1 – CCM
2 – Versatec Microprocessor
4 – FX10 Std. w/o Communication
5 – FX10 w/Open N2 Com Card
6 – FX10 w/Lonworks Com Card
7 – FX10 w/BacNet Com Card
NOTES: Chassis only available with left piping option.
FX10 option is only available with remote wall-mounted thermostat control.
Voltage Availability
Voltage
115/60/1
09121518
••
208-230/60/1••• •
265/60/1••• •
Model
1/20/14
C – Copper
N - CuproNickel
1 – Unit Mounted T-Stat
2 – Remote Wall-Mounted T-Stat
02 March 2014D
3
Page 4
General Installation Information
ENVISION CONSOLE INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or
maintenance operations on a system, turn off main
power switches to the indoor unit. If applicable,
turn off the accessory heater power switch.
Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning
equipment can be hazardous due to system pressure and
electrical components. Only trained and qualified service
personnel should install, repair or service heating and air
conditioning equipment. Untrained personnel can perform
the basic maintenance functions of cleaning coils and
cleaning and replacing filters. All other operations should
be performed by trained service personnel. When working
on heating and air conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use a quenching cloth for brazing operations and
have a fire extinguisher available.
Moving and Storage
Move units in the normal “up” orientation. Do not stack
units. When the equipment is received, all items should be
carefully checked against the bill of lading to be sure all
crates and cartons have been received. Examine units for
shipping damage, removing the units from the packaging
if necessary. Units in question should also be internally
inspected. If any damage is noted, the carrier should make
the proper notation on the delivery receipt, acknowledging
the damage.
Refrigerant Systems
To maintain sealed circuit integrity, do not install service
gauges unless unit opertion appears abnormal. Compare
the change in temperature on the air side as well as the
water side to the Unit Operating Parameters tables. If the
unit’s performance is not within the ranges listed, and the
airflow and water flow are known to be correct, gauges
should then be installed and superheat and subcooling
numbers calculated. If superheat and subcooling are outside
recommended ranges, an adjustment to therefrigerant
charge may be necessary.
Water Piping
The proper water flow must be provided to each unit
whenever the unit operates. To assure proper flow, use
pressure/temperature ports to determine the flow rate.
These ports should be located at the supply and return
water connections on the unit. The proper flow rate cannot
be accurately set without measuring the water pressure
drop through the refrigerant-to-water heat exchanger.
All source water connections on commercial units are
fittings that accept a male pipe thread (MPT). Insert the
connectors by hand, then tighten the fitting with a wrench
to provide a leakproof joint. When connecting to an open
loop (groundwater) system, thread any copper MPT fitting
into the connector and tighten in the same manner as
described above.
• Choose level flooring surface (Correctable with shims. Do not pitch towards drain.)
• Location of wall support and fasteners required to secure chassis backplate.
• Easy access for both installation and service.
• Consider availability and ease of wiring, water piping and condensate drain.
• No obstructions to block airflow in front of the unit.
Step 3: Mark Unit Position
• Ensure that floor is level. If shims are required, make sure that the entire compressor compartment area is uniformly
shimmed and that the backplate mounting height is increased by the thickness of the shims used.
• Position backplate in desired equipment location. To further reduce the operating sound level of the unit, 1/8-inch thick
rubber matting may be placed under the chassis to eliminate vibration on hard flooring surfaces. (Make sure back plate
is level).
• Mark and cut floor or wall penetrations for electrical wiring, water and condensate piping.
Optional Electrical Disconnect and Motorized Outside Air Damper
• Mark and cut wall penetrations for field fabricated outside air duct sleeve.
• Align mounting holes with backplate and attach with screws supplied.
Figure 1
1=<A=:3 1/07<3 B
0/19 >:/B3
=>B7=</:
4CA323:31B@71/:
27A1=<<31 B=>B7=</:
E/::>3<3B@/B7=<
4=@E/B3@1=<<31B7=<
4:==@>3<3B@/B7=<
4=@E/B3 @1=<<31 B7 =<
E/B3@
7<
E/B3@
=CB
>B>:C5A
=>B7=</:
0/: :D/:D3 A
=>B7=</:
=>B7=</:6 =A3A
;=B=@7H32
2/; >3@
=>3<7<5
;=B=@7H32
2/; >3@
=>B7=</:
1=<A=:3
16/AA7A
1=<23<A/B 3
2@/7< :=1/B7=<
12
1=<A=:3
1/07<3 B
Page 13
ENVISION CONSOLE INSTALLATION MANUAL
Installation Steps cont.
Step 4: Provide Water and Condensate Drain Connections
• A two-pipe reverse return piping configuration is recommended as it equalizes the piping circuit lengths and delivers
even water flow to each unit. A direct return piping configuration may be used, but it may be difficult to achieve and
maintain proper water flow to the units.
• An air vent must be installed in the water distribution system.
• The supply and return water piping should be run through the wall or floor penetration and terminate with a ball valve.
The piping material used must comply with all local codes.
• Refer to: System Cleaning and Flushing procedures.
#Þf&Þ/@3//>>=F Þ
4@=;3253=416/AA7A
Þ4@=;4@=<B3253
=41/07<3 B
3:31 B@71/:
8C<1B7=<0=F
1=<23<A/B 3
2@/7< :=1/B7=<
&Þ
#Þ
13
Page 14
ENVISION CONSOLE INSTALLATION MANUAL
Installation Steps cont.
Step 5: Provide Line Voltage Wiring
• Check unit data plate located on control side of chassis for ampacity and fuse size.
• Remove electrical knockouts from chassis backplate.
• Run line voltage wiring through knockout and secure wiring to backplate or disconnect.
Step 6: Chassis Installation
• Level and secure backplate to wall.
• Position the chassis against back plate. Drive (2) screws through holes in lip of backplate into top flange of chassis.
Step 7: Final Electrical Connection
• Install flexible electrical conduit between the backplate or electrical disconnect and the unit mounted junction box.
• Make final wiring connections in disconnect and junction box, taking care to replace all covers when done. Wiring must
conform to NEC and/or all local codes. Refer to Electrical Data.
NOTE: It is necessary to make final wiring connections prior to securing unit chassis to back plate on right-hand piping
models with electrical disconnect.
Step 8: Final Water Connection
• For ease of installation and sound attenuation, high pressure (recommended) flexible hoses with a swivel fitting should
be provided. Apply Teflon® tape or sealant compound to threaded hose fittings.
• Combination shut-off/balancing valves should be installed on both the supply and return water lines of the unit.
• Flow control valves should be installed on the water discharge line.
• It is recommended that P/T ports be installed on the supply and return water lines.
Step 9: Set Unit Controls
• Locate the “continuous fan/cycle fan” switch within the electrical compartment of the chassis and set to desired position.
(Remote wall thermostat units do not use this optional switch.)
• Optional Control SettingsRemote Thermostat - Run low voltage wiring from unit to the desired thermostat location.
Mount and wire thermostat according to manufacturer’s recommendations.
Motorized Outside Air Damper - Locate the “damper on/damper off” damper switch within the electrical compartment
of the chassis and set to desired position.
Emergency Electrical Heat - Locate the “electric heat/normal/boilerless” control switch within the electrical compartment of the chassis and set to desired position.
Step 10: Secure the Cabinet Cover
• Position and lower cabinet over unit chassis. Apply pressure to the front of the cabinet to ensure that the back lip of the
cabinet hooks over the tabs provided on the backplate.
• Secure cabinet to chassis with mounting screws provided.
Step 11: Perform Final Unit Check
• Measure the pressure drop across the water coil and monitor water or air temperatures in both heating and cooling
modes. The measured values should fall within the acceptable ranges shown in the Startup Performance table.
14
Page 15
ENVISION CONSOLE INSTALLATION MANUAL
Installation Steps cont.
Field Converting Console
Chassis is normally configured with controls on right end and piping on left end (see Figure 3 top view). In this position
panel number 1 would be positioned against wall or back plate. Unit may also be turned 180° against wall or back plate. In
this position controls will be on left end and piping on right end panel number 2 would be positioned against wall or back
plate. Chassis must be enclosed with an approved cabinet enclosure.
Figure 3
Top view
Side view
1
2
1. Remove 4 screws from front kick panel on cabinet.
2. Remove cabinet from chassis by lifting and sliding cabinet
straight up.
3. Remove grille assembly from cabinet by removing 4 screws from
brackets located on the bottom of the grille and door assemblies.
4. Replace grille/door assemblies into cabinet repositioning pieces
1, 2, and 3 into the locations directly opposite the original positions.
Secure by replacing mounting brackets. (Note: Be sure that louvers
on the grille assembly are facing the proper direction when
replacing the grille section.)
5. Replace grille/frame assembly into cabinet, and secure by replacing
mounting brackets.
6. Replace cabinet by sliding it down over the top of the chassis.
7. Remove tab on leg that extends into return air opening. When the
grille side of the cabinet is flat against chassis there will be 4
holes that line up in the leg section. Only use 1 hole for alignment
for opposite side of grille. (Note: The tab can be removed by
twisting back and forth until it breaks off.)
8. Remove plastic strip from tab and replace on rough edge that the
tab was removed from.
9. Replace screws in font kick panel to secure cabinet to chassis.
10. Mount filter bracket in designated opening area. (Note: The filter
bracket will only fit in one direction if cabinet is installed properly.)
15
Figure 4
Depends on Cabinet Size
3
2
1
4
5
Page 16
System Cleaning and Flushing
ENVISION CONSOLE INSTALLATION MANUAL
Cleaning and Flushing
Prior to start up of any heat pump, the water circulating system must be
cleaned and flushed of all dirt and debris.
If the system is equipped with water shutoff valves, the supply and
return runouts must be connected together at each unit location (This
will prevent the introduction of dirt into the unit, see Figure 7). The
system should be filled at the water make-up connection with all air
vents open. After filling, vents should be closed.
The contractor should start the main circulator with the pressure reducing valve makeup open. Vents should be checked in sequence to bleed
off any trapped air and to verify circulation through all components of
the system.
As water circulates through the system, the contractor should check
and repair any leaks found in the piping system. Drain(s) at the lowest
point(s) in the system should be opened for initial flush and blowdown, making sure water fill valves are set at the same
rate. Check the pressure gauge at the pump suction and manually adjust the make-up water valve to hold the same positive pressure both before and after opening the drain valves. Flushing should continue for at least two hours, or longer if
required, until drain water is clean and clear.
The supplemental heater and/or circulator pump, if used, should be shut off. All drains and vents should be opened to
completely drain the system. Short-circuited supply and return runouts should now be connected to the unit supply and
return connections.
Figure 7: Flushing with Water
Shutoff Valve Equipped Systems
Return Runout
Supply Runout
Mains
Rubber Hose
Runouts Initially
Connected Together
Refill the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline
(pH 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze
designed for HVAC systems only. Environol™ brand antifreeze is recommended..
Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the system from dirty water conditions. Dirty water will result in system-wide degradation of performance, and solids may clog
valves, strainers, flow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor
service life and can cause premature unit failure.
In boiler/tower application, set the loop control panel set points to desired temperatures. Supply power to all motors and
start the circulating pumps. After full flow has been established through all components including the heat rejector (regardless of season), air vented and loop temperatures stabilized, each of the units will be ready for check, test and start up
and for air and water balancing.
Ground Source Loop System Checkout
Once piping is completed between the unit pumping system and ground loop, final purging and charging of the loop is
needed. A high pressure pump is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from
the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as
much air as possible; then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter). This is
normally adequate for good system operation. Loop static pressure may decrease soon after initial installation, due to pipe
expansion and loop temperature change. Running the unit for at least 30 minutes after the system has been completely
purged of air will allow for the “break-in” period. It may be necessary to adjust static loop pressure (by adding water) after
the unit has run for the first time. Loop static pressure will also fluctuate with the seasons. Pressures will be higher in the
winter months than during the cooling season. This fluctuation is normal and should be considered when charging the
system initially.
Insure the pump provides adequate flow through the unit by checking pressure drop across the heat exchanger.
Usually 2.25-3.0 GPM of flow per ton of cooling capacity is recommended in earth loop applications.
16
Page 17
ENVISION CONSOLE INSTALLATION MANUAL
Open Loop Ground Water Systems
Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent
mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure
proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in
unit capacity data tables in the specification catalog. 1.5-2 GPM of flow per ton of cooling capacity is recommended in open
loop applications.
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on
local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of
sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.
Note: For open loop/groundwater systems or systems that do not contain an antifreeze solution, set SW1-Switch #2 to the
“WELL” position
mended to eliminate water hammer.
Water Quality
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present,
a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose
heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service
mechanic, as special solutions and pumping equipment are required. Desuperheater coils can likewise become scaled and
possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require
occasional flushing.
(Refer to the Dip Switch Field Selection table). Slow opening/closing solenoid valves (type VM) are recom-
Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to
build-up and corrosion, along with reduced wear caused by acid cleaning.
AmmoniaLess than 2 ppmLess than 2 ppmLess than 20 ppm
Ammonia ChlorideLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia NitrateLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia HydroxideLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Ammonia SulfateLess than 0.5 ppmLess than 0.5 ppmLess than 0.5 ppm
Total Dissolved Solids (TDS)Less than 1000 ppm1000 - 1500 ppm1000 - 1500 ppm
LSI Index+0.5 to -0.5+0.5 to -0.5+0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
SulfatesLess than 125 ppmLess than 125 ppmLess than 200 ppm
2
+ (Ferrous)
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
7 - 97 - 97 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm< 0.2 ppm< 0.2 ppm
< 6 ft/sec< 6 ft/sec< 6 ft/sec
(Total Hardness)
less than 350 ppm
10 - 50 ppmLess than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12
17
Page 18
ENVISION CONSOLE INSTALLATION MANUAL
Electrical Connections
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wiring must be done in accordance with local codes or the National Electric Code, whichever is applicable.
208 Volt Operation
All Envision Series 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red and blue transformer wires must be switched.
Microprocessor Remote Thermostat Wiring
Figure 5
Requires common
connections or 24
VAC for activation
Field
Connections
24 VAC
COMMON
COMPRESSOR
REVERSING
VALVE
FAN
LOCKOUT
SIGNAL
SHUTDOWN
NIGHT
SETBACK
LOAD SHED
Connections
TB
R
C
Y
O
G
L
S
X2
X1
W2
Unit
Red
Black
Yellow
Orange
Green
Brown
Blue
Violet
Pink
18
Page 19
ENVISION CONSOLE INSTALLATION MANUAL
Electrical Data
ECM Motor
Model
09
12
15
18
HACR circuit breaker in USA only
Rated
Voltage
115/60/1104/12712.58.050.04.2512.314.320
208-230/60/1187/2536.44.121.02.66.77.710/15
265/60/1238/2926.74.322.02.56.87.910/15
115/60/1104/12714.89.550.04.2513.816.125
208-230/60/1187/2537.74.925.02.67.58.810/15
265/60/1238/2927.04.522.02.57.08.110/15
208-230/60/1187/2539.25.929.02.68.510.015
265/60/1238/2927.85.028.02.57.58.810/15
208-230/60/1187/25310.46.733.52.69.310.915
265/60/1238/2928.75.628.02.58.19.515
Voltage
Min/Max
Compressor
MCCRLALRA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
1/20/14
PSC Motors
Model
09
12
15
18
HACR circuit breaker in USA only1/20/14
Rated
Voltage
115/60/1104/12712.58.050.00.928.910.925
208-230/60/1187/2536.44.121.00.504.65.610/15
265/60/1238/2926.74.322.00.504.85.910/15
115/60/1104/12714.89.550.00.9210.412.830
208-230/60/1187/2537.74.925.00.505.46.610/15
265/60/1238/2927.04.522.00.505.06.110/15
208-230/60/1187/2539.25.929.00.696.68.110/15
265/60/1238/2927.85.028.00.655.76.910/15
208-230/60/1187/25310.46.733.50.697.49.115
265/60/1238/2928.75.628.00.656.37.710/15
Voltage
Min/Max
Compressor
MCCRLALRA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/
HACR
19
Page 20
Auxiliary Heat Ratings
ECM Motors
ENVISION CONSOLE INSTALLATION MANUAL
Model
09-12
(1 kW)
09-12
(2 kW)
15-18
(3 kW)
Always refer to unit nameplate data prior to installation.10/5/10
Air fl ow values are with dry coil and standard fi lter.
For wet coil performance fi rst calculate the face velocity of the air coil (Face Velocity [fpm] = Airfl ow [cfm]
/ Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by
0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg.
Low SpeedHigh Speed
CFM
ECM Motors
Model
09300325400
12300325400
15350450600
18350450600
Low SpeedMedium SpeedHigh Speed
20
CFM
Page 21
ENVISION CONSOLE INSTALLATION MANUAL
Wiring Schematics
CCM - ELECTRONIC THERMOSTAT208-230-265/60/1
Compressor
C
S
Grn
Electro nic THER MOSTAT
T2
Shu t d o wn
T5
Overide
J1
Red (30)
A Heat
B Cool
HL
Black (2 9)
Yellow (13)
T1
T3
T4
T6
PSC
Fan
Motor
Wht
White (28)
IN
PUT
Brn
Cap
High
Low
DOWN
Ther
mistor
24 V
AC
T3
T1
T2
T4
T6
T5
SHUT
White (18)
Red (17)
Red (11)
Black (2 5)
4
6
1
3
Black
Black
Red (11)
Black (1 2)
Black
Blue
Handi - Box
CC
Blk/Wh t (24 )
24 V Accessory
Ground
HP HP CC CG LO R CLP LPY
Lug
HP HP CC CG LO R CLP LPY
White (34)
Damper
Motor
D
R
RedBlk
Tan (33)
T1
T2
L2
Whit e ( 28 )
4
5
Aut o
2
Fan
Black
Red (15)
Red (16)
2
Black (2 7)
RB
5
Brown (26)
Red (19)
Yellow (10)
ST
T
Fan Mode Sw
Continuous
Red (17)
Red
Yellow (13)
Orange (14)Orange (21)
Blue (T6)
Yellow (13)
24VAC
Shutdown
Cycled
Red (19)
Black (1 2 )
Black (2 2 )
Black (2 2 )
Whit e (18 )
31
Whit e ( 20 )
RV
Not Used
RB
CC
L1
Green (00)
PB
1
2
3
Brown (26 )
Black
NOTE 1
Blue
230V
265V
Transformer
NOTE 2
FS
NOTE 3
Black (3 1 )
Red
208V
Yellow Black/White
HP
LP
Violet (5)
Violet (4)
Red (32)
24V
Black/White (1)
Red (2)
Brown ( 3 )
Violet (4)
Violet (5)
Black (6 )
Black (7 )
Blue (8)
Blue (9)
Yell ow (1 0)
Blue/Wht (36)
Blk/ W ht (2 3)
Unit
Power Supply
208- 230 /60/1 or
265-277/60/1
G
TEST
PIN
COMPRESSOR
CONTROL MODULE
Damper Sw
ON
OFF
Blue/Wht (35)
DT
Factory low voltage wiring
Factory line voltage wiring
Field low voltage wiring
Field line voltage wiring
Quick connect terminal
Wire n u t
CC -Compressor Contactor
DT - Dam per Term inal Bloc k
FS -Freeze Sensing Device
HP -High Pressure Switch
LP -Low P res s ur e Sw it c h
PB - Power Block
RB - Blower Relay
RV -Rev ers ing V alve C oil
ST -Ent er ing A ir Temper at ur e S ens or
Legend
21
HP
LP
T
Switch - High Pressure
Switch -Low Pressure
Relay coil
Capacitor
Thermistor
Temperatur e S wit c h
Notes:
1. Switch Red and Blue wires for 208 volt
operation
2. Terminal C of 24 V PB is used as “L”
output for Brown wire 3 f or L ockout.
3. Optional field installed freeze sensing
device.
CC - Compressor Contactor
DT - Damper Terminal Block
FS - Freeze Sensing Device
HP - High Pressure Switch
LP - Low Pressure Switch
PB - Power Block
RB - Blower Relay
RV - Reversing Valve Coil
ST - Entering Air Temperature Sensor
Legend
22
HP
LP
T
Switch - High Pressure
Switch - Low Pressure
Relay coil
Capacitor
Thermistor
Temperature Switch
Notes:
1. Switch Red and Blue wires for 208 volt
operation
2. Terminal C of 24 V PB is used as “L”
output for Brown wire 3 for Lockout.
3. Optional field installed freeze sensing device.
4. Factory wired. Refer to blower table settings.
L1
Field wire lug
Earth Ground
Relay Contacts N.O., N.C.
132
P
Polarized connector
Page 23
ENVISION CONSOLE INSTALLATION MANUAL
Wiring Schematics cont.
CCM w/EH - ELECTRONIC THERMOSTAT
Blue
PSC
Fan
Motor
Grn
Red (30)
HL
Black (29 )
Shut do wn
Brn
Wht
Cap
Whit e ( 28)
High
Low
Yell ow (4 4)
Yell ow (1 3)
Elec t ronic THERMOSTAT
A Heat
T1
T2
T3
T4
T5
Overide
T6
B Cool
J1
White
T2T1
EH
L2
4
6
1
3
Black
Black
Red (11)
Black (12 )
Black
4
RB
Red (19)
5
Aut o
2
Fan
ST
T
Red
(17)
Red
Black
Yellow (13)
Orange (14)
Blue (T6)
24VAC
Shutdown
Red (15)
Red (16)
Black (25)
Whit e (18 )
Red (17)
Red (11)
Ther
IN
PUT
mistor
24 V
AC
T3
T1
T2
T4
T6
T5
SHUT
DOWN
L1
Tan (41)Blue (40)
2
5
White
Black (27)
Brown (26)
Continuous
Fan Mode Sw
Cycled
208-230-265/60/1
Compressor
Handi -Box
NOTE 1
Blk/ W ht (2 3)
24 V Accessor y
Ground
Lug
Red
208V
Transf ormer
HP HP CC CG LO R CLP LPY
EH
CC
Blk /W ht (2 4)
Damper
Motor
24V
HP HP CC CG LO R CLP LPY
Blue (38)
Black (37 )
Whit e ( 34)
D
C
S
Blue
R
RedBlk
Tan (33)
T1
T2
CC
Brown (26 )
L1
L2
Blue (40)
Whit e (28 )
Tan ( 4 1 )
PB
Red (19)
Black (1 2 )
Black (2 2 )
1
3
E1
AQ
Brown (43)
Whit e (18)
Whit e (20 )
Yellow (44)
Orange (21)
RV
NOTE 4
RB
Gray (42 )
Normal
EH
Blue (T 6 )
31
A
C
D
Green (00)
NOTE 3
NOTE 2
FS
Black (31 )
Red (32)
Black
Blue
230V
265V
Yellow
Black/White
Black/White (1)
Red (2)
Brown (3)
Violet (4)
Violet (5)
Black (6 )
HP
Black (7 )
Blue (8)
LP
Blue (9)
Yellow (10)
Violet (4)
Red (39)
Viol et (5 )
Blue/Wht (36)Blue/Wht (35)
Unit
Power Supply
208-230/60/1 or
265-277/60/1
G
TEST
PIN
COM PRESSOR
CONTROL MODULE
2
E1
5
Damper Sw
ON
OFF
DT
4
Factory low voltage wiring
Factory line voltage wiring
Field low voltage wiring
Field line voltage wiring
Quick connect terminal
Wire n u t
AQ - A quas t at
CC - Com pr es s or C ont ac t or
DT -D am per Term inal B lock
E1 - Electric Heat Relay
EH - Electric Heat Contact or
FS - Freez e S ens ing Devic e
HP - High Pressure Swit ch
LP - Low Pressure Swit ch
PB - Power Block
RB - Blower Relay
RV - Reversing Valve Coil
ST - E ntering Air Temper at ur e S ens or
Legend
Legend
L1
Field wire lug
Eart h Ground
Relay Contact s -
N.O., N.C.
132
P
Polarized c onnect or
HP
LP
T
Switch - High Pressure
Switch -Low Pressure
Relay coil
Capacitor
Thermistor
Temperatur e S wit c h
Notes:
1. Switch Red and Blue wires for 208 volt
operation
2. Terminal C of 24 V PB is used as “L”
output for Brown wire 3 for Lockout.
3. Optional field installed freeze sensing
device.
4. Optional field installed aquastat.
6/10/08
23
Page 24
p
Wiring Schematics cont.
Legend for Schematic [A]
Blower of f delay
Com pres s or on delay
Short cycle delay
Minimum compressor on time
High pres s ure f ault rec ognit ion delay
Low pres s ure f ault rec ognit ion delay
Freez e s ens ing f ault rec ognit ion delay
Condens at e ov erf low f ault rec ognit ion delay
Low pres s ure f ault by pas s delay
Freez e s ens ing f ault by pas s delay
Mot oriz ed v alv e delay
Random s t art delay
Norm al C ont rol T im ing T able
30 seconds
10 seconds
5 minutes
60 sec onds (except f or f ault c ondit ion )
Less than 1 second
30 seconds
30 seconds
30 sec onds
2 minut es
2 minutes
90 sec onds
0 -25 seconds
ENVISION CONSOLE INSTALLATION MANUAL
208-230-265/60/1VERSATEC CONTROL - EH & REMOTE WALL THERMOSTAT
Versa t e c Logic Board P hysical Lay out
FANFANCOM
CC Relay
6
1
7
2
P2
8
3
9
4
10
5
CCG
CC
Fan R e la y
C
C
R
R
Blower of f delay
Com pres s or on delay
Short cycle delay
Minimum compressor on time
High pres s ure f ault rec ognit ion delay
Low pres s ure f ault rec ognit ion delay
Freez e s ens ing f ault rec ognit ion delay
Condens at e ov erf low f ault rec ognit ion delay
Low pres s ure f ault by pas s delay
Freez e s ens ing f ault by pas s delay
Mot oriz ed v alv e delay
Random s t art delay
5 sec onds
2 sec onds
15 sec onds
5 sec onds (except f or f ault c ondit ion )
Less t han 1 second
30 seconds
30 seconds
30 seconds
0 sec onds
0 sec onds
90 seconds
0 sec onds
LED D is play M ode T able
Tes t C ont rol T im ing T able
LEDNormal Display Mode
Drain
Wat e r Flo w
High Pres s
Low Pres s
Air Flow
Status
DHW Limit
HWD
LED
Drain
Wat e r Flo w
High Press
Low Pres s
Air Flow
Status
DHW Limit
HWD
*Flashing Status light indicates microprocessor is functioning properly. Solid "on" indicates a
micro
SW1 - # 4 On, SW2 Off
Drain pan over f low loc kout
FS ther m istor (loop < 15° F, well < 30° F ) lock out
High press ure > 600 P S I loc kout
Low press ur e < 40 PSI loc k out
Not us ed
Micr opr oces s or m alf unc t ion *
Not Used
SW 2 stat us (Off =down pos it ion, On= up pos it ion )
Current Faul t Status
SW1- # 4 On, SW2 On
Drain pan over f low
FS ther m istor (loop
High press ure >600 PS I
Low press ur e < 40 P S I
Not us ed
Not us ed
Not us ed
SW2 in the On position
rocessor malfunctio n.
< 15°F, well <30°F )
Diagnostic Modes
Inputs
SW1-#4 Off , SW2 Off
Not Used
Off position
Outp uts
SW1-#4 Off, SW2 On
Y
G
O
ES
NS
LS
Compressor
Not Used
On position
FAN
ES
NS
LS
P3
P1
RCYOGLOESNSLS
Microprocessor
Logic Cont rol
17P529A01
SW1
Logic Board D I P Sw it c h Set t ings
SwitchOFFON
Test - Selected timings sped up to facilitate
SW1 - 1
troubleshooting
Loop - Closed loop freeze sensing setting (15°F)
SW1 - 2
Enables NS features
SW1 - 3
IO Display * - Enabl es Input/Output display on external
SW1 - 4
LED board*
SW1 - 5
Motorized Valve - 1.5 minute compressor on delay
OFF * - Normal or Input display mode activated
SW2
*Refer to LED Display Mode table for position of SW1-4 and SW2
Normal - Standard timings
Well - Open loop freeze sensing setting (30°F)
Normal - Standard thermostat operation
Normal * - Unit status display
Normal - Standard delay on call from
compressor used
ON * - Current fault or Output display
mode activated
Operational Logic T able
Mode
O
Htg
Clg
FanGON
InputsFanCompRV
Y,O
Y
ON
ON
ON
ON
OFF
OFF
ON
OFF
24
Page 25
ENVISION CONSOLE INSTALLATION MANUAL
Wiring Schematics cont.
Schematic [A]
Black
PSC
Fan
Motor
Low
White (28)
Brn/Wht
Brn
Cap
LS2
White
T2T1
L2
Blue (40)
LS1
White
EH
L1
Tan ( 4 1)
Fan Speed
Switch
Grn
Black(29)
High
HL
Red (30)
208-230-265/60/1VERSATEC CONTROL - EH & REMOTE WALL THERMOSTAT
Compressor
C
S
Blu
Tan ( 3 6)
T2T1
R
Red
Blk
CC
L1L2
Black (3 1 )
Red (32)
Handi - B ox
Ground
Lug
Unit
Power Supply
208-230/60/1 or
265-277/60/1
G
Red
Black (2 5 )
DAMPER M ODE
Damper
Motor
White (34)
Red 208V
Transf ormer
24V
Yellow
FAN
Black/ White
R
R
C
C
10
Green (00)
P2
Black (47)1
Black (4 6 )
6
2
Blue (45)
7
Blue (44 )
3
Brown(43)
8
Orange (42)
4
9
Orange (41)
5
Yellow
Yellow
HP
LP
CO
Gray (42 )
RV
FS
T
RB
42
Off
On
Blue/Wht (35)
DT
D
Blue/Wht (36)
CC
Brown (43)
Red(19)
Red (39)
Blue (38 )
EH
Black(27)
Black (2 2 )
COM
CC
5
4
E1
2
Black (37 )
CCG
CPU
SW1
OnOff
1
Test / Nor mal
2
Loop / Well
3
Inputs / Normal
4
Ou tp u ts / No r ma l
5
Motorized Valve / No rm a l
Blue 265V
Blue 230V
13
RB
FAN
P1
NOTE 5
Black Com
Orange (21)
LSNSESLOGOYCR
Red
Bl ack
Yellow
Orange
Pink
Bl ue
Violet
Brown
Green
White
E1
T
Relay ContactsN.O., N.C.
Thermistor
Re lay coil
Factory low voltage wiring
Factory line voltage wiring
Field low voltage wiring
Field line voltage wiring
DC voltage PCB traces
Internal junction
Quick connect terminal
Wire nut
L1
Field wire lug
Ground
Black/
White
MV
NOTE 2
P
Black/
White
Legend
132
Legend
Switch - High pressure
Switch -Low pressure
Polarized connector
Condensate Overflow
25
CRY1OGLS
X2 X1 W1
Terminal Board
AQ – Aquastat
CC – Compres s or Contactor
CO – Condensate Overflow
DT – Damper Terminal Block
E1 – Electric Heat Relay
EH – Electric Heat Contactor
ES – Emergency Shutdown
FS – Freeze Se nsing Device
HP – Hig h Pressure Sw itch
LP – Low Pressure Switch
LS – Loadshed
MV – Motorized Valve
NS – Night Setback
RB – Blower Power Relay
RV – Reversing Valve Coil
SW1 – D IP Swit c h #1
NOTE 1
NOTE 3
AQ
Notes:
1 -Requires common connection or 24 VAC for
activation.
2 -When field installed 24VAC motorized
valve is used, connect to C and Y or SV terminals.
3 -Optional field installed aquastat for use with single heat
4 -Check installlation wiring information for
specific thermostat hookup instructions.
5 -Switch blue and red wires for 208V operation.
97P786-046/10/08
Page 26
ENVISION CONSOLE INSTALLATION MANUAL
Wiring Schematics cont.
FX10 - EH208-230-265/60/1
Compressor
S
C
Handi - B ox
Red
MEHS
Red (20)
Black
Yellow
Ground
PB1
L1
L2
HP
RB
Lug
RV
R
BlkRed
Tan
T1
T2
L2
L1
Black
Yell ow (3 3)
Molex
Plug
20
19
18
Black (1)
17
Black (111)
Black (310)
Yellow (9)
Orange (7)
Black (6 )
Black (5 )
Blue (4)
Gray (3)
Black (2)
Black
(12)
Yellow (16)
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
Blue 240V
277V
NOTE 1
Red 208V
Blk
Power S upply
208-230/60/1 or
265-277/60/1
Blk/Wht
White
CC
Blk/Wht
Unit
G
Transf ormer
Yellow
Blk
Orange
EHC
NOTE 5
24VAC
24V COM
Alarm
Acc 1
Acc 2
Fan
Rev Valve
Comp
Setpoint Shift
AI Com
Room Sens or
Sensor Com
Tem p Oc c
TB
R
C
L
X1
X2
G
O
Y1
SS
AIC
RS
SC
TO
LC1
LC2
Black (11 1 )
Black (31 0 )
PB2
L2
L1
Molex
Plug
NOTE 2
Black (3 1)
Fan Spe e d
NOTE 3
Switch
NOTE 4
Grn
HL
Blk
Red
HighLow
FS
DA
Org/Wht (12)
Green (17)
Orange (19)
Red (120)
Yellow ( 21)
CP/FP
Gray (26 )
ES
OS
PSC
Fan
Motor
CO
DF/AP
Brown (1)
Brown (2)
T
Wht /B lu ( 6)
T
Blk/Red (9)
Blu/ W h t (10 )
Org/Bck (11)
Gry /Wht (1 4 )
Black (6 )
Black (2 2 )
Violet (23)
Red (24)
LP
Blue (27)Blue (32 )
Pink (28)
Blk /W ht (2 9)
Orange (30)
Brn
Red (120)
White (5)
Brn/Wht
11K
Cap
White
Blue
Blu
EHC
L1
Black(121)
Yellow (35)
A33
White
LS2
Black (515)
Blk/ W ht (3 6)
TAN
BLUE
Black (1 31 )
CC
Black (3 4 )
D09
D08
D07
D06
D05
D04
D03
D02
D01
LS1
White
T2T1
L2
RB
Black
J8
5VDC
23
-
24
AI3
+
25
-
26
AI5
+
27
-
28
AI4
+
29
-
30
AI6
+
31
-
32
AI2
+
33
5VDC
34
-
35
AI1
+
36
37
38
J2
39
40
41
J10
42
43
44
45
46
47
48
J9
49
50
51
52
53
54
55
56
LED
5VDC
PWM2
PWM2 Com
PWM1
24VAC Com
DI12
DI11
DI10
DI9
DI8
DI7
DI 3/4/5/6/ Com
DI6
DI5
DI4
DI3
DI2
9VDC
DI1
A21A12
A23
Black
Black (6 )
Gree n ( 37)
24VAC
24VAC Com
GROUND
A14
A24
A34
A25 A2 2
A32
A31A35
A13
A11
A15
Johnson FX-10
J7
Factory low voltage wiring
Factory line voltage wiring
Field low voltage wiring
Field line voltage wiring
Field Zone Sensor Wiring
T
Internal junction
Quick conn ect t ermina l
Wire nut
L1
Field wire lug
Ground
Relay Contacts-
N.O., N.C.
Thermistor -Johnson Control
Re lay coil
Open Jumper
Closed Jumper
P
Legend
Switch -High pressure
Switch - Low pressure
Polarized con n ector
132
Condensate Overflow
26
CC - Compressor Contactor
CO - Condensat e Overf low
CP/FP - Compressor Proving/Fan Prov ing
DA -Disc har ge A ir Temper ature
DF/AP - Dirty Filter /Air P r ov ing
EHC - Electric Heat Contactor
EHR - Electric Heat Relay
ES - Emergency Shutdown
FS - Freez e S ens ing Devic e
HP -H igh P r es s u re S wit ch
LP - Low Pressure Switch
MEHS - M anual E H S wit c h
OS - Occupied Switch
RB -Blower P ower Replay
RV -Rev ers ing V alve Coil
TB - Terminal Block
Notes:
1 -Switch Blue and Red wires for 208V operation
2 -Disconnect for 15 degree freeze protection
3 -Acc 1 output is cycled with the compressor.
4 -Acc 2 output is cycled with the fan.
5 - R, C, Y1, O, and G inputs are for use with a wall mounted
thermostat.
is a more reliable replacement for
electro-mechanical control applications.
It features a small microprocessor
board that handles the lockout function
of the unit. A second microporcessor
handles the unit mounted thermostat for
maintaining accurate room temperature.
Versatec ControlThe Versatec Control is a
microprocessor based board that adds
the features of emergency shutdown
(ES), night setback (NS), water freeze
sensing (FS), Load Shed (LS) and
condensate overfl ow (CO). The
Versatec Control also features Optional
Field servicing LED's for mode, Fault
and diagnostic indication.
Residential and commercial
applications requiring minimal but
reliable controls. Includes Random
Start, High and low pressure
switches and auto changeover
capability.
Residential and commercial
applications requiring more controls
features than CCM and Includes
Random Start, High and low
pressure switches, auto changeover
capability, emergency shutdown
(ES), night setback (NS), load shed
(LS), water freeze sensing (FS), and
condensate overfl ow (CO).
Dial thermostat with Hi and
Low fan speeds, and auto
changeover or cont fan
selection switches.
Optional fi eld servicing LED
board for mode, fault and
diagnostic indication
NoneUnit Mounted Digital
Dial Thermostat
Remote Mounted
Standard Thermostat
NoneUnit Mounted Digital
Dial Thermostat
Remote Mounted
Standard Thermostat
FX10The FX10 microprocessor control is self
contained control featuring LP, LOC,
HP, LWT, and condensate overfl ow
fault modes can be displayed on BAS
system. Optional handheld Medium User
Interface (MUI) Control can be used for
additional setup or servicing. Program
customization is possible. This control is
suited for both single and dual capacity
compressors as well as PSC and ECM
fan motors.
FX10 w/ N2FX10 Control functions as both unitary
heat pump control and DDC communication, therefore detail operational and
fault information is available to BAS.
Other features are same as FX10 with
addition of Johnson Controls N2 compatibility.
FX10 w/ LonWorksFX10 Control functions as both unitary
heat pump control and DDC communication, therefore detail operational and
fault information is available to BAS.
Other features are same as FX10 with
addition of LonWorks compatibility.
FX10 w/ BACnetFX10 Control functions as both unitary
heat pump control and DDC communication, therefore detail operational and
fault information is available to BAS.
Other features are same as FX10 with
addition of BACnet compatibility.
Commercial applications using single and dual capacity compressors
with either PSC or ECM fan motors.
Also suitable for multi-compressor
products. Cannot be integrated
with centralized building automation
systems. Software can be customized for specifi c projects.
Same as FX10 with Johnson
Controls N2 BAS compatibility.
Same as FX10 with LonWorks BAS
compatibility.
Same as FX10 with BACnet BAS
compatibility.
Due to communication speed,
no more than 40 units should
be connected to a single trunk
of the network.
Optional Medium User
Interface (MUI) can be
used as a
fi eld service tool.
Optional Medium User
Interface (MUI) can be
used as a
fi eld service tool.
Optional Medium User
Interface (MUI) can be
used as a
fi eld service tool.
Optional Medium User Interface (MUI) can be mounted
or used as a
fi eld service tool.
StandaloneRemote Mounted
Johnson
Controls
N2 network
LonWorksRemote Mounted
BACnet - MS/
TP
(19,200 Baud
Rate)
Standard Thermostat
Remote Mounted
Sensor
Remote Mounted
Standard Thermostat
Remote Mounted
Sensor
Standard Thermostat
Remote Mounted
Sensor
Remote Mounted
Standard Thermostat
Remote Mounted
Sensor
Standard CCM Control Features
Compressor control module (CCM) controls are standard
on the Envision console heat pump. This control features
unit mounted thermostat and switches,
Features of the standard control are:
• Easy to understand color coded thermostat
adjustment markings.
• Large, rocker type mode and fan switches.
• Internally mounted fan switch to choose cycled or
constant fan operation.
• High pressure and low pressure safety controls to
protect the unit components.
• Lockout circuit to shut down unit operation upon
receipt of a fault indicator from the safety controls.
• A 24 volt control circuit allows for safe and
easy diagnosis.
27
Page 28
Envision Console Controls cont.
ENVISION CONSOLE INSTALLATION MANUAL
The user selects either “Heat/Cool” or “Fan Only” on the
mode switch, then either “High” or “Low” at the fan speed
switch. The temperature can be controlled by rotating the
thermostat control knob.
Figure 6: Unit Mounted Control
The “Fan Only” setting provides constant fan operation.
In the “Heat” mode, a call for heat by the thermostat closes
the compressor contactor contacts, energizing the compressor, which will run until the thermostat is satisfied.
In the “Cool” mode, a call for cooling by the
thermostat energizes the reversing valve and closes the
compressor contactor contacts, energizing the compressor, which will run until the thermostat is satisfied.
Optional Versatec Microprocessor
Control Features
The Versatec microprocessor board provides control of
the entire unit as well as outputs for status modes, faults
and diagnostics. The control system is a microprocessorbased control board that is located in the unit control box.
This feature is available for either unit mounted controls
or optional remote wall mounted thermostat. A 9-pin low
voltage terminal strip provides all necessary terminals for
the wall mounted thermostat.
Startup
The unit will not operate until all the inputs and safety
controls are checked for normal operating conditions.
Fault Retry
All faults are retried twice before finally locking the unit
out to prevent nuisance service calls.
Component Sequencing Delays
Components are sequenced and delayed for optimum unit
performance.
Short Cycle Protection and Random Start
The control allows a minimum on or off time of 5 minutes
for short cycle protection. A random time delay of 0 to
30 seconds is generated after each power-up to prevent
simultaneous start up of all units within a building after the
release from an unoccupied cycle or power loss.
The emergency electric heat operation in the “Heat/Cool”
mode is subject to the setting of the internally mounted
mode switch. The optional, factory installed electric heat
will operate when the internally mounted mode switch is
in the “Emergency Heat” mode. In the “Heat” mode, a call
for heating energizes the fan and electric heater contactor,
energizing the electric heat elements and fan, which will
run until the thermostat is satisfied. When the internally
mounted mode switch is in the “Normal/Boilerless” mode
the unit operates in its normal “Heat/Cool” operation,
unless there is an aquastat controller. When the normally
open circuit of the aquastat closes and the unit is in the
heating mode, it will switch to the “Emergency Heat”
condition until the thermostat is satisfied or the aquastat
opens restarting the compressor.
If either the low or high pressure safety switches are
opened, the compressor and reversing valve are disabled
by the lockout relay. Unit operation will resume only after
the voltage to the unit is interrupted or the mode switch is
placed in the “Off” position.
If the electric heat limit switches are opened, the electric
heat is disabled.
Night Setback
A grounded signal to common or connecting 24 VAC to
the NS terminal will initiate the night setback mode.
Load Shed
A grounded signal to common or connecting 24 VAC to
the LS terminal places the controller into the load shed
mode. The compressor will become disabled and the fan
will start upon a thermostat call for heating or cooling.
Emergency Shutdown
A grounded signal to common or connecting 24 VAC to
the ES terminal places the controller into the emergency
shutdown mode. The compressor and fan operation are
suspended while in the emergency shutdown mode.
Condensate Overflow Protection
The board incorporates an impedance liquid sensor at the
top of the condensate drain pan. Upon a continuous 30second sensing of the condensate, the cooling operation of
the unit is suspended.
Safety Controls
The microprocessor board receives separate signals from
a high pressure switch for safety, a low pressure switch to
28
Page 29
ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls cont.
prevent loss of refrigerant charge and a low suction temperature thermistor for freeze sensing. Upon a continuous
30-second measurement of the fault (immediate for high
pressure), compressor operation is stopped.
Control Tables for Optional Versatec Microprocessor
Logic Board DIP Switch Settings
SwitchOFFON
SW1 - 1
SW1 - 2
SW1 - 3
SW1 - 4
SW1 - 5
Normal Control TimingOperational Logic
Blower off delay
Compressor on delay
Short cycle delay
Miniumum compressor on time
High pressure fault recognition delay
low pressure fault recognition delay
Freeze sensing fault recognition delay
Condensate overflow fault recognition delay
Low pressure fault bypass delay
Freeze sensing fault bypass delay
Power on delay
Test - Selected timings sped up to facilitate troubleshootingNormal - Standard timings
Commercial - Enables NS features when TA32U02 thermostat is usedNormal - Standard thermostat operation
IO Display* - Enables Input/Output display on external LED boardNormal* - Unit status display
Configures board for 2-speed compressor without fanConfigures board for 2-speed compressor with fan
30 seconds
10 seconds
5 minutes
2 minutes (except for fault condition)
Less than 1 second
30 seconds
30 seconds
30 seconds
2 minutes
2 minutes
5 minutes
ModeInputsFanCompRV
Htg
Clg
Fan
YONONOFF
Y,OONONON
GONOFFOFF
Test Control Timing
Blower off delay
Compressor on delay
Short cycle delay
Miniumum compressor on time
High pressure fault recognition delay
low pressure fault recognition delay
Freeze sensing fault recognition delay
Condensate overflow fault recognition delay
Low pressure fault bypass delay
Freeze sensing fault bypass delay
Power on delay
Fault off time
5 seconds
2 seconds
15 seconds
5 seconds (except for fault condition)
Less than 1 second
30 seconds
30 seconds
30 seconds
0 seconds
0 seconds
15 seconds
5 minutes
Diagnostic Modes
LED
DrainDrain pan overflowYCompressor
Water FlowFS thermistor (loop <15°F, well <30°F)GFAN
High PressHigh pressure >600 PSIOO
Low Press Low pressure <40 PSIESES
Air FlowNot usedNSNS
StatusNot usedLSLS
DHW LimitNot usedNot usedNot used
HWDSW2 in the On positionOff positionOn position
Current Fault Status
SW1 - #4 On, SW2 On
Inputs
SW1 - #4 Off, SW2 Off
Outputs
SW1 - #4 Off, SW2 On
29
Page 30
Envision Console Controls cont.
ENVISION CONSOLE INSTALLATION MANUAL
Optional FX10 Control
Main FX 10 Board
The optional FX10 control provides unparalleled capability
in several areas including performance monitoring, zoning,
humidity, energy management, and service diagnosis, and
then communicates it all thru standard DDC protocols like
N2, Lon and BACnet (MS/TP @ 19,200 Baud rate).
The most unique feature is integrating the FX10 into the
Envision series as both the heat pump and DDC controller
providing both a cost advantage and providing features
not typically found on WLHP controls. This integration
allows heat pump monitoring sensors, status and service
diagnosis faults to be communicated thru the DDC direct
to the building automation system (BAS), giving building
supervisors detailed and accurate information on every
piece of equipment without removing an access panel.
Random Start
A delay of 1 to 120 seconds is generated after each powerup to prevent simultaneous startup of all units within a
building after the release from an unoccupied cycle or
power loss.
Emergency Shutdown
A field-applied dry contact can be used to place the
control into emergency shutdown mode. During this mode,
all outputs on the board are disabled.
Freeze Detection Limit
Field selectable for 15° or 30°F (-9° or -1°C)
Installation Options
• Standalone controlled by standard room thermostat
• Standalone with a Zone Temperature Sensor (must
have user interface to change set points beyond
the allowed +/- 5°F)
• Integrated into BAS by adding communication module
Accessory Outputs
Quantity 2. One cycled with blower, other with compressor.
User Interface
4 x 20 backlit LCD.
FX10 Advanced Control Overview
The Johnson Controls FX10 board is specifically designed
for commercial heat pumps and provides control of the
entire unit as well as input ports for Open N2, LonTalk,
BACnet (MS/TP @ 19,200 Baud rate) communication
protocols as well as an input port for a user interface. The
user interface is an accessory item that can be used to aid
in diagnostics and unit setup. A 16-pin low voltage terminal
board provides terminals for common field connections.
The FX10 Control provides:
• Operational sequencing
• High and low-pressure switch monitoring
• General lockout
• Freeze detection
• Condensate overflow sensing
• Lockout mode control
• Emergency shutdown mode
• Random start and short cycle protection
Short Cycle Protection
Allows a minimum compressor “off” time of four minutes
and a minimum “on” time of two minutes.
Optional Plug-in Communication Modules (compatible with standard BAS protocols)
• Open N2
• LonTalk
• BACnet (MS/TP @ 19,200 Baud rate)
Display
Requires DLI Card/Kit. Up to 2 displays, either 1 local
and 1 remote, or 2 remote. (A 2-display configuration
requires identical displays.) Local display can be up to
3 meters from the controller, power supply, and data
communication. Remote display can be up to 300 meters
from the controller. Remote display must be independently
powered with data communication done via 3 pole
shielded cable.
30
Page 31
ENVISION CONSOLE INSTALLATION MANUAL
system (BAS). This means that not o
Envision Console Controls cont.
Control Timing & Fault Recognition Delays
Lead compressor “ON” delay ..........................................90 seconds
(not applicable for single compressor models)
Minimum compressor “ON” time ...................................... 2 minutes
(except for fault condition)
Short cycle delay ..................................................................... 5 minutes
Random start delay ....................................................... 0-120 seconds
High pressure fault ................................................................. <1 second
The FX10 is a microprocessor based control that not
only monitors and controls the heat pump but also can
communicate any of this information back to the building
automation system (BAS). This means that not only does
MUI and will be held in memory until the unit is power
cycled. Relative humidity can be read by a 0-5VDC
humidity sensor that is displayed over the network. If you
are using an ECM2.3 blower motor the control can enable
dehumidification mode based on a set point in the control.
The dehumidification set point itself can also be changed
over a BAS or with a MUI. Dehumidification mode can also
be enabled by the BAS. Because the FX10 is not factory
configured to read CO
application assistance.
The FX10 control has unused analog and digital inputs
for field installed items such as air temperature, water
temperature, CO
unused binary and PWM outputs that can be commanded
over the BAS for field use. An optional Medium User
Interface (MUI) for control setup and advanced diagnostics
is available with some mounting kits, MUIK1 - Panel mount
version and the MUIK2-Wall mount version.
2
levels, contact the factory for
2
or current status switches. The control has
Zone Sensors
There are two options for zone sensors that can be used
with the FX10 control. Both sensors use a Johnson controls
A99 positive temperature coefficient type sensor. The
TAXXJ02 has a set point adjustment now which will give
the end user a +/- 5°F adjustment from the set point as
well as a push button that can be used for temporary
occupancy. The control leaves the factory set to operate
with a TAXXJ02 sensor and can be changed to read the
TAXXA01 sensor through a building automation system or
with a user interface.
the control monitor the heat pump at the unit you can also
monitor and control many the features over the BAS. This
clearly puts the FX10 in a class of its own.
The control will enumerate all fault conditions (HP, LP, CO,
LOC, and Freeze Detection) over a BAS as well as display
them on a medium user interface (MUI). HP, LP, CO and
Freeze Detection faults can all be reset over a BAS. A
Loss Of Charge fault can not be reset or bypassed until
the problem has been corrected. A MUI is invaluable as a
service tool for the building service team.
The unit can be commanded to run by a typical heat
pump thermostat or run based on heating and cooling
set points supplied by a BAS. The control board is wired
with quick connect harnesses for easy field change out
of a bad control board. All ECM2.3 variable blower speed
settings can be changed over a BAS or with a MUI. The
control has an input programmed to enable field installed
emergency heat in the event that the compressor is locked
out. This input can also be commanded on from a BAS
as needed. An alarm history can be viewed through the
Standard Features
• Anti Short Cycle
• High Pressure Protection
• Low Pressure Protection
• Freeze Detection
• Loss Of Charge Detection
• Random Start
• Display for diagnostics
• Reset Lockout at disconnect or through BAS
• 2 Accessory outputs
• Optional BAS add-on controls
DDC Operation and Connection
Other optional network protocol boards that can be added
to the FX10 are:
• Johnson Control N2
• LonWorks
• BACnet
- MS/TP @ 19,200 Baud rate
- Limit devices to 30 on a single trunk line.
31
Page 32
Envision Console Controls cont.
ENVISION CONSOLE INSTALLATION MANUAL
Control and Safety Feature Details
Emergency Shutdown
The emergency shutdown mode can be activated by a
command from a facility management system or a closed
contact on BI-2. The default state for the emergency
shutdown data point is off. When the emergency shutdown
mode is activated, all outputs will be turned off immediately
and will remain off until the emergency shutdown mode is
de-activated. The first time the compressor starts after the
emergency shutdown mode has been de-activated, there
will be a random start delay present.
Lockout Mode
Lockout mode can be activated by any of the following
fault signals: refrigerant system high pressure, refrigerant
system low pressure, freeze detection, and condensate
overflow. When any valid fault signal remains continuously
active for the length of its recognition delay, the controller
will go into fault retry mode, which will turn off the
compressor. After the Compressor short cycle delay,
the compressor will attempt to operate once again. If
three consecutive faults occur in 60 minutes during a
single heating or cooling demand, the unit will go into
lockout mode, turning off the compressor, enabling the
alarm output, and setting the blower back to low speed
operation until the controller is reset. If the control faults
due to the low pressure input (BI-3) being open during
the pre-compressor startup check, the control will go into
lockout mode immediately, disabling the compressor from
starting and enabling the alarm output (BO-6). The lockout
condition can be reset by powering down the controller, by
a command from the BAS, or by the holding the ESC and
Return keys on the MUI for 5 seconds.
Freeze Detection Limit (AI-5)
The freeze detection limit sensor will monitor the liquid
refrigerant temperature entering the water coil in the
heating mode. If the temperature drops below the freeze
detection limit trip point for the recognition delay period,
the condition will be recognized as a fault. The freeze
detection limit trip point will be factory set for 30°F and
will be field selectable for 15°F by removing a jumper wire
on BI-5. The freeze detection limit fault condition will be
bypassed 2 minutes at normal compressor startup, to allow
the refrigeration circuit to stabilize. If the freeze detection
limit sensor becomes unreliable at any time compressor
operation will immediately be suspended until the problem
is corrected. This should be displayed as an alarm on the
BAS and the MUI. This alarm will be reported a “Water Low
Temp Limit” fault.
the compressor output immediately and count the fault. The
compressor minimum on time does not apply if the highpressure switch opens. The compressor will not restart until
the compressor short cycle time delay has been satisfied.
Low Pressure (BI-3)
The low-pressure switch shall be a normally closed (NC)
switch that monitors the systems refrigerant pressure. The
input shall be checked 15 seconds before compressor start
up to be sure the pressure switch is closed and then ignored
for the first 2 minutes after the compressor output (BO-2) is
enabled. If the switch is open continuously for (30) seconds
during compressor operation the compressor output (BO-2)
will be disabled. The compressor will not restart until the
compressor short cycle time delay has been satisfied.
Condensate Overflow
The condensate overflow sensing circuit will monitor
the condensate level as a resistance input to AI-3. If
the condensate water level rises resulting in the input
resistance rising above the set point for the recognition
delay period, the condition will be recognized as a fault.
The condensate will be subjected to a (30) second
lockout delay which requires that the fault be sensed for a
continuous (30) seconds before suspending unit operation.
Alarm Output (BO-6)
The alarm output will be enabled when the control is in the
lockout mode and will be disabled when the lockout is reset.
Test Mode
Raising the zone temperature input (AI-1) reading to 180–
220°F or by holding the ESC and down arrow keys on the
MUI for 5 seconds will put the control into test mode. In
test mode the random start delay and the compressor
fixed on delay time will both be shortened to 5 seconds
and the reversing valve will be allowed to cycle with out
shutting down the compressor. If an MUI is connected
to the control LED 8 will flash and the words “Test Mode
Enabled” will be shown on the LCD display when the
control is in test mode. Test mode will be disabled after
a power cycle, 30 minute timeout, or by holding the ESC
and Up arrow keys on the MUI.
Sequence of Operation
Power Fail Restart
When the controller is first powered up, the outputs will
be disabled for a random start delay. The delay is provided
to prevent simultaneous starting of multiple heat pumps.
Once the timer expires, the controller will operate normally.
High Pressure (BI-11)
The high-pressure switch shall be a normally closed (NC)
switch that monitors the systems refrigerant pressure. If the
input senses the high-pressure switch is open it must disable
Random Start Delay
This delay will be used after every power failure, as well as
the first time the compressor is started after the control
exits the unoccupied mode or the emergency shutdown
32
Page 33
ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls cont.
mode. The delay should not be less than 1 second and not
longer than 120 seconds. If the control is in test mode the
random start delay will be shortened to 5 seconds.
Compressor Fixed On Delay Time
The Compressor Fixed On Delay Time will ensure that the
compressor output (B02) is not enabled for (90) seconds
after the control receives a call to start the compressor.
This delay is adjustable from 30 – 300 seconds over a BAS
or a MUI. If the control is in test mode the Compressor
Fixed On Delay Timer will be shortened to 5 seconds.
Compressor Minimum On Delay
The compressor minimum on delay will ensure that the
compressor output is enabled for a minimum of (2)
minute each time the compressor output is enabled. This
will apply in every instance except in the event the high
pressure switch is tripped or emergency shutdown then
the compressor output will be disable immediately.
Compressor Short Cycle Delay Time
The compressor short cycle time delay will ensure that
the compressor output will not be enabled for a minimum
of (5) minutes after it is disabled. This allows for the
system refrigerant pressures to equalize after the
compressor is disabled.
Heating Cycle
On a call for heating, the blower enable output and
accessory output 2 will turn on immediately after the
random start delay timer has been satisfied. If the
compressor short cycle time delay has been satisfied,
the compressor will turn on after the blower enable and
accessory output 2 are on and the fixed compressor start
delay timers have been satisfied.
Auxiliary heat output can be controlled over the BAS.
Set Point Control Mode
In set point control mode the reversing valve output
will be disabled. As the temperature drops below the
heating set point and begins to operate in the heating
proportional band, the low capacity compressor
output (BO-2) will be enabled. A PI loop in the
programming of the control will determine when
the full capacity compressor output (BO-4) is to be
enabled. The compressor must be operating in low
capacity for a minimum of 30 seconds before the full
capacity compressor output can be enabled.
Thermostat Control Mode
In thermostat mode the compressor will be cycled
based on Y1 calls from a room thermostat. When
the control receives a Y1 command (BI-7) from the
thermostat, the compressor output (BO2) will be
enabled. During the heating cycle the reversing valve
will be commanded into the off position.
Cooling Cycle
On a call for cooling, the blower enable output and
accessory output 2 will turn on immediately after the
random start delay timer has been satisfied. If the
compressor short cycle time delay has been satisfied,
the compressor will turn on after the blower enable and
accessory output 2 are on and the fixed compressor start
delay timers have been satisfied.
Set Point Control Mode
In set point control mode the reversing valve output
will be enabled. As the temperature falls below the
cooling set point and begins to operate in the cooling
proportional band, the low capacity compressor
output (BO-2) will be enabled. A PI loop in the
programming of the control will determine when
the full capacity compressor output (BO-4) is to be
enabled. The compressor must be operating in low
capacity for a minimum of 30 seconds before the full
capacity compressor output can be enabled.
Thermostat Control Mode
In thermostat mode the compressor will be cycled
based on Y1 calls from a room thermostat. When
the control receives a Y1 command (BI-7) from the
thermostat, the compressor output (BO2) will be
enabled. During the cooling cycle the reversing valve
will be commanded into the “ON” position.
Emergency Heat/Network Enabled Output (BO5)
This output is set from the factory to enable/disable
emergency heat. If a problem occurs with the unit resulting
in the compressor being locked out in heating mode,
the control will automatically enable this output to turn
on field installed electric heat. This output is interlocked
with the blower proving input BI-6 (Blower proving
sensors must be field supplied and installed). BI-6 must
be connected to PB2 position 3 (see unit schematic) in
the field if no blower proving sensor is desired. There is a
configurable parameter available through a BAS network
that must be enabled if this output is to be commanded
over the BAS network.
MUI Alarm History Reporting
If a fault occurs the fault will be recorded in history for
display on the medium user interface in the History Menu.
Each fault type will be displayed in the history menu with
a number between 0 and 3. A reading of 3+ will mean
that fault has occurred more than three times in the past.
The history menu can be cleared with a power cycle only.
Alarm date and time are not included in the history.
33
Page 34
Envision Console Controls cont.
Inputs and Outputs Configuration
Field Selectable Options
Freeze Detection Limit Set Point (BI-5)
The freeze detection limit set point input allows you to
adjust the freeze detection limit set point (AI-5). When the
jumper is installed on BI-5 (Wire #24) the freeze detection
limit set point is factory set for 30°F. When the jumper on
BI-5 (Wire #24) is removed the freeze detection limit set
point will be 15°F.
Accessory Outputs (BO-7 and BO-8)
Accessory Output 1 will be energized 90 seconds prior
to the compressor output being energized. Accessory
Output 2 will be energized with the fan output (BO-1).
When the corresponding compressor output is turned
off the accessory output will be deactivated immediately.
These outputs are selectable for normally open or normally
closed operation through the Medium User interface or
through the Building Automation System.
ENVISION CONSOLE INSTALLATION MANUAL
SINGLE and DUAL STAGE WATER-TO-AIR
Input NameInput Output NameOutput
Zone Temp 1AI 1 Fan EnableBO1
Relative Humidity InputAI 2 Comp – Low CapacityBO2
Condensate LevelAI 3 Reversing Valve BO3
Universal Temp InputAI 4 Comp – Full CapacityBO4
Water Coil Low Temperature LimitAI 5 Network Output/EH OutputBO5
Warm/Cool Adjust and Temp OccAI 6 AlarmBO6
MUI (LCD User interface) for diagnostics
and commissioning.
• MUIK3 - Panel Mount, Portable
• MUIK4 - Wall Mount
34
Page 35
ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls cont.
FX10 User Interface (MUI) Physical Layout
Power LED
Alarm LED
Up ArrowRight Arrow
LED 1
LED 4
LED 8
Alarm LED - Indicates a Lock-Out or a bad Freeze Sensor
Power LED - Shows FX processor is operational
LED 1 - Flashing shows Compressor 1 running
Left ArrowDown Arrow
LED 3 - On shows Fan running
LED 4 - On shows Reversing Valve in cool
LED 8 - Flashing shows unit in ‘Test’ Mode
LED 2 - Flashing shows Full Capacity Compressor running
MUI Menu Navigation for Single Compressor - Envision Water-to-Air
Escape (ESC)
Button
Return Button
Info Status Temps Outputs Settings Maint Alarms Alm-History
Info
WFI
Envision Series
PROFXENV-XX
3/8/07
Status
Run Mode Auto
Eff Occup’y Occ
Y1 Input OFF
Y2 Input OFF
G Input OFF
O Input OFF
Occ Input Occ
Temp Occ Inp OFF
Condensate NML
Emg Input Run
Lo Press ON
Hi Press ON
Rndm Tmr 0
BI-4 Input OFF
Welcome
Temps
Zone Temp 77.2 ºF
Dis Air Temp 51.0 ºF
Eff Clg Setpt 70.0°F
Eff Htg Setpt 66.0°F
Water Coil 77.8°F
Low WC Limit 30.0°F
Humidity 56.7 %RH
WarmCool AI 14.6
WarmCoolAdj 0.2
OutputsSettings
nvoFanStatus ON
CmpCmd Status OFF
Cmp Capacity OFF
Rev Valve Heat
X1 Output OFF
X2 Output OFF
PWMOut 98%
BO5 OFF
BO9 OFF
AO2 Output 0%
Unit of Measure F
Occ Clg Setpt 73.9 ºF
Occ Htg Setpt 69.9 ºF
Unocc Clg 84.0 ºF
Unocc Htg 60.0 ºF
DeHumSetpt 0%
SensorSelect TAXXJ02
35
Page 36
ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls cont.
MUI Menu Navigation for Single Compressor - Envision Water-to-Air
Alarms
ALARM SUMMARY
^/High Pressure
Maintenance
MinClgSetpt 60.0 ºF
MaxHtgSetpt 89.9 ºF
W Coil LoLim1 30.0 ºF
W Coil LoLim2 15.0 ºF
TmpOccTime 120 min
Rev Vl v Default Heati n g
BO5 Mode Network
CompStrtDly 90 sec
SpaceT Offset -1 ºF
DehumEnaDis Dis
Acc1 Action On Comp
Acc2 A ction On Fan
Alm-History
Alarm #Events
Condensate 0
Hi Pressure 0
Low Pressure 0
Low Temp 0
Bad Sensor 0
Press right arrow key
one time from
Maintenance Menu
NOTE: This FX10 applicati on implements an alarm history which is reset
only by cycling power. This history shows on the Alm-History page. Any
alarm showing 4+ events has occurred more than 4 times.
Alarm lock-outs
Return keys simultaneously for a minimum of 15 seconds, or by
commanding the nviAlarmReset over the BAS network.
Test mode
for a minimum of 15 seconds and releasing. Test mode times out after 30
minutes, and may also be ended by pressing ‘ESC’ and Up Arrow
simultaneously and releasing. Test Mode bypasses the On Delay (90 sec)
and Random Start timers for quicker troubleshooting. It also allows cycling
the reversing valve without compressor shutdown.
ECM
SW1 OFF
SW2 OFF
SW3 ON
SW4 OFF
SW5 OFF
SW6 OFF
SW7 ON
SW8 OFF
SW9 OFF
SW10 ON
SW11 OFF
SW12 OFF
No more than three
speeds should be “ON”
at one time
are reset by cyc ling power, by pressing the “ESC” and
is enabled by holdi ng the ‘Esc’ and Down Arrow simultaneously
36
Page 37
ENVISION CONSOLE INSTALLATION MANUAL
Unit Startup Notes
Emergency Electric Resistance Heat
A factory-installed emergency electric heater package is
available. Rated for 2,000 watts on models NC09 through
NC12 and 3,000 watts on models NC15 through NC18.
The heater package consists of ni-cad elements, ceramic
insulators, and thermal limit switches. A concealed, chassis
mounted rocker switch controls the heater mode operation
and allows the field installation of an aquastat for boilerless
unit operation.
Electrical Disconnect
Field installed on the optional chassis back plate, the console disconnect provides a permanent electrical connection
to the main electrical supply branch. Wiring between the
disconnect and the unit chassis is field supplied and allows
the electrical power source to the chassis to be interrupted
for unit servicing.
Non-Fused
Constructed of heavy gauge galvanized steel, the
rocker style disconnect switch provides reliable electrical control. Wiring pigtails, using 12-gauge wires, are
factory installed to simplify field wiring.
Fused
Similar in construction to the non-fused electrical
disconnect. The fused disconnect is available in five
models with equipment rated fuses to provide additional circuit protection. The fuses are panel mounted
to allow easy inspection and removal without removing
the cover on the disconnect.
CFD-10 - 10 amp rated fuse
CFD-12 - 12 amp rated fuse
CFD-15 - 15 amp rated fuse
CFD-20 - 20 amp rated fuse
CFD-25 - 25 amp rated fuse
Hydronic Loop Controller for
Boiler/Tower Installations
The hydronic loop controller is a microprocessor based
control panel for control of water loop heat rejector (tower),
heat supplier (boiler), and/or water well pumps and circulation pumps. Includes audible and visual alarms, temperature
indication, and add-on options of low switches, remote
alarm sensor wells and pump alternator.
Motorized Outside Air Damper
A field installed motorized outside air damper is available
to allow the introduction of fresh air into the conditioned
space through an outside vent. The damper motor is powered by 24 volts with a spring-close design in the event of
a power failure. The damper blade and housing are constructed of aluminum for corrosion resistance and the blade
includes a neoprene gasket to prevent air infiltration during
off cycles. The damper assembly is installed on the optional
chassis back plate and a two-wire low voltage connection
simplifies wiring. A concealed, chassis mounted rocker
switch allows the damper to be disabled
37
Page 38
ENVISION CONSOLE INSTALLATION MANUAL
Unit Startup Checklist / Unit Startup Steps
Before Powering Unit, Check The Following:
• High voltage is correct and matches nameplate.
• Fuses, breakers and wire size correct.
• Low voltage wiring complete.
• Piping completed and water system cleaned and flushed.
• Air is purged from closed loop system.
• Isolation valves are open, water control valves or loop pumps wired.
• Condensate line open and correctly pitched.
• Transformer switched to 208V if applicable.
• Dip switches are set correctly, if applicable.
• Blower rotates freely
• Air filter is clean and in position.
• Service/access panels are in place.
• Return air temperature is between 50-80ºF heating and 60-95ºF cooling.
• Check air coil cleanliness to insure optimum performance. Clean as needed according to maintenance guidelines. To
obtain maximum performance the air coil should be cleaned before startup. A 10-percent solution of dishwasher
detergent and water is recommended for both sides of coil, a thorough water rinse should follow.
Startup Steps
Note: Complete the Equipment Start-Up/Commissioning Check Sheet during this procedure. Refer to thermostat
operating instructions and complete the startup procedure.
1. Initiate a control signal to energize the blower motor. Check blower operation.
2. Initiate a control signal to place the unit in the cooling mode. Cooling setpoint must be set below room temperature.
3. Be sure that the compressor and water control valve or loop pump(s) are activated.
4. Verify that the water flow rate is correct by measuring the pressure drop through the heat exchanger using the P/T
plugs and comparing to unit capacity data in specification catalog.
5. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables).
6. Check for an air temperature drop of 15°F to 25°F across the air coil, depending on the fan speed and entering water
temperature.
7. Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or loop
pumps deactivate.
8. Initiate a control signal to place the unit in the heating mode. Heating set point must be set above room temperature.
9. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables).
10. Check for an air temperature rise of 20°F to 35°F across the air coil, depending on the fan speed and entering water
temperature.
11. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pump
deactivate.
12. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required.
13. Set system to desired normal operating mode and set temperature to maintain desired comfort level.
14. Instruct the owner/operator in the proper operation of the thermostat and system maintenance.
Note: Be certain to fill out and forward all warranty registration papers.
38
Page 39
ENVISION CONSOLE INSTALLATION MANUAL
Unit Operating Parameters
Single Speed Models
Entering
Water Temp
°F
Water Flow
GPM/Ton
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
09-18
Superheat
09-18
Subcooling
1.5127 - 144205 - 2255 - 1010 - 1418 - 2218 - 22
50
3.0120 - 140185 - 2057 - 155 - 108 - 1018 - 22
1.5139 - 154280 - 3008 - 118 -1218 - 2218 - 22
70
3.0137 - 152250 - 2709 - 127 - 118 - 1018 - 22
1.5143 - 158360 - 3808 - 119 - 1318 - 2216 - 20
90
3.0141 - 156330 - 3509 - 128 - 128 - 1016 - 20
Heating
Cooling
Entering
Water Temp
°F
Water Flow
GPM/Ton
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
09-18
Superheat
09-18
Subcooling
1.573 - 79279 - 3047 - 132 - 67 -1018 - 24
30
3.079 - 85285 - 3108 - 142 - 63 - 620 - 26
1.5103 - 109308 - 3338 - 124 - 88 - 1120 - 26
50
3.0110 - 116315 - 3409 - 134 - 84 - 722 - 28
1.5140 - 146330 - 36510 - 147 - 1111 - 1426 - 32
70
3.0146 - 153340 - 37510 - 147 - 117 - 1028 - 34
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.
Water Temp
Rise °F
Water
Temp Drop
°F
Air Temp
Drop °F DB
Air Temp
Rise °F DB
Unit Operating Limits
Operating Limits
Air Limits
Min. Ambient Air457.2457.2
Rated Ambient Air8026.77021.1
Max. Ambient Air10037.88529.4
Min. Entering Air5010.0404.4
Rated Entering Air db/wb80.6/66.227/196820.0
Max. Entering Air db/wb110/8343/28.38026.7
Water Limits
Min. Entering Water30-1.120-6.7
Normal Entering Water50-11010-43.330-70-1.1
Max. Entering Water12048.99032.2
Notes:
Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy
temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The
operating limits are dependant upon three primary factors: 1) water temperature, 2) return air temperature, and 3)
ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be
at the normal level for proper and reliable unit operation.
CoolingHeating
(°F)(°C)(°F)(°C)
39
Page 40
DEALER:
PHONE #: DATE:
PROBLEM:
MODEL #:
ENVISION CONSOLE INSTALLATION MANUAL
SERIAL #:
COOLING CYCLE ANALYSIS
Unit Amp Draw:
°F
AIR
COIL
°F
Line Voltage:
EXPANSION
VALVE
LIQUID LINE
°F
PSIPSI
BRINE IN
Loop:Open
COAX
SOURCE
BRINE OUT
Startup/Troubleshooting Form
PSI
°F
Closed
REVERSING
VALVE
PSI =SAT F
°F°F
SAT °F=
SUCTION
COMPRESSOR
DISCHARGE
°
F
Superheat
Subcooling
°
Heat of Extraction/Rejection = GPM x 500 (485 for water/antifreeze) x ∆T
Note: DO NOT hook up pressure gauges unless there appears to be a performance problem.
HEATING CYCLE ANALYSIS
Unit Amp Draw:
°F
AIR
COIL
°F
Line Voltage:
°
LIQUID LINE
EXPANSION
VALVE
F
PSIPSI
BRINE IN
Loop:Open
COAX
SOURCE
BRINE OUT
PSI
°F
Closed
SAT °F=
SUCTION
COMPRESSOR
REVERSING
VALVE
°F°F
DISCHARGE
°
F
PSI =SAT F
Superheat
Subcooling
°
40
Page 41
ENVISION CONSOLE INSTALLATION MANUAL
Pressure Drop
ModelGPM
1.21.00.90.80.70.6
09
12
15
18
1.82.32.22.01.91.8
2.53.83.73.53.33.1
1.50.90.80.70.60.5
2.31.71.51.41.31.1
3.53.02.72.52.42.2
2.01.71.61.51.41.3
3.03.33.23.02.92.8
4.55.75.55.35.14.9
3.01.71.61.51.41.3
4.04.14.03.93.73.6
5.57.97.67.47.26.9
Pressure Drop (psi)
30°F50°F70°F90°F110°F
12/14/09
41
Page 42
Preventive Maintenance
ENVISION CONSOLE INSTALLATION MANUAL
Water Coil Maintenance
1. Keep all air out of the water. An open loop system should
be checked to ensure that the well head is not allowing
air to infiltrate the water line. Lines should always be
airtight.
2. Keep the system under pressure at all times. It is
recommended in open loop systems that the water
control valve be placed in the discharge line to prevent
loss of pressure during off cycles. Closed loop systems
must have positive static pressure.
Note: On open loop systems, if the installation is in an area
with a known high mineral content (125 PPM or greater) in
the water, it is best to establish with the owner a periodic
maintenance schedule so the coil can be checked regularly.
Should periodic coil cleaning be necessary, use standard
coil cleaning procedures which are compatible with either
the cupronickel or copper water lines. Generally, the more
water flowing through the unit the less chance for scaling.
Other Maintenance
Filters
Filters must be clean to obtain maximum performance.
They should be inspected monthly under normal operating
conditions and be replaced when necessary. Units should
never be operated without a filter.
Condensate Drain
In areas where airborne bacteria produce a slime in the
drain pan, it may be necessary to treat chemically to
minimize the problem. The condensate drain can pick up lint
and dirt, especially with dirty filters. Inspect twice a year to
avoid the possibility of overflow.
Blower Motors
Blower motors are equipped with sealed ball bearings and
require no periodic oiling.
Air Coil
The air coil must be cleaned to obtain maximum
performance. Check once a year under normal operating
conditions and, if dirty, brush or vacuum (with a brush
attachment) clean. Care must be taken not to damage the
aluminum fins while cleaning.
CAUTION: Fin edges are sharp.
Replacement Procedures
Obtaining Parts
When ordering service or replacement parts, refer to the
model number and serial number of the unit as stamped on
the serial plate attached to the unit. If replacement parts
are required, mention the date of installation of the unit
and the date of failure, along with an explanation of the
malfunctions and a description of the replacement parts
required.
In-Warranty Material Return
Material may not be returned except by permission of authorized warranty personnel. Contact your local distributor
for warranty return authorization and assistance.
42
Page 43
ENVISION CONSOLE INSTALLATION MANUAL
Notes
43
Page 44
ENVISION CONSOLE INSTALLATION MANUAL
Revision Guide
Pages:Description:Date:By:
AllUpdated With Aluminum Air Coils02 Mar 2014DS
44Added Revision Guide02 Mar 2014DS
44
Page 45
Manufactured by
WaterFurnace International, Inc.
9000 Conservation Way
Fort Wayne, IN 46809
www.waterfurnace.com