Environmental Technology SST–2 Installation And Operation Manual

®
Freeze Protection Thermostats
MODELS SST–2
Part Number 22744
MANUAL
®
Installation and Operation Manual
Environmental Technology, Inc.
1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239 FAX (574) 233-2152 or (888) 234-4238 http://www.networketi.com/
22804 11/07 (800) 234-4239 http://www.networketi.com Environmental Technology, Inc.
Model SST–2
2 of 12 Environmental Technology, Inc.
11/07 22804(800) 234-4239http://www.networketi.com
Safety
Make all electrical connections in compliance with the National Electric Code (NFPA 70) and local electrical code. If you have questions concerning the installation or application, contact Customer Service.
Additional Information
More information is regularly made available through our website, www.networketi.com. Please visit us online for datasheets, manuals, white papers, technical articles and more. The most current and up to date version of this and every other manual for our products can be found in Acrobat (pdf) format to view online or to print. This is to assist you in installing and using our products to the best effect possible. If you have any comments about this or any other material from Environmental Technology please contact us.
Contacting Environmental Technology
For assistance, contact Customer Service. Offi ce hours are 8:00 AM until 5:00 PM ET.
Voice: (800) 234.4239 (USA and Canada) or (574) 233.1202 (elsewhere)
Fax: (888) 234.4238 (USA and Canada) or (574) 233.2152 (elsewhere)
E-mail: helpdesk@networketi.com
Mail: Environmental Technology, Inc.
1850 North Sheridan Street
South Bend, IN 46628
Model SST–2
General
Description
The C-UL-US listed SST–2 Freeze Protection Thermostat replaces electromechanical thermostats in cost-sensitive applications requiring ground fault equipment protection (GFEP). The SST is classifi ed to UL and CSA safety standards by UL for use in temperature-regulation applications. It is the ideal low-cost thermostat for areas not subject to mechanical abuse.
Specifi cations
General
Area of use Nonhazardous locations Approvals
Type 873 Temperature Regulating Equipment
109R
Enclosure
Protection NEMA 4x Cover attachment Polycarbonate cover, machine screws Entries 1 × 3/4" entry (bottom right) for NEC Class 2 sensor connections
3 × 1-1/16" entries (bottom left and left) for supply, load power and (right) NEC Class
2 alarm relay connections
Material Polycarbonate Mounting Wall mounted
22804 11/07 (800) 234-4239 http://www.networketi.com 3 of 12Environmental Technology, Inc.
Model SST–2
Front Panel Interface
Status indicator SUPPLY (green) power applied
SUPPLY (green, fl ashing) bad thermistor HEAT (yellow) call for heat GFEP (red) ground fault condition GFEP (red, fl ashing) failed GFEP test GFEP (red, fl ashing, rapid) GFEP test in progress
Remote Interface
Alarm relay Isolated SPDT 1 AMP Class 2 contact Summary alarms No Power
Ground Fault Condition GFEP function test failure Bad or missing Thermistor
Control
Supply voltage 120, 208, 240 or 277 volts, single phase (automatically selected) Contact type Two Form A DPST Maximum Ratings Voltage: 277 VAC
Current: 30 amps
Temperature Sensor
Set point 40°F (4.4°C) Dead band 2°F (1°C) Sensor type Thermistor network Circuit type NEC Class 2 Lead Length Up to 2,000' (610m) using 12 AWG 2-wire jacketed cable
Up to 500' (152m) using 18 AWG 2-wire jacketed cable
Ground Fault Equipment Protection (GFEP)
Set point 30 mA Automatic self test Mode A: Verifi es GFEP function before contactors operate
Mode B: Verifi es GFEP function every 24 hours
Manual test/reset TEST/RESET switch on front panel
Environmental
Operating temperature −40°F to 130°F (−40°C to 55°C) Storage temperature −67°F to 167°F (−55°C to 75°C)
Installation
Unpacking
Immediately inspect the packing material for damage. Unpack the SST–2, taking care not to damage the packaging material. Save the packaging material until normal operation has been established. If the unit must be returned, take care to ensure that it is repackaged as it was received.
Packing List
22744 SST–2 Freeze Protection Thermostat 19272 Temperature Sensor 22804 SST–2 Installation and
Operation Manual
4 of 12 Environmental Technology, Inc.
11/07 22804(800) 234-4239http://www.networketi.com
Initial Inspection
Inspect the SST for shipping damage. If any of the following problems are
found contact the Customer Service Department.
• Contents incomplete or incorrect
• Internal or external mechanical damage Customer service is available between 8:00 a.m. and 5:00 p.m. ET at
(574) 233-1202 or (800) 234-4239. In the event of shipping damage, keep the packing materials for inspection by the carrier. Normally, Environmental Technology, Inc. will repair or replace the SST without waiting for the claims settlement.
Location
Housed in a NEMA 4X rated enclosure, the SST freeze protection thermostat
can be mounted in either indoor or outdoor environments. The SST was designed to operate over an ambient temperature range of −40° to 136°F (−40° to 58°C).
Using the integral mounting fl anges, the SST is intended to be installed
on a fi xed, fl at, vertical surface. The mounting fl anges accommodate fasteners.
The SST freeze protection thermostat nonmetallic enclosure is furnished with
3
/4" (21mm) conduit entries. The lower conduit entries provide for line voltage
two supply branch circuit conductors. The conduit entry at the top-left of the enclosure is for heater load branch circuit conductors. The installed weather-tight fi tting is for the low voltage, NEC Class 2, temperature sensor. The Temperature Sensor may be located up to 2,000' (610m) from the SST.
1
/4" (6mm)
Model SST–2
Supply Voltage
The SST freeze protection thermostat operates from 120, 208, 240 or 277 VAC
at 50/60 Hz. For line supply and load connections, use 10 AWG or larger wires rated for at least 75°C (167°F) at 300 VAC.
Contactor Ratings
The heater contactor provides two (2) Form A (DPST) defi nite purpose contacts
rated for up to 30 amp AC heater loads at voltages at or below 277 VAC.
77/16"
(189mm)
11/
16”
(27mm)
41/4"
(108mm)
Conduit Entry
11/
16”
(27mm)
Conduit Entry
3
/8" (10mm) Ø
Temperature Sensor
Figure 1: SST–2 dimensions. See Appendix A.
22804 11/07 (800) 234-4239 http://www.networketi.com 5 of 12Environmental Technology, Inc.
17/16" (37mm)
20' (6m) Sensor Cable,
3
/16" (5mm) Ø
Model SST–2
CONNECT LINE 2 (OR NEUTRAL) FROM INCOMING POWER TO BOTH LINE 2 RED AND NEUTRAL/WHITE INSIDE SST2 ENCLOSURE. THIS CONNECTION PROVIDES POWER TO THE CONTROLLER.
FOR REMOTE
ALARM
CONTROL VIA
ISOLATED
SPOT CLASS 2
CONTACT
CONNECT BLACK SENSOR WIRE TO
ONE BLUE WIRE IN SST2
ENCLOSURE, AND CONNECT RED
SENSOR WIRE TO THE OTHER BLUE
WIRE. (PRE-WIRED IN AMBIENT
SST2-AMB MODEL)
208/240VAC
50/60 HZ
SAFETY GROUND
PHASE PHASE
CONNECT LINE 2 (OR NEUTRAL) FROM INCOMING POWER TO BOTH LINE 2 RED AND NEUTRAL/WHITE INSIDE SST2 ENCLOSURE. THIS CONNECTION PROVIDES POWER TO THE CONTROLLER.
120, 277VAC
50/60 HZ
SAFETY GROUND
NEUTRAL
PHASE
SAFETY GROUND
FOR REMOTE ALARM ONLY
CONNECT BLACK SENSOR WIRE TO ONE BLUE WIRE IN SST2 ENCLOSURE, AND CONNECT RED SENSOR WIRE TO
THE OTHER BLUE WIRE
IN AMBIENT SENSING SST2-AMB
MODEL, SENSOR IS MOUNTED ON
SIDE OF ENCLOSURE AND PRE-
WIRED. FOR PIPE SENSING
APPLICATIONS INSTALL SENSOR
ON OPPOSITE SIDE OF PIPE
FROM HEATER CABLE. CABLE
CAN BE CUT SHORTER OR
REQUIRED. FOR EXTENSION USE
2C/ #18 JACKETED CABLE.
FOR REMOTE
ALARM CONTROL
VIA ISOLATED
SPOT CLASS 2
CONTACT
EXTENDED UP TO 500' IF
6 of 12 Environmental Technology, Inc.
11/07 22804(800) 234-4239http://www.networketi.com
NEC Class 2 Low Voltage Connections
All low voltage wiring shall use 18 AWG or greater stranded conductors with thermoplastic insulation rated for at least 75°C (194°F) at 300 VAC. The temperature sensor is supplied with a 20' (6m) 2-wire jacketed cable lead. The temperature sensor lead may be up to 500' (152.4m) using 18 AWG 2-wire jacketed cable, or up to 2,000' (609.6m) using 12 AWG 2-wire jacketed cable.
Temperature Sensor
The Temperature Sensor is required for the operation of the SST. The Temperature Sensor connects via wire nuts to the two blue wires in the SST enclosure. It does not matter which sensor wire is connected to which blue wire in the enclosure. The sensor should be located near the heater being controlled and is used to monitor its temperature.
Operating Instructions
Power On Startup Test
When power is applied to the SST–2 freeze protection thermostat, the LED indicator lights in the SST enclosure will cycle for two seconds and then turn off, except for the green SUPPLY indicator, which will remain lit whenever the SST senses supply power.
Next, the SST–2 freeze protection thermostat performs a self-test of the ground fault circuitry. This is the same test automatically performed approximately every 24 hours. Failure of the ground fault circuitry self-test will disable the SST; call Customer Service.
Model SST–2
Operation
The SST–2 freeze protection thermostat does not require user attention during normal operation.
Status indicator SUPPLY (green) power applied
SUPPLY (green, fl ashing) bad thermistor HEAT (yellow) call for heat GFEP (red) ground fault condition GFEP (red, fl ashing) failed GFEP test GFEP (red, fl ashing, rapid) GFEP test in progress
GFEP Test
To manually verify the operation of the ground fault circuitry, momentarily press the GFEP TEST/RESET switch on the SST. This should not normally be necessary as the SST will test the ground fault circuitry when power is applied to the unit and once approximately every 24 hours as long as power is supplied to the unit.
GFEP Reset
In the event that a ground fault condition is detected by the SST heaters will be turned off, if on, and heaters will be prevented from further operation until the ground fault condition has been reset. The red GFEP Fault indicator will be continuously on as long as there is power to the SST and a ground fault condition
22804 11/07 (800) 234-4239 http://www.networketi.com 7 of 12Environmental Technology, Inc.
Model SST–2
remains. The ground fault condition will be persistent and will be remembered by the SST even if the unit loses power.
To clear the ground fault condition momentarily press the GFEP TEST/RESET
switch on the SST.
Maintenance
The SST–2 does not require routine maintenance.
For technical help, questions or comments concerning this product or any Environmental Technology, Inc. prod ucts contact the Customer Service Department between 8:00am and 5:00pm ET at:
Voice: 800.234.4239 (USA and Canada) or 574.233.1202 (elsewhere)
Fax: 888.234.4238 (USA and Canada) or 574.233.2152 (elsewhere)
E-mail: helpdesk@networketi.com
8 of 12 Environmental Technology, Inc.
11/07 22804(800) 234-4239http://www.networketi.com
Appendix A. SST–2 Dimensions.
41/4"
(108mm)
77/16"
(189mm)
Model SST–2
11/
16”
(27mm)
Conduit Entry
11/
16”
(27mm)
Conduit Entry
3
/8" (10mm) Ø
Temperature Sensor
22804 11/07 (800) 234-4239 http://www.networketi.com 9 of 12Environmental Technology, Inc.
17/16" (37mm)
20' (6m) Sensor Cable,
3
/16" (5mm) Ø
Model SST–2
Appendix B. SST–2 Wiring Diagram.
CONNECT LINE 2 (OR NEUTRAL) FROM INCOMING POWER TO BOTH LINE 2 RED AND NEUTRAL/WHITE INSIDE SST2 ENCLOSURE. THIS CONNECTION PROVIDES POWER TO THE CONTROLLER.
FOR REMOTE
ALARM
CONTROL VIA
ISOLATED
SPOT CLASS 2
CONTACT
CONNECT BLACK SENSOR WIRE TO
ONE BLUE WIRE IN SST2
ENCLOSURE, AND CONNECT RED
SENSOR WIRE TO THE OTHER BLUE
WIRE. (PRE-WIRED IN AMBIENT
SST2-AMB MODEL)
10 of 12 Environmental Technology, Inc.
11/07 22804(800) 234-4239http://www.networketi.com
Appendix C. SST–2 Wiring.
Model SST–2
208/240VAC
50/60 HZ
SAFETY GROUND
PHASE PHASE
CONNECT LINE 2 (OR NEUTRAL) FROM INCOMING POWER TO BOTH LINE 2 RED AND NEUTRAL/WHITE INSIDE SST2 ENCLOSURE. THIS CONNECTION PROVIDES POWER TO THE CONTROLLER.
120, 277VAC
50/60 HZ
SAFETY GROUND
NEUTRAL
PHASE
SAFETY GROUND
FOR REMOTE ALARM ONLY
FOR REMOTE
ALARM CONTROL
VIA ISOLATED
SPOT CLASS 2
CONTACT
CONNECT BLACK SENSOR WIRE TO ONE BLUE WIRE IN SST2 ENCLOSURE, AND CONNECT RED SENSOR WIRE TO
THE OTHER BLUE WIRE
IN AMBIENT SENSING SST2-AMB
MODEL, SENSOR IS MOUNTED ON
SIDE OF ENCLOSURE AND PRE-
WIRED. FOR PIPE SENSING
APPLICATIONS INSTALL SENSOR
ON OPPOSITE SIDE OF PIPE
FROM HEATER CABLE. CABLE
CAN BE CUT SHORTER OR
EXTENDED UP TO 500' IF
REQUIRED. FOR EXTENSION USE
2C/ #18 JACKETED CABLE.
22804 11/07 (800) 234-4239 http://www.networketi.com 11 of 12Environmental Technology, Inc.
Model SST–2
ORDERING INFORMATION
Order Number Description
22744 Model SST–2 Freeze Protection Thermostat 19272 Temperature Sensor (included)
LIMITED WARRANTY
ETI’s two year limited warranty covering defects in workmanship and materials applies. Contact Cus tom er Service for complete warranty information.
DISCLAIMER
Environmental Technology, Inc. makes no representations or warranties, either expressed or implied, with respect to the contents of this publication or the products that it describes, and specifi cally disclaims any implied warranties of mer chant abil i ty or fi tness for any particular purpose. En vi ron men tal Technology, Inc. reserves the right to revise this pub li ca tion, and to make changes and im prove ments to the products described in this publication, with out the ob li ga tion of En vi ron men tal Tech nol o gy, Inc. to notify any person or or ga ni za tion of such revisions, chang es or improvements.
The ETI logo, Snow Switch, Floorstat, Tracon, We Manage Heat, APS, RCU, CIT, GIT, SIT are reg is tered trademarks of En vi ron men tal Technology, Inc. Copyright © 2006 Environmental Technology, Inc. All rights reserved.
12 of 12 Environmental Technology, Inc.
11/07 22804(800) 234-4239http://www.networketi.com