Envirovent Mr Venty ECO2 Loft, Mr Venty ECO2 Twin Installation Manual For Users

ECO
2
Loft & ECO2 Twin
INSTALLATION GUIDE FOR ENGINEER / INSTALLER
1
2
Safety
IMPORTANT
Be sure to have read and understood these instructions before beginning the installation process.
Smoke Detectors
It is important that any open side of the plastic diffuser is not positioned within 1m of a smoke detector. If the diffuser cannot be repositioned, up to two sides of the diffuser may be closed off using the plastic blanking plate supplied (Loft only) so that the open sides face a minimum
1.5m unobstructed path away from the detector. In 3 floor properties a metal fire diffuser should be fitted at minimum of 1m from the detector (see page 9).
SAFETY AND RECOMMENDATIONS
All wiring must comply with Building
Regulations and the current I.E.E. Wiring Regulations (BS7671) or the equivalent standards for your country. The final installation should be examined and tested by a qualified electrician.
Precautions must be taken to avoid
the back-flow of gases into the dwelling from the open flue of gas or other fuel-burning appliances.
Make sure the mains supply
complies with the rating label for voltage, frequency and phase.
This appliance can be used by
children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.
3
Thank you for choosing EnviroVent
The fastest growing ventilation company in the UK.
You are about to install a product that is designed to outlast the life-cycle of the building. Once installed the unit will operate continuously for 5 years and beyond without a major service. Please therefore ensure that this product is treated with care and installed properly i.e. for the life of the building. If the unit is mishandled you might break it! This invalidates the warranty.
And remember, if you have any problems please call our dedicated Technical Team. We are always pleased to help and in an emergency will come out to site quickly, completely free of charge.
HOTLINE: 0345 27 27 810
Made in Harrogate UK
4
Pre-Installation Checklist
Check that the loft has adequate cross flow ventilation.
Check that all party walls are intact, seek advice if the wall is missing or broken.
Check that any flue which passes through the loft is not damaged, seek advice if the flue is in a poor state of repair.
Check for any flued appliance which may draw air from the loft, report to the client.
Check for any holes in the ceilings which may allow leakage of air to the loft and repair as appropriate.
Check that the water storage tank is covered.
Description Item
8 X FOAM PADS
4 X PENNY WASHERS
4 X PLASTER BOARD
PLUGS
4 X WOOD SCREWS
(10 X 1.5)
4 X WOOD SCREWS
(10 X 3)
4 X WOOD SCREWS
(8 X 1)
4 X WOOD SCREWS
(8 X 1.5)
ROLL OF INSULATION
TAPE
FIXING KIT
5
Installation Diagrams
STANDARD INSTALLATION
Also see page 8 for ECO2 Twin installation method, and page 9 for installations in 3 storey properties.
Installation diagram for the ECO
2
Loft Unit
UNIT DIMENSIONS
Dimensions of the ECO2 Loft Unit - 470 x 405 x 372mm
*Unswitched fuse spur fitted with 3 Amp fuse
230V A.C.
3 core mains lead
For fixing instructions, please refer to the fixing instructions
(Fig. 1) on page 6
405mm
Heater enable/disable switch (Heater version only) volt-free
*Subject to capacity, it is possible to connect the ECO2 Loft Unit with heater to a lighting circuit. If in doubt, wire through a ring main supply. Ensure the volt-free heater enable/disable switch is fitted in a suitable position for the user. This appliance must be earthed.
372mm
470mm
650mm x 50mm x 25mm batten
Ceiling joists
Contents for unit
1 x Cardboard template 1 x Diffuser 1 x Fixing kit (page 4) 1 x Unswitched fused spur 1m x Ø200mm Flexi duct
Additional contents for unit with heater
1 x Heater enable switch
6
Installation Instructions
FIRST STAGE
Position a dustsheet beneath the site you have chosen for cutting the hole for the diffuser. Protect your lungs with a mask. Enter the loft space with the ECO2 Loft and check there are no obstructions to your chosen position for the diffuser. Using the template supplied mark the hole for the diffuser and cut the 220mm hole in the plasterboard (see page 9 for additional ECO2 Twin installation instructions). N.B The unit is designed to be taken apart and re-assembled to overcome restricted access through small loft hatches.
SECOND STAGE
Position the ECO2 Loft on 50mm x 25mm wooden battens (not supplied) laid across the joists or raised platform if the insulate is thicker than the joists so that the ducting between the unit and the diffuser is not impeded. Lightly screw the drilled battens to the joist through the rubber mounts and metal penny washer provided. Fit the ducting to the unit spigot using half of the tape provided.
THIRD STAGE
Push ducting through the hole in the ceiling. Return to the hallway and connect the ducting onto the neck of the diffuser using rest of the tape provided. Ensure that the diffuser is aligned correctly with the walls of the hallway. Adjust if necessary. Fix the diffuser in position using plasterboard plugs and the screws provided.
FOURTH STAGE
The ECO2 Loft must only be installed by a competent person and should be connected to an electrical supply in accordance with the current electrical regulations. A disconnection device should be used in the fixed wiring.
FIFTH STAGE
Check the unit is working correctly. Set the unit’s controls according to the house size and check that the filters are securely in place.
SIXTH STAGE
Method of operation: Adjust the settings on the top of the unit by pressing the house setting button. By pressing the button, the correct ventilation rate for the size of the house can be selected i.e. if the unit is on SMALL / TRICKLE and the button is pressed, the unit will then switch to MEDIUM.
Similarly, if the unit is on BOOST and the button is pressed, the unit will then switch to SMALL / TRICKLE.
As a rule of thumb, the setting on the ECO2 Loft should match the number of bedrooms i.e. 1 - 4
PRESS BUTTON
LARGE
PRESS
BUTTON
PRESS
BUTTON
PRESS
BUTTON
SMALL / TRICKLE
MEDIUM BOOST
10 x 3 screw
Penny washer
Foam pad
Foam pad
50mm x 25mm batten with 20mm clearance hole
Existing joist
Fig.1 Fixing Instructions
7
Installation Instructions
SIXTH STAGE cont. - Wireless units only
To pair additional remote control switches:
1. Turn the unit off at the isolation point.
2. Restore power; for 20 seconds from restart the unit will be in pairing mode.
3. Press the remote button once within the 20 seconds and the control will pair to the unit.
4. Successful pairing is indicated by a green light on the control.
N.B: When the battery needs replacing, unscrew the front cover. The battery is located on the back of the cover.
Battery type - 3V Lithium, CR2032.
To change speed setting
Next press moves the unit to the
next speed and so on. When the
speed is chosen the LED remains
on for a few seconds
On commission the unit will
default to the trickle flow rate
with heater enable on
Press button once, to indicate
current fan speed and heater
status. LEDs stay on constant
for a few seconds
8
If the two LEDs situated just above the button flash alternately red and green (when it is pressed) the control will need to be reprogrammed. Call your maintenance company or EnviroVent for advice.
Heater enable ON
Auto LED stays on constant for a few seconds.
Heater enable OFF
Auto LED flashes for a few seconds.
Boost
(Green)
(Green)
Remote Control out of range (Red)
Heater enable
(Red)
Remote Control in range (Green)
LED Colours
Constant Red
Flashing Red
Constant Green
For heater enable/disable
Press button for five
seconds turns heater
enable off. LED will flash
red for a few seconds
Press button for five seconds
turns heater enable on. LED will show constant red for a
few seconds
9
ECO2 Twin Installation Instructions
Twin Spigot
This addition to the fixing instructions explains the methodology of installing the twin spigot system.
This variation to the ECO
2
Loft is necessary where:
The hallway is very small, particularly when there is limited heating in the house
The loft hatch fills the hallway ceiling
Air is required to be diffused into a remote zone, such as a bedroom
Cut two 105mm holes in the ceiling in the positions chosen where air is required to be delivered. Use the distance from the ECO
2
Loft Unit to each hole to balance/favour airflow:
i. Equal air supply required - diffusers equidistant from unit ii. More air supply required in hallway - short run to diffuser in the hall
(This is the recommended method of installation)
Connect the flexi ducting to the twin spigot and hold in position with a cable tie on each outlet.
ECO2 Twin Installation
Example of installation: More air is required in hall - shorter run
HALL
Vent One
BEDROOM
Vent Two
Contents for unit with heater
1 x Fixing kit 1 x Unswitched fuse spur 2 x Mini diffuser 1 x Cable tie 2m x 3m x 100mm Flexi duct
Additional contents for unit with heater
1 x Heater enable switch
10
Installation Instructions
Installations in 3 storey dwellings ECO
2
Loft
Fire Installation Kit
For installations in 3 storey dwellings, it is necessary to fit an ECO
2
Loft with a fire kit, EnviroVent part number: KIT-PIV-SMOKE. It is important to follow the installation instructions that come with the kit.
Installation checks and maintenance
The fire system should be checked at installation to ensure proper function. The diffuser should be periodically checked to ensure they have not been activated and that they are still delivering air into the property. In the case of a fire, the system should be thoroughly checked.
Smoke alarm
For installations in 3 storey dwellings the ECO
2
Loft should be wired in such a way that it shuts down completely when the smoke alarm system is triggered. This can be done by linking the ECO2 Loft to relay type smoke alarm (N/C), see schematic. When the relay is triggered by the alarm, power to the unit will be interrupted and the unit will stop. When the alarm resets, power will be resumed to the unit and the ECO2 Loft will resume working at its previous settings.
Ø125mm metal fire diffuser
ECO2 Twin
For installations in 3 storey dwellings, it is necessary to fit an ECO2 Twin with a fire kit, EnviroVent part number: KIT-PIV-SMOKE.
EnviroVent Ltd EnviroVent House Hornbeam Business Park Harrogate HG2 8PA
T / 0345 27 27 807 F / 01423 301 022 E / enquiries@envirovent.com W / envirovent.com
E&OE | MKT ENV246-V7-08.03.17
Due to our policy of continuous innovation and improvement EnviroVent reserves the right to alter products specification and appearance without notice.
We want to hear from you
Your feedback is important to us as we strive to improve our products, services, and overall customer experience. Please email us to help us serve you better: feedback@envirovent.com
AFTER INSTALLING THIS FAN PLEASE PASS ONTO END USER
DO NOT THROW AWAY
Delivering innovative and sustainable ventilation solutions worldwide
Please read carefully to ensure simple installation and a long trouble free life for the user.