Enviro WINDSOR 50-1578 User Manual

SHERWOOD INDUSTRIES IS AN ENVIRONMENTALLY RESPONSIBLE COMPANY. THIS MANUAL IS PRINTED ON RECYCLED
PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE
PAPER.
PELLET STOVE
WINDSOR
TECHNICAL MANUAL
Contact your building or fire officials about restrictions and
installation inspection requirements in your area.
PLEASE READ THIS ENTIRE MANUAL BEFORE INSTALLATION AND USE OF THIS PELLET-BURNING ROOM HEATER. FAILURE TO FOLLOW THESE INSTRUCTIONS
COULD RESULT IN PROPERTY DAMAGE, BODILY INJURY OR EVEN DEATH.
50-1578
Table of Contents
Safety Warnings & Recommendations.........................................................................3
Installation...............................................................................................................6
Rating Label Location.....................................................................................6
Deciding Where to Locate your Pellet Appliance................................................6
Removing Pellet Stove From Pallet...................................................................6
Dimensions & Specications............................................................................7
Clearances to Combustibles.............................................................................8
Alcove Clearances...........................................................................................8
Vent Termination Requirements.......................................................................9
Exhaust And Fresh Air Intake Locations..........................................................10
Outside Fresh-Air Connection.........................................................................10
Corner Through Wall Installation....................................................................11
Horizontal Exhaust Through Wall Installation..................................................11
Vertical Rise with Horizontal Termination Installation (Recommended)..............13
Through Concrete Wall With Vertical Rise Installations.....................................13
Inside Vertical Installations............................................................................14
Outside Vertical Installations..........................................................................15
Hearth Mount Installation..............................................................................16
Installation with Exterior Mounted Exhaust Blower...........................................17
Through Wall Vertical Installation With Exhaust Blower....................................19
Thermostat Installation.................................................................................20
Slider/Damper Setting...................................................................................20
Installation..............................................................................................................21
Troubleshooting......................................................................................................22
Wiring Diagram.......................................................................................................25
Parts List - Components...........................................................................................26
Parts List - Cast.......................................................................................................28
Parts Diagram - Components....................................................................................29
Parts Diagram - Steel & Cast....................................................................................30
Installation Data Sheet............................................................................................31
2
Safety Warnings & Recommendations
* This manual is designed for the technician in conjunction with the owner’s manual. *
Please read this entire Owner’s Manual before installing or operating your ENVIRO Pellet Stove. Failure to follow these instructions may result in property damage, bodily injury or even death. Any unauthorized modification of the appliance or use of replacement parts not recommended by the manufacturer is prohibited. All national and local regulations and European Standards shall be complied with when installing this appliance.
Caution: Do not connect to any air distribution duct or system.
Warning: Parts of the appliance, especially the external surfaces, will be hot to touch when in operation so use due care and the fire gloves provided. Never place wood, paper, furniture,
drapes or other combustible materials within 80cm (31”) of the front of the unit, 20cm (7”) from each side, and 10cm (4”) from the back of the unit. Do not let children or pets touch it when it is hot.
To prevent the possibility of a fire, ensure that the appliance is properly installed by adhering to the installation instructions. An ENVIRO dealer will be happy to assist you in obtaining information with regards to your local building codes and installation restrictions.
FIRE EXTINGUISHER AND SMOKE DETECTION: All homes with a pellet burning stove should have at least one fire extinguisher in a central location known to all in the household. Smoke detectors should be installed and maintained in the room containing the stove when installing and operating a pellet burning appliance. If it sounds the alarm, correct the cause but do not deactivate. You may choose to relocate the smoke detection devise within the room; DO NOT REMOVE THE SMOKE DETECTOR FROM THE ROOM.
CHIMNEY OR RUN AWAY FIRE: Call local fire department. Close the draft fully. Extinguish the fire in the burn pot liner with a cup of water and close the door. Examine the flue pipes, chimney, attic, and roof of the house, to see if any part has become hot enough to catch fire. If necessary, spray with fire extinguisher or water from the garden hose. IMPORTANT: Do not operate the stove again until you are certain the chimney and its lining have not been damaged.
FUEL: This pellet stove is designed and approved to only burn wood pellet fuel with up to 3% ash content. Dirty fuel will adversely affect the operation and performance of the unit and may void the warranty. Check with your dealer for fuel recommendations. THE USE OF CORDWOOD IS PROHIBITED BY LAW. When filling fuel hopper, open lid on top of unit, check hopper for foreign objects, empty the bag into the hopper, DO NOT OVER FILL, and ensure hopper lid closes completely. DO NOT use this appliance as an incinerator. DO NOT use unsuitable and non recommended fuels, including liquid fuels.
KEEP ASH PAN FREE OF RAW FUEL. DO NOT PLACE UNBURNED OR NEW PELLET FUEL IN ASH PAN. A fire in the ash pan may occur.
SOOT: Operation of the stove with insufficient combustion air will result in the formation of soot which will collect on the glass, the heat exchanger, the exhaust vent system, and may stain the outside of the house. This is a dangerous situation and is inefficient. Frequently check your stove and adjust the slider/ damper as needed to ensure proper combustion. See: “SLIDER/DAMPER SETTING”.
3
Safety Warnings & Recommendations
CLEANING: There will be some build up of fly ash and small amounts of creosote in the exhaust. This will vary due to the ash content of the fuel used and the operation of the stove. It is advisable to inspect and clean the exhaust vent semi-annually or every two tons of pellets. The appliance, flue gas connector and the chimney flue require regular cleaning. Check them for blockage prior to re-lighting after a prolonged shut down period.
ASHES: Disposed ashes should be placed in a metal container with a tight fitting lid. The closed container of ashes should be on a non-combustible surface, well away from all combustible materials pending final disposal. If the ashes are disposed of by burial in soil or otherwise locally dispensed, they should be retained in the closed container until all cinders have been thoroughly cooled.
IMPORTANT: The door and ash drawer cover must be kept closed except during ignition, refueling and removal of residue material to prevent fume spillage.
GLASS: Do not abuse the glass by striking or slamming the door. Do not attempt to operate the stove with broken glass. The stove uses ceramic glass. Replacement glass must be purchased from an ENVIRO dealer. Do not attempt to open the door and clean the glass while the unit is in operation or if glass is hot. To clean the glass, use a soft cotton cloth and mild window cleaner, gas or wood stove glass cleaner, or take a damp paper towel and dip into the fly ash. This is a very mild abrasive and will not damage the glass.
ELECTRICAL: The use of a surge protected power bar is recommended. The unit must be grounded. The grounded electrical cord should be connected to a standard 220-240 volts (2.0-2.3 Amps), 50 hertz electrical outlet and also must be accessible. If this power cord should become damaged, a replacement power cord must be purchased from the manufacturer or a qualified ENVIRO dealer. Be careful that the electrical cord is not trapped under the appliance and that it is clear of any hot surfaces or sharp edges. This unit’s maximum power requirement is 525 watts.
OPERATION: The door and ash drawer cover must be kept closed securely when the unit is in operation to prevent fume spillage and for proper and safe operation of the pellet stove. Also ensure all gaskets on the door are checked and replaced when necessary.
CAUTION: When operating during adverse weather, if the unit exhibits dramatic changes in combustion stop using the unit immediately.
INSTALLATION: Contact your local building or fire official to obtain a permit and any information on installation restrictions and inspection requirements for your area. All local regulations, including those referring to national and European Standards need to be complied with when installing this appliance.
Be sure to maintain the structural integrity of your home when passing a vent through walls, ceilings, or roofs. It is recommended that the unit be secured into its position in order to avoid any displacement. This appliance must be installed on a floor with an adequate load bearing capacity. If an existing construction doesn’t meet these prerequisite, suitable measures (e.g. load distributing plate) shall be taken to achieve it.
DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.
DO NOT CONNECT THIS UNIT TO A CHIMNEY FLUE SERVING ANOTHER APPLIANCE.
4
Safety Warnings & Recommendations
FRESH AIR: Outside Fresh Air connection is optional. Fresh Air must be connected to all units installed in “Air Tight Homes” or where required by local codes.
Consider all large air moving devices when installing your unit and provide room air accordingly. NOTE: Extractor fans when operating in the same room or space as the appliance, may cause problems. Limited air for combustion may result in poor performance, smoking and other side effects of poor combustion.
The stove’s exhaust system works with negative combustion chamber pressure and a slightly positive chimney pressure. It is very important to ensure that the exhaust system be sealed and airtight. The ash pan and viewing door must be locked securely for proper and safe operation of the pellet stove.
Do not burn with insufficient combustion air. A periodic check is recommended to ensure proper combustion air is admitted to the combustion chamber. Setting the proper combustion air is achieved by adjusting the slider damper located on the left side of the stove.
Minor soot or creosote may accumulate when the stove is operated under incorrect conditions such as an extremely rich burn (black tipped, lazy orange flames).
If you have any questions with regards to your stove or the above-mentioned information, please feel free to contact your local dealer for further clarification and comments.
SINCE SHERWOOD INDUSTRIES LTD. HAS NO CONTROL OVER THE INSTALLATION OF YOUR STOVE, SHERWOOD INDUSTRIES LTD. GRANTS NO WARRANTY IMPLIED OR STATED FOR THE INSTALLATION OR MAINTENANCE OF YOUR STOVE. THEREFORE, SHERWOOD INDUSTRIES LTD. ASSUMES NO RESPONSIBILITY FOR ANY CONSEQUENTIAL DAMAGE(S).
SAVE THIS INSTRUCTION MANUAL FOR FUTURE REFERENCE
5
Installation
Hold-down brackets.
RATING LABEL LOCATION:
The rating label is located on the back of the hopper.
DECIDING WHERE TO LOCATE YOUR PELLET APPLIANCE:
1. Check clearances to combustibles (see INSTALLATION - CLEARANCES TO COMBUSTIBLES and INSTALLATION - ALCOVE CLEARANCES).
2. Do not obtain combustion air from an attic, garage or any unventilated space. Combustion air may be obtained from a ventilated crawlspace.
3. Do not install the stove in a bedroom.
4. You can vent the stove through an exterior wall behind the unit or connect it to an existing masonry or metal chimney (must be lined if the chimney is over 6” (15 cm) diameter, or over 28 inches² (180 cm²) cross sectional area). An interior vent can be used with approved pipe passing through the ceiling and roof.
5. Locate the stove in a large and open room that is centrally located in the house. This will optimize heat circulation.
6. The power cord is 8 feet (2.43 m) long and may require a grounded extension cord to reach the nearest electrical outlet.
REMOVING PELLET STOVE FROM PALLET:
Remove screws from the two (2) hold-down brackets that secure the Windsor to the pallet. Lift the brackets up to unhook from the chassis.
Figure 1: Removing Freestanding Stove From the Pallet.
6
271/8"
(689mm)
253/4"
(653mm)
257/8"
(659mm)
153/8"
(390mm)
141/4"
(360mm)
241/8"
(614mm)
DIMENSIONS & SPECIFICATIONS:
Installation
Figure 2: Windsor Dimensions.
Table 1: Windsor Specifications.
Classification Testing Standard Description
Class I IP-20 EN14785:2006 Residential Wood Pellet Heater
Voltage Current Frequency
220 - 240 V 2.0 - 2.3 Amps 50 Hz
Maximum Power Requirement Fuel type Calorific value of Pellet used
525W (1793 BTU/hr) wood pellets - 6mm (”) dia. ≥ 5.10 kWh/kg (≥ 8000 BTU/lb)
Maximum Flue Gas Temperature Mean Flue Gas Temperature Mean Flue Gas Temperature (Reduced)
230°C (446°F) 180.5°C (357°F) 128.5°C (263°F)
Nominal Heat Output CO emissions from Combustion Energy Efficiency
6.9 KWh (23544 BTU) 0.035% 82.6%
Reduced Heat Output CO emissions from Combustion (Reduced Output) Energy Efficiency (Reduced Output)
2.3 KWh (7848 BTU) 0.052% 77.3%
CO2 at Nominal Output Nominal Fuel Consumption Rate Unit with Full Hopper
8.16% 1.65 Kg/hr (3.64 lb/hr)* ~ 151kg (333lb)
CO2 at Reduced Output Fuel Consumption Rate (Reduced Output) Hopper Capacity
4.142% 0.59 Kg/hr (1.30 lb/hr)* ~ 20kg (45lb)
*Note: Consumption will vary with the type of fuel used.
7
Minimum Width
1220mm (48")
Minimum Height
1220mm (48")
Maximum Depth
915mm (36")
Back wall
Side wall
Adjacent
wall
100mm
(4")
100mm (4")
200mm
(77/8 inches)
150mm
(6")
Floor Protection
Installation
CLEARANCES TO COMBUSTIBLES:
These dimensions are minimum clearances but it is recommended that you ensure sufficient room for serving, routine cleaning and maintenance.
Side wall to unit 200mm (7 inches) Back wall to unit 100mm (4 inches) Corner to unit 100mm (4 inches) In Front of unit 800mm (31” inches)
This pellet stove requires floor protection. The floor protection must be non-combustible, extending beneath the stove the full width and depth of the unit including 150mm (6“) in front for ember protection.
Hearth Pad Size: Width: 650 mm (25 ”) Depth: 815mm (32 ”)
ALCOVE CLEARANCES:
This unit may be installed in an alcove. Maintain the clearances to combustibles shown in Figure 4.
Minimum Alcove width 1220mm (48 inches) Minimum Alcove height 1220mm (48 inches) Maximum Alcove depth 915mm (36 inches)
Install vent at clearances specified by the vent manufacturer.
Figure 3: Minimum Clearances to Combustibles for
Freestanding Windsor.
8
Figure 4: Alcove Clearances.
Installation
Air Supply Inlet
Gas Meter
Restriction Zone
(Termination not allowed)
Termination Cap
G
G
Opens
Opens
Opens
D
F
B
B
A
I
H
K
G
G
L
C
E
VENT TERMINATION REQUIREMENTS:
IT IS RECOMMENDED THAT YOUR PELLET STOVE BE INSTALLED BY AN AUTHORIZED DEALER/INSTALLER.
Table 2: Use in conjunction with Figure 5 for allowable exterior vent termination locations.
Letter Minimum Clearance Description
A 24 in (61 cm) Above grass, top of plants, wood, or any other combustible materials.
B 48 in (122 cm) Beside/below any door or window that may be opened. (18” (46 cm) if outside
fresh air install.)
C 12 in (30 cm) Above any door or window that may be opened. (9” (23 cm) if outside fresh air
install.)
D 24 in (61 cm) To any adjacent building, fences and protruding parts of the structure.
E 24 in (61 cm) Below any eave or roof overhang
F 12 in (30 cm) To outside corner.
G 12 in (30 cm) To inside corner, combustible wall (vertical and horizontal terminations).
H 3 ft (91 cm) within a height
of 15 ft (4.5 m) above the
meter/regulator assembly
I 3 ft (91 cm) From any forced air intake of other appliance
J 12 in (30 cm) Clearance to non-mechanical air supply inlet to building, or the combustion air
K 24 in (61 cm) Clearance above roof line for vertical terminations.
L 7 ft (2.13 m) Clearance above paved sidewalk or paved driveway located on public property.
To each side of center line extended above natural gas or propane meter/ regulator assembly or mechanical vent.
inlet to any appliance.
1. Do not terminate the
vent in any enclosed or semi-enclosed areas such as a carport, garage, attic, crawlspace, narrow walkway, closely fenced area, under a sundeck or porch, or any location that can build up a concentration of fumes such as stairwells, covered breezeway, etc.
2. Vent surfaces can become
Figure 5: Use in conjunction with Table 2 for allowable exterior vent termination
locations.
hot enough to cause burns if touched by children. Non-combustible shielding or guards may be required.
3. Termination must exhaust above the inlet elevation. It is recommended that at least five feet of vertical pipe be installed outside when the appliance is vented directly through a wall, to create some natural draft to prevent the possibility of smoke or odor during appliance shut down or power failure. This will keep exhaust from causing a nuisance or hazard from exposing people or shrubs to high temperatures. In any case, the safest and preferred venting method is to extend the vent through the roof vertically.
4. Distance from the bottom of the termination and grade is 12” (30 cm) minimum. This is conditional upon the plants and nature of grade surface. The exhaust gases are hot enough to ignite grass, plants and shrubs located in the vicinity of termination. The grade surface must not be lawn.
5. If the unit is incorrectly vented or the air to fuel mixture is out of balance, a slight discoloration of the exterior of the house might occur. Since these factors are beyond the control of Sherwood Industries Ltd, we grant no guarantee against such incidents.
NOTE: Venting terminals shall not be recessed into walls or siding.
9
10
1
/2
(265 mm)
8
1
/2
(216 mm)
12
7
/8
(326 mm)
8
3
/8
(214 mm)
4
3
/8
(112 mm)
Installation
 
 




EXHAUST AND FRESH AIR INTAKE LOCATIONS:
INSTALL VENT AT CLEARANCES SPECIFIED BY THE VENTING MANUFACTURER
10
Figure 6: Inlet and Outlet Location.
EXHAUST
Base of unit to center of flue 270 mm (10 ”) Side of unit to center of flue 308 mm (12 ”) Center of unit to center of flue 19 mm (”)
FRESH AIR INTAKE.
Base of unit to center of intake 222 mm (8 ”) Side of unit to center of intake 197 mm (7 ”) Center of unit to center of flue 130 mm (5 ”)
OUTSIDE FRESH-AIR CONNECTION:
This Heater must have adequate air for proper combustion in the room that it is installed.
A Fresh-air intake is strongly recommended for all installations. Failure to install intake air may result in improper
combustion as well as the unit smoking during power failures.
The inlet to the intake must be below and a minimum of 305mm (12”) away from the unit exhaust outlet.
Outside fresh air is mandatory when installing this unit in airtight homes.
When connecting to an outside fresh air source, do not use plastic or combustible pipe. A 50mm minimum (2”) ID (inside diameter) steel, aluminum or copper pipe should be used. It is recommended, when you are installing a fresh air system, to keep the number of bends in the pipe to a minimum.
Figure 7: Outside Air Connection.
100mm
(4")
100mm
(4")
Fresh Air Intake
Wall thimble
manufactured
by pellet vent
manufacturer.
Installation
CORNER THROUGH WALL INSTALLATION:
Figure 8: Corner Installation.
HORIZONTAL EXHAUST THROUGH WALL INSTALLATION:
Vent installation: install vent at clearances specified by the vent manufacturer.
A chimney connector shall not pass through an attic or roof space, closet or similar concealed spaces, or a floor, or ceiling. Where passage through a wall or partition of combustible construction is desired, the installation must conform with all local regulations, including those referring to regional, national or European Standards. Use 80mm stainless steel vent pipe to exhaust the unit to the outside.
1. Choose a location for your stove that meets the requirements stated in this manual and allows
installation with the least amount of interference to house framing, plumbing, wiring, etc.
2. Install a non-combustible hearth pad (where necessary).
3. Place the appliance 375 mm (15”) away from the wall. If the stove is to be set on a hearth pad, set
the unit on it.
4. Locate the center of the exhaust pipe on the stove. Extend that line to the wall. Once you have located
the center point on the wall, refer to pellet vent manufacturer installation instructions for correct hole size and clearance to combustibles.
5. Install the wall thimble as per the instructions written on the thimble. Maintain an effective vapour
barrier in accordance with local building codes.
6. Install a length of 80mm (3”) vent pipe into the wall thimble. The pipe should install easily into the
thimble.
7. Install the fresh air intake (see OUTSIDE FRESH AIR CONNECTION).
8. Connect the exhaust vent pipe to the exhaust pipe on the stove. Seal the connection with high
temperature silicone.
11
Exhaust
80mm (3") or 100mm (4")
Vent Pipe
Wall Thimble
45oElbow with Screen
or Termination Cap
High Temperature RTV
Silicone Required
Fresh Air Intake
Wall framing
Wall thimble
Termination cap
Vent pipe
Horizontal frame for thimble
 
9. Push the stove straight back, leaving a minimum of 100mm (4”) clearance from the back of the stove to the wall. Seal the vent pipe to the thimble with high temperature silicone.
10. The pipe must extend at
least 30 cm (12”) away from the building. If necessary, bring another length of pipe to the outside of the home to connect to the first section. Do not forget to place high temperature silicone around the pipe that passes through the thimble.
Installation
Figure 9: Straight through wall Installation.
11. Install a vertical pipe, or if all requirements for direct venting are met, install vent termination. The
stainless steel cap termination manufactured by the vent manufacturer is recommended. However, when the vent terminates several feet above ground level and there are no trees, plants, etc. within several feet, a 45° elbow can be used as termination. The elbow must be turned down to prevent rain from entering.
NOTE:
• Some horizontal through wall installations may require a “T” and 91 to 152 cm (3 to 5 feet) of vertical
pipe outside the building to help naturally draft in the unit.
• This may be required if a proper burn
cannot be maintained, after the stove has been tested and the airflow set.
• This is due to the back pressure in the
exhaust caused by airflow around the structure.
• All sections of pipe must have three (3)
screws evenly spaced and all horizontal and vertical vent sections located within the house must have a bead of high temperature silicone installed on the male end of the pipe before installation to create a gas tight seal.
Figure 10: Straight through Wall Installation - Side View.
12
Installation
Wall framing
Wall thimble
Termination cap
Vertical section of vent pipe
Horizontal frame for thimble
Clean out tee
90°elbow
 
Concrete Wall
Wall framing
Wall thimble
Termination cap
Vertical section of vent pipe
Clean out tee
 
Wall strap
90°elbow
Horizontal frame for thimble
VERTICAL RISE WITH HORIZONTAL TERMINATION INSTALLATION (RECOMMENDED):
A 45° elbow with a rodent screen may be used in place of the termination cap (or stainless steel termination hood).
Figure 11: Through Wall with Horizontal Termination.
THROUGH CONCRETE WALL WITH VERTICAL RISE INSTALLATIONS:
A 45° down elbow with a rodent screen may be used in place of the termination cap (or stainless steel termination hood).
Installation to use if there is a concrete or retaining wall in line with exhaust vent on pellet stove.
The termination must be 305mm (12”) from the outside wall and 305mm (12”) above the ground.
Figure 12: Vertical rise with Horizontal Termination.
13
Storm Collar
Roof Flashing
Roof Rafters
Fire Stop with
Support Collar
Ceiling Joist
Vertical Vent Pipe
Clean Out Tee
with Pipe Adapter
ENVIRO Windsor
Note: All vent sections must maintain 3" (75mm) clearances to combustibles.
Rain cap - ensure cap is at
least 900mm (3 feet) above
the roof at the lowest point
Installation
INSIDE VERTICAL INSTALLATIONS:
1. Choose a stove location that is ideal. See the section “DECIDING WHERE TO LOCATE YOUR PELLET APPLIANCE.”
2. Place a non-combustible hearth pad where necessary.
3. Place the unit on the hearth pad (if installed on a carpeted surface) and space the unit in a manner
so when the pellet vent is installed vertically, it will be 100mm (4”) away from a combustible wall.
4. Locate the center of the fresh
air intake pipe on the unit. Match that center with the same point on the wall and cut a hole about 40mm (1”) in diameter.
5. Install the fresh air intake
pipe.
6. Install the tee with clean out.
7. Install the pellet vent upward
from there. When you reach the ceiling, make sure that the vent goes through the ceiling fire stop. Maintain a 100mm (4”) distance to combustibles and keep attic insulation away from the vent pipe. Maintain an effective vapor barrier.
8. Finally, extend the pellet
vent to go through the roof flashing.
9. Ensure that the rain cap is
approximately 900 mm (36”) above the roof.
Figure 13: Inside Vertical Installation.
14
Installation
Rain cap
Flashing
900mm
(36")
100mm
(4")
Tee with cleanout
Fresh air
intake
75mm (3") Clearance
Support
bracket
Type "L"
vent
OUTSIDE VERTICAL INSTALLATIONS:
To accomplish a outside vertical pipe installation, follow steps 1 through 5 in the “INSIDE VERTICAL INSTALLATIONS
- FREESTANDING section and then finish it by performing the following (refer to Figure 14).
1. Install a tee with clean out on the outside of the house.
2. Install vent pipe upward from the tee. Make sure that you install support brackets to keep the vent straight and secure.
3. Install ceiling thimble and secure the flashing as you go through the roof.
4. Ensure that the rain cap is approximately 900 mm (36”) above the roof.
Figure 14: Outside Vertical Installation.
15
Storm Collar
Existing Masonary Flue
Flexible Vent Connector (use this 1.5m (5ft) section of pipe to vent past the fireplace damper or smoke shelf)
Seal Plate
Fireplace Damper Location
Vertical Vent Pipe (single wall stainless flex pipe or solid PL vent)
Existing Fireplace
ENVIRO Windsor
Clean Out Tee
Rain cap - ensure cap is at least 900mm (3 ft) above the roof at the lowest point
Floor
Protection
Combustible Floor
Masonry Fireplace
Min 150mm
(6")
Mantel Minimum 200mm (8") from top of stove
Damper Removed or Fastened Open
Clean-out
Fresh-air intake should com from chimney. If holes
intake can be taken
through back of the
fireplace or through
the ash dump.
HEARTH MOUNT INSTALLATION:
Figure 15: Hearth Mount - Side View.
Installation
1. Lock fireplace damper in the open position.
2. Install a positive flue connector at the fireplace dampers.
3. Connect a clean-out tee or a 90° elbow to the exhaust pipe.
4. Install flexible stainless steel liner or listed pellet vent to the top of the chimney.
16
Figure 16: Hearth Mount - Over View.
Install blower
motor onto
exhaust blower
housings.
Completed assembly.
Exhaust Motor
Cover Plate
Access Panel
Installation
INSTALLATION WITH EXTERIOR MOUNTED EXHAUST BLOWER:
The WINDSOR can be equipped with an externally mounted exhaust blower (PART #50-492). This optional kit will include all components necessary to install the exhaust blower on any external vertical wall surface.
Choose a location for your stove that meets the requirements stated in this manual and allows installation with the least amount of interference to house framing, plumbing, wiring, etc.
Included in the exterior mounted exhaust blower kit are: 1 - Exhaust blower housing box. 1 - Blower cover plate. 1 - Hardware bag
1. Open the left side of the unit and disconnect the exhaust blower wires from the harness. Remove the exhaust blower by undoing the six (6) 6mm (”) hex head sheet metal screws that fasten the blower to the housing.
2. Remove the back grill from the exterior exhaust vent housing and remove the round cover plate installed on the blower housing.
3. Install the round cover plate over the gasketed opening in the stove where the exhaust motor was removed from.
4. Install the exhaust blower motor in the Exterior Vent Housing Box onto the exhaust blower housing.
Figure 17: Removing Exhaust Blower.
5. Follow the procedures for INSTALLATION - HORIZONTAL EXHAUST THROUGH WALL INSTALLATION. Place the unit in the desired location. Cut the hole in the wall at the desired location. Install a wall thimble.
6. Drill holes in the wall thimble in the corresponding locations for wire and fresh air if needed. Install wire clamps and feed wire through the hole in the thimble into the house. Tighten clamp on wire and attach green ground wire (at the symbol) with the screw and star washer provided.
7. Attach a short or an adjustable section of 80mm (3”) of double wall pellet vent through the wall thimble to the stove. Seal all joints with silicone. Maintain clearances to combustibles.
8. Apply silicone to the pipe in the Exhaust Box, slide the pipe into the exhaust vent. Mount the Exhaust Box to the house. Reinstall the back grill on the Exterior Vent Housing Box. Apply normal venting practices when installing the vertical vent pipe.
Figure 18: Exterior Exhaust Blower.
17
Installation
Vent termination cap
(stainless steel termination
hood) or 45° elbow with
rodent screen
90° elbow
Wall strap
(recommended with
use of vent pipe)
Exterior blower
and housing
Vent pipe or 610mm
(2 foot) riser
Pipe adapter (if using riser)
Wall framing
Wall thimble
Horizontal frame for thimble
Armour cable supplying power to exterior blower
Siding
9. Connect the wires in the stove. Re-install the left side access cover to the stove and the back grill on the exterior vent housing.
10. Set the Slider Damper as described in the INSTALLATION - SLIDER/DAMPER SETTING“ section.
NOTE:
Ensure that all vent connections are installed by placing three (3) screws evenly spaced and a small bead of high temperature silicone at each chimney connection. Also ensure that all vertical vent sections are properly supported and that all clearances to combustibles are maintained in accordance with the vent manufacturer’s specifications.
Figure 19: Exhaust Blower Installation; Horizontal Termination.
TO SUPPLY POWER TO THE EXHAUST BLOWER:
Install an amour coated electrical cable from the exhaust blower housing, through the wall thimble, and attach to the pre-drilled hole in the left hand rear hopper pillar. Hook up to wires from the wiring harness for the exhaust blower. All electrical connections must be in accordance with local code requirements (see WIRING DIAGRAM).
18
Storm Collar
Roof Flashing
Roof Rafters
Roof Sheathing
Ceiling Joist
Vertical Vent Pipe
Outside Vent
Termination
Exterior Wall
Sheathing
Rain cap - ensure
cap is at least
900mm (3 ft)
above the roof at
the lowest point
THROUGH WALL VERTICAL INSTALLATION WITH EXHAUST BLOWER:
Refer to INSTALLATION - INSTALLATION WITH EXTERIOR MOUNTED EXHAUST BLOWER and INSTALLATION - OUTSIDE VERTICAL INSTALLATIONS. Ensure that vent pipe is properly secured to wall using wall straps. Maintain clearances to
combustibles on vent pipe as well as unit.
Installation
Figure 20: Exhaust Blower Installation; Vertical Termination.
19
Installation
Remove jumper wire and install
thermostat wires here.
Note: Some parts have been removed in order to see components more clearly.
Slider Damper Plate
Exhaust Channel
Exhaust Blower
THERMOSTAT INSTALLATION:
1. Install the wall thermostat (12 or 24 Volt rated) in a location that is not to close too the unit but will
effectively heat the desired area.
2. Connect the Thermostat or Timer using an 2 x 18 gauge wire from the unit to the thermostat.
If the unit has been placed in the HI / LOW mode, the unit will be taken to a low or idle setting when the thermostat is not calling for heat. When the thermostat calls for heat, the unit will go to the setting that is displayed on the control board Heat Indicator. If the heat in the room becomes to great, the high limit switch may turn the stove off and the switch will have to be manually reset. To reset the high limit switch, remove the right cabinet side. The switch is found behind the control panel. Avoid setting off the high limit switch.
Figure 21: Thermostat wire placement.
SLIDER/DAMPER SETTING:
THE SLIDER / DAMPER MUST BE SET AT TIME OF INSTALLATION, IT IS USED TO REGULATE THE AIRFLOW THROUGH THE PELLET STOVE.
A Qualified Service Technician or Installer must set the Slider Damper.
The slider damper should be set only on a hot stove (operating for thirty (30) minutes or more) by placing a Magnahelic Pressure Gauge in the firebox (test port is located in the center of the stove just below the door opening). Set the slider damper so that the pressure reads 0.18” to 0.20” W.C.
(44.8 to 49.8 Pa). Some fuels may require higher or lower settings. The
pressure readings are taken through a hole in the front of the firebox under the door, using a Magnehelic Gauge.
20
Figure 22: Slider / Damper
Installation
The slider damper is located behind the left cab side. Undo the two (2) T-20 torx screws that hold the inspection cover on the left side and remove.
The combustion exhaust blower is a variable speed blower controlled by the heat output button. This blower will decrease the vacuum pressure inside the stove and as the heat output button is turned down. The vacuum pressure inside the firebox will increase as the combustion exhaust blower increases in speed (higher heat output setting).
• If the fire should happen to go out and the heat output indicator has been set on the lowest setting, the Slider Damper should be pushed in slightly, decreasing the air in the firebox.
• If, after long periods of burning, the fire builds up and overflows the burn pot or there is a build up of clinkers, this would be a sign that the pellet quality is poor, this requires more primary air, the slider damper must be pulled out to compensate. Pulling the slider damper out gives the fire more air.
The easiest way to make sure that an efficient flame is achieved is to understand the characteristics of
the fire.
• A tall, lazy flame with dark orange tips requires more air – Open slider (pull out) slightly.
• A short, brisk flame, like a blowtorch, has too much air – Close slider (push in) slightly.
• If the flame is in the middle of these two characteristics with a bright yellow/orange, active flame with no black tips then the air is set for proper operation.
SPECIAL NOTES:
Pellet quality is a major factor in how the pellet stove will operate. If the pellets have a high moisture content or ash content the fire will be less efficient and has a higher possibility of the fire building up and creating clinkers (hard ash build-up). If this happens, pull the Slider Damper out slightly to increase the air flow to the fire.
Figure 23: Efficient Flame.
21
Troubleshooting
DO NOT:
● Service the stove with wet hands. The stove is an electrical appliance, which may pose a shock hazard if handled improperly. Only qualified technicians should deal with possible internal electrical failures.
● Do not remove from the firebox any screws without penetrating oil lubrication.
● Hold the ON / OFF BUTTON down. This is a momentary contact switch and can be damaged if held down too long.
WHAT TO DO IF:
1. The stove will not start.
2. The stove will not operate when hot.
3. The exhaust blower will not function normally.
4. Light # 2 on Heat output bar flashing.
5. The auger motor will not function normally.
6. The 200 °F (93 °C) high limit temperature sensor has tripped.
7. The convection blower will not function normally.
8. Ignitor- the pellets will not light.
9. Control settings (Heat Level) has no effect on the fire.
10. The stove keeps going out.
*NOTE: All troubleshooting procedures should be carried out by qualified technicians or installers.
1. The stove will not start.
üMake sure the stove is plugged in and the wall outlet is supplying power. üPush the ON /OFF button. You may need to wait approximately 30 seconds for circuit board to initiate
the stove is on.
üIf the control board has been placed in the on/off thermostat mode, then turn the thermostat up to
call for heat.
üCheck the heat level indicator. - If the # 2 light is flashing refer to “4. Light # 2 on Heat output bar
flashing.”)
üCheck the fuse on the circuit board. üIf the unit still does not start, contact your local service dealer for service.
2. The stove will not operate when hot.
üCheck the heat level indicator if a fire is not detected, or if the fire has gone out the #3 light will
flash because the exhaust temperature sensor’s contacts have opened.
üCheck the hopper for fuel. üIncorrect air damper setting. - Excessive air may consume the fire too quickly before the next drop of
fuel, leaving completely unburned fuel in the burn pot liner. - Insufficient air will cause build up, further restricting the air flow through the burn pot liner. This in turn will cause the fuel to burn cold and very slowly. Fuel may build up and smother the fire. In this case clean the burn pot. (Note: the unit may
require a change to the vent system or installation of fresh air to correct air to fuel ratio problems).
üCombustion blower failure. - The combustion blower is not turning fast enough to generate the proper
vacuum in the fire box. Visual check – is the blower motor turning.
üCheck the exhaust blower voltage across the blower wires (>=220V on #5 setting and >= 165V on
#1 setting). – Replace the Circuit Board if the Voltage reading is less than 160V. with a line voltage >220V AC.
22
Troubleshooting
üCheck vacuum levels in the exhaust channel by bypassing the vacuum switch, then remove the vacuum
hose from vacuum switch. Check exhaust vacuum readings by placing the open end of the vacuum hose on a Magnahelic Gauge (readings must be above 0.18” to 0.20” W.C. (44.8 to 49.8 Pa) on low fire). If the motor fails to reach a 0.10” W.C. readings, then replace the combustion blower.
üPoor quality fuel – insufficient energy in the fuel to produce enough heat to keep the stove burning or
operational.
üExhaust temperature sensor failure. – Bypass sensor located on exhaust blower if stove now operates
properly, the unit may require cleaning or a new sensor. Contact your local dealer for service.
üThe burn pot liner may require cleaning. Build up in the burn pot will cause the unit to shut off. üCheck the fuse on the circuit board. üContact your local dealer for service.
3. The exhaust motor will not function normally.
üOpen the left side access panel; check all connections against the wiring diagram. üSee “2. The stove will not operate when hot.” Section.
4. Light # 2 on Heat output bar flashing (The Vacuum Switch contacts have opened for more than 15 sec.) üPinch, break or blockage in vacuum hose - check hose for pinch points or damage, replace or re-route
as required. Blow out vacuum hose
üBlocked hose barb on exhaust channel - use a paper clip to clean out hose barb or remove the vacuum
hose from the vacuum switch and blow into the hose to remove blockage.
üBlocked exhaust / venting system - have stove and venting cleaned and inspected. üSevere negative pressure in area where unit is installed - check the operation by opening a window,
does this solve the problem? If it does, install fresh air intake to unit or room. Venting system may require vertical section to move termination into a low pressure zone.
üVacuum switch failure - bypass the vacuum switch, if this corrects the problem check for above problems
before replacing the vacuum switch.
üDamage to gray wires between circuit board and vacuum switch - inspect wires and connectors üCombustion blower failure - the combustion blower is not turning fast enough to generate the proper
vacuum in the exhaust channel. Visual check; is the blower motor turning? Check the exhaust blower voltage across the blower wires (>=220V on #5 setting and >= 165V on #1 setting). – Replace the Circuit Board if the Voltage reading is less than 160V. with a line voltage >220V AC.
üCheck vacuum levels in the exhaust channel by bypassing the vacuum switch, then remove the Vacuum
hose from Vacuum Switch. Check exhaust vacuum readings by placing the open end of the Vacuum Hose on a Magnahelic Gauge. (readings must be above .10” W.C. on low fire).
If the motor fails to reach a 0.10” W.C. readings, then replace the combustion blower
To reset Circuit Board after a trouble code - push the ON/OFF button
5. The auger motor will not function normally.
üThe burn pot liner may require cleaning. Build up in the burn pot will cause the unit to shut off. üCheck for obstructions in the hopper system. üEnsure door is closed and ash pan is closed. The auger motor will stop if there is not enough vacuum
in the stove.
üCall your local dealer for service. Auger light flashes but auger motor does not turn at all.
23
Troubleshooting
üIf the auger gear box does not turn but the motor’s armature does try to spin then the auger is jammed.
– Try to break apart jam by poking at the jam through the drop tube. If this fails then empty the hopper and remove the auger cover **remember to re-seal the cover after installation**
üCheck the fuse on the circuit board.
6. The 200 °F ( 93 °C) high limit temperature sensor has tripped.
üReset sensor and determine cause – was it convection blower failure or 160 °F ( 71 °C) temperature
sensor failure? Bypass the 160 °F ( 71 °C) sensor, does the convection blower come on high? If no, replace the blower. If yes, replace sensor (located on the left side of the firewall).
üCheck the fuse on the circuit board.
7. The convection blower will not function normally.
üClean all grill openings at the back and below unit . üPress the fan button; does the fan come on? Press again to verify that the blower turns on; if, not
contact your local dealer for service.
8. Ignitor- the pellets will not light.
(Everything else in the stove operates but the ignitor will not light the pellets.) üMake sure the burn pot liner is up tight and square to the ignitor tube by pushing the burn pot back
against the ignitor tube.
üCheck to see if the exhaust blower is operating. If not, contact your local dealer for service. üCheck the fuse on the circuit board.
NOTE: The ignitor should be bright orange in color. If not replace the ignitor.
9. Control settings (Heat Level) has no effect on the fire.
üNote: If the system light is flashing the control board has complete control of the unit. When the units
system light becomes solid then control of the unit is given back to the operator.
üIf there is no control of the heat level button make sure the thermostat is calling for heat. üCall your local dealer for service.
10. The stove keeps going out.
a) If the stove goes out and leaves fresh unburned pellets or cigarette-like ashes in the burn pot liner,
the fire is going out before the stove shuts off.
üCheck to see that the slider / damper is in the correct position. üTurn the heat level up slightly (poor quality pellets will require slightly higher settings). üSet the auger trim till the #1 and #5 lights are illuminated.
b) If the stove goes out and there are partially burned pellets left in the burn pot liner, the stove has shut down due to a lack of air, exhaust temperature, or power failure.
üAdjust the slider / damper. üCheck to see if the stove needs a more complete cleaning. üTurn the heat level up slightly (poor quality pellets will require slightly higher settings). üDid the power go out?
üContact your local dealer for service.
24
Wiring Diagram
Connect
Thermostat
Here
Red
Red
Red
Red
Brown
Brown
Brown
Brown
White
White
White
White
White
White
Orange Orange
Orange Orange
Yellow
Yellow
Grey
Grey
Purple
Purple
Blue
Black
Black
Black
Blue
Black
Armor Cable Supplied
Vacuum
Switch
Combustion
Blower
Optional Exterior
Exhaust Blower
Ignitor
Exhaust
Temperature
Sensor
5 Amp
Fuse
High Limit
Temperature
Sensor
Convection
Blower
Auger Motor
Thermostat
Ground
Ground
240V Filter
Brown Blue
Yellow
25
Parts List - Components
Reference
Number
1 120 °F (49 °C) Ceramic Fan Temperature Sensor EC-001 2 Auger Motor - 220V EF-001-220V 3 High Limit Temp Sensor 200 °F (93 °C) Manual Reset EF-016
4 4
5 Ignitor - 220V 20-016-220V
6 Heat Exchanger Rod 50-181 7 Cast Brick Panel - Left 50-183 8 Cast Brick Panel - Right 50-184
9 Cast Brick Panel - Center 50-1585 10 Brick Panel Retainers (set of 2) 50-185 11 Inner Door Complete with Glass & Tape 50-1671 12 Glass With Tape 50-1468
13 Inner Door Handle 50-189 14 Door Hinge Bracket 50-1530 15 Ash Pan With Painted Knob 50-191 16 Rear Casting Mounts - Right & Left 50-197 17 Bottom Casting Mounts - Right & Left 50-198 18 Front Casting Mounts - Right & Left 50-199 19 Door Knob - Brushed Nickel 50-262 20 Air Deector 50-363
21 Convection Blower - 220V 50-513
Description
Silicone Hose EF-018 External Exhaust Back EF5-143 External Exhaust Box EF5-144 External Exhaust Bottom EF5-145 NZ Power Cord - 220V 20-011
IEC Power Cord - 220V 20-013
Door Screen 50-177
Inner Door Only - Painted 50-1672
External Exhaust Kit (80mm pipe) 50-492
Self Adhesive Vinyl Spacers (set of 4) 50-1149 Dual bulb door gasket - 10 ft (3.05m) 50-634
Part
Number
26
Parts List - Components
Reference
Number
22 IEC Power Cord Inlet Socket 50-713
23 Circuit Board 5 Amp Fuses - 220V (Pair) 50-834 24 Exhaust Starter Tube 80mm x 2” Long 50-898 25 Combustion/ Exhaust Blower - 220V 50-900
26 Ignition Burn Pot 50-1366 27 Vacuum Switch - Low Presure 50-1390 28 Burn Pot Liner with Sides 50-1401 29 Control Panel with Decal 50-1481 29 Control Panel Decal 50-1482 30 Circuit Board with Thermostat Switch - 220V 50-1522
31 Hopper Lid with Hinges 50-1580 32 Fan Cover 50-1581 33 Slider Damper 50-1582 34 Ignitor Tube 50-1583 35 EMI Filter 50-1584 36 Back grill 50-1586 37 Access Panel - Right 50-1587 38 Access Panel - Left 50-1588 39 Pewter Knob 50-1589
40 Auger 50-1626
Description
Auger Motor Mount 50-687 Auger Plate with bushing 50-688 Auger Mounting Hardware 50-689
Hinge Pin - Silver 50-750 Oval Ceramic Gasket 50-766
Door Bolt, Hardened Bushing & Nut 50-995
Gloves 50-1525
Windsor International Owner’s Manual 50-1577 Windsor International Technical Manual 50-1578
Wiring Harness 50-1625
Part
Number
27
Parts List - Cast
Reference
Number
41 Cast Ash Shelf - Painted 50-192 42 Cast Front Complete (Doors & Ash Shelf) - Painted 50-202 43 Cast Side Left - Painted 50-203 44 Cast Side Right - Painted 50-204 45 Cast Grate - Painted 50-205 46 Cast Top Only (No Grate) - Painted 50-206
Description
Complete Cast Body - Painted 50-576 Complete Cast Body - Antique White 50-577 Complete Cast Body - Diamond Black 50-578 Complete Cast Body - Inferno Red 50-579 Complete Cast Body - Pearl Grey 50-580 Complete Cast Body - Wedgewood Blue 50-581 Complete Cast Body - Westport Green 50-582 Complete Cast Body - Antique Chestnut 50-867
Part
Number
28
WINDSOR - Components
May 2007










Parts Diagram - Components
29
WINDSOR - Steel & Cast
May 2007































Parts Diagram - Steel & Cast
30
Installation Data Sheet
The following information must be recorded by the installer for warranty purposes and future reference.
NAME OF OWNER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
MODEL:___________________________________
SERIAL NUMBER:___________________________
DATE OF PURCHASE: _____________ (dd/mm/yyyy)
NAME OF DEALER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
NAME OF INSTALLER:
_________________________________________
DATE OF INSTALLATION:___________(dd/mm/yyyy)
MAGNEHELIC AT INSTALL:___________________
INSTALLER’S SIGNATURE:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
WARRANTY: If you have any concerns with your unit please contact the dealer where you purchased
the stove.
MANUFACTURED BY:
6782 OLDFIELD RD. SAANICHTON, BC, CANADA V8M 2A3
SHERWOOD INDUSTRIES LTD.
www.enviro.com
May 16, 2007
C-11304
31
Loading...