Envision NCW09-18, NCS09-18, NCE09-18 Installation Manual

Page 1
CONSOLE
• R-410A Refrigerant
• 0.75-1.5 Ton Single Speed
Installation Information
Water Piping Connections
Electrical
Startup Procedures
Troubleshooting
Preventive Maintenance
Envision Console Installation Manual
IM1010CNA 03/14
Page 2
Table of Contents
Model Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
General Installation Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
Installation Steps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-15
System Cleaning and Flushing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Open Loop Ground Water Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Auxiliary Heat Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Blower Performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
ENVISION CONSOLE INSTALLATION MANUAL
Wiring Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21-26
Envision Console Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27-36
Unit Startup Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Unit Startup Checklist/Unit Startup Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Unit Operating Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Unit Operating Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
Startup/Troubleshooting Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Pressure Drop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Replacement Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Revision Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
2
Page 3
ENVISION CONSOLE INSTALLATION MANUAL
NC S 09 L 0 1 1 C
4-5 6 7 8 9 10
Vintage
B – PSC Blower & Aluminum Air Coil C – ECM Blower & Aluminum Air Coil
Non-Standard Option
Details
SS – Standard Option
Air Coil/Insulation Option
5 – AlumiSeal
TM
/Extended Range
8 – No Coating/Standard Range
Sound Kit
A – None B – Blanket
Auxiliary Electric
Heat
N – None B – 1.0kW (09-12) C – 2.0kW (09-12) D – 3.0kW (15-18)
Motorized Outside Air Dam
per
(Field Installed)
N – None M – Motorized Damper
Water Coil Option
Thermostat Control
Rev.:
N
11
31-2
N B 5 SS
12 13 14
15-16
C
17
Model Nomenclature
N
Model
NC – Envision Series Console
Cabinet Configuration
C – Chassis Only
W – Chassis with Cabinet S – Chassis Slope Top
E – Chassis with Extended Slope Top
Unit Capacity
09, 12, 15, 18
Piping Option
L – Left R – Right
Voltage
0 – 208-230/60/1 2 – 265/60/1 9 – 115/60/1 (09 & 12)
Unit Control
1 – CCM 2 – Versatec Microprocessor 4 – FX10 Std. w/o Communication 5 – FX10 w/Open N2 Com Card 6 – FX10 w/Lonworks Com Card 7 – FX10 w/BacNet Com Card
NOTES: Chassis only available with left piping option. FX10 option is only available with remote wall-mounted thermostat control.
Voltage Availability
Voltage
115/60/1
09 12 15 18
••
208-230/60/1 ••• •
265/60/1 ••• •
Model
1/20/14
C – Copper N - CuproNickel
1 – Unit Mounted T-Stat 2 – Remote Wall-Mounted T-Stat
02 March 2014D
3
Page 4
General Installation Information
ENVISION CONSOLE INSTALLATION MANUAL
Safety Considerations
WARNING: Before performing service or maintenance operations on a system, turn off main power switches to the indoor unit. If applicable, turn off the accessory heater power switch. Electrical shock could cause personal injury.
Installing and servicing heating and air conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair or service heating and air conditioning equipment. Untrained personnel can perform the basic maintenance functions of cleaning coils and cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating and air conditioning equipment, observe precautions in the literature, tags and labels attached to the unit and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use a quenching cloth for brazing operations and have a fire extinguisher available.
Moving and Storage
Move units in the normal “up” orientation. Do not stack units. When the equipment is received, all items should be carefully checked against the bill of lading to be sure all crates and cartons have been received. Examine units for shipping damage, removing the units from the packaging if necessary. Units in question should also be internally inspected. If any damage is noted, the carrier should make the proper notation on the delivery receipt, acknowledging the damage.
Refrigerant Systems
To maintain sealed circuit integrity, do not install service gauges unless unit opertion appears abnormal. Compare the change in temperature on the air side as well as the water side to the Unit Operating Parameters tables. If the unit’s performance is not within the ranges listed, and the airflow and water flow are known to be correct, gauges should then be installed and superheat and subcooling numbers calculated. If superheat and subcooling are outside recommended ranges, an adjustment to therefrigerant charge may be necessary.
Water Piping
The proper water flow must be provided to each unit whenever the unit operates. To assure proper flow, use pressure/temperature ports to determine the flow rate. These ports should be located at the supply and return water connections on the unit. The proper flow rate cannot be accurately set without measuring the water pressure drop through the refrigerant-to-water heat exchanger.
All source water connections on commercial units are fittings that accept a male pipe thread (MPT). Insert the connectors by hand, then tighten the fitting with a wrench to provide a leakproof joint. When connecting to an open loop (groundwater) system, thread any copper MPT fitting into the connector and tighten in the same manner as described above.
4
Page 5
ENVISION CONSOLE INSTALLATION MANUAL
Dimensional Data - Flat Top Cabinet
NCW09-18
@756B@3BC@<
@3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E<
B=>
4
32
/
47:B3@0@/193B 47:B3@0@/193B
6
23B/7:0
BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E<
4@=<B
0 5
1
7
0/
8
23B/7:0
BE7AB3FB3<232 B/00/19/<2 4=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E<
:34B@3BC@<
@3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E<
Flat Top
Configuration
09-12
15-18
in. 45.0 10.8 25.7 9.2 35.0 6.1 2.3 44.1 10.3 4.3
cm. 114.3 27.3 65.2 23.4 88.9 15.6 5.8 112.0 26.0 10.9
in. 50.0 12.3 25.7 9.2 35.0 6.1 3.3 49.1 11.8 4.3
cm. 127.0 31.1 65.2 23.4 88.9 15.6 8.3 124.7 29.8 10.9
Overall Cabinet
AB C D E F GHI J
Width Depth Height Gr i l l e Li d
Grille
Length
Grille
Width
5
Page 6
Dimensional Data - Slope Top Cabinet
NCS09-18
ENVISION CONSOLE INSTALLATION MANUAL
@756B@3BC@<
@3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E<
/
47:B3@0@/193B
23B/7:/
BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E<
:34B@3BC@<
B=>
4
2
3
/
6
4@=<B
0 5
8
7
0
47:B3@0@/193B
1
23B/7:0
BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E<
@3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E<
Slope Top
Configuration
09-12
15-18
in. 45.0 11.1 28.6 9.2 35.0 6.1 2.8 44.1 10.3 4.3
cm. 114.3 28.2 72.6 23.4 88.9 15.6 7.2 112.0 26.0 10.9
in. 50.0 12.6 29.1 9.2 35.0 6.1 2.5 49.1 11.8 4.3
cm. 127.0 32.0 73.9 23.4 88.9 15.6 6.4 124.7 29.8 10.9
Over all Cabi net
AB C D E F GHI J
Width Depth Hei ght Gril l e Li d
Grille
Length
Grille
Width
6
Page 7
ENVISION CONSOLE INSTALLATION MANUAL
Dimensional Data - Extended Slope Top Cabinet
NCE09-18
@756B@3BC@< B=>
2 3
/
/
6
4@=<B
@3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E<
23B/7:/
BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E<
:34B@3BC@<
4
0 5
1
7
47:B3@0@/193B47:B3@0@/193B
8
23B/7:0
BE7AB3FB3<232B/0 0/19/<24=@B6C<B7: B/00@3/9A=44 =<:G0@3/9=44 B/0A/;3A723/A 5@7::3:72/AA6=E<
0
@3;=D3>:/AB71AB@7> 4@=;0@=93<B/0/<2 @3>:/13=<0@=93< 3253=4:35/AA6=E<
Ext. Slope Top Configuration
09-12
15-18
in. 50.0 12.6 29.1 9.2 35.0 6.1 2.4 49.1 12.0 4.3
cm. 127.0 32.0 73.9 23.4 88.9 15.6 6.1 124.7 30.5 10.9
in. 55.0 12.6 29.1 9.2 35.0 6.1 2.5 54.1 11.8 4.3
cm. 139.7 32.0 73.9 23.4 88.9 15.6 6.4 137.4 29.8 10.9
Over all Cabi net
AB C D E F GHI J
Width Depth Hei ght Grill e Li d
Grille
Length
Grille
Width
7
Page 8
ENVISION CONSOLE INSTALLATION MANUAL
Dimensional Data - Right Return Controls Detail
1=<B@=:>/<3: @3;=D34=@/113AA B=1=<B@=:0=F
4/<=>B7=<AE7B16
3:31B@7163/B;=23 <=@;/:0=7:3@:3AA AE7B16=>B7=</:
2/;>3@=<=44AE7B16
1=;>@3AA=@ /113AA>/<3: @3;=D324=@ 1:/@7BG 0=B6A723A
=>B7=</:0/19>:/B3 @3?C7@324=@ 2/;>3@7<AB/::/B7=<
47:B3@
6/<2G0=F
=>B7=</: 4CA32 <=<4CA32 27A1=<<31B
:=ED=:B/53 B3@;7</:A 4F@3;=B3E/:: AB/B=>B7=<A=<:G
1=<23<A/B3 2@/7<1=<<31B7=<
=>B7=</: 0/::D/:D3A
=>B7=</: 6=A397BA
=CBA723/7@ 2/;>3@=>B7=< 473:27<AB/::32
8
Page 9
ENVISION CONSOLE INSTALLATION MANUAL
Dimensional Data - Right Return Chassis
Data = inches (cm)
9.38
(23.8)
COMPRESSOR
ACCESS PANEL
WATER OUT 1/2˝ FPT
Models 09-12
CONTROL PANEL
WATER IN 1/2˝ FPT
25.25 (64.1)
21.4
(54.4)
20.0
(50.8)
37.88 (96.2)
28.5
(72.4)
BLOWER ACCESS PANEL
FILTER
10.31 (26.2)
4.5
(11.4)
0.86 (2.2)
2.0
(5.1)
1.0
(2.5)
1.78
(4.5)
11.0
(27.9)
4.37
(11.1)
1.5
(3.8)
1.5
(3.8)
8.88
(22.6)
COMPRESSOR
ACCESS PANEL
WATER OUT 1/2˝ FPT
WATER IN 1/2˝ FPT
25.25 (64.1)
20.6
(52.3)
Models 15-18
42.88
(108.9)
CONTROL PANEL
BLOWER ACCESS PANEL
FILTER
11.75
(29.8)
4.5
(11.4)
0.86 (2.2)
2.0
(5.1)
19.5
(49.5)
34.0
(86.4)
1.0
(2.5)
12.0
(30.5)
4.32
(11.0)
1.5
(3.8)
1.5
(3.8)
5.5
(14.0)
9.25
(23.5)
2.75 (7.0)
43.37
(110.2)
28.0
(71.1)
OPTIONAL BACK PLATE
13.9
(35.3)
0.66
DAMPER OPENING
(1.7)
CONDENSATE DRAIN CONNECTION
12.03 (30.6)
COMPRESSOR
ACCESS PANEL
1.64
(4.2)
19.83 (50.4)
25.65 (65.2)
CONDENSATE DRAIN CONNECTION
48.25
(122.6)
33.0
(83.8)
1.62 (4.1)
OPTIONAL BACK PLATE
25.80 (65.5)
20.0
12.18
(30.9)
(50.8)
5.4
(13.7)
11.78 (29.9)
2.75 (7.0)
13.9
(35.3)
0.83 (2.1)
DAMPER OPENING
COMPRESSOR
ACCESS PANEL
9
Page 10
ENVISION CONSOLE INSTALLATION MANUAL
Dimensional Data - Left Return Controls Detail
:=ED=:B/53 B3@;7</:A 4F@3;=B3E/:: AB/B=>B7=<A=<:G
=>B7=</: 4CA32 <=<4CA32 27A1=<<31B
=>B7=</: 0/::D/:D3A
=>B7=</: 6=A397BA
1=;>@3AA=@ /113AA>/<3: @3;=D324=@ 1:/@7BG 0=B6A723A
1=<B@=:>/<3: @3;=D34=@/113AA B=1=<B@=:0=F
2/;>3@=<=44AE7B16
3:31B@7163/B;=23 <=@;/:0=7:3@:3AA AE7B16=>B7=</:
4/<=>B7=<AE7B16
=>B7=</: 3:31B@7163/B
6/<2G0=F
47:B3@
1=<23<A/B3 2@/7<1=<<31B7=<
=>B7=</:0/19>:/B3 @3?C7@324=@ 2/;>3@7<AB/::/B7=<
=CBA723/7@ 2/;>3@=>B7=< 473:27<AB/::32
10
Page 11
ENVISION CONSOLE INSTALLATION MANUAL
Dimensional Data - Left Return Chassis
Data = inches (cm)
1.50 (3.8)
1.50 (3.8)
4.37
(11.1)
Models 09-12
BLOWER ACCESS PANEL
FILTER
WATER OUT 1/2˝ FPT
WATER IN 1/2˝ FPT
25.25
(64.1)
21.4
(54.4)
20.0
(50.8)
28.5
(72.4)
0.86 (2.2)
(5.1)
2.0
37.88 (96.2)
CONTROL PANEL
10.31 (26.2)
4.5
(11.4)
9.38
(23.8)
COMPRESSOR
ACCESS PANEL
1.00 (2.5)
1.78
(4.5)
11.0
(27.9)
1.50 (3.8)
1.50 (3.8)
4.32
(11.0)
Models 15-18
WATER OUT 1/2˝ FPT
WATER IN 1/2˝ FPT
25.25 (64.1)
20.6
(52.3)
42.88
(108.9)
34.0
(86.4)
CONTROL PANEL
BLOWER ACCESS PANEL
FILTER
0.86 (2.2)
2.0
(5.1)
19.5
(49.5)
11.75 (26.2)
4.5
(11.4)
8.88
(22.6)
COMPRESSOR ACCESS PANEL
1.00
(2.5)
12.0
(30.5)
25.65
(65.1)
19.83
(50.4)
1.62 (4.1)
12.03 (30.5)
COMPRESSOR
ACCESS PANEL
2.75 (7.0)
0.66
(1.7)
CONDENSATE DRAIN CONNECTION
43.37
(110.2)
28.00 (71.1)
OPTIONAL BACK PLATE
13.90
(35.3)
DAMPER OPENING
9.25
(23.5)
5.50
(14.0)
25.80 (65.5)
COMPRESSOR
ACCESS PANEL
11
20.0
(50.8)
1.62 (4.1)
12.18 (30.9)
CONDENSATE DRAIN CONNECTION
OPTIONAL BACK PLATE
2.75
(7.0)
0.83
(2.1)
48.25
(122.6)
13.90 (35.3)
33.0
(83.8)
11.78 (29.9)
DAMPER OPENING
5.50
(14.0)
Page 12
ENVISION CONSOLE INSTALLATION MANUAL
Installation Steps
Step 1: Unpack Equipment and Inspect for Damage
Step 2: Determine Equipment Location
• Choose level flooring surface (Correctable with shims. Do not pitch towards drain.)
• Location of wall support and fasteners required to secure chassis backplate.
• Easy access for both installation and service.
• Consider availability and ease of wiring, water piping and condensate drain.
• No obstructions to block airflow in front of the unit.
Step 3: Mark Unit Position
• Ensure that floor is level. If shims are required, make sure that the entire compressor compartment area is uniformly shimmed and that the backplate mounting height is increased by the thickness of the shims used.
• Position backplate in desired equipment location. To further reduce the operating sound level of the unit, 1/8-inch thick rubber matting may be placed under the chassis to eliminate vibration on hard flooring surfaces. (Make sure back plate is level).
• Mark and cut floor or wall penetrations for electrical wiring, water and condensate piping.
Optional Electrical Disconnect and Motorized Outside Air Damper
• Mark and cut wall penetrations for field fabricated outside air duct sleeve.
• Align mounting holes with backplate and attach with screws supplied.
Figure 1
1=<A=:3 1/07<3 B 0/19 >:/B3 =>B7=</:
4CA323:31B@71/: 27A1=<<31 B=>B7=</:
E/::>3<3B@/B7=< 4=@E/B3@1=<<31B7=<
4:==@>3<3B@/B7=< 4=@E/B3 @1=<<31 B7 =<
E/B3@ 7<
E/B3@ =CB
>B>:C5A =>B7=</:
0/: :D/:D3 A =>B7=</:
=>B7=</:6 =A3A
;=B=@7H32 2/; >3@ =>3<7<5
;=B=@7H32 2/; >3@ =>B7=</:
1=<A=:3 16/AA7A
1=<23<A/B 3 2@/7< :=1/B7=<
12
1=<A=:3 1/07<3 B
Page 13
ENVISION CONSOLE INSTALLATION MANUAL
Installation Steps cont.
Step 4: Provide Water and Condensate Drain Connections
• A two-pipe reverse return piping configuration is recommended as it equalizes the piping circuit lengths and delivers even water flow to each unit. A direct return piping configuration may be used, but it may be difficult to achieve and maintain proper water flow to the units.
• An air vent must be installed in the water distribution system.
• The supply and return water piping should be run through the wall or floor penetration and terminate with a ball valve. The piping material used must comply with all local codes.
• Refer to: System Cleaning and Flushing procedures.
Pipe Locations
Figure 2
1=<A=:3 1/07<3 B
E/B 3@1= <<31 B7=<A
1=<A=:3 16/AA7A
4CA323 :3 1B@7 1/: 27A1=<<3 1B =>B7=</:
"D /113AA=@G
#Þ f &Þ/@3 / />>=F  Þ 4@=;32 53 =416/AA7A !Þ4@=;4:==@
B/@53B/@3/4=@ E/::>3<3B@/B7=<
B/@53B/@3/4=@ 4:==@>3<3B@/B7=<
1/07<3 B3FB3<2A B=B67A>=7<B
#Þf&Þ/@3//>>=F Þ 4@=;3253=416/AA7A Þ4@=;4@=<B3253 =41/07<3 B
3:31 B@71/: 8C<1B7=<0=F
1=<23<A/B 3 2@/7< :=1/B7=<
13
Page 14
ENVISION CONSOLE INSTALLATION MANUAL
Installation Steps cont.
Step 5: Provide Line Voltage Wiring
• Check unit data plate located on control side of chassis for ampacity and fuse size.
• Remove electrical knockouts from chassis backplate.
• Run line voltage wiring through knockout and secure wiring to backplate or disconnect.
Step 6: Chassis Installation
• Level and secure backplate to wall.
• Position the chassis against back plate. Drive (2) screws through holes in lip of backplate into top flange of chassis.
Step 7: Final Electrical Connection
• Install flexible electrical conduit between the backplate or electrical disconnect and the unit mounted junction box.
• Make final wiring connections in disconnect and junction box, taking care to replace all covers when done. Wiring must conform to NEC and/or all local codes. Refer to Electrical Data.
NOTE: It is necessary to make final wiring connections prior to securing unit chassis to back plate on right-hand piping models with electrical disconnect.
Step 8: Final Water Connection
• For ease of installation and sound attenuation, high pressure (recommended) flexible hoses with a swivel fitting should be provided. Apply Teflon® tape or sealant compound to threaded hose fittings.
• Combination shut-off/balancing valves should be installed on both the supply and return water lines of the unit.
• Flow control valves should be installed on the water discharge line.
• It is recommended that P/T ports be installed on the supply and return water lines.
Step 9: Set Unit Controls
• Locate the “continuous fan/cycle fan” switch within the electrical compartment of the chassis and set to desired position. (Remote wall thermostat units do not use this optional switch.)
• Optional Control Settings­Remote Thermostat - Run low voltage wiring from unit to the desired thermostat location. Mount and wire thermostat according to manufacturer’s recommendations. Motorized Outside Air Damper - Locate the “damper on/damper off” damper switch within the electrical compartment of the chassis and set to desired position. Emergency Electrical Heat - Locate the “electric heat/normal/boilerless” control switch within the electrical compart­ment of the chassis and set to desired position.
Step 10: Secure the Cabinet Cover
• Position and lower cabinet over unit chassis. Apply pressure to the front of the cabinet to ensure that the back lip of the
cabinet hooks over the tabs provided on the backplate.
• Secure cabinet to chassis with mounting screws provided.
Step 11: Perform Final Unit Check
• Measure the pressure drop across the water coil and monitor water or air temperatures in both heating and cooling
modes. The measured values should fall within the acceptable ranges shown in the Startup Performance table.
14
Page 15
ENVISION CONSOLE INSTALLATION MANUAL
Installation Steps cont.
Field Converting Console
Chassis is normally configured with controls on right end and piping on left end (see Figure 3 top view). In this position panel number 1 would be positioned against wall or back plate. Unit may also be turned 180° against wall or back plate. In this position controls will be on left end and piping on right end panel number 2 would be positioned against wall or back plate. Chassis must be enclosed with an approved cabinet enclosure.
Figure 3
Top view
Side view
1
2
1. Remove 4 screws from front kick panel on cabinet.
2. Remove cabinet from chassis by lifting and sliding cabinet straight up.
3. Remove grille assembly from cabinet by removing 4 screws from brackets located on the bottom of the grille and door assemblies.
4. Replace grille/door assemblies into cabinet repositioning pieces 1, 2, and 3 into the locations directly opposite the original positions. Secure by replacing mounting brackets. (Note: Be sure that louvers on the grille assembly are facing the proper direction when replacing the grille section.)
5. Replace grille/frame assembly into cabinet, and secure by replacing mounting brackets.
6. Replace cabinet by sliding it down over the top of the chassis.
7. Remove tab on leg that extends into return air opening. When the grille side of the cabinet is flat against chassis there will be 4 holes that line up in the leg section. Only use 1 hole for alignment for opposite side of grille. (Note: The tab can be removed by twisting back and forth until it breaks off.)
8. Remove plastic strip from tab and replace on rough edge that the tab was removed from.
9. Replace screws in font kick panel to secure cabinet to chassis.
10. Mount filter bracket in designated opening area. (Note: The filter bracket will only fit in one direction if cabinet is installed properly.)
15
Figure 4
Depends on Cabinet Size
3
2
1
4
5
Page 16
System Cleaning and Flushing
ENVISION CONSOLE INSTALLATION MANUAL
Cleaning and Flushing
Prior to start up of any heat pump, the water circulating system must be cleaned and flushed of all dirt and debris.
If the system is equipped with water shutoff valves, the supply and return runouts must be connected together at each unit location (This will prevent the introduction of dirt into the unit, see Figure 7). The system should be filled at the water make-up connection with all air vents open. After filling, vents should be closed.
The contractor should start the main circulator with the pressure reduc­ing valve makeup open. Vents should be checked in sequence to bleed off any trapped air and to verify circulation through all components of the system.
As water circulates through the system, the contractor should check and repair any leaks found in the piping system. Drain(s) at the lowest point(s) in the system should be opened for initial flush and blowdown, making sure water fill valves are set at the same rate. Check the pressure gauge at the pump suction and manually adjust the make-up water valve to hold the same posi­tive pressure both before and after opening the drain valves. Flushing should continue for at least two hours, or longer if required, until drain water is clean and clear.
The supplemental heater and/or circulator pump, if used, should be shut off. All drains and vents should be opened to completely drain the system. Short-circuited supply and return runouts should now be connected to the unit supply and return connections.
Figure 7: Flushing with Water Shutoff Valve Equipped Systems
Return Runout
Supply Runout
Mains
Rubber Hose
Runouts Initially Connected Together
Refill the system with clean water. Test the system water for acidity and treat as required to leave the water slightly alkaline (pH 7.5 to 8.5). The specified percentage of antifreeze may also be added at this time. Use commercial grade antifreeze designed for HVAC systems only. Environol™ brand antifreeze is recommended..
Once the system has been filled with clean water and antifreeze (if used), precautions should be taken to protect the sys­tem from dirty water conditions. Dirty water will result in system-wide degradation of performance, and solids may clog valves, strainers, flow regulators, etc. Additionally, the heat exchanger may become clogged which reduces compressor service life and can cause premature unit failure.
In boiler/tower application, set the loop control panel set points to desired temperatures. Supply power to all motors and start the circulating pumps. After full flow has been established through all components including the heat rejector (re­gardless of season), air vented and loop temperatures stabilized, each of the units will be ready for check, test and start up and for air and water balancing.
Ground Source Loop System Checkout
Once piping is completed between the unit pumping system and ground loop, final purging and charging of the loop is needed. A high pressure pump is needed to achieve adequate flow velocity in the loop to purge air and dirt particles from the loop itself. Antifreeze solution is used in most areas to prevent freezing. Flush the system adequately to remove as much air as possible; then pressurize the loop to a static pressure of 40-50 PSI (summer) or 50-75 PSI (winter). This is normally adequate for good system operation. Loop static pressure may decrease soon after initial installation, due to pipe expansion and loop temperature change. Running the unit for at least 30 minutes after the system has been completely purged of air will allow for the “break-in” period. It may be necessary to adjust static loop pressure (by adding water) after the unit has run for the first time. Loop static pressure will also fluctuate with the seasons. Pressures will be higher in the winter months than during the cooling season. This fluctuation is normal and should be considered when charging the system initially.
Insure the pump provides adequate flow through the unit by checking pressure drop across the heat exchanger. Usually 2.25-3.0 GPM of flow per ton of cooling capacity is recommended in earth loop applications.
16
Page 17
ENVISION CONSOLE INSTALLATION MANUAL
Open Loop Ground Water Systems
Always maintain water pressure in the heat exchanger by placing water control valves at the outlet of the unit to prevent mineral precipitation. Use a closed, bladder-type expansion tank to minimize mineral formation due to air exposure. Insure proper water flow through the unit by checking pressure drop across the heat exchanger and comparing it to the figures in unit capacity data tables in the specification catalog. 1.5-2 GPM of flow per ton of cooling capacity is recommended in open loop applications.
Discharge water from the unit is not contaminated in any manner and can be disposed of in various ways, depending on local codes, i.e. recharge well, storm sewer, drain field, adjacent stream or pond, etc. Most local codes forbid the use of sanitary sewer for disposal. Consult your local building and zoning departments to assure compliance in your area.
Note: For open loop/groundwater systems or systems that do not contain an antifreeze solution, set SW1-Switch #2 to the “WELL” position mended to eliminate water hammer.
Water Quality
In ground water situations where scaling could be heavy or where biological growth such as iron bacteria will be present, a closed loop system is recommended. The heat exchanger coils in ground water systems may, over a period of time, lose heat exchange capabilities due to a buildup of mineral deposits inside. These can be cleaned, but only by a qualified service mechanic, as special solutions and pumping equipment are required. Desuperheater coils can likewise become scaled and possibly plugged. In areas with extremely hard water, the owner should be informed that the heat exchanger may require occasional flushing.
(Refer to the Dip Switch Field Selection table). Slow opening/closing solenoid valves (type VM) are recom-
Units with cupronickel heat exchangers are recommended for open loop applications due to the increased resistance to build-up and corrosion, along with reduced wear caused by acid cleaning.
Material Copper 90/10 Cupronickel 316 Stainless Steel
pH Acidity/Alkalinity
Scaling
Corrosion
Iron Fouling
(Biological Growth)
Erosion
NOTES: Grains = ppm divided by 17
mg/L is equivalent to ppm
Calcium and
Magnesium Carbonate
Hydrogen Sulfide
Chlorine Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Chlorides Less than 20 ppm Less than 125 ppm Less than 300 ppm
Carbon Dioxide Less than 50 ppm 10 - 50 ppm 10 - 50 ppm
Ammonia Less than 2 ppm Less than 2 ppm Less than 20 ppm
Ammonia Chloride Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Nitrate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Hydroxide Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Ammonia Sulfate Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm
Total Dissolved Solids (TDS) Less than 1000 ppm 1000 - 1500 ppm 1000 - 1500 ppm
LSI Index +0.5 to -0.5 +0.5 to -0.5 +0.5 to -0.5
Iron, FE
Bacterial Iron Potential
Iron Oxide
Suspended Solids
Threshold Velocity
(Fresh Water)
Less than 0.5 ppm (rotten egg
Sulfates Less than 125 ppm Less than 125 ppm Less than 200 ppm
2
+ (Ferrous)
smell appears at 0.5 ppm)
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
7 - 9 7 - 9 7 - 9
(Total Hardness)
less than 350 ppm
< 0.2 ppm < 0.2 ppm < 0.2 ppm
< 6 ft/sec < 6 ft/sec < 6 ft/sec
(Total Hardness)
less than 350 ppm
10 - 50 ppm Less than 1 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
(Total Hardness)
less than 350 ppm
Less than 1 ppm, above this
level deposition will occur
Less than 10 ppm and filtered
for max. of 600 micron size
2/22/12
17
Page 18
ENVISION CONSOLE INSTALLATION MANUAL
Electrical Connections
General
Be sure the available power is the same voltage and phase as that shown on the unit serial plate. Line and low voltage wir­ing must be done in accordance with local codes or the National Electric Code, whichever is applicable.
208 Volt Operation
All Envision Series 208/230 units are factory wired for 230 volt operation. For 208 volt operation, the red and blue trans­former wires must be switched.
Microprocessor Remote Thermostat Wiring
Figure 5
Requires common
connections or 24 VAC for activation
Field
Connections
24 VAC
COMMON
COMPRESSOR
REVERSING
VALVE
FAN
LOCKOUT
SIGNAL
SHUTDOWN
NIGHT
SETBACK
LOAD SHED
Connections
TB
R
C
Y
O
G
L
S
X2
X1
W2
Unit
Red
Black
Yellow
Orange
Green
Brown
Blue
Violet
Pink
18
Page 19
ENVISION CONSOLE INSTALLATION MANUAL
Electrical Data
ECM Motor
Model
09
12
15
18
HACR circuit breaker in USA only
Rated
Voltage
115/60/1 104/127 12.5 8.0 50.0 4.25 12.3 14.3 20
208-230/60/1 187/253 6.4 4.1 21.0 2.6 6.7 7.7 10/15
265/60/1 238/292 6.7 4.3 22.0 2.5 6.8 7.9 10/15
115/60/1 104/127 14.8 9.5 50.0 4.25 13.8 16.1 25
208-230/60/1 187/253 7.7 4.9 25.0 2.6 7.5 8.8 10/15
265/60/1 238/292 7.0 4.5 22.0 2.5 7.0 8.1 10/15
208-230/60/1 187/253 9.2 5.9 29.0 2.6 8.5 10.0 15
265/60/1 238/292 7.8 5.0 28.0 2.5 7.5 8.8 10/15
208-230/60/1 187/253 10.4 6.7 33.5 2.6 9.3 10.9 15
265/60/1 238/292 8.7 5.6 28.0 2.5 8.1 9.5 15
Voltage
Min/Max
Compressor
MCC RLA LRA
Fan
Motor
FLA
Total
Unit FLA
Min
Circ
Amp
Max Fuse/ HACR
1/20/14
PSC Motors
Model
09
12
15
18
HACR circuit breaker in USA only 1/20/14
Rated
Voltage
115/60/1 104/127 12.5 8.0 50.0 0.92 8.9 10.9 25
208-230/60/1 187/253 6.4 4.1 21.0 0.50 4.6 5.6 10/15
265/60/1 238/292 6.7 4.3 22.0 0.50 4.8 5.9 10/15
115/60/1 104/127 14.8 9.5 50.0 0.92 10.4 12.8 30
208-230/60/1 187/253 7.7 4.9 25.0 0.50 5.4 6.6 10/15
265/60/1 238/292 7.0 4.5 22.0 0.50 5.0 6.1 10/15
208-230/60/1 187/253 9.2 5.9 29.0 0.69 6.6 8.1 10/15
265/60/1 238/292 7.8 5.0 28.0 0.65 5.7 6.9 10/15
208-230/60/1 187/253 10.4 6.7 33.5 0.69 7.4 9.1 15
265/60/1 238/292 8.7 5.6 28.0 0.65 6.3 7.7 10/15
Voltage
Min/Max
Compressor
MCC RLA LRA
Fan
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max Fuse/ HACR
19
Page 20
Auxiliary Heat Ratings
ECM Motors
ENVISION CONSOLE INSTALLATION MANUAL
Model
09-12
(1 kW)
09-12
(2 kW)
15-18
(3 kW)
Always refer to unit nameplate data prior to installation. 10/5/10
Rated
Voltage
208/60/1 197/254 818 2.45 3.93 6.4 8.0 10 230/60/1 197/254 1000 2.60 4.35 7.0 8.7 15
265/60/1 239/291 1000 2.50 3.77 6.3 7.8 10
208/60/1 197/254 1636 2.45 7.86 10.3 12.9 20 230/60/1 197/254 2000 2.60 8.70 11.3 14.1 25
265/60/1 239/292 2000 2.50 7.55 10.1 12.6 20
208/60/1 197/254 2454 2.45 11.80 14.3 17.8 30 230/60/1 197/254 3000 2.60 13.04 15.6 19.6 35
265/60/1 239/292 3000 2.50 11.32 13.8 17.3 30
Voltage
Min./Max.
Heater
Element
Watts
Fan
Motor
FLA
Heater
Element
FLA
Total
Unit FLA
Min.
Circuit
Amp.
Max.
Fuse/
Brkr.
PSC Motors
Model
09-12
(1 kW)
09-12
(2 kW)
15-18
(3 kW)
Rated
Voltage
208/60/1 197/254 818 0.50 3.93 4.4 5.5 10 230/60/1 197/254 1000 0.50 4.35 4.9 6.1 10
265/60/1 239/291 1000 0.50 3.77 4.3 5.3 10 208/60/1 197/254 1636 0.50 7.86 8.4 10.5 15 230/60/1 197/254 2000 0.50 8.70 9.2 11.5 20
265/60/1 239/292 2000 0.50 7.55 8.1 10.1 15 208/60/1 197/254 2454 0.69 11.80 12.5 15.6 25 230/60/1 197/254 3000 0.69 13.04 13.7 17.2 30
265/60/1 239/292 3000 0.65 11.32 12.0 15.0 25
Voltage
Min./Max.
Heater
Element
Watts
Fan
Motor
FLA
Heater
Element
FLA
Total
Unit FLA
Min.
Circuit
Amp.
Max.
Fuse/
Brkr.
10/5/10
Blower Performance Data
PSC Motors
Model
09 300 350
12 300 350 15 450 500 18 450 500
Factory settings are in Bold
Air fl ow values are with dry coil and standard fi lter.
For wet coil performance fi rst calculate the face velocity of the air coil (Face Velocity [fpm] = Airfl ow [cfm] / Face Area [sq ft]). Then for velocities of 200 fpm reduce the static capability by 0.03 in. wg, 300 fpm by
0.08 in. wg, 400 fpm by 0.12in. wg. and 500 fpm by 0.16 in. wg.
Low Speed High Speed
CFM
ECM Motors
Model
09 300 325 400
12 300 325 400 15 350 450 600 18 350 450 600
Low Speed Medium Speed High Speed
20
CFM
Page 21
ENVISION CONSOLE INSTALLATION MANUAL
Wiring Schematics
CCM - ELECTRONIC THERMOSTAT 208-230-265/60/1
Compressor
C
S
Grn
Electro nic THER MOSTAT
T2
Shu t d o wn
T5
Overide
J1
Red (30)
A Heat
B Cool
HL
Black (2 9)
Yellow (13)
T1
T3
T4
T6
PSC
Fan
Motor
Wht
White (28)
IN
PUT
Brn
Cap
High
Low
DOWN
Ther
mistor
24 V AC
T3
T1
T2
T4
T6
T5
SHUT
White (18) Red (17) Red (11)
Black (2 5)
4
6
1
3
Black
Black
Red (11)
Black (1 2)
Black
Blue
Handi - Box
CC
Blk/Wh t (24 )
24 V Accessory
Ground
HP HP CC CG LO R CLP LPY
Lug
HP HP CC CG LO R CLP LPY
White (34)
Damper
Motor
D
R
Red Blk
Tan (33)
T1
T2
L2
Whit e ( 28 )
4
5
Aut o
2
Fan
Black
Red (15)
Red (16)
2
Black (2 7)
RB
5
Brown (26)
Red (19)
Yellow (10)
ST
T
Fan Mode Sw
Continuous
Red (17)
Red
Yellow (13)
Orange (14) Orange (21)
Blue (T6)
Yellow (13)
24VAC
Shutdown
Cycled
Red (19)
Black (1 2 )
Black (2 2 )
Black (2 2 )
Whit e (18 )
31
Whit e ( 20 )
RV
Not Used
RB
CC
L1
Green (00)
PB
1
2
3
Brown (26 )
Black
NOTE 1
Blue 230V 265V
Transformer
NOTE 2
FS
NOTE 3
Black (3 1 )
Red
208V
Yellow Black/White
HP
LP
Violet (5)
Violet (4)
Red (32)
24V
Black/White (1) Red (2) Brown ( 3 ) Violet (4) Violet (5) Black (6 ) Black (7 ) Blue (8)
Blue (9) Yell ow (1 0)
Blue/Wht (36)
Blk/ W ht (2 3)
Unit
Power Supply
208- 230 /60/1 or
265-277/60/1
G
TEST
PIN
COMPRESSOR
CONTROL MODULE
Damper Sw ON
OFF
Blue/Wht (35)
DT
Factory low voltage wiring Factory line voltage wiring
Field low voltage wiring Field line voltage wiring
Quick connect terminal
Wire n u t
CC -Compressor Contactor DT - Dam per Term inal Bloc k FS -Freeze Sensing Device HP -High Pressure Switch LP -Low P res s ur e Sw it c h PB - Power Block RB - Blower Relay RV -Rev ers ing V alve C oil ST -Ent er ing A ir Temper at ur e S ens or
Legend
21
HP
LP
T
Switch - High Pressure
Switch -Low Pressure
Relay coil
Capacitor
Thermistor
Temperatur e S wit c h
Notes:
1. Switch Red and Blue wires for 208 volt operation
2. Terminal C of 24 V PB is used as “L” output for Brown wire 3 f or L ockout.
3. Optional field installed freeze sensing device.
6/10/08
Field wire lug
L1
Eart h Ground Relay Contac ts -
N.O., N.C.
132
P
Polarized c onnec t or
Page 22
ENVISION CONSOLE INSTALLATION MANUAL
High Lo w NC*09 Oran ge Brown NC*12 Brown/White Orange NC*15 Oran ge Brown NC*18 Brown/White Orange
Blower Setti ngs
Wiring Schematics, cont.
CCM w/ECM - ELECTRONIC THERMOSTAT 208-230-265/60/1
ECM
Shut down
Note 4
Overide
J1
Motor
ECM
Motor
Module
Grn
Brown
Orange
Brown/Whtite
Yellow (13)
Electronic THERMOSTAT
A Heat
T1
T2
T3
T4
T5
T6
B Cool
PUT
IN
Fan Switch
High
Low
White (18)
Red (17)
Red (11)
Ther
mistor
24 V
AC
T3
T1
T2
T4
T6
T5
SHUT
DOWN
Black (25)
Mode Switch
4
6
1
Auto
Fan
3
Black
Black
Red
Black (12)
Red (11)
Orange
5
Red
2
Red (15)
Red (16)
4
ST
T
Red (19)
RB
Red (17)
Yellow (13)
Orange (14)
Blue (T6)
24VAC
Shutdown
Yellow (13)
2
5
Red
Black
Black (27)
Brown (26)
Yellow (10)
Fan Mode Sw
Continuous
Cycled
White (18)
1
White (20)
RV
Orange (21)
Not Used
Compressor
C
S
Blue
Handi - Box
CC
Blk/Wht (24)
24 V Accessory
R C
LO
CG
CC
HP
HP
LP
LP
Y
Ground
Lug
R C
LO
CG
CC
HP
HP
LP
LP
Y
White (34)
Damper
Motor
D
R
Red Blk
Tan (33)
T1
T2
L2
Red (19)
Black (12)
Black (22)
Black (22)
3
RB
CC
L1
Green (00)
PB
1
2
3
Brown (26)
Black
Blue 230V 265V
Transformer
NOTE 2
FS
NOTE 3
NOTE 1
Violet (5)
Violet (4)
HP
LP
Black (31)
Red
208V
Yellow
Red (32)
24V
Black/White
Black/White (1)
Red (2)
Brown (3)
Violet (4)
Violet (5)
Black (6)
Black (7)
Blue (8) Blue (9) Yellow (10)
Blue/Wht (36)
Blk/Wht (23)
Unit
Power Supply
208-230/60/1 or
265-277/60/1
G
TEST
PIN
COMPRESSOR
CONTROL MODULE
Damper Switch
ON
OFF
Blue/Wht (35)
DT
Factory low voltage wiring
Factory line voltage wiring
Field low voltage wiring
Field line voltage wiring
Quick connect terminal
Wire nut
CC - Compressor Contactor DT - Damper Terminal Block FS - Freeze Sensing Device HP - High Pressure Switch LP - Low Pressure Switch PB - Power Block
RB - Blower Relay RV - Reversing Valve Coil ST - Entering Air Temperature Sensor
Legend
22
HP
LP
T
Switch - High Pressure
Switch - Low Pressure
Relay coil
Capacitor
Thermistor
Temperature Switch
Notes:
1. Switch Red and Blue wires for 208 volt operation
2. Terminal C of 24 V PB is used as “L” output for Brown wire 3 for Lockout.
3. Optional field installed freeze sensing device.
4. Factory wired. Refer to blower table settings.
L1
Field wire lug
Earth Ground
Relay Contacts ­N.O., N.C.
132
P
Polarized connector
Page 23
ENVISION CONSOLE INSTALLATION MANUAL
Wiring Schematics cont.
CCM w/EH - ELECTRONIC THERMOSTAT
Blue
PSC
Fan
Motor
Grn
Red (30)
HL
Black (29 )
Shut do wn
Brn
Wht
Cap
Whit e ( 28)
High
Low
Yell ow (4 4) Yell ow (1 3)
Elec t ronic THERMOSTAT
A Heat
T1
T2
T3
T4
T5
Overide
T6
B Cool
J1
White
T2 T1
EH
L2
4
6
1
3
Black
Black
Red (11)
Black (12 )
Black
4
RB
Red (19)
5
Aut o
2
Fan
ST
T
Red (17)
Red
Black
Yellow (13)
Orange (14)
Blue (T6)
24VAC
Shutdown
Red (15)
Red (16)
Black (25)
Whit e (18 ) Red (17) Red (11)
Ther
IN
PUT
mistor
24 V AC
T3
T1
T2
T4
T6
T5
SHUT
DOWN
L1
Tan (41)Blue (40)
2
5
White
Black (27)
Brown (26)
Continuous
Fan Mode Sw
Cycled
208-230-265/60/1
Compressor
Handi -Box
NOTE 1
Blk/ W ht (2 3)
24 V Accessor y
Ground
Lug
Red
208V
Transf ormer
HP HP CC CG LO R CLP LPY
EH
CC
Blk /W ht (2 4)
Damper
Motor
24V
HP HP CC CG LO R CLP LPY
Blue (38)
Black (37 )
Whit e ( 34)
D
C
S
Blue
R
Red Blk
Tan (33)
T1
T2
CC
Brown (26 )
L1
L2
Blue (40) Whit e (28 )
Tan ( 4 1 )
PB
Red (19)
Black (1 2 ) Black (2 2 )
1
3
E1
AQ
Brown (43)
Whit e (18)
Whit e (20 )
Yellow (44)
Orange (21)
RV
NOTE 4
RB
Gray (42 )
Normal
EH
Blue (T 6 )
31
A
C D
Green (00)
NOTE 3
NOTE 2
FS
Black (31 )
Red (32)
Black
Blue 230V 265V
Yellow
Black/White
Black/White (1) Red (2) Brown (3) Violet (4) Violet (5) Black (6 )
HP
Black (7 ) Blue (8)
LP
Blue (9) Yellow (10)
Violet (4) Red (39)
Viol et (5 )
Blue/Wht (36) Blue/Wht (35)
Unit
Power Supply
208-230/60/1 or
265-277/60/1
G
TEST
PIN
COM PRESSOR
CONTROL MODULE
2
E1
5
Damper Sw
ON
OFF
DT
4
Factory low voltage wiring Factory line voltage wiring
Field low voltage wiring Field line voltage wiring
Quick connect terminal
Wire n u t
AQ - A quas t at CC - Com pr es s or C ont ac t or DT -D am per Term inal B lock E1 - Electric Heat Relay EH - Electric Heat Contact or FS - Freez e S ens ing Devic e HP - High Pressure Swit ch LP - Low Pressure Swit ch PB - Power Block RB - Blower Relay RV - Reversing Valve Coil ST - E ntering Air Temper at ur e S ens or
Legend
Legend
L1
Field wire lug Eart h Ground Relay Contact s -
N.O., N.C.
132
P
Polarized c onnect or
HP
LP
T
Switch - High Pressure
Switch -Low Pressure
Relay coil
Capacitor
Thermistor
Temperatur e S wit c h
Notes:
1. Switch Red and Blue wires for 208 volt operation
2. Terminal C of 24 V PB is used as “L” output for Brown wire 3 for Lockout.
3. Optional field installed freeze sensing device.
4. Optional field installed aquastat.
6/10/08
23
Page 24
p
Wiring Schematics cont.
Legend for Schematic [A]
Blower of f delay Com pres s or on delay Short cycle delay Minimum compressor on time High pres s ure f ault rec ognit ion delay Low pres s ure f ault rec ognit ion delay Freez e s ens ing f ault rec ognit ion delay Condens at e ov erf low f ault rec ognit ion delay Low pres s ure f ault by pas s delay Freez e s ens ing f ault by pas s delay Mot oriz ed v alv e delay Random s t art delay
Norm al C ont rol T im ing T able
30 seconds 10 seconds 5 minutes 60 sec onds (except f or f ault c ondit ion )
Less than 1 second 30 seconds 30 seconds 30 sec onds 2 minut es 2 minutes 90 sec onds 0 -25 seconds
ENVISION CONSOLE INSTALLATION MANUAL
208-230-265/60/1VERSATEC CONTROL - EH & REMOTE WALL THERMOSTAT
Versa t e c Logic Board P hysical Lay out
FAN FANCOM
CC Relay
6
1
7
2
P2
8
3
9
4
10
5
CCG
CC
Fan R e la y C C
R R
Blower of f delay Com pres s or on delay Short cycle delay Minimum compressor on time High pres s ure f ault rec ognit ion delay Low pres s ure f ault rec ognit ion delay Freez e s ens ing f ault rec ognit ion delay Condens at e ov erf low f ault rec ognit ion delay Low pres s ure f ault by pas s delay Freez e s ens ing f ault by pas s delay Mot oriz ed v alv e delay Random s t art delay
5 sec onds 2 sec onds 15 sec onds 5 sec onds (except f or f ault c ondit ion ) Less t han 1 second 30 seconds 30 seconds 30 seconds 0 sec onds 0 sec onds 90 seconds 0 sec onds
LED D is play M ode T able
Tes t C ont rol T im ing T able
LED Normal Display Mode
Drain
Wat e r Flo w
High Pres s
Low Pres s
Air Flow Status DHW Limit HWD
LED
Drain Wat e r Flo w High Press
Low Pres s Air Flow
Status DHW Limit HWD
*Flashing Status light indicates microprocessor is functioning properly. Solid "on" indicates a micro
SW1 - # 4 On, SW2 Off Drain pan over f low loc kout
FS ther m istor (loop < 15° F, well < 30° F ) lock out High press ure > 600 P S I loc kout Low press ur e < 40 PSI loc k out Not us ed Micr opr oces s or m alf unc t ion * Not Used SW 2 stat us (Off =down pos it ion, On= up pos it ion )
Current Faul t Status
SW1- # 4 On, SW2 On Drain pan over f low FS ther m istor (loop High press ure >600 PS I Low press ur e < 40 P S I Not us ed Not us ed Not us ed SW2 in the On position
rocessor malfunctio n.
< 15°F, well <30°F )
Diagnostic Modes
Inputs
SW1-#4 Off , SW2 Off
Not Used
Off position
Outp uts
SW1-#4 Off, SW2 On Y G O
ES NS LS
Compressor
Not Used On position
FAN
ES NS LS
P3
P1
RCYOGLOESNSLS
Microprocessor
Logic Cont rol
17P529A01
SW1
Logic Board D I P Sw it c h Set t ings
Switch OFF ON
Test - Selected timings sped up to facilitate
SW1 - 1
troubleshooting
Loop - Closed loop freeze sensing setting (15°F)
SW1 - 2
Enables NS features
SW1 - 3
IO Display * - Enabl es Input/Output display on external
SW1 - 4
LED board*
SW1 - 5
Motorized Valve - 1.5 minute compressor on delay
OFF * - Normal or Input display mode activated
SW2
*Refer to LED Display Mode table for position of SW1-4 and SW2
Normal - Standard timings
Well - Open loop freeze sensing setting (30°F)
Normal - Standard thermostat operation
Normal * - Unit status display
Normal - Standard delay on call from compressor used
ON * - Current fault or Output display mode activated
Operational Logic T able
Mode
O
Htg Clg
Fan G ON
Inputs Fan Comp RV
Y,O
Y
ON ON
ON ON
OFF
OFF
ON
OFF
24
Page 25
ENVISION CONSOLE INSTALLATION MANUAL
Wiring Schematics cont.
Schematic [A]
Black
PSC
Fan
Motor
Low
White (28)
Brn/Wht
Brn
Cap
LS2
White
T2 T1
L2
Blue (40)
LS1
White
EH
L1
Tan ( 4 1)
Fan Speed
Switch
Grn
Black(29)
High
HL
Red (30)
208-230-265/60/1VERSATEC CONTROL - EH & REMOTE WALL THERMOSTAT
Compressor
C
S
Blu
Tan ( 3 6)
T2 T1
R
Red
Blk
CC
L1L2
Black (3 1 )
Red (32)
Handi - B ox
Ground
Lug
Unit Power Supply 208-230/60/1 or
265-277/60/1
G
Red
Black (2 5 )
DAMPER M ODE
Damper
Motor
White (34)
Red 208V
Transf ormer
24V
Yellow
FAN
Black/ White
R R
C C
10
Green (00)
P2
Black (47)1 Black (4 6 )
6 2
Blue (45)
7
Blue (44 )
3
Brown(43)
8
Orange (42)
4 9
Orange (41)
5
Yellow Yellow
HP LP CO
Gray (42 )
RV FS
T
RB
42
Off
On
Blue/Wht (35)
DT
D
Blue/Wht (36)
CC
Brown (43)
Red(19)
Red (39)
Blue (38 )
EH
Black(27)
Black (2 2 )
COM
CC
5
4
E1
2
Black (37 )
CCG
CPU
SW1
OnOff
1
Test / Nor mal
2
Loop / Well
3
Inputs / Normal
4
Ou tp u ts / No r ma l
5
Motorized Valve / No rm a l
Blue 265V
Blue 230V
13
RB
FAN
P1
NOTE 5
Black Com
Orange (21)
LSNSESLOGOYCR
Red
Bl ack
Yellow
Orange
Pink
Bl ue
Violet
Brown
Green
White
E1
T
Relay Contacts­N.O., N.C.
Thermistor
Re lay coil
Factory low voltage wiring Factory line voltage wiring Field low voltage wiring Field line voltage wiring
DC voltage PCB traces Internal junction Quick connect terminal
Wire nut
L1
Field wire lug Ground
Black/ White
MV
NOTE 2
P
Black/ White
Legend
132
Legend
Switch - High pressure
Switch -Low pressure
Polarized connector
Condensate Overflow
25
CRY1OGLS
X2 X1 W1
Terminal Board
AQ – Aquastat
CC – Compres s or Contactor CO – Condensate Overflow DT – Damper Terminal Block E1 – Electric Heat Relay EH – Electric Heat Contactor
ES – Emergency Shutdown
FS – Freeze Se nsing Device HP – Hig h Pressure Sw itch LP – Low Pressure Switch LS – Loadshed MV – Motorized Valve NS – Night Setback RB – Blower Power Relay RV – Reversing Valve Coil SW1 – D IP Swit c h #1
NOTE 1
NOTE 3
AQ
Notes: 1 -Requires common connection or 24 VAC for
activation. 2 -When field installed 24VAC motorized
valve is used, connect to C and Y or SV terminals. 3 -Optional field installed aquastat for use with single heat
4 -Check installlation wiring information for specific thermostat hookup instructions.
5 -Switch blue and red wires for 208V operation.
97P786-04 6/10/08
Page 26
ENVISION CONSOLE INSTALLATION MANUAL
Wiring Schematics cont.
FX10 - EH 208-230-265/60/1
Compressor
S
C
Handi - B ox
Red
MEHS
Red (20)
Black
Yellow
Ground
PB1
L1 L2
HP
RB
Lug
RV
R
BlkRed
Tan
T1
T2
L2
L1
Black
Yell ow (3 3)
Molex Plug
20
19
18
Black (1)
17
Black (111)
Black (310)
Yellow (9)
Orange (7)
Black (6 )
Black (5 )
Blue (4)
Gray (3)
Black (2)
Black
(12)
Yellow (16)
16 15
14
13 12
11
10
9 8 7
6 5 4
3 2 1
Blue 240V
277V
NOTE 1
Red 208V
Blk
Power S upply 208-230/60/1 or
265-277/60/1
Blk/Wht
White
CC
Blk/Wht
Unit
G
Transf ormer
Yellow
Blk
Orange
EHC
NOTE 5
24VAC
24V COM
Alarm
Acc 1
Acc 2
Fan
Rev Valve
Comp
Setpoint Shift
AI Com
Room Sens or
Sensor Com
Tem p Oc c
TB
R
C
L
X1
X2
G
O
Y1
SS
AIC
RS
SC
TO
LC1
LC2
Black (11 1 ) Black (31 0 )
PB2
L2
L1
Molex
Plug
NOTE 2
Black (3 1)
Fan Spe e d
NOTE 3
Switch
NOTE 4
Grn
HL
Blk
Red
High Low
FS
DA
Org/Wht (12)
Green (17)
Orange (19)
Red (120)
Yellow ( 21)
CP/FP
Gray (26 )
ES
OS
PSC Fan
Motor
CO
DF/AP
Brown (1)
Brown (2)
T
Wht /B lu ( 6)
T
Blk/Red (9)
Blu/ W h t (10 )
Org/Bck (11)
Gry /Wht (1 4 )
Black (6 )
Black (2 2 ) Violet (23) Red (24)
LP
Blue (27)Blue (32 )
Pink (28)
Blk /W ht (2 9) Orange (30)
Brn
Red (120)
White (5)
Brn/Wht
11K
Cap
White
Blue
Blu
EHC
L1
Black(121)
Yellow (35)
A33
White
LS2
Black (515)
Blk/ W ht (3 6)
TAN
BLUE
Black (1 31 )
CC
Black (3 4 )
D09
D08
D07
D06
D05 D04
D03
D02
D01
LS1
White
T2 T1
L2
RB
Black
J8
5VDC
23
-
24
AI3
+
25
-
26
AI5
+
27
-
28
AI4
+
29
-
30
AI6 +
31
-
32
AI2 +
33
5VDC
34
-
35
AI1
+
36 37 38
J2
39 40 41
J10
42 43 44 45 46 47 48
J9
49 50 51 52 53 54 55 56
LED 5VDC
PWM2 PWM2 Com PWM1
24VAC Com DI12 DI11 DI10 DI9 DI8 DI7
DI 3/4/5/6/ Com DI6 DI5 DI4 DI3 DI2 9VDC DI1
A21A12
A23
Black
Black (6 )
Gree n ( 37)
24VAC
24VAC Com
GROUND
A14
A24
A34
A25 A2 2
A32
A31A35
A13
A11
A15
Johnson FX-10
J7
Factory low voltage wiring Factory line voltage wiring
Field low voltage wiring
Field line voltage wiring Field Zone Sensor Wiring
T
Internal junction
Quick conn ect t ermina l
Wire nut
L1
Field wire lug
Ground
Relay Contacts-
N.O., N.C.
Thermistor -Johnson Control
Re lay coil
Open Jumper
Closed Jumper
P
Legend
Switch -High pressure
Switch - Low pressure
Polarized con n ector
132
Condensate Overflow
26
CC - Compressor Contactor CO - Condensat e Overf low CP/FP - Compressor Proving/Fan Prov ing DA -Disc har ge A ir Temper ature DF/AP - Dirty Filter /Air P r ov ing EHC - Electric Heat Contactor EHR - Electric Heat Relay ES - Emergency Shutdown FS - Freez e S ens ing Devic e HP -H igh P r es s u re S wit ch LP - Low Pressure Switch MEHS - M anual E H S wit c h OS - Occupied Switch RB -Blower P ower Replay RV -Rev ers ing V alve Coil TB - Terminal Block
Notes:
1 -Switch Blue and Red wires for 208V operation 2 -Disconnect for 15 degree freeze protection 3 -Acc 1 output is cycled with the compressor. 4 -Acc 2 output is cycled with the fan. 5 - R, C, Y1, O, and G inputs are for use with a wall mounted thermostat.
6/10/08
Page 27
ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls
Control General Description Application Display/Interface Protocol Thermostat Options
CCM Control The CCM (Compressor control module)
is a more reliable replacement for electro-mechanical control applications. It features a small microprocessor board that handles the lockout function of the unit. A second microporcessor handles the unit mounted thermostat for maintaining accurate room temperature.
Versatec Control The Versatec Control is a
microprocessor based board that adds the features of emergency shutdown (ES), night setback (NS), water freeze sensing (FS), Load Shed (LS) and condensate overfl ow (CO). The Versatec Control also features Optional Field servicing LED's for mode, Fault and diagnostic indication.
Residential and commercial applications requiring minimal but reliable controls. Includes Random Start, High and low pressure switches and auto changeover capability.
Residential and commercial applications requiring more controls features than CCM and Includes Random Start, High and low pressure switches, auto changeover capability, emergency shutdown (ES), night setback (NS), load shed (LS), water freeze sensing (FS), and condensate overfl ow (CO).
Dial thermostat with Hi and Low fan speeds, and auto changeover or cont fan selection switches.
Optional fi eld servicing LED board for mode, fault and diagnostic indication
None Unit Mounted Digital
Dial Thermostat
Remote Mounted Standard Thermostat
None Unit Mounted Digital
Dial Thermostat
Remote Mounted Standard Thermostat
FX10 The FX10 microprocessor control is self
contained control featuring LP, LOC, HP, LWT, and condensate overfl ow fault modes can be displayed on BAS system. Optional handheld Medium User Interface (MUI) Control can be used for additional setup or servicing. Program customization is possible. This control is suited for both single and dual capacity compressors as well as PSC and ECM fan motors.
FX10 w/ N2 FX10 Control functions as both unitary
heat pump control and DDC communica­tion, therefore detail operational and fault information is available to BAS. Other features are same as FX10 with addition of Johnson Controls N2 compat­ibility.
FX10 w/ LonWorks FX10 Control functions as both unitary
heat pump control and DDC communica­tion, therefore detail operational and fault information is available to BAS. Other features are same as FX10 with addition of LonWorks compatibility.
FX10 w/ BACnet FX10 Control functions as both unitary
heat pump control and DDC communica­tion, therefore detail operational and fault information is available to BAS. Other features are same as FX10 with addition of BACnet compatibility.
Commercial applications using sin­gle and dual capacity compressors with either PSC or ECM fan motors. Also suitable for multi-compressor products. Cannot be integrated with centralized building automation systems. Software can be custom­ized for specifi c projects.
Same as FX10 with Johnson Controls N2 BAS compatibility.
Same as FX10 with LonWorks BAS compatibility.
Same as FX10 with BACnet BAS compatibility.
Due to communication speed, no more than 40 units should be connected to a single trunk of the network.
Optional Medium User Interface (MUI) can be used as a eld service tool.
Optional Medium User Interface (MUI) can be used as a eld service tool.
Optional Medium User Interface (MUI) can be used as a eld service tool.
Optional Medium User Inter­face (MUI) can be mounted or used as a eld service tool.
Standalone Remote Mounted
Johnson Controls N2 network
LonWorks Remote Mounted
BACnet - MS/ TP (19,200 Baud Rate)
Standard Thermostat Remote Mounted
Sensor
Remote Mounted Standard Thermostat
Remote Mounted Sensor
Standard Thermostat Remote Mounted
Sensor
Remote Mounted Standard Thermostat
Remote Mounted Sensor
Standard CCM Control Features
Compressor control module (CCM) controls are standard on the Envision console heat pump. This control features unit mounted thermostat and switches, Features of the standard control are:
• Easy to understand color coded thermostat adjustment markings.
• Large, rocker type mode and fan switches.
• Internally mounted fan switch to choose cycled or constant fan operation.
• High pressure and low pressure safety controls to protect the unit components.
• Lockout circuit to shut down unit operation upon receipt of a fault indicator from the safety controls.
• A 24 volt control circuit allows for safe and easy diagnosis.
27
Page 28
Envision Console Controls cont.
ENVISION CONSOLE INSTALLATION MANUAL
The user selects either “Heat/Cool” or “Fan Only” on the mode switch, then either “High” or “Low” at the fan speed switch. The temperature can be controlled by rotating the thermostat control knob.
Figure 6: Unit Mounted Control
The “Fan Only” setting provides constant fan operation.
In the “Heat” mode, a call for heat by the thermostat closes the compressor contactor contacts, energizing the com­pressor, which will run until the thermostat is satisfied.
In the “Cool” mode, a call for cooling by the thermostat energizes the reversing valve and closes the compressor contactor contacts, energizing the compres­sor, which will run until the thermostat is satisfied.
Optional Versatec Microprocessor Control Features
The Versatec microprocessor board provides control of the entire unit as well as outputs for status modes, faults and diagnostics. The control system is a microprocessor­based control board that is located in the unit control box. This feature is available for either unit mounted controls or optional remote wall mounted thermostat. A 9-pin low voltage terminal strip provides all necessary terminals for the wall mounted thermostat.
Startup
The unit will not operate until all the inputs and safety controls are checked for normal operating conditions.
Fault Retry
All faults are retried twice before finally locking the unit out to prevent nuisance service calls.
Component Sequencing Delays
Components are sequenced and delayed for optimum unit performance.
Short Cycle Protection and Random Start
The control allows a minimum on or off time of 5 minutes for short cycle protection. A random time delay of 0 to 30 seconds is generated after each power-up to prevent simultaneous start up of all units within a building after the release from an unoccupied cycle or power loss.
The emergency electric heat operation in the “Heat/Cool” mode is subject to the setting of the internally mounted mode switch. The optional, factory installed electric heat will operate when the internally mounted mode switch is in the “Emergency Heat” mode. In the “Heat” mode, a call for heating energizes the fan and electric heater contactor, energizing the electric heat elements and fan, which will run until the thermostat is satisfied. When the internally mounted mode switch is in the “Normal/Boilerless” mode the unit operates in its normal “Heat/Cool” operation, unless there is an aquastat controller. When the normally open circuit of the aquastat closes and the unit is in the heating mode, it will switch to the “Emergency Heat” condition until the thermostat is satisfied or the aquastat opens restarting the compressor.
If either the low or high pressure safety switches are opened, the compressor and reversing valve are disabled by the lockout relay. Unit operation will resume only after the voltage to the unit is interrupted or the mode switch is placed in the “Off” position.
If the electric heat limit switches are opened, the electric heat is disabled.
Night Setback
A grounded signal to common or connecting 24 VAC to the NS terminal will initiate the night setback mode.
Load Shed
A grounded signal to common or connecting 24 VAC to the LS terminal places the controller into the load shed mode. The compressor will become disabled and the fan will start upon a thermostat call for heating or cooling.
Emergency Shutdown
A grounded signal to common or connecting 24 VAC to the ES terminal places the controller into the emergency shutdown mode. The compressor and fan operation are suspended while in the emergency shutdown mode.
Condensate Overflow Protection
The board incorporates an impedance liquid sensor at the top of the condensate drain pan. Upon a continuous 30­second sensing of the condensate, the cooling operation of the unit is suspended.
Safety Controls
The microprocessor board receives separate signals from a high pressure switch for safety, a low pressure switch to
28
Page 29
ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls cont.
prevent loss of refrigerant charge and a low suction tem­perature thermistor for freeze sensing. Upon a continuous
30-second measurement of the fault (immediate for high pressure), compressor operation is stopped.
Control Tables for Optional Versatec Microprocessor
Logic Board DIP Switch Settings
Switch OFF ON
SW1 - 1
SW1 - 2
SW1 - 3
SW1 - 4
SW1 - 5
Normal Control Timing Operational Logic
Blower off delay
Compressor on delay
Short cycle delay
Miniumum compressor on time
High pressure fault recognition delay
low pressure fault recognition delay
Freeze sensing fault recognition delay
Condensate overflow fault recognition delay
Low pressure fault bypass delay
Freeze sensing fault bypass delay
Power on delay
Test - Selected timings sped up to facilitate troubleshooting Normal - Standard timings
Loop - Closed loop freeze sensing setting (15°F) Well - Open loop freeze sensing setting (30°F)
Commercial - Enables NS features when TA32U02 thermostat is used Normal - Standard thermostat operation
IO Display* - Enables Input/Output display on external LED board Normal* - Unit status display
Configures board for 2-speed compressor without fan Configures board for 2-speed compressor with fan
30 seconds
10 seconds
5 minutes
2 minutes (except for fault condition)
Less than 1 second
30 seconds
30 seconds
30 seconds
2 minutes
2 minutes
5 minutes
Mode Inputs Fan Comp RV
Htg
Clg
Fan
YONONOFF
Y,OONONON
G ON OFF OFF
Test Control Timing
Blower off delay
Compressor on delay
Short cycle delay
Miniumum compressor on time
High pressure fault recognition delay
low pressure fault recognition delay
Freeze sensing fault recognition delay
Condensate overflow fault recognition delay
Low pressure fault bypass delay
Freeze sensing fault bypass delay
Power on delay
Fault off time
5 seconds
2 seconds
15 seconds
5 seconds (except for fault condition)
Less than 1 second
30 seconds
30 seconds
30 seconds
0 seconds
0 seconds
15 seconds
5 minutes
Diagnostic Modes
LED
Drain Drain pan overflow Y Compressor
Water Flow FS thermistor (loop <15°F, well <30°F) G FAN
High Press High pressure >600 PSI O O
Low Press Low pressure <40 PSI ES ES
Air Flow Not used NS NS
Status Not used LS LS
DHW Limit Not used Not used Not used
HWD SW2 in the On position Off position On position
Current Fault Status
SW1 - #4 On, SW2 On
Inputs
SW1 - #4 Off, SW2 Off
Outputs
SW1 - #4 Off, SW2 On
29
Page 30
Envision Console Controls cont.
ENVISION CONSOLE INSTALLATION MANUAL
Optional FX10 Control
Main FX 10 Board
The optional FX10 control provides unparalleled capability in several areas including performance monitoring, zoning, humidity, energy management, and service diagnosis, and then communicates it all thru standard DDC protocols like N2, Lon and BACnet (MS/TP @ 19,200 Baud rate).
The most unique feature is integrating the FX10 into the Envision series as both the heat pump and DDC controller providing both a cost advantage and providing features not typically found on WLHP controls. This integration allows heat pump monitoring sensors, status and service diagnosis faults to be communicated thru the DDC direct to the building automation system (BAS), giving building supervisors detailed and accurate information on every piece of equipment without removing an access panel.
Random Start
A delay of 1 to 120 seconds is generated after each power­up to prevent simultaneous startup of all units within a building after the release from an unoccupied cycle or power loss.
Emergency Shutdown
A field-applied dry contact can be used to place the control into emergency shutdown mode. During this mode, all outputs on the board are disabled.
Freeze Detection Limit
Field selectable for 15° or 30°F (-9° or -1°C)
Installation Options
• Standalone controlled by standard room thermostat
• Standalone with a Zone Temperature Sensor (must have user interface to change set points beyond the allowed +/- 5°F)
• Integrated into BAS by adding communication module
Accessory Outputs
Quantity 2. One cycled with blower, other with compressor.
User Interface
4 x 20 backlit LCD.
FX10 Advanced Control Overview
The Johnson Controls FX10 board is specifically designed for commercial heat pumps and provides control of the entire unit as well as input ports for Open N2, LonTalk, BACnet (MS/TP @ 19,200 Baud rate) communication protocols as well as an input port for a user interface. The user interface is an accessory item that can be used to aid in diagnostics and unit setup. A 16-pin low voltage terminal board provides terminals for common field connections. The FX10 Control provides:
• Operational sequencing
• High and low-pressure switch monitoring
• General lockout
• Freeze detection
• Condensate overflow sensing
• Lockout mode control
• Emergency shutdown mode
• Random start and short cycle protection
Short Cycle Protection
Allows a minimum compressor “off” time of four minutes and a minimum “on” time of two minutes.
Optional Plug-in Communication Modules ­(compatible with standard BAS protocols)
• Open N2
• LonTalk
• BACnet (MS/TP @ 19,200 Baud rate)
Display
Requires DLI Card/Kit. Up to 2 displays, either 1 local and 1 remote, or 2 remote. (A 2-display configuration requires identical displays.) Local display can be up to 3 meters from the controller, power supply, and data communication. Remote display can be up to 300 meters from the controller. Remote display must be independently powered with data communication done via 3 pole shielded cable.
30
Page 31
ENVISION CONSOLE INSTALLATION MANUAL
system (BAS). This means that not o
Envision Console Controls cont.
Control Timing & Fault Recognition Delays
Lead compressor “ON” delay ..........................................90 seconds
(not applicable for single compressor models)
Minimum compressor “ON” time ...................................... 2 minutes
(except for fault condition)
Short cycle delay ..................................................................... 5 minutes
Random start delay ....................................................... 0-120 seconds
High pressure fault ................................................................. <1 second
Low pressure fault ...............................................................30 seconds
Freeze detection fault ...........................................................30 seconds
Condensate overflow fault ...............................................30 seconds
Low pressure fault bypass ................................................... 2 minutes
Freeze detection fault bypass ............................................ 2 minutes
Optional FX10 Microprocessor and BAS Interface
The FX10 is a microprocessor based control that not only monitors and controls the heat pump but also can communicate any of this information back to the building automation system (BAS). This means that not only does
MUI and will be held in memory until the unit is power cycled. Relative humidity can be read by a 0-5VDC humidity sensor that is displayed over the network. If you are using an ECM2.3 blower motor the control can enable dehumidification mode based on a set point in the control. The dehumidification set point itself can also be changed over a BAS or with a MUI. Dehumidification mode can also be enabled by the BAS. Because the FX10 is not factory configured to read CO application assistance.
The FX10 control has unused analog and digital inputs for field installed items such as air temperature, water temperature, CO unused binary and PWM outputs that can be commanded over the BAS for field use. An optional Medium User Interface (MUI) for control setup and advanced diagnostics is available with some mounting kits, MUIK1 - Panel mount version and the MUIK2-Wall mount version.
2
levels, contact the factory for
2
or current status switches. The control has
Zone Sensors
There are two options for zone sensors that can be used with the FX10 control. Both sensors use a Johnson controls A99 positive temperature coefficient type sensor. The TAXXJ02 has a set point adjustment now which will give the end user a +/- 5°F adjustment from the set point as well as a push button that can be used for temporary occupancy. The control leaves the factory set to operate with a TAXXJ02 sensor and can be changed to read the TAXXA01 sensor through a building automation system or with a user interface.
the control monitor the heat pump at the unit you can also monitor and control many the features over the BAS. This clearly puts the FX10 in a class of its own.
The control will enumerate all fault conditions (HP, LP, CO, LOC, and Freeze Detection) over a BAS as well as display them on a medium user interface (MUI). HP, LP, CO and Freeze Detection faults can all be reset over a BAS. A Loss Of Charge fault can not be reset or bypassed until the problem has been corrected. A MUI is invaluable as a service tool for the building service team.
The unit can be commanded to run by a typical heat pump thermostat or run based on heating and cooling set points supplied by a BAS. The control board is wired with quick connect harnesses for easy field change out of a bad control board. All ECM2.3 variable blower speed settings can be changed over a BAS or with a MUI. The control has an input programmed to enable field installed emergency heat in the event that the compressor is locked out. This input can also be commanded on from a BAS as needed. An alarm history can be viewed through the
Standard Features
• Anti Short Cycle
• High Pressure Protection
• Low Pressure Protection
• Freeze Detection
• Loss Of Charge Detection
• Random Start
• Display for diagnostics
• Reset Lockout at disconnect or through BAS
• 2 Accessory outputs
• Optional BAS add-on controls
DDC Operation and Connection
Other optional network protocol boards that can be added to the FX10 are:
• Johnson Control N2
• LonWorks
• BACnet
- MS/TP @ 19,200 Baud rate
- Limit devices to 30 on a single trunk line.
31
Page 32
Envision Console Controls cont.
ENVISION CONSOLE INSTALLATION MANUAL
Control and Safety Feature Details
Emergency Shutdown
The emergency shutdown mode can be activated by a command from a facility management system or a closed contact on BI-2. The default state for the emergency shutdown data point is off. When the emergency shutdown mode is activated, all outputs will be turned off immediately and will remain off until the emergency shutdown mode is de-activated. The first time the compressor starts after the emergency shutdown mode has been de-activated, there will be a random start delay present.
Lockout Mode
Lockout mode can be activated by any of the following fault signals: refrigerant system high pressure, refrigerant system low pressure, freeze detection, and condensate overflow. When any valid fault signal remains continuously active for the length of its recognition delay, the controller will go into fault retry mode, which will turn off the compressor. After the Compressor short cycle delay, the compressor will attempt to operate once again. If three consecutive faults occur in 60 minutes during a single heating or cooling demand, the unit will go into lockout mode, turning off the compressor, enabling the alarm output, and setting the blower back to low speed operation until the controller is reset. If the control faults due to the low pressure input (BI-3) being open during the pre-compressor startup check, the control will go into lockout mode immediately, disabling the compressor from starting and enabling the alarm output (BO-6). The lockout condition can be reset by powering down the controller, by a command from the BAS, or by the holding the ESC and Return keys on the MUI for 5 seconds.
Freeze Detection Limit (AI-5)
The freeze detection limit sensor will monitor the liquid refrigerant temperature entering the water coil in the heating mode. If the temperature drops below the freeze detection limit trip point for the recognition delay period, the condition will be recognized as a fault. The freeze detection limit trip point will be factory set for 30°F and will be field selectable for 15°F by removing a jumper wire on BI-5. The freeze detection limit fault condition will be bypassed 2 minutes at normal compressor startup, to allow the refrigeration circuit to stabilize. If the freeze detection limit sensor becomes unreliable at any time compressor operation will immediately be suspended until the problem is corrected. This should be displayed as an alarm on the BAS and the MUI. This alarm will be reported a “Water Low Temp Limit” fault.
the compressor output immediately and count the fault. The compressor minimum on time does not apply if the high­pressure switch opens. The compressor will not restart until the compressor short cycle time delay has been satisfied.
Low Pressure (BI-3)
The low-pressure switch shall be a normally closed (NC) switch that monitors the systems refrigerant pressure. The input shall be checked 15 seconds before compressor start up to be sure the pressure switch is closed and then ignored for the first 2 minutes after the compressor output (BO-2) is enabled. If the switch is open continuously for (30) seconds during compressor operation the compressor output (BO-2) will be disabled. The compressor will not restart until the compressor short cycle time delay has been satisfied.
Condensate Overflow
The condensate overflow sensing circuit will monitor the condensate level as a resistance input to AI-3. If the condensate water level rises resulting in the input resistance rising above the set point for the recognition delay period, the condition will be recognized as a fault. The condensate will be subjected to a (30) second lockout delay which requires that the fault be sensed for a continuous (30) seconds before suspending unit operation.
Alarm Output (BO-6)
The alarm output will be enabled when the control is in the lockout mode and will be disabled when the lockout is reset.
Test Mode
Raising the zone temperature input (AI-1) reading to 180– 220°F or by holding the ESC and down arrow keys on the MUI for 5 seconds will put the control into test mode. In test mode the random start delay and the compressor fixed on delay time will both be shortened to 5 seconds and the reversing valve will be allowed to cycle with out shutting down the compressor. If an MUI is connected to the control LED 8 will flash and the words “Test Mode Enabled” will be shown on the LCD display when the control is in test mode. Test mode will be disabled after a power cycle, 30 minute timeout, or by holding the ESC and Up arrow keys on the MUI.
Sequence of Operation
Power Fail Restart
When the controller is first powered up, the outputs will be disabled for a random start delay. The delay is provided to prevent simultaneous starting of multiple heat pumps. Once the timer expires, the controller will operate normally.
High Pressure (BI-11)
The high-pressure switch shall be a normally closed (NC) switch that monitors the systems refrigerant pressure. If the input senses the high-pressure switch is open it must disable
Random Start Delay
This delay will be used after every power failure, as well as the first time the compressor is started after the control exits the unoccupied mode or the emergency shutdown
32
Page 33
ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls cont.
mode. The delay should not be less than 1 second and not longer than 120 seconds. If the control is in test mode the random start delay will be shortened to 5 seconds.
Compressor Fixed On Delay Time
The Compressor Fixed On Delay Time will ensure that the compressor output (B02) is not enabled for (90) seconds after the control receives a call to start the compressor. This delay is adjustable from 30 – 300 seconds over a BAS or a MUI. If the control is in test mode the Compressor Fixed On Delay Timer will be shortened to 5 seconds.
Compressor Minimum On Delay
The compressor minimum on delay will ensure that the compressor output is enabled for a minimum of (2) minute each time the compressor output is enabled. This will apply in every instance except in the event the high pressure switch is tripped or emergency shutdown then the compressor output will be disable immediately.
Compressor Short Cycle Delay Time
The compressor short cycle time delay will ensure that the compressor output will not be enabled for a minimum of (5) minutes after it is disabled. This allows for the system refrigerant pressures to equalize after the compressor is disabled.
Heating Cycle
On a call for heating, the blower enable output and accessory output 2 will turn on immediately after the random start delay timer has been satisfied. If the compressor short cycle time delay has been satisfied, the compressor will turn on after the blower enable and accessory output 2 are on and the fixed compressor start delay timers have been satisfied.
Auxiliary heat output can be controlled over the BAS.
Set Point Control Mode
In set point control mode the reversing valve output will be disabled. As the temperature drops below the heating set point and begins to operate in the heating proportional band, the low capacity compressor output (BO-2) will be enabled. A PI loop in the programming of the control will determine when the full capacity compressor output (BO-4) is to be enabled. The compressor must be operating in low capacity for a minimum of 30 seconds before the full capacity compressor output can be enabled.
Thermostat Control Mode
In thermostat mode the compressor will be cycled based on Y1 calls from a room thermostat. When the control receives a Y1 command (BI-7) from the thermostat, the compressor output (BO2) will be
enabled. During the heating cycle the reversing valve will be commanded into the off position.
Cooling Cycle
On a call for cooling, the blower enable output and accessory output 2 will turn on immediately after the random start delay timer has been satisfied. If the compressor short cycle time delay has been satisfied, the compressor will turn on after the blower enable and accessory output 2 are on and the fixed compressor start delay timers have been satisfied.
Set Point Control Mode
In set point control mode the reversing valve output will be enabled. As the temperature falls below the cooling set point and begins to operate in the cooling proportional band, the low capacity compressor output (BO-2) will be enabled. A PI loop in the programming of the control will determine when the full capacity compressor output (BO-4) is to be enabled. The compressor must be operating in low capacity for a minimum of 30 seconds before the full capacity compressor output can be enabled.
Thermostat Control Mode
In thermostat mode the compressor will be cycled based on Y1 calls from a room thermostat. When the control receives a Y1 command (BI-7) from the thermostat, the compressor output (BO2) will be enabled. During the cooling cycle the reversing valve will be commanded into the “ON” position.
Emergency Heat/Network Enabled Output (BO5)
This output is set from the factory to enable/disable emergency heat. If a problem occurs with the unit resulting in the compressor being locked out in heating mode, the control will automatically enable this output to turn on field installed electric heat. This output is interlocked with the blower proving input BI-6 (Blower proving sensors must be field supplied and installed). BI-6 must be connected to PB2 position 3 (see unit schematic) in the field if no blower proving sensor is desired. There is a configurable parameter available through a BAS network that must be enabled if this output is to be commanded over the BAS network.
MUI Alarm History Reporting
If a fault occurs the fault will be recorded in history for display on the medium user interface in the History Menu. Each fault type will be displayed in the history menu with a number between 0 and 3. A reading of 3+ will mean that fault has occurred more than three times in the past. The history menu can be cleared with a power cycle only. Alarm date and time are not included in the history.
33
Page 34
Envision Console Controls cont.
Inputs and Outputs Configuration
Field Selectable Options
Freeze Detection Limit Set Point (BI-5)
The freeze detection limit set point input allows you to adjust the freeze detection limit set point (AI-5). When the jumper is installed on BI-5 (Wire #24) the freeze detection limit set point is factory set for 30°F. When the jumper on BI-5 (Wire #24) is removed the freeze detection limit set point will be 15°F.
Accessory Outputs (BO-7 and BO-8)
Accessory Output 1 will be energized 90 seconds prior to the compressor output being energized. Accessory Output 2 will be energized with the fan output (BO-1). When the corresponding compressor output is turned off the accessory output will be deactivated immediately. These outputs are selectable for normally open or normally closed operation through the Medium User interface or through the Building Automation System.
ENVISION CONSOLE INSTALLATION MANUAL
SINGLE and DUAL STAGE WATER-TO-AIR Input Name Input Output Name Output
Zone Temp 1 AI 1 Fan Enable BO1 Relative Humidity Input AI 2 Comp – Low Capacity BO2 Condensate Level AI 3 Reversing Valve BO3 Universal Temp Input AI 4 Comp – Full Capacity BO4 Water Coil Low Temperature Limit AI 5 Network Output/EH Output BO5 Warm/Cool Adjust and Temp Occ AI 6 Alarm BO6
Occupied BI 1 Accessory 2 Output BO8 Emergency Shutdown BI 2 Network Controlled Output B09 Stage 1 Low Pressure BI 3 Network Viewable Input 1 BI 4 ECM2 Fan PWM1 Water Coil Low Temp Limit Set Point BI 5 Network Controlled Output PWM2 Network Viewable Input 2 BI 6 Thermostat Y1 BI 7 Thermostat Y2 BI 8 Thermostat O BI 9 Thermostat G B10 Stage 1 High Pressure BI11 Compressor Proving BI12
XP10 Expansion Card Input Name Input Output Name Output
Unused AI 1 Unused BO 1 Unused AI 2 Unused BO 2 Unused AI 3 Unused BO 3 Unused AI 4 Unused BO 4
Accessory 1 Output BO7
Control Accessories
Zone Sensors
• TAXXJ02 Room Command Module
• TAXXA01 LCD Room Command Module
• A99 Sensor
MUI (LCD User interface) for diagnostics and commissioning.
• MUIK3 - Panel Mount, Portable
• MUIK4 - Wall Mount
34
Page 35
ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls cont.
FX10 User Interface (MUI) Physical Layout
Power LED
Alarm LED
Up Arrow Right Arrow
LED 1
LED 4
LED 8
Alarm LED - Indicates a Lock-Out or a bad Freeze Sensor Power LED - Shows FX processor is operational LED 1 - Flashing shows Compressor 1 running
Left Arrow Down Arrow
LED 3 - On shows Fan running LED 4 - On shows Reversing Valve in cool LED 8 - Flashing shows unit in ‘Test’ Mode
LED 2 - Flashing shows Full Capacity Compressor running
MUI Menu Navigation for Single Compressor - Envision Water-to-Air
Escape (ESC) Button
Return Button
Info Status Temps Outputs Settings Maint Alarms Alm-History
Info
WFI Envision Series PROFXENV-XX 3/8/07
Status
Run Mode Auto Eff Occup’y Occ Y1 Input OFF Y2 Input OFF G Input OFF O Input OFF Occ Input Occ Temp Occ Inp OFF Condensate NML Emg Input Run Lo Press ON Hi Press ON Rndm Tmr 0 BI-4 Input OFF
Welcome
Temps
Zone Temp 77.2 ºF Dis Air Temp 51.0 ºF Eff Clg Setpt 70.0°F Eff Htg Setpt 66.0°F Water Coil 77.8°F Low WC Limit 30.0°F Humidity 56.7 %RH WarmCool AI 14.6 WarmCoolAdj 0.2
Outputs Settings
nvoFanStatus ON CmpCmd Status OFF Cmp Capacity OFF Rev Valve Heat X1 Output OFF X2 Output OFF PWMOut 98% BO5 OFF BO9 OFF AO2 Output 0%
Unit of Measure F Occ Clg Setpt 73.9 ºF Occ Htg Setpt 69.9 ºF Unocc Clg 84.0 ºF Unocc Htg 60.0 ºF DeHumSetpt 0% SensorSelect TAXXJ02
35
Page 36
ENVISION CONSOLE INSTALLATION MANUAL
Envision Console Controls cont.
MUI Menu Navigation for Single Compressor - Envision Water-to-Air
Alarms
ALARM SUMMARY
^/High Pressure
Maintenance
MinClgSetpt 60.0 ºF MaxHtgSetpt 89.9 ºF W Coil LoLim1 30.0 ºF W Coil LoLim2 15.0 ºF TmpOccTime 120 min Rev Vl v Default Heati n g BO5 Mode Network CompStrtDly 90 sec SpaceT Offset -1 ºF DehumEnaDis Dis Acc1 Action On Comp Acc2 A ction On Fan
Alm-History
Alarm #Events Condensate 0 Hi Pressure 0 Low Pressure 0 Low Temp 0 Bad Sensor 0
Press right arrow key
one time from
Maintenance Menu
NOTE: This FX10 applicati on implements an alarm history which is reset only by cycling power. This history shows on the Alm-History page. Any alarm showing 4+ events has occurred more than 4 times.
Alarm lock-outs
Return keys simultaneously for a minimum of 15 seconds, or by commanding the nviAlarmReset over the BAS network.
Test mode
for a minimum of 15 seconds and releasing. Test mode times out after 30 minutes, and may also be ended by pressing ‘ESC’ and Up Arrow simultaneously and releasing. Test Mode bypasses the On Delay (90 sec) and Random Start timers for quicker troubleshooting. It also allows cycling the reversing valve without compressor shutdown.
ECM
SW1 OFF SW2 OFF SW3 ON SW4 OFF SW5 OFF SW6 OFF SW7 ON SW8 OFF SW9 OFF SW10 ON SW11 OFF SW12 OFF
No more than three
speeds should be “ON”
at one time
are reset by cyc ling power, by pressing the “ESC” and
is enabled by holdi ng the ‘Esc’ and Down Arrow simultaneously
36
Page 37
ENVISION CONSOLE INSTALLATION MANUAL
Unit Startup Notes
Emergency Electric Resistance Heat
A factory-installed emergency electric heater package is available. Rated for 2,000 watts on models NC09 through NC12 and 3,000 watts on models NC15 through NC18. The heater package consists of ni-cad elements, ceramic insulators, and thermal limit switches. A concealed, chassis mounted rocker switch controls the heater mode operation and allows the field installation of an aquastat for boilerless unit operation.
Electrical Disconnect
Field installed on the optional chassis back plate, the con­sole disconnect provides a permanent electrical connection to the main electrical supply branch. Wiring between the disconnect and the unit chassis is field supplied and allows the electrical power source to the chassis to be interrupted for unit servicing.
Non-Fused
Constructed of heavy gauge galvanized steel, the rocker style disconnect switch provides reliable electri­cal control. Wiring pigtails, using 12-gauge wires, are factory installed to simplify field wiring.
Fused
Similar in construction to the non-fused electrical disconnect. The fused disconnect is available in five models with equipment rated fuses to provide addi­tional circuit protection. The fuses are panel mounted to allow easy inspection and removal without removing the cover on the disconnect. CFD-10 - 10 amp rated fuse CFD-12 - 12 amp rated fuse CFD-15 - 15 amp rated fuse CFD-20 - 20 amp rated fuse CFD-25 - 25 amp rated fuse
Hydronic Loop Controller for Boiler/Tower Installations
The hydronic loop controller is a microprocessor based control panel for control of water loop heat rejector (tower), heat supplier (boiler), and/or water well pumps and circula­tion pumps. Includes audible and visual alarms, temperature indication, and add-on options of low switches, remote alarm sensor wells and pump alternator.
Motorized Outside Air Damper
A field installed motorized outside air damper is available to allow the introduction of fresh air into the conditioned space through an outside vent. The damper motor is pow­ered by 24 volts with a spring-close design in the event of a power failure. The damper blade and housing are con­structed of aluminum for corrosion resistance and the blade includes a neoprene gasket to prevent air infiltration during off cycles. The damper assembly is installed on the optional chassis back plate and a two-wire low voltage connection simplifies wiring. A concealed, chassis mounted rocker switch allows the damper to be disabled
37
Page 38
ENVISION CONSOLE INSTALLATION MANUAL
Unit Startup Checklist / Unit Startup Steps
Before Powering Unit, Check The Following:
• High voltage is correct and matches nameplate.
• Fuses, breakers and wire size correct.
• Low voltage wiring complete.
• Piping completed and water system cleaned and flushed.
• Air is purged from closed loop system.
• Isolation valves are open, water control valves or loop pumps wired.
• Condensate line open and correctly pitched.
• Transformer switched to 208V if applicable.
• Dip switches are set correctly, if applicable.
• Blower rotates freely
• Air filter is clean and in position.
• Service/access panels are in place.
• Return air temperature is between 50-80ºF heating and 60-95ºF cooling.
• Check air coil cleanliness to insure optimum performance. Clean as needed according to maintenance guidelines. To obtain maximum performance the air coil should be cleaned before startup. A 10-percent solution of dishwasher detergent and water is recommended for both sides of coil, a thorough water rinse should follow.
Startup Steps
Note: Complete the Equipment Start-Up/Commissioning Check Sheet during this procedure. Refer to thermostat operating instructions and complete the startup procedure.
1. Initiate a control signal to energize the blower motor. Check blower operation.
2. Initiate a control signal to place the unit in the cooling mode. Cooling setpoint must be set below room temperature.
3. Be sure that the compressor and water control valve or loop pump(s) are activated.
4. Verify that the water flow rate is correct by measuring the pressure drop through the heat exchanger using the P/T plugs and comparing to unit capacity data in specification catalog.
5. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables).
6. Check for an air temperature drop of 15°F to 25°F across the air coil, depending on the fan speed and entering water temperature.
7. Adjust the cooling setpoint above the room temperature and verify that the compressor and water valve or loop pumps deactivate.
8. Initiate a control signal to place the unit in the heating mode. Heating set point must be set above room temperature.
9. Check the temperature of both the supply and discharge water (Refer to Unit Operating Parameters tables).
10. Check for an air temperature rise of 20°F to 35°F across the air coil, depending on the fan speed and entering water temperature.
11. Adjust the heating setpoint below room temperature and verify that the compressor and water valve or loop pump deactivate.
12. During all testing, check for excessive vibration, noise or water leaks. Correct or repair as required.
13. Set system to desired normal operating mode and set temperature to maintain desired comfort level.
14. Instruct the owner/operator in the proper operation of the thermostat and system maintenance.
Note: Be certain to fill out and forward all warranty registration papers.
38
Page 39
ENVISION CONSOLE INSTALLATION MANUAL
Unit Operating Parameters
Single Speed Models
Entering
Water Temp
°F
Water Flow
GPM/Ton
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
09-18
Superheat
09-18
Subcooling
1.5 127 - 144 205 - 225 5 - 10 10 - 14 18 - 22 18 - 22
50
3.0 120 - 140 185 - 205 7 - 15 5 - 10 8 - 10 18 - 22
1.5 139 - 154 280 - 300 8 - 11 8 -12 18 - 22 18 - 22
70
3.0 137 - 152 250 - 270 9 - 12 7 - 11 8 - 10 18 - 22
1.5 143 - 158 360 - 380 8 - 11 9 - 13 18 - 22 16 - 20
90
3.0 141 - 156 330 - 350 9 - 12 8 - 12 8 - 10 16 - 20
Heating
Cooling
Entering
Water Temp
°F
Water Flow
GPM/Ton
Suction
Pressure
PSIG
Discharge
Pressure
PSIG
09-18
Superheat
09-18
Subcooling
1.5 73 - 79 279 - 304 7 - 13 2 - 6 7 -10 18 - 24
30
3.0 79 - 85 285 - 310 8 - 14 2 - 6 3 - 6 20 - 26
1.5 103 - 109 308 - 333 8 - 12 4 - 8 8 - 11 20 - 26
50
3.0 110 - 116 315 - 340 9 - 13 4 - 8 4 - 7 22 - 28
1.5 140 - 146 330 - 365 10 - 14 7 - 11 11 - 14 26 - 32
70
3.0 146 - 153 340 - 375 10 - 14 7 - 11 7 - 10 28 - 34
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB. Heating performance based on entering air temperature of 70º F DB.
Water Temp
Rise °F
Water
Temp Drop
°F
Air Temp
Drop °F DB
Air Temp
Rise °F DB
Unit Operating Limits
Operating Limits
Air Limits
Min. Ambient Air 45 7.2 45 7.2 Rated Ambient Air 80 26.7 70 21.1 Max. Ambient Air 100 37.8 85 29.4 Min. Entering Air 50 10.0 40 4.4 Rated Entering Air db/wb 80.6/66.2 27/19 68 20.0 Max. Entering Air db/wb 110/83 43/28.3 80 26.7
Water Limits
Min. Entering Water 30 -1.1 20 -6.7 Normal Entering Water 50-110 10-43.3 30-70 -1.1 Max. Entering Water 120 48.9 90 32.2
Notes:
Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependant upon three primary factors: 1) water temperature, 2) return air temperature, and 3) ambient temperature. When any of the factors are at the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation.
Cooling Heating
(°F) (°C) (°F) (°C)
39
Page 40
DEALER: PHONE #: DATE: PROBLEM: MODEL #:
ENVISION CONSOLE INSTALLATION MANUAL
SERIAL #:
COOLING CYCLE ANALYSIS
Unit Amp Draw:
°F
AIR
COIL
°F
Line Voltage:
EXPANSION
VALVE
LIQUID LINE
°F
PSI PSI
BRINE IN
Loop: Open
COAX
SOURCE
BRINE OUT
Startup/Troubleshooting Form
PSI
°F
Closed
REVERSING
VALVE
PSI = SAT F
°F°F
SAT °F=
SUCTION
COMPRESSOR
DISCHARGE
°
F
Superheat Subcooling
°
Heat of Extraction/Rejection = GPM x 500 (485 for water/antifreeze) x ∆T
Note: DO NOT hook up pressure gauges unless there appears to be a performance problem.
HEATING CYCLE ANALYSIS
Unit Amp Draw:
°F
AIR
COIL
°F
Line Voltage:
°
LIQUID LINE
EXPANSION
VALVE
F
PSI PSI
BRINE IN
Loop: Open
COAX
SOURCE
BRINE OUT
PSI
°F
Closed
SAT °F=
SUCTION
COMPRESSOR
REVERSING
VALVE
°F°F
DISCHARGE
°
F
PSI = SAT F
Superheat Subcooling
°
40
Page 41
ENVISION CONSOLE INSTALLATION MANUAL
Pressure Drop
Model GPM
1.2 1.0 0.9 0.8 0.7 0.6
09
12
15
18
1.8 2.3 2.2 2.0 1.9 1.8
2.5 3.8 3.7 3.5 3.3 3.1
1.5 0.9 0.8 0.7 0.6 0.5
2.3 1.7 1.5 1.4 1.3 1.1
3.5 3.0 2.7 2.5 2.4 2.2
2.0 1.7 1.6 1.5 1.4 1.3
3.0 3.3 3.2 3.0 2.9 2.8
4.5 5.7 5.5 5.3 5.1 4.9
3.0 1.7 1.6 1.5 1.4 1.3
4.0 4.1 4.0 3.9 3.7 3.6
5.5 7.9 7.6 7.4 7.2 6.9
Pressure Drop (psi)
30°F 50°F 70°F 90°F 110°F
12/14/09
41
Page 42
Preventive Maintenance
ENVISION CONSOLE INSTALLATION MANUAL
Water Coil Maintenance
1. Keep all air out of the water. An open loop system should be checked to ensure that the well head is not allowing air to infiltrate the water line. Lines should always be airtight.
2. Keep the system under pressure at all times. It is recommended in open loop systems that the water control valve be placed in the discharge line to prevent loss of pressure during off cycles. Closed loop systems must have positive static pressure.
Note: On open loop systems, if the installation is in an area with a known high mineral content (125 PPM or greater) in the water, it is best to establish with the owner a periodic maintenance schedule so the coil can be checked regularly. Should periodic coil cleaning be necessary, use standard coil cleaning procedures which are compatible with either the cupronickel or copper water lines. Generally, the more water flowing through the unit the less chance for scaling.
Other Maintenance
Filters
Filters must be clean to obtain maximum performance. They should be inspected monthly under normal operating conditions and be replaced when necessary. Units should never be operated without a filter.
Condensate Drain
In areas where airborne bacteria produce a slime in the drain pan, it may be necessary to treat chemically to minimize the problem. The condensate drain can pick up lint and dirt, especially with dirty filters. Inspect twice a year to avoid the possibility of overflow.
Blower Motors
Blower motors are equipped with sealed ball bearings and require no periodic oiling.
Air Coil
The air coil must be cleaned to obtain maximum performance. Check once a year under normal operating conditions and, if dirty, brush or vacuum (with a brush attachment) clean. Care must be taken not to damage the aluminum fins while cleaning.
CAUTION: Fin edges are sharp.
Replacement Procedures
Obtaining Parts
When ordering service or replacement parts, refer to the model number and serial number of the unit as stamped on the serial plate attached to the unit. If replacement parts are required, mention the date of installation of the unit and the date of failure, along with an explanation of the malfunctions and a description of the replacement parts required.
In-Warranty Material Return
Material may not be returned except by permission of au­thorized warranty personnel. Contact your local distributor for warranty return authorization and assistance.
42
Page 43
ENVISION CONSOLE INSTALLATION MANUAL
Notes
43
Page 44
ENVISION CONSOLE INSTALLATION MANUAL
Revision Guide
Pages: Description: Date: By:
All Updated With Aluminum Air Coils 02 Mar 2014 DS
44 Added Revision Guide 02 Mar 2014 DS
44
Page 45
Manufactured by WaterFurnace International, Inc. 9000 Conservation Way Fort Wayne, IN 46809 www.waterfurnace.com
IM1010CNA 03/14
©2014 WaterFurnace International, Inc., 9000 Conservation Way, Fort Wayne, IN 46809-9794. WaterFurnace has a policy of continual product research and development and
reserves the right to change design and specifi cations without notice.
Product: Envision Series Console Type: Geothermal/Water Source Heat Pumps Size: 0.75-1.5 Ton Document: Installation Manual
Loading...