Envision NDS026 Series, NDS064 Series, NDS072 Series, NDS038 Series, NDS049 Series Installation Manual

Installation Information
Water Piping Connections
Electrical Data
Startup Procedures
Troubleshooting
Preventive Maintenance
NDS Installation Manual
IM1004SN 03/11
Table of Contents
Model Nomenclature........................................................... 4
General Installation Information ................................................5-8
Water Quality ................................................................. 8
Water Piping.................................................................. 9
Electrical Data ................................................................10
Thermostat Wiring ............................................................10
Dimensional Data..............................................................11
Physical Data .................................................................11
Model Nomenclature - Air Handler ...............................................12
Coil Data - Air Handler .........................................................12
Physical Data - Air Handler .....................................................13
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Model Nomenclature - Coil .....................................................13
Refrigerant Coil Compatibility...................................................13
Wiring Schematics..........................................................14-17
Microprocessor Control .....................................................18-21
Operation Logic Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
DIP Switch Settings........................................................... 22
Refrigeration ............................................................. 23-24
Line Set Sizes ................................................................ 24
Pressure/Temperature Conversion Chart for R-410A............................... 25
Operating Parameters......................................................... 26
Pressure Drop................................................................ 27
Compressor and Thermistor Resistance ......................................... 27
Refrigerant Circuit Guideline ................................................... 28
Heat of Extraction/Rejection Data .............................................. 28
Reference Calculations........................................................ 29
Legend ..................................................................... 29
Operating Limits .............................................................29
Startup and Troubleshooting................................................ 30-32
Preventative Maintenance ..................................................... 33
Replacement Procedures ......................................................33
Service Parts List ............................................................. 34
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Model Nomenclature
1 2 3
D S
N
Model Type
N = Envision
Compressor Type
D = Dual Capacity
Cabinet Configuration
S = Outdoor Split
Unit Capacity 026
038 049 064 072
NOTE: *026-049 uses the FC1-GL and 060-072 uses the FC2-GL, the flow center is factory installed. If these flow centers do not meet the flow requirements, select A = None for digit 10.
4-6
0497A819010A11C
Coax Options
C = Copper N = Cupronickel
Flow Center
A = None B = Flow Center*
IntelliStart Options
0 = No IntelliStart 3 = IntelliStart
Voltage
1 = 208-230/60/1
Vintage
A = Current
4
General Installation Information
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to both units. Turn off accessory heater power switch if applicable. Electrical shock could cause personal injury. Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply, such as the following safety measures:
• Follow all safety codes.
• Wear safety glasses and work gloves.
• Use a quenching cloth for brazing operations.
• Have a fire extinguisher available for all brazing operations.
Moving and Storage
Move units in the normal “up” orientation. Units may be moved and stored per the information on the packaging. Do not stack more than three units in total height. Do not attempt to move units while stacked. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
Condensate Drain
Follow the blower coil manufacturer’s instructions.
Duct System
All blower coil units/air coils must be installed as specified by the manufacturer’s installation instructions; however, the following recommendations should considered to minimize noise and service problems.
An air filter must always be installed upstream of the air coil on the return air side of the air handler or furnace. If there is limited access to the filter rack for normal maintenance, it is suggested that a return air filter grill be installed. Be sure that the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the filter and plugging the air coil.
In applications using galvanized metal ductwork, a flexible duct connector is recommended on both the supply and return air plenums to minimize vibration from the blower. To maximize sound attenuation of the unit blower, the supply and return plenums should include an internal duct liner of 1-inch thick glass fiber or be constructed of ductboard. Insulation is usually not installed in the supply branch ducts. Ducts in unconditioned areas should be wrapped with a minimum of 1-inch duct insulation. Application of the unit to uninsulated ductwork in an unconditioned space is not recommended as the unit’s performance will be adversely affected. If the air handler is connected to existing ductwork, a previous check should have been made to assure that the duct system has the capacity to handle the air required for the unit application. If ducting is too small, as in replacement of heating only systems, larger ductwork should be installed. All existing ductwork should be checked for leaks and repairs made accordingly. The duct systems and diffusers should be sized to handle the design airflow quietly. If air noise or excessive airflow is a problem, the blower speed can be changed to a lower speed to reduce airflow. This will reduce the performance of the unit slightly in heating; however, it will increase the temperature rise across the air coil. Airflow must still meet minimum requirements.
Split Unit Location
Locate the split compressor section away from areas that may disturb the customer and in a way that allows easy removal of the access panels and the top of the cabinet. Provide sufficient room to make water, electrical and refrigerant line connections and allow space for service personnel to perform maintenance. The NDS split is approved for outdoor installation when properly installed.
Air Coil Location
Refer to the air handler manufacturer’s instructions for the blower coil unit for details on installing the air handling portion of the system.
Equipment Selection
The following guidelines should be used when mating an Envision Split to an air handler/coil.
• Select R-410A components only.
• Match the air handler to the air handler coil data table.
• Indoor matching adjustable TXV is factory installed on every NAH air handler/coil. Fixed orifice or cap tube systems should not be used.
• Minimum of two (2) blower speeds
Utilizing Existing Coil or Air Handler
It is recommended that a new R-410A air handler be installed with an Envision Split considering the long term
5
NDS OUTDOOR SPLIT INSTALLATION MANUAL
General Installation Information cont.
benefits of reliability, warranty, etc. versus the short term installation cost savings. However, the existing air handler may be retained provided the following:
Coil currently is R-410A rated
Coil uses a TXV. No capillary or fixed orifice systems should be used
A life expectancy of more than 7 years remaining for the air handler and components
Flush air coil and line set
When utilizing the existing air coil or line set, only flushing compounds that vaporize should be used; which means they are packaged in a pressurized disposable cylinder. It is preferable to use a flushing agent that removes oil, water, and acid, plus, is biodegradeable and non-toxic. The flushing agent should be safe to use with both HCFC and HFC refrigerants. Once a flushing agent has been selected, follow the instructions provided with the product.
The first step should be purging the lines or air coil with nitrogen. Purging with nitrogen first will remove some of the particulate and residual oil which will allow the flushing agent to work better. Never blow the flushing agent through a compressor, filter drier, or txv as it will cause the components to fail.
When flushing is complete and the final system is assembled, an acid check should be preformed on the system. Acid test kits are available from most HVACR distributors.
An air filter must always be installed upstream of the air coil on the return air side of the air handler or furnace. If there is limited access to the filter rack for normal maintenance, it is suggested that a return air filter grille be installed. Be sure that the return duct is properly installed and free of leaks to prevent dirt and debris from bypassing the filter and plugging the air coil.
Ensure that the line set size is appropriate to the capacity of the unit (refer to Line Set Sizes table). Line sets should be routed as directly as possible, avoiding unnecessary bends or turns. All wall penetrations should be sealed properly. Line set should not come into direct contact with water pipes, floor joists, wall studs, duct work, floors, walls and brick. Line set should not be suspended from joists or studs with a rigid wire or strap which comes into direct contact with the tubing. Wide hanger strips which conform to the shape of the tubing are recommended. Isolate hanger straps from line set insulation by using metal sleeves bent to conform to the shape of insulation. Line set insulation should be pliable, and should completely surround the refrigerant line.
NOTE: Improper installation of equipment may result in undesirable noise levels in the living areas.
Typical Split System Application ­Remote Blower Coil
Connection to Air Coil
Typical Split System Application - Remote Blower Coil and Typical Split System Heat Pump Coil Add-on Fossil Fuel Furnace illustrations show typical Envision Split installations. The Line Set Sizes table shows typical line set diameters and maximum length. Line sets over 60 feet are not recommended. If the line set is kinked or deformed and cannot be reformed, the bad section of pipe should be replaced. A restricted line set will affect unit performance. As in all R-410A equipment, a reversible liquid line filter drier is required to ensure all moisture is removed from the system. This drier should be replaced whenever “breaking into” the system for service. All line sets should be insulated with a minimum of 1/2” closed cell insulation. All exterior insulation should be painted with UV resistant paint or covering to ensure long insulation life.
Air Handler Installation
Air handlers used with dual capacity units must be capable of operating with a minimum of 2 blower speeds. Refer to the manufacturer’s instructions for the blower coil unit for details on installing the air handling portion of the system. All blower coil units/air coils must be installed as specified by the manufacturer’s installations instructions. However, the following recommendations should be considered to minimize noise and service problems.
Insulated
Suction Line
Lineset
To Air Handler
Condensate Drain (must be trapped)
Disconnect
Low
Voltage Wire
Remote Air Handler
(Maximum Recommended Distance is
60' Between Units)
Supply
Duct
Air
Handler
Return
Duct
6
General Installation Information cont.
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Dual Fuel Systems
Envision units can be connected to fossil fuel furnaces that include an A-coil or slab coil. Dual fuel installations utilize the Envision heat pump for heating until the point that auxiliary heat is called for on the thermostat. At that point, the furnace will be enabled and the heat pump will be disabled. The Envision heat pump provides air conditioning through the furnace’s refrigerant coils.
Refer to the furnace manufacturer’s installation manual for the furnace installation, wiring and coil insertion. A WaterFurnace Dual Fuel thermostat or a field-installed DPST relay is required. See the Typical Split System Heat Pump Coil Add-on Fossil Fuel Furnace illustration for typical Dual Fuel application.
Typical Split System Heat Pump Coil Add-on Fossil Fuel Furnace
Disconnect
Insulated
Suction Line
In add-on Envision Split applications, the coil should be located in the supply side of the furnace to avoid condensation damage to the furnace heat exchanger. A high temperature limit should be installed upstream of the coil to de-energize the compressor whenever the furnace is operating. Without this switch, the Envision Split will trip out on high pressure. A dual fuel thermostat can remove the Y1 and Y2 calls when a W call is energized to allow gas furnace backup on an Envision Split application. Refer to the Thermostat Wiring section for details.
Supply Duct
"A" or
Slab Coil
Lineset To Air Handler
Wire From Furnace
Thermostat
Wire To
Thermostat
Return
Duct
Condensate
Drain
(must be trapped)
Up-Flow
Fossil Fuel
Furnace
7
NDS OUTDOOR SPLIT INSTALLATION MANUAL
mpp 02 naht sseLmpp 2 naht sseLmpp 2 naht sseLainommA
mpp 5. naht sseLmpp 5. naht sseLmpp 5. naht sseLetafluS ainommA
Water Quality
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period
with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing. Failure to adhere to the guidelines in the water quality table
could result in loss of warranty. of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Hot water generator coils can likewise become scaled and possibly plugged. In areas
pH Acidity/Alkalinity 9 - 7 9 - 7 9 -7
Scaling Calcium and Magnesium Carbonate (Total Hardness) less than 350 ppm (Total Hardness) less than 350 ppm (Total Hardness) less than 350 ppm
Hydrogen Sulfide
Corrosion mpp 5. naht sseLmpp 5. naht sseLmpp 5. naht sseLedirolhC ainommA
LSI Index
Iron Fouling
(Biological Growth) Iron Oxide
Erosion Suspended Solids
Note:
Grains = PPM divided by 17 mg/l is equivalent to PPM
Bacterial Iron Potential
Less than .5 ppm (rotten egg smell
appears at 0.5 PPM)
+
0.5 to -.05
Less than 1 ppm. Above this level
deposition will occur.
Less than 10 ppm and filtered for max of
600 micron size
Units with cupronickel heat exchangers are recommended
for open loop applications due to the increased resistance
to build-up and corrosion, along with reduced wear caused
by acid cleaning.
+
0.5 to -.05
Less than 1 ppm. Above this level
deposition will occur.
Less than 10 ppm and filtered for max of
600 micron size
Less than 1 ppm. Above this level
Less than 10 ppm and filtered for max of
+
0.5 to -.05
deposition will occur.
600 micron size
leetS sselniatS 613lekciN-orpuC 01/09reppoClairetaM
mpp 1 naht sseLmpp 05 - 01
mpp 002 naht sseLmpp 521 naht sseLmpp 521 naht sseLsetafluS
mpp 5. naht sseLmpp 5. naht sseLmpp 5. naht sseLenirolhC
mpp 003 naht sseLmpp 521naht sseLmpp 02 naht sseLsedirolhC
mpp 05 -01mpp 05 - 01mpp 05 naht sseLedixoiD nobraC
mpp 5. naht sseLmpp 5. naht sseLmpp 5. naht sseLetartiN ainommA mpp 5. naht sseLmpp 5. naht sseLmpp 5. naht sseLedixordyH ainommA
mpp 0051-0001mpp 0051-0001mpp 0001 naht sseL)SDT( sdiloS devlossiD latoT
mpp 2. < mpp 2. < mpp2. <
ces/tf 6<ces/tf 6 <ces/tf 6 < )retaW hserF( yticoleV dlohserhT
8
Water Piping
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Residential NDS split units are supplied standard with GeoLink swivel connections with P.T. ports.
CAUTION: Water piping exposed to outside temperatures may be subject to freezing.
Water Piping
The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger.
Closed Loop - Earth coupled Systems (Outdoor Installations)
Locate unit on an air pad with access hole as shown below. When mounting on an existing concrete pad, holes must be bored through to accommodate 1 1/4-inch P.E. pipe with 1/2-inch insulation.
Connecting To Earth Loop
The earth loop trench should be continued directly under the unit as shown in the Typical Split System Outdoor Installation Using Closed Loop. Make the connections to optional fittings from the loop circulator pump(s) and ensure proper backfill to support the loop pipe during trench settling. All 1 1/4-inch piping should be insulated with a minimum of 1/2-inch closed cell insulation from below the ground surface to the loop circulator.
Flow Center Installation
Flow centers FC1-GL or FC2-GL, as needed, may be internally mounted on the NDS splits, Two stub tubes with barbs are pre connected to the coax. Two tubes with brass fittings, to adapt to the flow center, 2 hoses to connect between the two sets of tubes, and four hose clamps are included with each NDS unit. The brass adapter fittings have plastic swivel connectors that also accept 1 in. O.D. copper pipe (sweat).
NOTE: For ease of installation, attach provided hoses to coax first and then trim to fit to elbows on flow center.
Typical Split System Outdoor Installation Using Closed Loop
IMPORTANT: A freeze detection thermostat is installed in the unit to automatically start loop circulator pump if loop temperature drops below 20°F. Loop freeze detection should also be maintained to the lowest temperature the insulated loop may encounter in the case of power failure.
Open Loop (Indoor Installations)
NDS Splits can be installed on an open loop system, but only indoors. All NDS Splits are supplied with GeoLink swivel connectors. The swivel connectors will also accept a 1 in. O.D. copper pipe (sweat) which can be connected in an open loop system.
Loop Supply and Return Piping
9
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Typical EZ Wiring Diagram
Electrical Data
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable. See unit electrical data for fuse or cicuit breaker sizing information.
Model
026
038
049
064
072
Rated
Voltage
208-230/60/1 197/253 16.0 10.2 52.0 18.0 5.4 15.6 17.0 25
208-230/60/1 197/253 26.0 16.6 82.0 29.0 5.4 22.0 23.4 40
208-230/60/1 197/253 33.0 21.1 96.0 34.0 5.4 26.5 2 7. 9 50
208-230/60/1 197/253 40.0 25.6 118.0 41.0 5.4 31.0 32.4 60
208-230/60/1 197/253 42.5 2 7.2 150.0 53.0 5.4 32.6 34.0 60
Rated voltage of 208-230/60/1. HACR circuit breaker in USA only. Min/Max voltage of 197/253. All fuses Class RK-5 * With optional IntelliStart
Thermostat Wiring
Thermostat Wiring
Air Handler
C
R
W
G
Common Common
24 VAC
Fan
Thermostat
Y1
Y2
O
L
C
R
W
G
Voltage
Min/Max
1st Stage Compressor
2nd Stage Compressor
Reversing Valve
Fault Signal
24 VAC
Compressor Ext
MCC RLA LRA LRA*
Thermostat Wiring for Dual Fuel Applications
Envision Split
Y1
Y2
O
P1
Lo
C
R
Fossil Fuel
Furnace
C
R
W
G
Auxiliary Heat Relay
Loop
FLA
Thermostat
Y1
Y2
O
L
Common Common
24 VAC
Fan
C
R
G
W
Unit FLA
1st Stage Compressor
2nd Stage Compressor
Reversing Valve
Fault Signal
24 VAC
Total
Auxiliary
Heat Relay
Min
Circ
Amp
Max Fuse/ HACR
Envision Split
Y1
Y2
O
LO
C
R
Shut
Down
1/17/11
P1
P2
Air Handler transformer must be at least 75 VA.
Note: Field installed DPST dual fuel relay
(Required for dual fuel installation) or use TP32U03 or TP32U04
10
Auxiliary Heat Relay
= chassis
NDS OUTDOOR SPLIT INSTALLATION MANUAL
Dimensional Data
Cabinet Dimensions and Refrigerant Piping Connections
Top View
B
Rear View
J
K
L
WATER OUT
WATER IN
Suction Line
Connection
Liquid Line
Connection
Front View
D
E
F
H
I
G
Lineset connections are braze type internally mounted
Side View
Side View
M
Model A B C D E F G H I J K L M
in
026 thru 072
Refer to Physical Dimensions and Piping Connections drawings
36.0 23.9 26.7 9.3 7.1 9.0 5.6 8.2 10.7 18.9 8.7 14.8 7.0
[cm] [91.4] [60.7] [67.8] [23.7] [18.0] [22.8] [14.2] [20.9] [27.2] [48.0] [22.1] [37.6] [17.8]
A
C
Physical Data
Model 026 038 049 064 072
Compressor (1 each) Dual Capacity Scroll Factory Charge R-410A, oz [kg] 52 [1.47] 56 [1.59] 90 [2.55] 92 [2.61] 104 [2.95]
Coax and Water Piping
Water Connections Size - Swivel- in [mm] GeoLink Swivel Connectors Brass Service Valve - Liquid Line - in [mm] 3/8 [9.525] 1/2 [12.7] Brass Service Valve - Suction Line - in [mm] 5/8 [15.875] 3/4 [19.05] 7/8 [22.2 25] Coax and Piping Water Volume - gal [l] 0.7 [2.6] 1.3 [4.9] 1.6 [6.1] 1 .6 [6.1] 1.6 [6.1] Weight - Operating, lb [kg] 189 [86] 236 [107] 250 [ 113] 271 [123] 290 [132] Weight - Packaged, lb [kg] 209 [95] 256 [116] 270 [122] 291 [132] 3 10 [141]
All units have TXV expansion devices, and 1/2 in. [12.2 mm] and 3/4 in. [19.1 mm] electrical knockouts. Brass service valves are sweat type valves.
10/29/08
11
Loading...
+ 25 hidden pages