SHERWOOD INDUSTRIES IS AN ENVIRONMENTALLY RESPONSIBLE COMPANY. THIS MANUAL IS PRINTED ON RECYCLED
PAPER.
PLEASE KEEP THESE INSTRUCTIONS FOR FUTURE REFERENCE
Westport
B Y : S H E R W O O D I N D U S T R I E S L T D
OWNER’S MANUAL
INSTALLER:
Leave this manual with the appliance.
CONSUMER:
Retain this manual for future reference.
WHAT TO DO IF YOU SMELL GAS
• Open windows/extinguish any
open ame.
• Do not try to light any appliance.
• Do not touch any electrical switch
or use any phone in your building.
• Immediately call your gas supplier
from a neighbour’s phone. Follow
the gas supplier’s instructions.
• If you cannot reach your gas
supplier, call the re department.
FOR YOUR SAFETY: Do not store or use gasoline or
other ammable vapours and liquids in the vicinity of
this or any other appliance.
WARNING: If the information in this manual is
not followed exactly, a re or explosion may result
causing property damage, personal injury or loss of
life. Installation and service must be performed by a
qualied installer, service agency or the gas supplier.
This appliance may be installed in an
after-market permanently located,
manufactured (mobile) home,
where not prohibited by local codes.
This appliance is only for use with
the type of gas indicated on the
rating plate. This appliance is not
convertible for use with other gases,
unless a certied kit is used.
Massachusetts installations (Warning): This product must be installed by a licensed plumber or
gas tter when installed within the Commonwealth of Massachusetts. Other Massachusetts code
requirements: Flexible connector must not be longer than 36in., a shut off valve must be installed;
only direct vent sealed combustion products are approved for bedrooms/bathrooms. A carbon
monoxide detector is required in all rooms containing gas red direct vent appliances. The replace
damper must be removed or welded in the open position prior to installation of a replace insert.
50-1033
Page 2
Safety Precautions
FOR SAFE INSTALLATION AND OPERATION OF YOUR “ENVIRO” HEATER,
PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:
• All ENVIRO gas-red appliances must be installed
in accordance with their instructions. Carefully read all
the instructions in this manual rst. Consult the building
authority having jurisdiction to determine the need for
a permit prior to commencing the installation.
• NOTE: Failure to follow these instructions could
cause a malfunction of the replace, which could
result in death, serious bodily injury, and/or property
damage.
• Failure to follow these instructions may also void
your re insurance and/or warranty.
GENERAL
• Installation and repair should be done by a
qualied service person. The appliance should be
inspected before the rst use and, at least, annually
by a qualied service person. More frequent
cleaning may be required due to excessive lint from
carpeting, bedding material, etc. It is imperative the
control compartments, burners and circulating air
passageways of the appliance be kept clean.
• Due to high temperatures, the appliance should
be located out of high trafc areas and away from
furniture and draperies.
Children and adults should be alerted to the
hazards of high surface temperatures and
should stay away to avoid burn or clothing
ignition.
• Young children should be carefully supervised
when in the same room as the appliance.
• Clothing or other ammable materials should not
be placed on or near the appliance.
FOR YOUR SAFETY
• Installation and service must be performed by a
qualied installer, service agency or gas supplier.
• This installation must conform to local codes or, in
the absence of local codes, to the current CAN/CGAB149 installation code (Canada) or National Fuel Gas
Code ANSI Z223.1.2 (USA)
• To prevent injury, do not allow anyone who is
unfamiliar with the stove to operate it.
• To prevent injury, if the pilot or pilot and
burners have gone out on their own, open the
glass door and wait 5 minutes to air out before
attempting to re-light the stove.
• Always keep the area around these appliances
clear of combustible material, gasoline and other
ammable liquids and vapours.
• These appliances should not be used as a drying
rack for clothing or for hanging Christmas stockings/
decorations.
• Due to the paint curing on the stove, a faint odor
and slight smoking will likely be noticed when the
stove is rst used. Open a window until the smoking
stops.
Always connect this gas stove to a vent system and
vent to the outside of the building envelope. Never
vent to another room or inside the building. Make sure
the specied vent pipe is used, properly sized and of
adequate height to provide sufcient draft. Inspect
the venting system annually for blockage and signs of
deterioration.
WARNING: Failure to position the parts in accordance
with the diagrams in this booklet, or failure to use only
parts specically approved with this appliance, may
result in property damage or personal injury.
WARNING: Do not operate with the glass front
removed, cracked or broken. Replacement of the
glass should be done by a licensed or qualied service
person.
• Never use solid fuels such as wood, paper,
cardboard, coal, or any ammable liquids, etc., in this
appliance.
• Do not use this heater if any part has been under
water. Immediately call a qualied service technician
to inspect the heater and to replace any part of the
control or gas control systems that have been under
water.
• Do not abuse the glass by striking it or slamming
the door shut.
Installation Data Sheet.........................................................................................................48
3
Page 4
Codes And Approvals
DIRECT VENT ONLY: This type is identied by the sux DV. This appliance draws all of its air for
combustion from outside the dwelling, through a specially designed vent pipe system.
TOP VENT DV Certied for installation from 0-4500 ft (0-1372 m)
REAR VENT DV Certied for installation from 0-4500 ft (0-1372 m) with 36” (915 mm)
snorkel (refer to ‘Converting Top Vented into Rear Vented’).
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at
elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate
guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
• This appliance has been tested by INTERTEK (Warnock Hersey) and found to comply with the
established VENTED GAS FIREPLACE HEATER standards in CANADA and the USA as follows:
VENTED GAS FIREPLACE HEATER (Westport DV; NG/LPG)
TESTED TO: ANSI Z21.88a-2003/CSA 2.33a-2003 VENTED GAS FIREPLACE HEATERS
CAN/CGA 2.17-M91 GAS FIRED APPLIANCES FOR HIGH ALTITUDES
CSA P.4.1-02 TESTING METHOD FOR MEASURING ANNUAL FIREPLACE EFFICIENCY
This ENVIRO WESTPORT Fireplace:
• Has been certied for use with either natural or propane gases. (See rating label.)
• Is not for use with solid fuels.
• Is approved for bedroom or bed sitting room. (IN CANADA: must be
installed with a listed wall thermostat. IN USA: see current ANSI Z223.1
for installation instructions.)
• Must be installed in accordance with local codes. If none exist, use current
installation code CAN/CGA B149 in Canada or ANSI Z223.1/NFPA 54 in the
USA.
• Must be properly connected to an approved venting system and not connected
to a chimney ue serving a separate solid-fuel burning appliance.
IMPORTANT NOTICE (Regarding rst re up): When the unit is turned
on for the rst time, it should be turned onto high without the fan on for
the rst 4 hours. This will cure the paint, logs, gasket material and other
products used in the manufacturing process. It is advisable to open a
window or door, as the unit will start to smoke and can irritate some people.
After the unit has gone through the rst burn, turn the unit off including the
pilot, let the unit get cold then remove the glass door and clean it with a
good gas replace glass cleaner, available at your local ENVIRO dealer.
4
Page 5
Specifications
WARNING:
Operation of this heater when not connected to a properly installed and maintained venting system can
result in carbon monoxide (CO) poisoning and possible death.
Dimensions:
1
/8"
25 ¾"
(65.3cm)
15
(39.0cm)
27"
(68.6cm)
25 ¾"
(65.4cm)
25 ¾"
(65.3cm)
16 5/8"
(42.2cm)
15 ¾"
(40.0cm)
1
/8"
17
(43.5cm)
Floor to center of flue
REAR VENT
23½” (59.7 cm)
27"
(68.5cm)
Figure 1: Westport Exterior Dimensions.
Rating LabeL Location:
The Rating Label is located on a plate hang on the back left of the unit.
5
Page 6
Operating Instructions
For Your Safety, Read Safety Precautions And
Lighting Instructions Before Operating
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY
RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OF LOSS OF LIFE.
PiLot Lighting instRuctions:
installation, adjustment, alteration, service or maintenance can cause property damage, personal injury, or loss of life. Refer to owner's
manual. Installation and service must be performed by a qualified installer, service agency or the gas supplier
out repeat steps 4 th
1. Flip burner switch to 'OFF'.
2. Turn the gas control knob clockwise to the 'OFF' position.
4. Open door. Wait five (5) minutes to clear out any gas. Close door. If you
smell gas, including near the f
1. STOP! Read the safety information above on this label.
2. Turn off all electrical power to this appliance.
3. Turn off the gas control knob clockwise to the off position.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliances. Do not touch any electrical switch. Do not
use any phone in your building.
Immediately call your gas su
following
these instructions exactly.
B) BEFORE LIGHTING, smell all around the appliance area for gas and next to
the floor because some gas is heavier than air and will settle on the floor.
A) This appliance is equipped with a pilot, which must be lit by hand by
information. If you do not smell gas go to the next step.
5. Find pilot located to the right behind the side log. Turn the gas control
knob counter-clockwise to 'PILOT'.
Push the gas control in fully and hold.
Keep knob depressed for about 30 seconds
after pilot is lit. Release knob. If pilot goes
have ventilation air. See installation and operating instructions manual. Keep burner and control compartment clean. WARNING: Improper
CAUTION:
FOR YOUR SAFETY: Do not operate this fireplace with the glass removed, cracked, or broken. Replacement of this glass should be
installed with provisions for combustion and by a licensed or qualified person! This appliance needs fresh air for safe operation and must
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY, A FIRE OR EXPLOSION MAY RESULT
rough 5.
pplier from a neighbours phone. Follow the gas
loor, STOP! Follow 'B' in the above safety
CAUSING PROPERTY DAMAGE, PERSONAL INJURY, OR LOSS OF LIFE.
HOT WHILE OPERATING. DO NOT TOUCH. KEEP CHILDREN, CLOTHING, FURNITURE,
GASOLINE, OR OTHER FLAMMABLE VAPOURS AWAY.
FOR YOUR SAFETY REA D BEFORE O PERATING
TO T URN OFF GAS TO APPLIANCE
LIGHT ING INSTRUCTIONS
If you cannot reach your gas supplier, call the fire department.
C) Use only your hands to push in or turn the gas control knob; NEVER
use tools. If the knob will not push in or turn by hand, do not try
may result in a fire or explosion.
D) Do not use this appliance if any part has been underwater. Immediately
call a qualified service technician to inspect the appliance and to replace
any part of the control system and any gas control which has been
7. Turn on the electrical power to the unit.
performed.
3. Turn off all electrical power to the appliance if service is to be
WARNING: This gas valve has a lockout device, which will not allow
the pilot burner to be relit until the ther
knob does not pop up when released, stop and immediately call
your service technician or gas supplier.
6. Turn the gas control knob counter-clockwise to the 'ON'
position. Flip the burner switch
to 'ON' THEN TURN THE 'HI/LOW'
knob to the desired setting.
under water.
mocouple has cooled. If the
TP TH TP TH
T
O
L
I
P
I
H
O
L
C-10381
O
N
F
O
F
IN OUT
P
T
I
O
L
to repair,
Figure 2. Lighting Instruction Label
6
Page 7
Operating Instructions
PiLot Light:
1. Turn off the gas to the replace. If not recently done, remove the glass and let the unit air out
for at least ve (5) minutes to clear out any gas. Turn on gas to the heater. Leak test all joints
with soapy water. NEVER USE OPEN FLAME FOR LEAK TESTING.
2. Start the pilot by pressing the gas control knob and turning it to PILOT.
While holding the gas control knob in, press the piezo ignitor several
times until the pilot light starts. Hold the gas control knob in for 30
seconds. Check that the pilot has fully engulfed the thermocouple
assembly (see Figure 3).
3. Start the main burner by turning the gas control knob to ON and then
turn the rocker switch to ON. Check that all burner ports have ame.
Thermopile
Thermocouple
4. Leak test all gas joints again.
Figure 3. Pilot Flame
aiR shutteR:
The air shutter is controlled with the primary air adjustment rod located behind the gas valve shown in
Figure 4.
The air shutter allows the amount of air coming into the replace to be adjusted in order to accommodate
different climates and venting arrangements. Start the pilot and then the burner. Make sure the pilot
ame is burning normally and none of the burner ports are plugged. Let the replace burn for roughly
fteen (15) minutes and then examine the ames, compare the ames to Figure 61.
The ideal ame will be blue at the base and light
orange above. The ames should be of medium
height. If the ames look like this, no venturi
adjustment is needed. If the ames are fairly
short and mostly blue, the replace is getting
too much air. Therefore, the air shutter should
be closed slightly until the correct ames are
achieved. Flames that are very orange, with tall,
dark, stringy tips, are not getting enough air.
Open the venturi until the ames clean up. If the
venturi is opened, or closed all the way, and the
correct ames cannot be attained, turn off the
gas and contact the dealer.
Gas valve
regulator
Gas valve
Primary air
adjustment rod
Figure 4: Gas Valve In Place on Unit.
Table 1: Venturi Information.
Venturi Setting
Natural GasPropane
1
/16” min.
3
/16” min.
Warning: Incorrect venturi adjustment may lead
to improper combustion, which is a safety hazard.
Contact the dealer if there is any concern about the
venturi adjustment.
7
Page 8
Operating Instructions
For Your Safety, Read Safety Precautions And
Lighting Instructions Before Operating
RemotecontRoLs (oPtionaL):
This replace can use an optional remote control or an optional cordless wall thermostat. If either of
these are to be used to control the replace for the majority of the time, leave the ON/OFF switch (on the
control panel) in the remote/thermostat position. Consult the instructions included with the remote/wall
thermostat for operation guidelines.
bLoweR sPeeD (oPtionaL):
The blower will come on only when the replace is up to temperature (approximately 20 minutes). The
speed of the fan can be changed by turning the fan control knob. To turn the blower off, turn the knob
COUNTER CLOCKWISE until it “clicks” off.
1
It is advisable not to operate the blower below
and running the blower at lower speeds could also cause premature fan failure.
noRmaL sounDs DuRing oPeRation:
/3 speed as it puts a strain on the windings of the blower
Table 2: Normal Sounds
ComponentSound & Reason
WestportCreaking when heating up or cooling down.
BurnerLight pop or poof when turned off; this is more common with LP units.
Temperature SensorClinking when it senses to turn the blower on or off.
Pilot FlameQuiet whisper while the pilot ame in on.
Blower / FanAir movement that increase and decreases with the speed of the blower. The
blower is pushing the heat from the replace into the room.
Gas Control ValveDull click when turning on or off, this is the valve opening and closing.
8
Page 9
Maintenance And Service
Routine maintenance:
At least once a year, run through the following procedures to ensure the system is clean and working
properly. Check the burner to see if all the ports are clear and clean. Check the pilot to make sure it is not
blocked by anything. The pilot ame should be blue with little or no yellow on the tips.
Warning: Clearances must be sufcient to allow access for maintenance and service
Warning: Failure to position the parts in accordance with this manual, or failure to use only parts
specically approved with this appliance may result in property damage or personal injury.
The venting system must be periodically examined; it is recommended the examination is done by a
qualied agency.
cLeaning the gLass:
When the replace has cooled, remove the face of the replace along with the glass. See Maintenance
and Service - GlaSS door reMoval. Check the gasket material on the back of the glass, making sure that it
is attached and intact.
During a cold start up, condensation will sometimes form on the glass. This is a normal condition with all
replaces. However, this condensation can allow dust and lint to cling to the glass surface. Initial paint
curing of the appliance can leave a slight lm behind the glass, a temporary problem. The glass will need
cleaning about two weeks after installation. Use a mild glass cleaner and a soft cloth; abrasive cleaners will damage the glass and plated surfaces. Depending on the amount of use, the glass
should require cleaning no more than two or three times a season. Do not clean the glass when it is
hot.
cLeaning the FiRebox:
Remove the logs carefully, as they are very fragile. Gently remove all the embers and rock wool and
place on a paper towel. Vacuum the bottom of the rebox thoroughly. Carefully clean any dust off the
logs and remove any lint from the burner and pilot. At this time, inspect the burner pan for cracking or
severe warping. If a problem is suspected, contact the dealer. Check the logs for deterioration or large
amounts of soot; a small amount on the bottom side of the logs is normal. Replace the logs and embers
as in the loG Setand eMber inStallation section. If new/more embers and rock wool are required, contact
your nearest ENVIRO dealer.
change batteRyin ignition moDuLe:
If the unit does not spark when lighting, the battery in the
electronic ignition could need replacing.
Located on the left hand rear corner of the unit is a small
rectangular hole. Located here is the electronic ignition module
(see Figure 5). Remove the battery cover, located on the left side
of the module, and replace the AA battery.
Reinstall the battery cover and check for spark by depressing the
pilot knob located on the control panel.
Electronic
ignition module
Figure 5: Electronic Ignition Module
Location.
9
Page 10
Maintenance And Service
RePLacingthe gLass:
The glass in the replace is a high temperature ceramic. If the glass is damaged in any way, a factory
replacement is required (see PartS liSt - coMPonentS). Wear gloves when handling damaged glass door
assembly to prevent personal injury. When the glass door assembly is being transported, it must be
wrapped in newsprint and tape and/or a strong plastic bag. Do not operate with the glass front removed,
cracked or broken. Removal and replacement of the glass from the door must be done by a licensed or
qualied service person. The glass must be purchased from an ENVIRO dealer. No substitute
materials are allowed.
To Replace:
• Open door, and remove the glass carefully.
• Install the new piece of glass with the large bulb in the gasket tape against the unit. Place the joint
in the tape in a bottom corner. Close door.
gLass DooR RemovaL:
Turn unit off and wait until the appliance has cooled down. Remove the cast iron top from the unit by
lifting straight up. Lift the two door handles located on either side of the door and lift the glass door
assembly straight up and out (see Figure 6 and 7).
Carefully open the two doors and remove if necessary.
Ensure the door is properly fastened after cleaning before
attempting to re-light the appliance.
Figure 6: Handles for Removing Door.Figure 7: Removing of Door.
buRneR RemovaL:
1. Remove the glass as shown in the Maintenanceand Service - GlaSS door reMoval.
2. Carefully remove the log set and ember material.
3. Remove the two (2) screws (located on the outside edges of the burner) that hold the burner to the
chassis inside the re box, see Figure 8. Remove the burner tray from the rebox.
10
Page 11
Maintenance And Service
FueL conveRsion:
TO BE INSTALLED BY A QUALIFIED SERVICE AGENCY ONLY
Please read and understand these instructions before installing.
Warning: This conversion kit shall be installed by a qualied service agency in accordance
with the manufacturer’s instructions and all applicable codes and requirements of the
authority having jurisdiction. If the information in these instructions is not followed
exactly, a re, explosion or production of carbon monoxide may result causing property
damage, personal injury or loss of life. The qualied service agency is responsible for
the proper installation of this kit. The installation is not proper or complete until the
operation of the converted appliance is checked as specied in the manufacturer’s
instructions supplied with the kit.
Carefully inspect all parts supplied with this conversion kit. If any parts have been damaged or are
missing, contact your dealer, distributor or courier company to have them replaced before starting this
installation.
Conversion Kit Installation:
1. Turn control knob on the gas valve to the “OFF” position and shut the gas supply off at the shut-off
valve upstream of the unit. CAUTION:
The gas supply must be shut off prior to
disconnecting the electrical power and
before proceeding with the conversion.
Allow the valve and unit to cool down to
Rotate handles
and remove the
door and glass.
Pilot assembly moved
from firebox for clarity.
room temperature.
2. Remove the glass as shown in the
Maintenanceand Service - GlaSS door
reMoval.
3. Carefully remove the log set and ember
material if they are installed.
4. Remove the burner as shown in the
Maintenanceand Service - burner reMoval.
Lift off the pilot
head and replace
with proper pilot
orifice for fuel type
to be used.
5. Convert the burner orice(s):
a) Remove the main burner orice with a
½ inch deep socket.
b) Put a bead of pipe-thread sealant or
approved Teon tape on the orice
threads before installing into the brass
elbow.
c) Install the new orice(s) from the kit
Using a ½" deep
socket remove/reinstall
the main burner orifice.
Venturi adjustment
bracket.
Undo the two
(2) screws that
hold burner in
the firebox.
into the brass elbow.
Figure 8: Unit burner shown apart.
11
Page 12
Redo-ring
isnotvisible
Redo-ring
isvisible
LPGConfiguration
Loosen
Tighten
Maintenance And Service
6. Convert the pilot injector:
a) Pull the pilot hood straight up to access
the pilot injector.
5
b) Using a
remove the pilot injector.
c) Install the new pilot injector supplied
with this conversion kit. Simply screw
the new injector inside the pilot hood
using the Allen key,
d) Reinstall the hood by placing the hood
on the assembly, line up the key way,
and snap into place.
7. Convert the SIT gas valve:
a) Remove the black protection cap from
the HI/LO knob by hand shown in Figure 9.
b) Insert a 5/32” or 4 mm Allen wrench into
the hexagonal key-way of the screw (see
Figure 10), rotate it counter-clockwise
until it is free and extract it.
c) Check that the screw is clean and if
necessary remove dirt.
d) Flip the screw (refer to Figure 11).
e) Using the Allen wrench as shown in
Figure 10, rotate the screw clockwise
until a torque of 9 inch lbs. WARNING! Do not over tighten the screw. It is
recommended that you grip the wrench by the short side.
f) Verify that if the conversion is from NG to LPG, the screw must be re-
assembled with the red o-ring visible (refer to Figure 12). If the conversion
is from LPG to NG, the red o-ring of the screw must be not visible.
g) Re-attach the black protection cap that was removed in step a (Figure 9).
8. Reinstall the burner, brick panels, log set, embers, and glass door. Also refer
Secondary inStallation - loG Setand eMberS inStallation. When re-installing the
to
burner, ensure that the burner to pilot hood relationship is similar to what is
shown in Figure 13. On some units you will need to pay special attention when
installing the burner that the venturi adjustment rod is properly installed into
the venturi adjustment piece welded to the burner venturi tube
9. Reconnect the main gas line if it was disconnected and open the shut-off valve at the gas line to the
unit.
10. Use a small brush to apply a warm soapy water solution to all gas connections (use a half dish soap
and half warm water). If a gas leak is present, bubbling will occur. Gas leaks can be repaired by
using an approved pipe thread sealant or approved Teon tape. NEVER USE AN OPEN FLAME WHEN
TESTING FOR LEAKS.
11. Reconnect the electrical power to the unit.
12. Relight the main burner in both the “HI” and “LO” positions to verify proper burner ignition and
operation and proper ame appearance. Also refer to
inStallation for a ame appearance picture.
13. MAKE SURE that the conversion label is installed on or close to the rating label to signify that the
unit has been converted to a different fuel type.
/32” or 4 mm Allen key,
Figure 9:
Removing valve
cap.
Figure 12: O-ring on valve screw.
Secondary inStallation - loG Setand eMberS
Figure 10: Removing
valve screw.
Figure 11: Flip
valve screw.
Figure 13. Ignitor
assembly beside the
burner.
12
Page 13
Initial Installation
QUALIFIED INSTALLERS ONLY
WARNING:
Operation of this heater when not connected to a properly installed and maintained venting system can
result in carbon monoxide (CO) poisoning and possible death.
PRePaRation FoR instaLLation:
• Remove the packaging from the appliance, and check to make sure there is no damage. If damage is
found, please report it to both the carrier and your dealer as soon as possible.
• Before beginning, carefully check the glass door and the log set
• Locate a position where the ue system of the stove can be properly installed without damaging the
integrity of the building; e.g. cutting a wall or ceiling joist.
• Check stove and ue system clearance requirements.
• Locate the stove where it can be accessed by a gas supply line.
• Locate the stove in a large and open room that is centrally located in the house. This will optimize heat
circulation and comfort.
• As the stove can be equipped with a convection fan, ensure that an electrical outlet is within 6 ft (1.8
m) of the stove.
• The ow of combustion and ventilation air must not be obstructed.
cLeaRancesto combustibLes:
A. Sidewall to unit 11 inches (27.9 cm)
B. Backwall to unit 2.5 inches (6.35 cm)
C. Corner to unit 2.5 inches (6.35 cm)
D. Ceiling 60 inches above oor (152.4 cm)
E. Floor (hard wood and linoleum) 0 inches
Note: When installing on a carpeted surfaces a noncombustible hearth pad must be used.
CLEARANCES MUST BE SUFFICIENT TO ALLOW ACCESS FOR MAINTENANCE AND SERVICE.
Back wall
B
A
Side wall
Front
Figure 14: Clearances to combustibles.
Adjacent wall
C
Adjacent wall
C
Front
PLanning youR instaLLation:
When planning your installation, it will be necessary to select the proper length of vent pipe for your
particular requirements. It is important to note when passing through a wall, the maximum allowable
wall thickness is 10 inches (25.4 cm), 1½ inches (3.8 cm) clearance to combustibles must be maintained.
Select the amount of vertical rise desired for “vertical-to-horizontal” type installations. To determine
the length of vent pipe required for vertical installations, measure the distance from the appliance ue
outlet to the ceiling, the ceiling thickness, the vertical rise through the attic or second story, and allow
for sufcient vent height above the roof line. For two story applications, a re stop is required at each
oor level. If an offset is needed in the attic, additional pipe and elbows will be required. To connect the
venting system to the appliance ue outlet, a twist-lock adapter is built into the appliance at the factory.
Refer to initial inStallation - vent confiGurationand reStrictor SettinGS for venting parameters.
Page 14
Initial Installation
QUALIFIED INSTALLERS ONLY
Round Support
Box/Wall Thimble
Your total vent pipe length must be within the
shaded area of Figure 23. If a 90° elbow is used
in the horizontal plane, 36” (91.4 cm) must be
subtracted from the allowable horizontal run.
Horizontal
Termination
Pipelength
90° Elbow
Pipelength
Figure 15: Common Horizontal Installation.
36" (915 mm)
Snorkel
There are three (3) basic types of Direct Vent
System installations. The three (3) types of
installations are shown in Figures 15 through
17.
Vertical
Termination
Storm Collar
Flashing
Ceiling Firestop
Round Support
Box/Wall Thimble
Cathedral Ceiling
Support Box
14
Round Support
Box/Wall Thimble
Onto Stove
Adaptor
Figure 17: Common Snorkel Installation.
2 ft (610 mm)
Pipelength
Pipelength
Pipelength
Figure 16: Common Vertical Installation.
Page 15
Initial Installation
QUALIFIED INSTALLERS ONLY
vent teRmination RestRictions:
N
O
D
E
C
B
L
F
Fixed
Closed
Openable
B
B
Openable
Fixed
Closed
H
G
G
M
B
A
J
I
Termination Cap
Figure 18. Vent Termination Restrictions, refer to Table 3.
Table 3: Vent termination clearances, refer to Figure 18.
LetterCanadian Installation
A12 in (30 cm)Clearance above grade, verandah, porch, deck, or balcony.
B12 in (30 cm) 9 in (23 cm)Clearance from window or door that may be opened.
C12 in (30 cm)*Clearance from permanently closed window (to prevent
D24 in (60 cm)*Vertical clearance to ventilated soft located above the
E18 in (45 cm)*Clearance to unventilated soft.
F12 in (30 cm)*Clearance to outside corner.
G12 in (30 cm)*Clearance to inside corner.
H3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly
I3 ft (91 cm)3 ft (91 cm)*Radial clearance around service regulator vent outlet.
J12 in (30 cm)9 in (23 cm)Clearance to non-mechanical air supply inlet to building, or
K6 ft (1.83 m)3 ft (91 cm) above if within 10
L7 ft (2.13 m
M12 in / 30 cm
N12 in (30 cm)*Clearance horizontally to any surface (such as an exterior
O12 in (30 cm)Clearance above roof line for vertical terminations.
1
In accordance with the current CSA B149, Natural Gas and Propane Installation Code.
2
In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.
* These numbers are only estimates. Clearance in accordance with installation codes and the requirements of the gas supplier.
t
A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings and it serves both dwellings.
+
Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
1
)t
+
NOTE: Venting terminals shall not be recessed into walls or siding.
Air Supply Inlet
US Installation
3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly*
ft (3 m) horizontally
7 ft (2.13 m)
12 in / 30 cm*
2
*t
+
Gas MeterG
condensation).
terminal, within a horizontal distance of 2 ft (60 cm) from
center line of terminal.
Clearance to each side of center line extended above
meter/regulator assembly.
the combustion air inlet to any other appliance.
Clearance to mechanical air supply inlet.
Clearance above paved sidewalk or paved driveway located
on public property.
Clearance under verandah, porch, deck, or balcony.
wall) for vertical terminations.
Restriction Zone
(Termination not allowed)
Description
K
A
15
Page 16
Wire
spacers
Initial Installation
QUALIFIED INSTALLERS ONLY
FiRePLace hoRizontaL vent Kit 50-1235:
Please read and understand these instructions before installing. Failure to follow
these instructions carefully could cause property damage or personal injury.
KIT COMPONENTS:
QntyDescriptionQntyDescription
1Horizontal direct vent termination cap4Wire spacers
Please ensure that all components are supplied with this kit. If components are missing or have
been damaged, contact your dealer, distributor, or courier company. Do not attempt the installation if
components are missing or damaged.
INSTALLATION INSTRUCTIONS:
1. Plan your installation and clearances to combustibles. Decide on a location for the unit that will meet
the clearances noted in the venting section, and any or all local code requirements.
2. Set the appliance in the desired location. Determine if any wall studs, electrical wiring, or plumbing
pipes are in the way of the venting system as it passes through the exterior wall. The replace location
should be adjusted if obstructions are found in the wall.
3. Project a line from the center point of the ue outlet upward and outward to the desired ue outlet
location on the exterior wall. Using this center point, scribe a 10” (25.4 cm) hole or square on the wall.
Cut the hole from the interior through the exterior wall surfaces.
4. Frame the hole as shown in Figure 26.
5. Trim the wall thimble to match the wall thickness as necessary. Install the wall thimble and secure
it to the inner wall frame using four (4) 1½” wood screws. If a wall is
greater than 8” (203mm) in depth, the clearance above the ex must be
4⅜” (111mm)
6. Apply a bead of Mill-Pac Black sealant to the new Ø4” (10 cm) by 5” (12.5
cm) provided ue collar adaptor. Press the ue collar into the ue outlet of
the replace so that the Mill-Pac seals the ue collar to the ue outlet.
7. Stretch both the Ø4” (10 cm) ex vent and the Ø6⅝” (16.25 cm) ex intake
liner to the length needed to ensure the ex can be easily connected to the
vent terminal.
8. Slide the Ø6⅝” (16.25 cm) ex intake liner
over the ex vent. Install four (4) wire
spacers around the ex pipe. Ensure the
wire spacers are positioned at either end of
the pipes, and at each end of any elbows in
the liners (refer to Figure 19 and 20).
9. Install the ex pipe assembly through
the wall thimble, ensure that this portion
of pipe slides through the outside wall
far enough to connect onto the vent
Figure 19: Wire Spacers.
termination cap.
9
/16” tech screws
Figure 20: Wire Spacer in Place.
16
Page 17
Flue Pipe Adaptor
Wall Framing
Wall Thimble
Fire Stop
Exhaust 4" Flex Pipe
Combusion Air 6
5
/8" Flex Pipe
Wire Spacers
Horizontal Vent Termination
Initial Installation
QUALIFIED INSTALLERS ONLY
10. Apply a bead of Mill-Pac Black sealant to
the top section of the Ø4” (10 cm) by 5”
(12.5 cm) ue collar adaptor previously
installed into the replace ue outlet.
Slide the Ø4” (10 cm) ex vent over
the ue collar and secure with three (3)
sheet metal screws evenly spaced.
11. Place a bead of high temperature
silicone on the intake collar of the
replace, slide the Ø6⅝” (16.25 cm)
ex intake liner over the collar, secure
the ex liner with three (3) sheet metal
screws evenly spaced.
12. On the outside of the exterior wall,
apply a bead of Mill-Pac Black sealant
to the Ø4” (10 cm) pipe of the vent
terminal. Slide the ex liner onto the
vent terminal and secure with three (3)
sheet metal screws evenly spaced.
13. Place a bead of high temperature
silicone on the intake collar of the vent
terminal, slide the Ø6⅝” (16.25 cm)
ex intake liner over the collar, secure
the ex liner with three (3) sheet metal
screws evenly spaced.
14. Attach the vent terminal to the outside of the house using four (4) wood screws provided.
15. Light the appliance and ensure proper operation.
Figure 21: Installation of Fireplace Horizontal Vent Kit.
otheR aPPRoveD vent PaRts:
Table 4: Approved Vent Manufacturers
ManufacturerTrade NameNominal Sizes
American Metal ProductsAmeriVent Direct4” - 6 5/8”
Security Chimneys International LTDSecure Vent4” - 6 5/8”
Selkirk MetalbestosDirect-Temp4” - 6 5/8”
Simpson Dura-VentDirect Vent GS4” - 6 5/8”
The Westport replace has been tested and certied for use with AMERICAN METAL PRODUCTS
“AMERIVENT DIRECT”, SIMPSON DURAVENT TYPE GS PIPE FOR GAS STOVES. SECURITY CHIMNEY’S
“SECURE VENT DIRECT VENT SYSTEM” and SELKIRK “DIRECT-TEMP VENT SYSTEM” kits are available
for horizontal and vertical venting. When using Simpson Duravent, it is recommended that, before
installation, a bead of RTV High Temperature Silicone should be applied to each outer vent joint, and MilPac to each inner joint. When planning an installation, it will be necessary to select the proper length of
vent pipe for the particular requirements.
WARNING: Do not mix parts from different vent manufacturers’ systems.
17
Page 18
Initial Installation
QUALIFIED INSTALLERS ONLY
EXCEPTION TO WARNING: This product has been evaluated by Intertek for using a Direct Vent GS
starting collar in conjunction with Secure Vent, Direct-Temp, and Ameri Vent Direct venting systems. Use
of these systems with the Direct Vent GS starting collar is deemed acceptable and does not affect the
Intertek WH listing of the appliance.
Table 5: Vent part numbers (Must state if galvanized or black wanted, PART NUMBERS).
Direct Vent GSDirect-Temp Secure VentAmeri Vent DirectDescription
9084DT-6SV4L66” pipe length
4D77” pipe length
9074DT-99” pipe length
9064DT-12SV4L124D1212” pipe length
9044DT-24SV4L244D224” pipe length
9034DT-36SV4L364D336” pipe length
9024DT-48SV4L484D448” pipe length
9454DT-EL45SV4EBR454D45B45° elbow, black
9904DT-EL90SV4EBR904D90B90° elbow, black
9504DT-VSSV4VSVinyl siding standoff/sheild
9424DT-WTSV4RSN4DWTWall thimble
9534DT-SCSV4FC4DSCStorm collar
9634DT-FSSV4BF4DFSPFire stop
9884DT-WS/BSV4BM4DWSWall strap/support/band
9704DT-HKASV0SHK4DHTK1
91111” to 14 ⅝” pipe, adjustable
4DT-AJ4D12A4” to 10” pipe , adjustable
SV4LA121½” to 12” pipe , adjustable
9434DT-AF64DFFlashing, 0/12 to 6/12 roof pitch
943S4DT-AF124DF12Flashing, 7/12 to 12/12 roof pitch
SV4FAFlashing, 1/12 to 7/12 roof pitch
SV4FBFlashing, 8/12 to 12/12 roof pitch
943FSV4FFlat ashing
9804DT-VCSV4CGV4DVCVertical termination
9914DT-HVCHigh wind vertical termination
Horizontal termination kit (SD: Basic Kit,
SEL: Kit A, SC: Standard Kit)
Figures 23 & 24 show the range of venting options, they show possible vent congurations if the unit is
top vented (see Figure 23) or rear vented (see Figure 24), for vertical and horizontal terminations, any
layout that remains within the shaded area is acceptable. Having the fewest number of elbows is ideal,
as they tend to disrupt air movement. Using 45˚ elbows is preferable to using 90˚ elbows. Also, a shorter
vent system will perform better than a longer one.
The ENVIRO WESTPORT has been designed with a built in restrictor
plate. The restrictor is designed to enhance ame appearance when
installing this unit with vertical chimneys as well as installations with
longer horizontal vent applications. It does this by controlling the
amount of air moving through the vent pipe.
Figure 23 shows the vent restrictor position required, relative to the
length of vent pipe. Longer vertical vent lengths necessitate greater
restriction; position 1 is open and position 5 is maximum restriction
(refer to Figure 22). To avoid injury, it is best to make this adjustment
when the replace is cool or use welder’s gloves or oven mitts.
Figure 22: Restrictor plate settings.
View showing fully
closed restrictor plate
View showing fully
open restrictor plate
1
2
3
4
5
1
2
3
4
5
Note: 0,0 in Figures 23 & 24 represent
the outlet of the ue collar elbow.
To access vent restrictor remove the valve
cover plate from the right rear corner of the
unit by undoing the two fastening screws.
Loosen the ¼” hex head screw and adjust to
the correct setting.
Slide the hex head screw to the next setting
and re-tighten the screw to secure in place.
The numbers in this chart represent the actual
vent restrictor settings. Although the numbers
do not appear on the unit use this as a guide
to follow.
Wait for unit to warm up to operating
temperature to ensure proper and clean
burning unit.
Figure 23. Possible Vent Congurations for Top Vented;
Vertical and Horizontal Terminations.
Figure 24. Possible Vent Congurations for Rear
Vented; Vertical and Horizontal Terminations.
19
Page 20
Initial Installation
QUALIFIED INSTALLERS ONLY
hoRizontaL instaLLation:
1. Set the appliance in the desired location. Check to determine if wall studs or roof rafters are in the
way when the venting system is attached. If this is the case, you may want to adjust the location of
the appliance.
2. Direct vent pipe and ttings are designed with special twist-lock
connections. Assemble the desired combination of black pipe and
elbows to the appliance adapter with pipe seams oriented towards
the wall or oor, as much out of view as possible.
Place a bead of Mil-Pac on the outer edge of the inner exhaust pipe
(non-ared end). Place a bead of high temperature silicone on the
male edge of the outer pipe. Push the pipe sections completely
together, then twist-lock one section clockwise approximately ¼
turn, until the two sections are fully locked. The female locking
lugs will not be visible from the outside, on black pipe. They may
be located by examining the inside of the female ends as shown in
Figure 25.
Notes:
(a) Twist-lock procedure: four (4) indentations, located on the female
end of the pipes and ttings, are designed to slide straight onto the
male ends of adjacent pipes and ttings, by orienting the four pipe
indentations so they match and slide into the four entry slots on the
male end.
(b) Horizontal runs of vent pipe must be supported every 36” (915mm).
Wall straps are available for this purpose, also when running horizontal
pipe minimum clearances to combustibles must be maintained;
2” (51mm) at top, 1½” (38mm) at sides, 1½” (38mm) at
bottom.
Sealant
Figure 25: Twist-Lock Connection
10"
(254mm)
10"
(254mm)
Female
Locking
Lugs
Male
Locking
Lugs
3. With the pipe attached to the stove in the correct location, mark the
wall for a 10” (25.4cm) x 10” (25.4 cm) square hole (refer to Figure
26). The center of the square hole should match the center line of
the horizontal pipe. Cut and frame the 10” (25.4cm) x 10” (25.4cm)
hole in the exterior wall where the vent will be terminated. Refer to
Figure 18. If the wall being
1
/4"
penetrated is constructed of
non-combustible material i.e.
masonry or concrete, a 7”
(17.8cm) hole is acceptable.
1
(3.2cm)
Fold strap
here
4. Position the horizontal vent
termination in the center
of the 10” (25.4cm) x 10”
Sheet metal
screws
(25.4cm) hole, and attach
to the exterior wall with
the four screws provided.
Before attaching the vent
termination to the exterior
20
Wall Thimble
Strap
Figure 27: Installing Decorative Wall Thimble.
Figure 26: Wall Framing Hole for
Horizontal Installation.
Woodscrews
Page 21
Initial Installation
Woodscrews(x4)
Cutvinylsidingawaytofitstandoff
Bolt(x4)required
Nut(x4)required
Woodscrew(x4)
QUALIFIED INSTALLERS ONLY
wall, run a bead of non-hardening mastic around the edges, so as to make a seal between the
termination and the wall. The arrow on the vent termination should be pointing up, insure that the
proper clearances to combustible materials are maintained.
5. Before connecting the horizontal run of the vent pipe to the vent termination, slide the black decorative
wall thimble cover over the vent pipe.
6. Slide the appliance and vent assembly towards the wall, carefully inserting the vent pipe into the
cap assembly. It is important that the vent pipe extend into the vent cap a sufcient distance with a
minimum of 1¼” (3.2cm) overlap. Secure the connection between the vent cap pipe and the vent cap
by attaching the two sheet metal straps extending from the vent cap assembly into the outer wall of
the vent pipe. Use the two sheet metal screws provided to connect the straps to the vent pipe. Bend
any remaining portion of the sheet metal straps back towards the vent cap, so the decorative wall
thimble will conceal it (see left image in Figure 27).
7. Slide the decorative wall thimble up to the wall surface and attach with the screws provided. Apply
decorative brass or chrome trim if desired (see right image in Figure 27).
NOTES:
(a) The four (4) wood screws provided should be replaced with the appropriate fasteners for stucco,
brick, concrete, or other types of siding.
(b) For buildings with vinyl siding, a vinyl siding standoff, should be installed between the vent cap and
the exterior wall (see Figure 28). Attach the vinyl siding standoff to the horizontal termination. The vinyl
siding standoff prevents excessive heat from possibly melting the vinyl siding material. Note that the
horizontal vent termination bolts onto the at portion of the vinyl siding standoff (shaded area in Figure
28), so that an air space will exist between the wall and the vent termination.
(c) Thehorizontal run of vent pipe must be level and should have a ¼ inch rise for every one
foot of run towards the termination. Never allow the vent to run downward. This could cause high
temperature and may present the possibility of a re.
(d) The location of the horizontal vent termination on the exterior wall must not be easily blocked or
obstructed. Refer to
(e) When installing a vent pipe in a chase the minimum clearance to combustibles is 2” (51 mm).
(f) Maintain manufacturer’s clearances to combustibles with venting.
1. Check the instructions for required clearances (air spaces) to combustibles when passing through
ceilings, walls, roofs, enclosures, attic rafters, or other nearby combustible surfaces. Do not pack air
spaces with insulation.
2. Set the gas appliance in the desired location. Drop a plumb bob down from the ceiling to the position
of the appliance ue exit, and mark the location where the vent will penetrate the ceiling. Drill a small
hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling,
mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters, or other
framing will obstruct the venting system. You may wish to relocate the appliance, or to offset, to avoid
cutting load bearing members.
3. To install the Round Support Box/Wall Thimble in
a at ceiling, cut a 10” square hole in the ceiling,
centered in the hole drilled in Step 2. Frame the
hole as shown in Figure 30.
4. Assemble the desired lengths of black pipe and
elbows necessary to reach from the appliance
adapter up through the Round Support Box.
Insure that all pipe and elbow connections are in
their fully twist-locked position.
5. Cut hole in the roof centered on the small
hole placed in the roof from Step 2. The hole
should be of sufcient size to meet minimum
requirements for Clearance to Combustibles, as
specied. Continue to assemble lengths of pipe
and elbows necessary to reach from the ceiling
support box up through the roof line. Galvanized
pipe and elbows may be utilized in the attic, as
well as above the roof line. The
galvanized nish is desirable
above the roof line, due to the
higher corrosion resistance.
Elbow Strap
6. Once the pipe sections have
been joined, and run up through
the hole in the roof, slip an elbow
strap over the exposed sections,
bend the support straps
outwards, and push the elbow
strap down to the roof level, as
shown in Figure 31. Tighten the
clamp around the pipe section.
Use a level to make sure the
pipe is truly vertical. With
roong nails, secure the support
straps to the roof. Seal the nails
holes heads with non-hardening
mastic. Trim the excess length of
the support straps that extend out beyond the edge of the ashing.
7. Slip the ashing over the pipe section protruding through the roof. Secure the base of the ashing to
the roof with roong nails. Use a non-hardening sealant between the uphill edge of the ashing and
the roof. Insure the roong material overlaps the top edge of the ashing as shown in Figure 30. Verify
that you have at least the minimum clearance to combustibles at the roof line.
8. Continue to add pipe sections until the height of the vent cap meets the minimum code requirements.
Refer to Figure 32 and Table 6. Note that for steep roof pitches, the vent height must be increased. In
high wind conditions, nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors
can result in poor draft, or down drafting. In these cases, increasing the vent height may solve the
problem.
9. Slip the storm collar over the pipe, and push it down to the top of the roof ashing as shown in Figure
31. Use the non-hardening sealant around the joint between the pipe and the storm collar.
10. Twist-lock the vent cap.
Figure 32: Height of Vertical Termination;
Reference Table 6.
Table 6: Minimum ‘H’ for Figure 32.
Roof PitchMinimum Height
FeetMeters
Flat to 7/1210.3
Over 7/12 to 8/121.50.46
Over 8/12 to 9/1220.61
Over 9/12 to 10/122.50.76
Over 10/12 to 11/123.250.99
Over 11/12 to 12/1241.22
Over 12/12 to 14/1251.52
Over 14/12 to 16/1261.83
Over 16/12 to 18/1272.13
Over 18/12 to 20/127.52.29
Over 20/12 to 21/1282.44
NOTES:
(a) If an offset is necessary in the attic to avoid obstructions, it is important to support the vent pipe
every 3 feet (91 cm), to avoid excessive stress on the elbows, and possible separation. Wall straps
are available for this purpose (see Figure 33).
(b) When ever possible, use 45° degree elbows instead of 90° degree elbows. The 45° degree elbow
offers less restriction to the ow of ue gases and intake air.
(c) For multi story installations. A ceiling restop is required at the second oor, and any subsequent
oors (see Figure 34). The opening should be framed to 10” (25.4 cm) x 10” (25.4 cm) inside
dimensions, in the same manner as shown in Figure 30.
(d) Any occupied areas above the rst oor, including closets and storage spaces, which the vertical vent
passes through, must be enclosed. The enclosure may be framed and sheet rocked with standard
building materials. However consult the appliance manufactures installation instructions for the
minimum allowable clearance between the outside of the vent pipe, and the combustible surfaces of
the enclosure. Do not ll any required air spaces with insulation.
2. Using the plumb bob, mark the centerline of
the venting system on the ceiling and drill a
small hole through the ceiling and roof at this
point. From the roof, locate the drill hole and
mark the outline of the “Cathedral Ceiling
Support Box”.
3. Remove shingles or other roof coverings as
necessary to cut the rectangular hole for the
“Support Box”. Cut the hole ⅛” larger than
the “Support Box” outline.
4. Lower the “Support Box” through the hole in
the roof until the bottom of the “Support Box”
protrudes at least 2 inches (5 cm) below the
ceiling. Align the “Support Box” both vertically
and horizontally with a level as shown in
Figure 35. Temporarily tack the “Support Box”
in the place through the inside walls and into
the roof sheathing.
24
Figure 35: Cathedral Ceiling Support Box Leveling.
Page 25
Initial Installation
21/2”(67mm)
InsideWall
OutsideWall
36”(915mm)Snorkel
OutsideWall
OutsideWall
21/2”(67mm)
QUALIFIED INSTALLERS ONLY
5. Using tin snips, cut the “Support Box” from the top corners
down to the roof line, and fold the resulting aps over the
roof sheathing (Figure 36). Before nailing it in to the roof,
run a bead of non-hardening mastic around the top edges
of the “Support Box”, to make a seal between the box and
the roof. Clean out any combustible material from the
inside of the “Support Box”.
6. Complete the cathedral ceiling installation by following the
same procedures outlined in Steps 4 through 9 for
inStallation - vertical inStallation.
coRneR instaLLations:
Do not interfere with the structural integrity of the walls.
When rear venting if a 90° bend is used the maximum horizontal vent that can be used is 6” (152mm)
and if a 45° bend is used the maximum horizontal vent that can be used is 12” (305mm). For installations
with a 36” (915 mm) snorkel refer to Figure 37 and
SettinGS. For other corner installations refer to Figure 38 and initial inStallation - vent confiGurationSand
reStrictor SettinGS.
This model is also certied and tested to vent into CLASS ‘A’ wood stove chimneys.
Place the freestanding direct vent appliance in the desired location.
Use a conversion kit from Simpson Duravent (931, 932,
or 933), or Security Chimney (SV4CCK1, SV4CCK2, or
SV4CCK1). Which kit is used will depending on the inner
diameter of the CLASS ‘A’ chimney that this appliance is
to be vented into.
Place a bead of high temperature silicone or mil-pac at
each connection to ensure a tight seal.
NOTE: An approved 4” (10 cm) diameter ex liner must
be used in the application.
NOTE: Use Simpson Dura Vent from the top of the
appliance until this vent reaches the CLASS ‘A’ chimney.
Install the retro adapter to the top section of GS direct
vent pipe and install the ex liner to the retro adapter.
Fully line the CLASS ‘A’ chimney with a minimum 4” (10
cm) ex liner to the top of the CLASS ‘A’ chimney.
Place a bead of high temperature silicone to the Simpson
Cap adapter and securely attach the ex liner to the
adapter.
Secure the cap adapter to the CLASS ‘A’ chimney
ensuring an airtight seal.
Install the vertical termination cap.
Light the unit and ensure proper operation.
THE USE OF ANY EXISTING CHIMNEY AS AN AIR INTAKE
IS NOT COVERED UNDER THE ANSI Z21.88-2002 CSA
2.33a-2002 TEST METHODS AND THE RESULTING ITS/
WH PRODUCT CERTIFICATION. THE CODE AUTHORITY
HAVING JURISDICTION MUST BE CONSULTED PRIOR
TO PROCEEDING WITH THIS INSTALLATION METHOD.
conveRting toP venteDinto ReaR venteD:
This unit has been shipped as a 30,000 Btu/hr top-vented freestanding unit. This unit can be converted
to a rear vented unit with a 36” (915 mm) snorkel for some installation applications.To convert this unit
to a rear vented model you must remove the ue pipe adapter and turn to the rear vent position. See
sections initial inStallation - inStallationof rear vented aPPliance.
1. Carefully remove the trivet and the stovetop. Place on a soft surface as not to damage the porcelain
nishes.
Figure 39: Assembly of Venting into a Class ‘A’
Chimney.
26
Page 27
Initial Installation
QUALIFIED INSTALLERS ONLY
2. Remove the four (4) ¼” screws that hold the ue collar elbow to the unit body (see Figure 40).
3. Carefully remove the elbow being sure not to damage the gasket that is glued to the ue collar elbow,
it seals the ue to the rebox.
4. Turn the elbow to the rear vent position and re-fasten with the screws removed in step 2 (see Figure
41).
Firebox Top
Flue Collar
Adapter
Undo four ¼"
screws that
hold flue collar
elbow to unit.
Figure 40: Step 3 of Converting Top Vented into
Rear Vented.
Figure 41: Step 4 of Converting Top
instaLLationoF ReaR venteD aPPLiance:
Place the unit into position.
Attach a small section of pipe on the unit and mark exterior wall
where vent would pass through the wall.
Cut a 10” (25.4 cm) minimum hole in the wall to maintain
clearances to combustibles. Frame hole as shown in Figure 26.
Install a wall thimble.
Install interior nished collar.
Install the vent section through the wall.
THIS UNIT MUST BE VENTED WITH A 36” (91 cm) SNORKEL KIT
IF UNIT IS RATED FOR 30,000 Btu/hr NG and 26,000 Btu/hr LP.
Seal around the vent terminal to the structure using a non
hardening mastic.
Minimum vent terminal 36"
(91.4cm) high snorkel kit.
Siding
Exterior wall
Drywall
Wall thimble
Inside finished collar
Vent pipe
Figure 42: Installation for Rear Vented;
30,000 Btu/hr.
27
Page 28
Initial Installation
QUALIFIED INSTALLERS ONLY
instaLLationoF toP venteD; hoRizontaL teRmination:
This is the most common type of installation style.
Set the unit in place.
Install a minimum 24” (61 cm) vertical chimney.
Install a 90° elbow, and mark the exterior wall where the vent would
pass through.
Cut a 10” (25.4 cm) minimum hole in the wall to maintain clearances
to combustibles around vent pipe. Frame hole if as shown in Figure
26.
Install wall thimble.
Install interior nished collar
Install the vent section through the wall and then install the vent
termination.
Seal around the termination using a non hardening mastic.
CORNER INSTALLATION:
This type of installation can be used in a corner installation. If a
90° elbow is used in the horizontal plane, 36” (91.4 cm) must be
subtracted from the allowable horizontal run shown in Figure 23.
instaLLationoF toP venteD; veRticaL teRmination:
Termination
Inside
finished collar
Wall thimble
Vent pipe
Drywall
Exterior wall
Siding
Figure 43: Installation for Top
Vented; Horizontal Termination.
Place the unit in place.
Drop a plumb bob from the ceiling to the center point of the
ue outlet.
Cut a 10” (25.4 cm) hole in the ceiling and the roof. Refer to
Figure 30.
Install the ceiling support and insulation guard.
Install the roof ashing. Ensure that the roof ashing is
installed under the roong material so that a watertight seal
is created.
Install the ue pipe from the top of the unit through the
roof.
Ensure that all ue pipe and unit maintain required clearances
to combustibles.
CORNER INSTALLATION:
This type of installation can be used in a corner installation.
If a 90° elbow is used in the horizontal plane, 36” (91.4 cm)
must be subtracted from the allowable horizontal run shown
in Figure 23.
Vent cap
Roof flashing
Roof
truss
Insulation
gaurd
Ceiling
support
Inside
finished collar
Flue pipe
Figure 44: Installation for Top Vented;
Vertical Termination.
28
Page 29
Initial Installation
QUALIFIED INSTALLERS ONLY
FReestanDing DRaFthooD aDaPtoR - 50-841:
This Drafthood Adaptor is a complete assembly and is ready to t onto your Westport in a vertical vent
application only. With the Drafthood Adaptor correctly installed and wired to the gas control valve. Your
Direct Vent Fireplace can be vented like a B-Vent Fireplace.
INSTALLATION:
WARNING: This Freestanding Drafthood Adaptor must be tted by a qualied service technician.
1. Remove the Drafthood Adaptor from the packaging. Ensure the unit and wire harness are undamaged. If
there is damage contact your dealer, distributor, or courier company before starting this installation.
2. Install the adaptor so the wires exit to the rear of the replace. Slide the Drafthood Adaptor over the
outlet pipe of the replace until the bottom of the adaptor collar stops on the top of the outlet. The
Drafthood Adaptor must be safely secured to the vent anges with either self-tapping screws and/or
high temperature sealant.
WARNING: During the tting of the Drafthood Adaptor, ensure that the wires are not pinched between
the adaptor and the collar and/or ue outlet. Ensure that the opening of the Drafthood Adaptor is not
blocked or obstructed.
3. Being careful not to run any wiring tight across metal edges; connect them to the valve and “ON/OFF”
switch (refer to Figure 45).
4. Adjust the restrictor plate
to position 2.5 of 5. See the
vent restrictor settings in
the instruction manual.
5. Adjust the embers on the
burner so they don’t cover
the burner ports.
WIRING DIAGRAM:
The replace connections
are labelled in Figure 45.
When installing the Drafthood
Adaptor onto a replace tted
with an optional wall switch or
an optional thermostat, remove
one wire from the switch to
the gas valve and connect the
Drafthood Adaptor harness as
shown in Figure 45.
Optional remote
control receiver
Purple
Figure 45: Wiring Diagram for Electrical Connection.
ON / OFF / Remote
thermostat switch
Grey
Blue
Optional
wall switch
Optional
Thermostat
Valve
Drafthood adaptor
o
300
F (149oC)
manual reset
temperature
sensor
Grey
Grey
GENERAL VENTING INFORMATION:
Canadian Installations
The venting system must be installed in accordance with the current CSA B149 installation code and/or
local codes having jurisdiction.
U.S.A. Installations
The venting system must be installed in accordance with the current National Fuel Gas Code, ANSI
Z223.1, and/or local codes having jurisdiction.
29
Page 30
Initial Installation
The minimum clearance to combustibles is 6” (150 mm) when using single wall venting and 1” (25 mm)
when using “B-vent” venting.
We strongly recommend installing an approved chimney liner in an existing brick chimney. This will
maximize the potential draft of the chimney and lessen the effects of slow chimney start-up.
VENTING OF A FIREPLACE FITTED WITH THE DRAFTHOOD ADAPTOR:
Note: Please refer to the chimney manufacturer’s installation instructions prior to commencing the
installation.
This unit may be vented to an existing masonry
chimney, or where no masonry chimney is available,
an approved “B-vent” chimney, or any other approved
constructed chimney/vent system (see Figure 46 &
47).
In either case, the replace may be connected to
the chimney/vent using a 4” (10 cm) single wall vent
connector.
When an existing masonry chimney is utilized for
the venting, we recommend the vent connector be
connected to an approved 4” (10 cm) diameter ue
liner running the full height of the chimney. In many
jurisdictions this ue liner may be mandatory.
6" (15cm)
optional
decorative
cover
4" (10cm)
vent
If 4” (10 cm) single wall vent is used, a minimum of
6” (15 cm) must be maintained between the vent
connector and any combustibles.
If 4” (10 cm) “B-vent” is used a minimum of 1” (25
Figure 46: Unit top venting styles.
mm) must be maintained between the vent connector and any combustibles.
CAUTION: A minimum vent height of 12’ (3.6 m) from the oor is required to effectively vent this
replace.
SPILLAGE TEST:
A spillage test must be performed prior
to leaving the installed replace with the
customer. Perform this test in the following
Check vent draft
at the top row of
opening.
manner:
1. Close all windows and doors in the room.
2. Start all exhaust fans in the house and the
furnace blower.
3. Light the replace and set to maximum
ame adjustment.
4. After a minimum of 10 minutes operation,
test the chimney draft with a smoke match
Figure 47: Unit rear
venting style.
at the top row of the pattern to conrm
that there is adequate draft or ‘pull’ at the
openings around the body of the Drafthood
Figure 48: Draft test place.
Adaptor, as shown in Figure 48.
30
Page 31
Initial Installation
AUTOMATIC SAFETY SHUT DOWN:
If the spill switch is activated and shuts off the main burner the following procedure should be
followed.
• Is the pilot ame still on? If not, the reason for the replace shut down is not the spill switch.
• Turn off the pilot ame and turn off all controls. Let replace to cool down.
• Check for blockages or restrictions in the ue and venting components.
• Restart the replace and check for vent draft as described earlier.
• Operate the replace in a normal manner.
• If the main burner shuts down again after a period of operation, turn off the replace and contact your
service technician.
SPILL SWITCH REPLACEMENT:
Use the following instructions to replace the
Safety Spill Switch.
1. Turn the unit off and allow it to cool.
2. Disconnect the spill switch wires from the
valve and on/off/remote rocker switch wire
(see Figure 45).
3. Remove the four mounting screws holding
the spill switch bracket and remove the
bracket (see Figure 49).
4. Remove and replace the spill switch with a
50-885 Spill Switch Assembly using a T-20
torx type driver.
5. Follow the reverse of the previous steps.
OPTIONAL FINISHING:
In installations where the ue connector is running from the drafthood into a non-combustible chimney
the following optional nishing technique can be used.
CAUTION: Installations where the ue connector or venting connects to, or passes through,
combustible walls or ceilings, the inner vent components must be ‘B-vent’. It is not allowable
in these applications to use single wall inner vent components.
For decorative purposes a 6” (15 cm) single wall black stove pipe may be installed over the 4” (10 cm)
single wall or ‘B-Vent’.
Note: The use of these components is for aesthetic purposes only and does not effect the
fact that the replace, when tted with the Drafthood Adaptor, is a Natural Vent appliance
and therefore draws air in through the Drafthood Adaptor intake ports.
Figure 49: Spill switch installation.
31
Page 32
Initial Installation
QUALIFIED INSTALLERS ONLY
gas Line connectionanD testing:
WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to
this appliance.
GAS LINE CONNECTION
Manifold
Pressure Tap
Inlet
Pressure Tap
•This stove is equipped with a certied exible pipe
located on the right side of the unit terminating in a ⅜”
male NPT tting. Consult your local authorities codes or
the CAN/CGA B 149 (1 or 2) installation code in Canada,
or in the USA gas installations follow either local codes
TP TH TP TH
O
L
H
I
IN OUT
F
O
F
P
I
L
O
T
O
N
or the current edition of the National Fuel Gas Code ANSI
P
I
T
L
Z223.1.
O
•The efciency rating of this appliance is a product
thermal efciency rating determined under continuous
operating conditions and was determined independently
of any installed system.
Pilot Adjustment
Screw
Figure 50: Fully Labeled Gas Valve.
Hi/Low
Knob
Gas Control
Knob
The appliance and its shutoff valves must be disconnected from the gas supply piping system during any
pressure testing where the pressure exceeds ½ PSIG (3.45 KPa) or damage will occur to the valve.
The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply piping system at test pressures equal to or less than
½ psig (3.45 KPa).
Always check for gas leaks with a soap and water solution after completing the
required pressure test.
TO TEST VALVE PRESSURES
The pressure taps are located on the left side of the valve
• Turn set screw 1 turn counter clockwise to loosen,
• Place 5/16” (8 mm) I.D. hose over pressure tap system.
• Check pressures using a manometer.
• When nished, release pressure, remove hose & tighten set screw.
Min. Manifold Pressure1.1” W.C. / 0.27KPa2.7” W.C. / 0.67KPa
Max Supply Pressure7.0” W.C. / 1.74KPa13.0” W.C. / 3.28KPa
Min. Supply Pressure5” W.C. / 1.24KPa12.0” W.C. / 2.98KPa
Max BTU/hr Input30,000 BTU/hr (8.80KW)26,500 BTU/hr (7.76KW)
Min. BTU/hr Input17,000 BTU/hr (4.98 KW)14,000 BTU/hr (4.10KW)
Venturi Setting
1
/16” min.
3
/16” min.
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
Page 33
Initial Installation
QUALIFIED INSTALLERS ONLY
eLectRicaL RequiRements FoR gas vaLveanD oPtionaL bLoweR:
The ENVIRO WESTPORT will operate without electrical power. This model has a millivolt gas control,
which uses the pilot ame to generate enough electricity to operate the main burners. The appliance
when equipped with an optional blower must be electrically connected and grounded in accordance with
local codes or in the absence of local codes, with the current CSA C22.1 CANADIAN ELECTRICAL CODE
Part 1, SAFETY STANDARDS FOR ELECTRICAL INSTALLATIONS, OR THE NATIONAL ELECTRICAL CODE
ANSI / NFPA 70 in the U.S.
ON/OFF/Remote
Thermostat Switch
Blue
Thermopile
Manifold
Pressure Tap
Gas Control
Valve
Thermocouple
Inlet
Pressure
Tap
70 ° F
O
Optional
Remote
Control
N
OFF
Purple
Grey
70 ° F
UP
DOWN
COOL / HEAT
PROGRAM
Optional
Wall Switch
Optional
Thermostat
Pilot Adjustment
Screw
Figure 51: Gas Control Valve and Optional Thermostat Wiring.
Table 8. Recommended Thermostat
Wire Size.
Fan
Wire SizeMax. Length
14 gauge100 ft (30.48 m)
16 gauge60 ft (18.29 m)
18 gauge40 ft (12.00 m)
20 gauge25 ft (7.62 m)
22 gauge18 ft (5.49 m)
White
White
Black
Fan
temperature
sensor
Power
Supply
Figure 52. Wiring Diagram For Fan Control.
Black
Fan
controller
CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation. Verify proper operation after servicing.
WARNING: Electrical grounding instructions. This appliance is equipped with a three-prong (grounding)
plug for your protection against shock hazard, and must be plugged directly into a properly grounded
three-prong outlet.
DO NOT cut or remove the grounding prong from this plug.
33
Page 34
Secondary Installation
PlacementPinforLeftRearLog
LedgeforLeftRearLog
instaLLationoF oPtionaL bLoweR:
1. Remove the pre-assembled blower from the packaging. Inspect the blower for damage. If damage
is noticed call your dealer, distributor or courier
company and have components replaced.
2. Ensure the temperature sensor will touch the
unit when mounted. If it does not touch, adjust
the sensor so it does.
2. Place the fan assembly behind the unit and
Control panel
(Fan control location)
Screw hole
Valve cover
Fan assembly
Figure 53: Optional Blower (Fan) Installation.
secure with the three screws provided, (as
shown in Figure 53).
3. Open the gas valve cover. Carefully cut the decal
portion on the control panel and install the fan
control switch in this location. See Figure 46 for
wiring of optional blower.
4. Plug the fan assembly into the wall outlet and
turn the unit on to ensure fan operation.
instaLLationoF Log setanD embeRs:
The placement of the logs is not arbitrary. If they are positioned incorrectly, the ames can be “pinched”
and will not burn correctly. The burner come with four (4) locator pins, and the right log has two (2)
ledges which make alignment easier. Using the pictures provided, carefully set the logs in place.
NOTE: The logs are fragile and
should be handled gently.
CAUTION: Use only the type of
ember material supplied with this
appliance. Due to the irregular
size of the ember material there
may be more than required. The
use of other foreign materials on
the burners may create dangerous
conditions.
If over time, through cleaning and
servicing, these embers require
replacement, contact the nearest
ENVIRO dealer for replacement
embers.
Figure 54: Step 1 of Log Placement.
34
Figure 55: Step 2 of Log Placement.
Page 35
PlacementforFrontLeftLog
LedgeforCenterLog
PlacementPin
forCenterLog
Secondary Installation
1. Carefully remove logs from
box. Check to ensure there is
no damage. It is very important
to install all logs in their proper
position to insure safe, optimum
operating conditions.
2. Place the log set into the
rebox. Locate each log by
seating it down onto the burner
tray support pins. Follow Figures
48 to 54 proper log placement.
3. A bag of ceramic ber
embers and rock wool embers
is provided gently remove the
ember material from the plastic
bag. Spread a layer loosely in
a random manner across the
burner tray. Do not allow any
embers to rest against pilot
assembly. (See diagram provided
for proper ember placement.)
Figure 56: Step 3 of Log Placement.
DO NOT pack this ember
material as this could create an
unsafe condition, leave embers
loose.
4. Upon the rst light up, watch
for ignition to ALL burner ports.
If a long delay is noted: First,
wait for the appliance to cool
down.
• Open the front door of the
appliance.
• Check to carefully reposition
the embers making sure that
burner ports are not plugged
solid or blocked.
Figure 57: Step 4 of Log Placement.
Figure 58: Complete Log Placement.
35
Page 36
Secondary Installation
Important note: When the unit is turned
on for the rst time, It should be turned onto
high without the fan on for the rst four (4)
hours. This will cure the paint, logs, gasket
material and the other products used in the
manufacturing process. It is advisable to
open a window or door, as the unit will start
to smoke and can irritate some people. After
the unit has gone through the rst burn turn
the unit off including the pilot, let the unit get
cold then remove the glass door and clean
it with a good gas replace glass cleaner,
available at your local ENVIRO dealer.
Maintenance and Service on how to remove
See
door to clean glass.
Figure 59: Log Placement with Rock Wool.
Figure 60: Log Placement with Rock Wool & Embers.
Figure 61: Appliance Burning.
CAUTION: NEVER OPERATE THIS APPLIANCE WITH THE GLASS DOOR REMOVED.
36
Page 37
Secondary Installation
instaLLationoF PaneL set:
Do not install when the unit is hot.
The brick panel set is fragile. Handle panels with care and avoid knocking them on the
placement pins or any other object.
1. Remove the two (2) screws from the
rear of the bafe, use a ¼” socket
or a at head screwdriver. Place the
provided brick bracket (Figure 62) at
the rear of the bafe with the slots
over the screw holes (see Figure 63).
Insert two (2) of the provided screws
into the two (2) holes along the
Figure 62: Brick panel bracket, slots shown.
bottom of the bafe.
Figure 63: Top brick panel in place, screws shown.Figure 64: Back brick panel in place.
2. Remove the two (2) screws from the front of the
bafe. Slide the top brick panel into the bottom
bracket and place the other brick bracket over the top
of the panel and line up the slots on the bracket with
the holes at the top of the bafe. Use two (2) of the
provided screws to hold the bracket in place. Ensure
the top panel is centered before tightening the four
(4) screws completely (refer to Figure 63).
3. Slide the bottom brick panel into place under/behind
the top panel bracket, the notched side is to rest on
the rebox bottom. The panel should rest ush with
the back of the rebox (refer to Figure 64).
4. Slide each side brick panel into place along the sides
Figure 65: Side brick panels in place.
of the rebox. The panels should rest ush with the
back panel and the sides of the rebox (refer to
Figure 65).
37
Page 38
Trouble Shooting
ProblemPossible CauseSolution
The main burner does not
ignite when called for.
Spark will not light the pilot
after repeatedly pressing the
spark ignitor.
Pilot will not remain lit.Problem with thermocouple
The gas valve may not be on.• Check that the gas control knob is in the “ON” position.
Thermostat is not calling for
heat.
Problem with gas valve.• Use a DC voltmeter to measure the voltage across the
Defective piezo ignitor.• Check connections to ignitor.
Broken spark electrode.• Check for broken ceramic insulation, replace electrode if
Misaligned spark electrode.• If spark is not arcing from electrode to pilot, loosen the
circuit.
• Adjust the thermostat several degrees above ambient
temperature.
TPTH and TP terminals. Main operator voltage: Open
circuit ≥ 325mV Closed circuit ≥ 100mV
• If voltage is not present, check the control circuit for
proper operation.
• If proper control system voltage is present, replace the
gas control.
• If ignitor connections are good but no spark, replace
ignitor.
broken.
screws on the pilot base adjust and tighten.
• Check for proper connection of the thermocouple to the
rear of the valve. If loose, fully tighten.
• Check pilot for full ame impingement around
thermocouple. If ame is too small, check gas pressure,
adjust pilot rate screw, check pilot head for damage.
• Check thermocouple voltage at valve. It must be greater
than 5 mV. If low, replace thermocouple.
Air in gas line (pilot dies while
knob is depressed).
Burners will not remain lit.Problem with thermopile
circuit.
Flame liftingLeak in vent pipe• Check for leaks in vent connections.
Improper vent conguration• Check vent conguration with manual.
Terminal may be recirculating
ue gases
Glass fogs upNormal Condition: after the appliance warms up the glass will clear.
**Due to additives in gas, glass may get hazy during operation** Clean as needed.
Blue FlamesNormal during start up: ames will yellow as the replace heats up.
Flames are burning “dirty” or
sooting
Remote control doesn’t workProblem with the remote• One or more of the batteries are dead. See remote
Flame impingement• Check log positioning.
Problem with replace• The on/off switch is turned to OFF.
• Bleed line.
• Check gas line pressure.
• Contact dealer.
• Check gas line pressure .
• Check for ame impingement on thermopile. If low, see
“Pilot will not remain lit”.
• Check thermopile for minimum of 300 mV when burner is
switched on.
• Check wiring to thermostat for breaks.
• Check to see if terminal is on correctly.
• May need to install high wind termination cap.
• Contact dealer.
• Increase primary air by opening the venturi shutter and/
or by opening the vent restrictor.
See also “Burners will not remain lit.”
control instructions.
• The gas control valve is turned to PILOT or OFF.
9120° Ceramic Fan Temperature Sensor EC-001
10
11ThermocoupleEC-009
11Spark Electrode with Ignitor Cable EC-011
11ThermopileEC-012
11Pilot Orice NG ThreadedEC-019
11Pilot Orice LP ThreadedEC-020
12Burner SwitchEC-026
13Fan Controller 115 V With Knob EC-039A
13Fan Controller Knob EC-040
Part DescriptionPart Number
S.I.T. Nova Valve Convertible50-1421
Pilot GasketEC-021
S.I.T. Piezo IgnitorEC-023
Domestic Power CordEC-042
HEYCO Strain ReliefEC-044
DV Vent Kit With CouplerEC-061
14Relief Door Gasket OnlyEGWP-087
14Window Channel TapeEGWP-089
141 Piece Glass With TapeEGWP-090
14Inner Door Only - PaintedEGWP-092
Burner Control Assembly LPEGWP-099
Burner Control Assembly NGEGWP-100
Door Hinge Pin - SilverEGWP-510
Fireplace ScreenEGWP-513
Shoulder Bolt, Hardened Bushing & Nut (Set of 2)EF-124
Door Knob - Brushed Nickel50-262
Electronic Ignition Module Switch50-329
Wiring Harness50-348
Pressure Relief Door With Gasket, Rod & Brackets50-366
Control Panel Decal50-461
Inner Door Complete (With Glass & Handles)50-463
Embers50-491
4” Flex Coupler50-497
26Dual Convection Blower 115 V (No Mount)50-512
Firebox Bafe50-533
Valve Extension Rod With Knob (1 per set)50-555
27Electronic Ignition Module50-589
28Control Panel50-690
Drafthood Adapter50-841
Drafthood Adaptor Spill Switch Assembly (with
Wiring Harness)
Drafthood Adaptor Decorative Brass Ring50-894
293 Flame Pilot Hood50-925
Owner’s Manual50-1033
Brick Panel Set50-1038
Log Set With Embers - Complete50-1041
Convertion Kit from LG to NG Convertible50-1442
Convertion Kit from NG to LG Convertible50-1443
S.I.T. Valve Conversion Screw With O-Ring50-1450
S.I.T. Valve Conversion Screw Cap50-1451
50-885
44
Page 45
Parts Diagram - Components
12
16
10
27
17
13
28
18
23
19
14
20
21
25
29
11
15
26
24
WESTPORT - Components
January 2005
22
9
45
Page 46
Warranty
Sherwood Industries Ltd. is the manufacturer of the Enviro line of heating products. At Sherwood Industries, our
commitment to the highest level of quality and customer service is the most important thing we do. Each Enviro stove
is built on a tradition of using only the nest materials and is backed by our Exclusive Lifetime Limited Warranty to
the original purchaser. With Enviro, you’re not just buying a replace or stove, you’re buying a company with years of
unequalled performance and quality.
Limited Lifetime Warranty:
Under this warranty, Sherwood Industries Ltd. covers the replace or stove body and accessories against defects in
materials and workmanship, for part repair or replacement for the rst seven (7) years and limited labour for the rst
two (2) years to the original purchaser. This Warranty covers: Firebox, Heat Exchanger, Steel Firebox Panels, Ceramic
Logs & Panels, Burner, Ceramic Glass, Pedestals, Panels and Legs. Please see the exclusions and limitation section
below as certain restrictions and exclusions apply to this warranty.
Limited Two (2) Year Warranty:
Under this warranty, Sherwood Industries Ltd. covers: Gas Assembly, Blower, Blower control, Temperature Sensors and
Wire Harness against defects in materials and workmanship, for part repair or replacement for the rst two (2) years
and limited labour for the rst two (2) years to the original purchaser. Please see the exclusions and limitation section
below as certain restrictions and exclusions apply to this warranty.
Limited One (1) Year Warranty:
Under this warranty, Sherwood Industries Ltd. covers all exterior surface nishes against defects in materials and
workmanship, for part repair or replacement and limited labour for the rst (1) year to the original purchaser. Please
see the exclusions and limitations section below as certain restrictions and exclusions apply to this warranty.
Here is how our Warranty works
If you have any concerns with your Enviro product, please contact the dealer where you purchased the replace or
stove. Your dealer shall make all claims under this warranty in writing.
To the Dealer
When lling out a warranty claim, please complete the following information on an ofcial warranty claim form:
Customer information: Name, address and telephone number of purchaser and date of purchase.
Dealer information: Date of installation, name of installer and dealer, serial number of the appliance, nature of
complaint, defects or malfunction, description and part numbers of any parts replaced.
To the Distributor
Sign and verify that work and information are correct.
Exclusions and Limitations:
1. This Warranty does not cover tarnish, discoloration or wear on the plating or paint.
2. This Warranty excludes wear and tear or breakage caused by cleaning, moving or service on log set and panels.
3. A qualied installer must install this stove or replace. This Limited Warranty covers defects in materials and workmanship
only if the product has been installed in accordance with local building and re codes; in their absence, refer to the owner’s
manual. If the product is damaged or broken as a result of any alteration, willful abuse, mishandling, accident, neglect, or
misuse of the product, the Limited Warranty does not apply.
4. The stove must be operated and maintained at all times in accordance with the instructions in the Owner’s Manual. If the
unit shows signs of neglect or misuse, it is not covered under the terms of this Warranty policy. Performance problems due
to operator error will not be covered by the Limited Warranty policy.
5. As this is a heating appliance, some changes in colour of surface nishes may occur. This is not a aw and as such is not
covered under this warranty.
6. Some minor expansion, contraction, or movement of certain parts and resulting noise, is normal and not a defect and,
therefore, is not covered under this Limited Warranty.
7. Misuse includes over-ring. Over-ring this appliance can cause serious damage and will nullify the Limited Warranty.
8. The Limited Warranty will cover glass thermal breakage only and will not cover misuse of the stove glass, including but not
limited to glass that is struck, has surface contaminates or has had harsh or abrasive cleaners used on it.
9. This warranty does not cover products made or provided by other manufacturers and used in conjunction with the
operation of this stove without prior authorization from Sherwood Industries Ltd. The use of such products may nullify the
Limited Warranty on this stove. If unsure as to the extent of this Limited Warranty, contact your authorized Enviro dealer
before installation.
10. Sherwood Industries Ltd. will not be responsible for inadequate performance caused by environmental conditions.
11. The Limited Warranty does not cover installation and operational related problems such as use of downdrafts or spillage
caused by environmental conditions. Environmental conditions include but are not limited to nearby trees, buildings, roof
tops, wind, hills, mountains, inadequate venting or ventilation, excessive offsets, negative air pressures or other inuences
46
Page 47
Warranty
caused by mechanical systems such as furnaces, fans, clothes dryers etc.
12. The Limited Warranty is void if:
a) The stove has been operated in atmospheres contaminated by chlorine, uorine or other damaging chemicals.
b) The stove is subject to submersion in water or prolonged periods of dampness or condensation.
c) Any damage to the unit, combustion chamber or other components due to water, or weather damage which is the result
of, but not limited to, improper chimney/venting installation.
c) Salt air in coastal areas or high humidity can be corrosive to the nish; these environments can cause rusting. Damage
caused by salt air or high humidity is not covered by the Limited Warranty.
13. Exclusions to the Limited Warranty include: injury, loss of use, damage, failure to function due to accident, negligence,
misuse, improper installation, alteration or adjustment of the manufacturer’s settings of components, lack of proper and
regular maintenance, alteration, or act of God.
14. The Limited Warranty does not cover damage caused to the replace or stove while in transit. If this occurs, do not
operate the stove and contact your courier and/or dealer.
15. Limited Warranty does not extend to or include rebox paint, door or glass gaskets with damage caused by normal wear
and tear, or exterior paint discoloration or chipping, worn gaskets, etc.
16. The Limited Warranty does not include damage to the unit caused by abuse, improper installation, or modication of the
unit.
17. Damage to plated surfaces caused by ngerprints, scratches, melted items, or other external scores and residues left on
the plated surfaces from the use of abrasive cleaners or polishes is not covered in this warranty.
18. The Limited Warranty does not cover tarnish, discoloration or wear on the plated surfaces.
19. The paint on the Metal Brick Liner may peel. This is due to the extreme conditions applied to the paint during normal
usage. It is not a aw and is not covered under warranty.
20. Sherwood Industries Ltd. is free of liability for any damages caused by the replace or stove, as well as inconvenience
expenses and materials. The Limited Warranty does not cover incidental or consequential damages.
21. The Limited Warranty does not cover any loss or damage incurred by the use or removal of any component or apparatus
to or from the Enviro replace or stove without the express written permission of Sherwood Industries Ltd. and bearing a
Sherwood Industries Ltd. label of approval.
22. Any statement or representation of Enviro products and their performance contained in Enviro advertising, packaging
literature, or printed material is not part of the Limited Warranty.
23. The Limited Warranty is automatically voided if the replace or stove’s serial number has been removed or altered in any
way. If the stove is used for commercial purposes, it is excluded from the Limited Warranty.
24. No dealer, distributor, or similar person has the authority to represent or warrant Enviro products beyond the terms
contained within the Limited Warranty. Sherwood Industries Ltd. assumes no liability for such warranties or representations.
25. Sherwood Industries Ltd. will not cover the cost of the removal or re-installation of the stove, hearth, facing, mantels,
venting or other components.
26. Labour to replace or repair items under this Limited Warranty will be covered per our warranty service fee reimbursement
schedule. Labour rates are set per component and as such total labour costs may not be covered.
27. Sherwood Industries Ltd. is not liable for freight or labour on any stove replaced in-eld and is not liable for travel costs
for service work. In the event of in-home repair work, the customer will pay any in-home travel fees or service charges
required by the Authorized Dealer.
28. At no time will Sherwood Industries Ltd. be liable for any consequential damages which exceed the purchase price of the
unit. Sherwood Industries Ltd. has no obligation to enhance or modify any stove once manufactured (example: as a stove
evolves, eld modications or upgrades will not be performed).
29. This Limited Warranty is applicable only to the original purchaser and it is non-transferable.
30. This warranty only covers Enviro products that are purchased through an authorized Enviro dealer.
31. If for any reason any section of the Limited Warranty is declared invalid, the balance of the warranty remains in effect and
all other clauses shall remain in effect.
32. The Limited Warranty is the only warranty supplied by Sherwood Industries Ltd., the manufacturer of the stove. All other
warranties, whether express or implied, are hereby expressly disclaimed and purchaser’s recourse is expressly limited to
the Limited Warranty.
33. Sherwood Industries Ltd. and its employees or representatives will not assume any damages, either directly or indirectly,
caused by improper usage, operation, installation, servicing or maintenance of this stove.
34. Sherwood Industries Ltd. reserves the right to make changes without notice. Please complete and mail the warranty
registration card and have the installer ll in the installation data sheet in the back of the manual for warranty and future
reference.
35. Sherwood Industries Ltd. is responsible for stocking parts for a maximum of seven (7) years after discontinuing the
manufacture or incorporation of the item into its products. An exception to this would be if an OEM supplier is not able
to supply a part.
47
Page 48
Installation Data Sheet
The following information must be recorded by the installer for warranty purposes and future reference.
NAME OF OWNER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
MODEL:___________________________________
SERIAL NUMBER:___________________________
DATE OF PURCHASE: _____________ (dd/mm/yyyy)
NAME OF DEALER:
_________________________________________
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
NAME OF INSTALLER:
_________________________________________
DATE OF INSTALLATION:___________(dd/mm/yyyy)
� NATURAL GAS (NAT) � PROPANE(LPG)
INLET GAS PRESSURE:_________in wc
MAIN BURNER ORIFICE:__________# DMS
PILOT ORIFICE #_________OR________in diam.
INSTALLER’S SIGNATURE:
_________________________________________
MANUFACTURED BY:
SHERWOOD INDUSTRIES LTD.
6782 OLDFIELD RD. SAANICHTON, BC, CANADA V8M 2A3
www.enviro.com
May 27, 2008
ADDRESS:
_________________________________________
_________________________________________
_________________________________________
PHONE:___________________________________
C-11290
48
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.