Envirovent POWER-170, POWER-250 Installation And Wiring Instructions

POWER-170 & 250
Installation and Wiring Instructions
Installation and Wiring Instructions
POWER-170 & 250 CENTRIFUGAL EXTRACTOR FANS
Suitable for kitchen applications
Check that the product is in perfect condition while unpacking. Any fault or damage caused in origin is covered by the EnviroVent guarantee. Please make sure that the product corresponds to the one you have ordered and that the details on the instruction label fulfil your requirements.
IMPORTANT:
BE SURE TO HAVE READ AND UNDERSTOOD THESE INSTRUCTIONS BEFORE BEGINNING THE INSTALLATION PROCESS
SAFETY AND RECOMMENDATIONS:
SITING A POWER 170 OR 250
All wiring must comply with Building Regulations and the current I.E.E. Wiring Regulations (BS7671) or the equivalent standards for your country. The final installation should be examined and tested by a competent person.
Do not install near sources of heat in excess of 40°C. Do not site fan near obstacles which can obstruct airflow. Position away from any source of water spray. Do not site in a shower enclosure. Ducted Applications. In circumstances where an excessive amount of moisture is
present in the air, then a condensation trap will need to be installed in the exhaust duct. Horizontal ducts should fall away from the fan unit. Ducts passing through an unheated roof void should be insulated.
POWER-250 HP & POWER-170 HP. These fans are fitted with automatic electronic humidity sensors. They should ideally be mounted on an inside wall between the major moisture source and the door to the other rooms of the building. Do not site closer than 100mm to cupboards, etc. Do not site above a radiator or other heat source. We recommend the HP models are mounted as shown in Fig.
2.1.
INSTALLATION: POWER
170 & 250
Fig. 1
Fig. 3
Fig. 3
Fig. 2
Fig. 4
Fig. 5
Fig. 6
Fig. 7
FAN
Fig. 8
Fig. 9
FAN
FAN
Fig. 10
%RH
%RH
ref.9019012300
ref.9019012300
POWER-170 & 250 CENTRIFUGAL EXTRACTOR FANS
Suitable for kitchen applications
DESCRIPTION
Suitable for both ceiling and wall installation, the POWER fans may be adapted to an individual duct or to a communal ventilation system (Fig. 1).
The discharge port, situated at the side on the back of the extractor housing, enables it to be installed anywhere on the wall or ceiling, even in inaccessible corners (Figs.2 & 3).
NOTE: Pullcord models DP and HP should be mounted as shown in Fig.2.1 If NOT mounted as Fig.2.1, a support (not supplied ) must guide the pullcord so that it does not rub the fan body. The pullcord (if used) MUST be easy to operate.
INSTALLATION
IMPORTANT: ENSURE THAT THE MAINS SUPPLY IS SWITCHED OFF BEFORE MAKING ELECTRICAL CONNECTIONS.
- Making use of the template enclosed, make a 100mm diameter round hole in the wall or ceiling.
NOTE: A 115mm dia. hole is required if a wall sleeve is utilised.
- Drill the holes for the screws and insert the respective plugs in them. Take the extractor fan and withdraw the grille by pressing on the shoulders at the bottom (Fig.4).
- Remove retaining screw and lift off the terminal box cover (Fig.5).
-The installation may be made with the cable flush fitted by piercing either of the two notches provided for this (Fig.6.1), or else with surface wiring, using the side cable inlet (Fig.6.2).
- Insert some 150mm of cable into the extractor housing and pass it through the cable clamp.
- Fix the extractor to the wall. Arrange the foam rubber provided, around the discharge port so that it fits closely to the duct. Secure the extractor housing to the wall by inserting and tightening its screws.
WIRING
WARNING: This fan MUST NOT be earthed. It is double insulated. This fan MUST be connected to a 220-240V 50Hz AC single phase mains supply.
There must be a double pole isolator in the installation with a contact separation of at least 3mm. Connections depend upon the model of POWER fan being installed and the required mode of operation.
Ensure that the mains supply is SWITCHED OFF before starting any wiring.
POWER 170 S AND 250 S
Single speed fan. Controlled by remote switch (e.g. light switch or Auto -Sensor), Fig.7. The neon indicator is lit when the fan is running.
POWER 170 P2S AND 250 P2S
Dual speed and OFF. Low speed running for permanent “trickle” ventilation / High speed override / OFF, controlled by integral pullcord switch, Fig.8. Pullcord switch sequence – OFF, LOW, HIGH. The neon indicator is lit when the fan is running.
The POWER 250 P2S only, may alternatively be connected for remote switching. The remote switch (e.g. light switch) will switch between permanent LOW speed “trickle” ventilation an HIGH speed override. There is no OFF position with remote switching. Use Fig.9 for wiring to a remote switch, when the integral pullcord switch must be set for LOW speed and the pullcord cut off close to the fan.
POWER 170 HP AND 170HP
The fan contains an integral humidity sensor. In automatic mode the control switches the fan on at LOW speed when the room Relative Humidity (RH) reaches the set-point. The fan will continue to run until the room RH falls below the set-point. To prevent night time tripping the humidity sensing is inactive below 10ºC.
The integral pullcord or a remote switch (e.g. light switch) will switch between automatic humidity control and manual override at HIGH speed. The Light Emitting Diode (LED) indicator will be lit for manual override. The LED will NOT light under automatic humidity control, even if the fan is running. There is no permanent OFF position.
Use Fig.8 for wiring the manual override by the integral pullcord. Use Fig.9 for wiring the manual override to a remote switch, when the pullcord must be switched to the automatic position (LED off) and the cord cut off close to the fan.
The humidity control is factory set to switch on at about 72% RH.
To LOWER the set-point use a small screwdriver to turn the adjuster ANTI-CLOCKWISE, Fig.10. This makes the controller MORE sensitive to RH, i.e. it will come on at a lower RH.
To RAISE the set -point use a small screwdriver to turn the adjuster CLOCKWISE, Fig 10. This makes the controller LESS sensitive to RH, i.e. it will come on at a higher RH.
NOTES: 1. Upon installation it is possible that the humidity control will make the fan run
continuously until it has acclimatized to the environment.
2. The fan uses a „soft start feature i.e. the motor will take several seconds to
reach speed.
POWER 170 T AND 250 T
Single speed with overrun timer. The fan must be wired to a remote switch (e.g. light switch),Fig.9. When switched “ON”, the fan will operate at full speed, and will continue to run for a pre-set time after the switch is turned “OFF”. The timer is factory set at 20 minutes. To reduce the operating time, turn the adjuster in an anti -clockwise direction, Fig.10. The neon indicator is lit when the fan is running.
After wiring is completed, replace terminal block cover and grille. Turn on mains supply and check operation.
N.B. If used in a lighting circuit, for reliable operation, we recommend a tungsten filament lamp. The manufacturers of some fluorescent and low energy lighting systems indicate that these can interfere with electronic timer circuits.
CLEANING AND MAINTENANCE
IMPORTANT: DISCONNECT FROM THE MAINS SUPPLY BEFORE CARRYING OUT CLEANING OR MAINTENANCE
The POWER fans have a safety switch which automatically isolates the fan motor when the outer grille is removed. In this way, the fan may be cleaned without any risk of electric shocks.
For cleaning purposes, remove the outer grille (Fig.4) and, if your model is a POWER 250, take out the filter at the back of it as well. The filter and the grille may be cleaned by hand in hot soapy water and the extractor housing wiped with a damp cloth.
We recommend you do not try to remove any more parts than those mentioned as any tampering would automatically cancel the guarantee.
All regulations and requirements MUST be strictly followed to prevent hazards to life and property both during and after installation, and during any subsequent servicing and maintenance.
AFTER SALES SERVICE
We recommend you not to dismantle or remove any other parts than those mentioned, as any tampering would automatically cancel the guarantee. If you detect any fault, contact EnviroVent on 01423 810810.
Thank you for choosing EnviroVent - the fastest growing ventilation company in the UK.
And remember, if you have any problems please call our dedicated Technical Team on the Hotline 0845 27 27 810.
All EnviroVent products are designed to be recycled when they reach the end of their working life. To save the environment and to reduce landfill, please call EnviroVent on 0845 27 27 810 to arrange for the fan to be returned to the factory.
EnviroVent Ltd EnviroVent House Hornbeam Business Park Harrogate HG2 8PA
GUARANTEE The POWER range products are covered by a two year guarantee,
subject to the specified maintenance stated within this booklet. In the event of any failure of the fan within two years of supply- excluding only wilful or careless damage – we will exchange the fan free of charge.
EnviroVent Ltd EnviroVent House Hornbeam Business Park Harrogate HG2 8PA
Name and address of purchaser ………………………………………………... Model ………………………………………………………………………………. Date of purchase …………………………………………………………………. Dealer stamp
EnviroVent Ltd
Harrogate
Hg2 8PA
01423 810 810
info@envirovent.com
Ref. 9023007701
Loading...