51.6 65.4 70.9 73.6 82.1 83.3 78.0 71.9
18.0 3 7.6 52.7 67. 5 73.5 74 .1 82.6 83.8 78.4 72.2 1/14/11
28
Page 29
Reference Calculations
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Heating Calculations:
LWT = EWT -
LAT = EAT +
TH = HC + HW
HE
GPM x 500
HC
CFM x 1.08
Cooling Calculations:
LWT = EWT +
LAT (DB) = EAT (DB) -
LC = TC - SC
SC
S/T =
TC
HR
GPM x 500
Legend
ABBREVIATIONS AND DEFINITIONS:
CFM = airflow, cubic feet/minute EWT = entering water temperature, Fahrenheit GPM = water flow in gallons/minute WPD = water pressure drop, PSI and feet of water EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb) HC = air heating capacity, MBTUH TC = total cooling capacity, MBTUH SC = sensible cooling capacity, MBTUH KW = total power unit input, kilowatts HR = total heat of rejection, MBTUH
SC
CFM x 1.08
HE = total heat of extraction, MBTUH HW = hot water generator capacity, MBTUH EER = Energy Efficiency Ratio = BTU output/Watt input COP = Coefficient of Performance = BTU output/BTU input LWT = leaving water temperature, °F LAT = leaving air temperature, °F TH = total heating capacity, MBTUH LC = latent cooling capacity, MBTUH S/T = sensible to total cooling ratio
Operating Limits
Operating Limits Cooling Heating
Air Limits
Minimum ambient air, DB -10°F [-23.3°C] -10°F [-23.3°C]
Rated ambient air, DB 80.0 [26.7°C] 70°F [21.1°C]
Maximum ambient air, DB 120 [48.8°C] 85°F [29°C]
Water Limits
Minimum entering water 30°F [-1°C] 20°F [-6.7°C]
Normal entering water 50-110°F [10-43°C] 30-70°F [-1 to 21°C]
Maximum entering water 120°F [49°C] 90°F [32°C]
Normal water flow
1.5 to 3.0 gpm per ton
[1.6 to 3.2 l/m per kW]
NOTES: Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependent upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.
29
Page 30
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Startup
Before Powering Unit, Check The Following:
High voltage is correct and matches nameplate.
Fuses, breakers and wire size correct.
Low voltage wiring complete.
Piping completed and water system cleaned and flushed.
Air is purged from closed loop system.
Isolation valves are open, water control valves or loop pumps wired.
Transformer switched to 208V if applicable.
DIP switches are set correctly.
DHW pump switch is “OFF” unless piping is completed and air has been purged.
Blower rotates freely.
Blower speed correct.
Air filter/cleaner is clean and in position.
Service/access panels are in place.
Return air temperature is between 50-80ºF heating and 60-95ºF cooling.
Check air coil cleanliness to ensure optimum performance. Clean as needed according to maintenance guidelines. To obtain maximum performance the air coil should be cleaned before startup. A 10-percent solution of dishwasher detergent and water is recommended for both sides of coil, a thorough water rinse should follow.
Startup Steps
NOTES: Complete the Equipment Start-Up/Commissioning
Check Sheet during this procedure. Refer to thermostat operating instructions and complete the startup procedure.
8. Decrease the cooling set point several degrees and verify high-speed blower operation.
9. Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or loop pumps deactivate.
10. Initiate a control signal to place the unit in the heating mode. Heating set point must be set above room temperature.
11. First stage heating will energize after a time delay.
12. Check the temperature of both the supply and discharge water (see Operating Parameters tables).
13. Check for an air temperature rise of 20°F to 35°F across the air coil, depending on the blower speed and entering water temperature.
14. If auxiliary electric heaters are installed, increase the heating setpoint until the electric heat banks are sequenced on. All stages of the auxiliary heater should be sequenced on when the thermostat is in the Emergency Heat mode. Check amperage of each element.
15. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pumps deactivate.
16. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required.
17. Set system to desired normal operating mode and set temperature to maintain desired comfort level.
18. Instruct the owner/operator in the proper operation of the thermostat and system maintenance.
NOTES: Be certain to fill out and forward all warranty registration papers.
1. Initiate a control signal to energize the blower motor. Check blower operation.
2. Initiate a control signal to place the unit in the cooling mode. Cooling setpoint must be set below room temperature.
3. First stage cooling will energize after a time delay.
4. Be sure that the compressor and water control valve or loop pump(s) are activated.
5. Verify that the water flow rate is correct by measuring the pressure drop through the heat exchanger using the P/T plugs and comparing to unit capacity data in specification catalog.
6. Check the temperature of both the supply and discharge water (see Operating Parameters tables).
7. Check for an air temperature drop of 15°F to 25°F across the air coil, depending on the blower speed and entering water temperature.
Final Evaluation
After the initial check of superheat/subcooling values in the heating mode, shut off the unit and allow it to sit 3 to 5 minutes until pressures equalize. Restart the unit in the cooling mode and check the values against those in the Operating Parameters tables. If the unit performs satisfactorily, charging is complete. If the unit does not perform to specifications, the charge may need to be readjusted until the values are close. Adding refrigerant will increase subcooling. Recovering some of the refrigerant will decrease subcooling and increase superheat. If the superheat/subcooling values are still not close to the specifications in the Operating Parameters tables, analyze refrigerant circuit operation.
30
Page 31
Startup and Troubleshooting
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Heating Cycle Analysis
Measure suction temperature here at TXV bulb in cooling modes.
Air
Coil
ClgTXV
COOLING TXV - ACTIVE RIGHT TO LEFT
filter/drier
Measure liquid line temperature and pressure here in both heating and cooling modes
Lineset
length
Bi-flow
Measure suction temperature here at TXV bulb in heating modes.
Volts ____
Amps ____
HtgTXV
COAX
EWT ____
LWT ____
HEATING TXV - ACTIVE LEFT TO RIGHT
Suct PSI____
Suct sat temp____
Suct temp____
Super heat____
Suction
Comp
Discharge
Hot Water Generator
Discharge PSI____
Disch. sat temp____
Liquid temp____
Sub cooling____
Note: DO NOT hook up pressure gauges unless there appears to be a performance problem.
Cooling Cycle Analysis
Measure suction temperature here at TXV bulb in cooling modes.
Air
Coil
ClgTXV
COOLING TXV - ACTIVE RIGHT TO LEFT
filter/drier
Measure liquid line temperature and pressure here in both heating and cooling modes
Lineset
length
Bi-flow
Measure suction temperature here at TXV bulb in heating modes.
Volts ____
Amps ____
HtgTXV
COAX
EWT ____ LWT ____
HEATING TXV-ACTIVE LEFT TO RIGHT
Suct PSI ____
Suct sat temp ____
Suct temp ____
Super heat ____
Suction
Comp
Discharge
Hot Water Generator
Discharge PSI ____
Disch. sat temp ____
Liquid temp ____
Sub cooling ____
31
Page 32
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Troubleshooting
Standard Microprocessor Controls
To check the unit control board for proper operation:
1. Disconnect thermostat wires at the control board.
2. Jumper the desired test input (Y1, Y2, W, O or G) to the R terminal to simulate a thermostat signal.
3. If control functions properly:
• Check for thermostat and field control wiring (use the diagnostic inputs mode).
LED Definitions and Diagnostics
Standard Microprocessor
LED
Drain
Water Flow
NORMAL
DISPLAY MODE
Field Selection DIPS
SW2- 1 On SW2- 1 Off SW2- 1 NA SW2- 1 NA SW2-
SW2- 6 On SW2- 6 On SW2- 6 Off SW2- 6 On SW2-
SW2- 7 On SW2- 7 On SW2- 7 On SW2- 7 Off SW2-
Drain Pan Overflow
Lockout
FD Thermistor
(Loop <15°F,
Well<30°F) Lockout
CURRENT
FAULT STATUS
Drain Pan Overflow Y1
FD Thermistor
(Loop <15°F,
Well<30°F)
4. If control responds improperly:
• Ensure that component being controlled is functioning (compressor, blower, reversing valve, etc.).
• Ensure that wiring from control to the component is functioning (refer to the LED Definition table below and use the diagnostic outputs mode).
• If steps above check properly, replace unit control.
DIAGNOSTIC MODES
INPUTS OUTPUTS 1 OUTPUTS 2
Y2
Compressor (On or Low)
Compressor (On or High)
Blower
Low
Blower
Medium
1 NA
6 Off
7 Off
High
Pressure
High Pressure >600
PSI Lockout
High Pressure >600 O Reversing Valve
Low
Pressure,
Comfort
Low Pressure <40/
Comfort Alert
Low Pressure <40/
Comfort Alert
Alert
Status
DHW Limit
DHW Off
Microprocessor
Malfunction
HWL Thermistor
>130°F
DHW Pump
Switch Off
Not Used SL1 Loop Pump 1 Aux Heat 3
HWL Thermistor
>130°F
DHW Pump Switch
Off
Refrigerant Systems
To maintain sealed circuit integrity, do not install service gauges unless unit operation appears abnormal. Compare the change in temperature on the air side as well as the water side to the Operating Parameters tables. If the unit’s performance is not within the ranges listed, and the airflow and water flow are known to be correct, gauges should then be installed and superheat and subcooling numbers calculated. If superheat and subcooling are outside recommended ranges, an adjustment to the refrigerant charge may be necessary.
Blower
High
G Blower Aux Heat 1
Not Used Loop Pump 2 Aux Heat 4
NOTES: Refrigerant tests must be made with hot water generator turned “OFF”. Verify that air and water flow rates are at proper levels before servicing the refrigerant circuit.
32
Page 33
Preventive Maintenance
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Water Coil Maintenance
1. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the water line. Lines should always be airtight.
2. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure.
NOTES: On open loop systems, if the installation is in an area with a known high mineral content (125 PPM or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water flowing through the unit the less chance for scaling.
Other Maintenance
Filters
Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating conditions and be replaced when necessary. Units should never be operated without a filter.
Condensate Drain
In areas where airborne bacteria produce a slime in the drain pan, it may be necessary to treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect twice a year to avoid the possibility of overflow.
Blower Motors
Blower motors on most air handlers are equipped with sealed ball bearings and require no periodic oiling.
Air Coil
The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum clean. Care must be taken not to damage the aluminum fins while cleaning.
CAUTION: Fin edges are sharp.
Replacement Procedures
Obtaining Parts
When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required.
In-Warranty Material Return
Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor for warranty return authorization and assistance.
33
Page 34
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Service Parts List
Part Description
Compressor 34P585-01 34P573-01 34P574-01 34P575-01 34P586-01
Run Capacitor 16P002D19 16P002D20 16P002D21 16P002D39
Sound Jacket 92P504A16
Power Harness 11P781-01
Compressor
Solenoid Harness 11P782-01
Accumulator 36P509-02 36P509-01
Coax 62I504B01 62I542B01 62I543B01
TXV 33P609-01 33P609-03 33P609-05 33P609-06
Reversing Valve 33P506-04 33P503-05 33P526-04
Components
Refrigeration
Filter Dryer 36P500B01 36P500B02
Comfort Alert 19P571-02
Contactor 13P004A03
Transformer 15P501B01
3 Pole Power Block 12P503-06
2 Pole Screw Term. Block 12P500A01
Electrical
Status Light Board 17P503-02
Harness, Status Light Board 11P783-01
Premier Board 17P513-07
Freeze Detection Thermistor 12P505B03
High Pressure Switch 35P506B02
Safeties
Sensors &
Low Pressure Switch 35P506B01
Part numbers subject to change 11/12/10
026 038 049 064 072
Dual Capacity Split Units
34
Page 35
Page 36
Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com
IM1004SN 03/11
©2011 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and
reserves the right to change design and specifications without notice.
Product: Envision NDS Type: Geothermal/Water Source Outdoor Split Heat Pump Size: 2-6 Tons Dual Capacity Document: Installation Manual
Loading...