Enviro CFR, VFR, VFL, CFL, CFRQ Installation Operation & Maintenance

BY JOHNSON CONTROLS
FAN POWERED VAV TERMINALS
INSTALLATION, OPERATION & MAINTENANCE
MODELS CFR, CFRQ, CFL, VFR & VFL
New Release
Form ET130.13-NOM3 (708)
LD13847
FORM ET130.13-NOM3 (708)
TABLE OF CONTENTS
SAFETY CONSIDERATIONS ........................................................................................................................4
INSPECTION .................................................................................................................................................5
STORAGE .....................................................................................................................................................5
PRE-INSTALLATION INSPECTION ..............................................................................................................5
SEQUENCE OF OPERATION .......................................................................................................................6
Parallel Flow ...........................................................................................................................................6
Series Flow .............................................................................................................................................6
INSTALLATION .............................................................................................................................................6
Clearances .............................................................................................................................................7
Hanging and Mounting Equipment Overhead ....................................................................................7
Duct Connections ..................................................................................................................................7
Critically Sound Applications ...............................................................................................................7
Coil Connections ...................................................................................................................................8
Electrical .................................................................................................................................................8
OPERATION ..................................................................................................................................................8
Start-Up ..................................................................................................................................................8
Power Requirements ...........................................................................................................................8
Primary Air Damper and Fan Adjustment ...........................................................................................8
Series Flow, PSC Motor with SCR .......................................................................................................9
Parallel Flow, PSC Motor with SCR .....................................................................................................9
Series Flow ECM Motor Balancing ....................................................................................................10
Commissioning ....................................................................................................................................10
Balancing .............................................................................................................................................10
Manual Fan CFM Adjustment ............................................................................................................. 11
Remote Fan CFM Adjustment ............................................................................................................11
Status LED ...........................................................................................................................................11
MAINTENANCE ..........................................................................................................................................11
Factory Provided Damper Actuator ...................................................................................................11
Damper Shaft .......................................................................................................................................11
Motor/Blower ........................................................................................................................................11
Cleaning ..........................................................................................................................................12
Replacement ...................................................................................................................................12
Coil ........................................................................................................................................................12
Cleaning ..........................................................................................................................................12
Replacement ...................................................................................................................................12
Electric Heat .........................................................................................................................................13
Replacement ...................................................................................................................................13
TROUBLESHOOTING GUIDELINES .........................................................................................................14
ECM SPECIFIC TROUBLESHOOTING GUIDELINES ...............................................................................15
Checking ECM Cables .........................................................................................................................15
VALVE CALIBRATION CHARTS ...............................................................................................................17
FAN CFM CALIBRATION CURVES - TABLE 3 ..........................................................................................18
IN-WARRANTY RETURN PROCEDURE ...................................................................................................19
SERIES FLOW TERMINAL UNIT WEIGHTS -TABLE 4 .............................................................................19
PARALLEL FLOW TERMINAL UNIT WEIGHTS - TABLE 5 ......................................................................20
REPLACEMENT PARTS LIST ....................................................................................................................20
2
FORM ET130.13-NOM3 (708)
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:
DANGER indicates an im mi nent ly hazardous situation which, if not avoid ed, will re sult in death or se ri ous injury.
WARNING indicates a potentially haz ard ous sit u a tion which, if not avoid ed, could result in death or se­ ri ous in ju ry.
CAUTION identifi es a hazard which could lead to damage to the ma chine, damage to other equip ment and/or en vi ron men tal pollution. Usually an in struc tion will be given, together with a brief ex pla na tion.
NOTE is used to highlight ad di tion al information which may be helpful to you.
3
FORM ET130.13-NOM3 (708)
SAFETY CONSIDERATIONS
The equipment covered in this manual is designed for safe and reliable operation when installed and operated within its’ design specifi cation limits. To avoid personal injury or damage to equipment or property while installing or operating this equipment, it is essential that qualifi ed, experience personnel familiar with local codes and regulations, perform these functions using good judgment and safe practices. See the following
cautionary statements.
ELECTRICAL SHOCK HAZARDS All power must be disconnected prior to installation and servicing this equip­ment. More then one source of power may be present. Disconnect, tag and lock out all power sources to avoid electrocution or shock hazards.
ROTATING EQUIPMENT HAZARD Fans may start automatically. Discon­nect all power and control circuits prior to servicing to avoid injury. Caution should be exercised due to the possibility of fans “free wheeling” due to connected duct air movement.
HOT PARTS HAZARD Electric heaters may start automati­cally. Disconnect all power and con­trol circuits prior to servicing to avoid burns.
Check that rigging and lifting equip­ment can safely support the equipment assembly and component weights.
All assemblies must be adequately secured during lifting and rigging by temporary supports and restraints until equipment is permanently fas­tened and set in its’ fi nal location per manufacturer’s guidelines.
All temporary and permanent equip­ment supports must be capable of safely supporting the equipment’s weight as well as any additional live, seismic or dead loads that may be encountered. All supports must be designed to meet applicable local codes and ordinances.
All fastening devices must be designed to mechanically lock the assembly in place without the capability of loosen­ing or breaking away due to system operation and vibration.
Dampers may activate automatically. Disconnect the control circuits or pneumatic control systems and secure all dampers when servicing damper, actuators or linkage to avoid injury.
Wear the appropriate personal protec­tive equipment (gloves, safety glasses, leather closed toe shoes, etc) when handling this equipment recognizing that sheet metal components are being handled.
4
FORM ET130.13-NOM3 (708)
INSPECTION
Upon receipt of equipment, carefully check all items
against the bill of lading to ensure that all equipment has
been received (including shipped loose items). Note any
discrepancy on the bill of lading before signing. Note
that “ship loose” items may be included with the base
unit or shipped (bulk) on a separate pallet.
Inspect all equipment for any signs of damage caused
during transit. On equipment with electric heat, make
sure to check the coil fi ns and/or make sure that the
resistance heat coils are not damaged. Note any
visual damage on the bill of lading before signing.
Immediately report all visual and concealed damage
to the carrier and fi le a claim with the carrier.
Locate the model number on the nameplate and check
that the correct equipment has been received. Verify
that all options have been included, such as controls,
fi lters, heating coils, etc. Also check that equipment
voltage agrees with the building parameters. If a
discrepancy is discovered between what was ordered and
received, contact your local Enviro -Tec representative
immediately.
Do not use fl ow sensor, connecting tubes, coil stubouts or damper shaft as a handle when lifting or moving equipment as damage may occur.
Do not handle by equipment’s heat­ing elements, as permanent damage will occur.
Do not work on damper until associ­ated actuator is disconnected.
Never pressurize equipment above specifi ed test pressure.
Protect adjacent fl ammable materials when brazing. Use fl ame and heat protection barriers where need. Have a fi re extinguisher at hand and ready for immediate use.
STORAGE
If equipment is to be stored prior to installation, observe the following precautions:
1. Choose a dry storage site that is reasonably level and sturdy to prevent undue stress or permanent damage to the equipment. Set equipment off ground if in moisture prone areas.
2. Cover entire equipment with protective tarp or moisture proof cover. Extend cover under equip­ment if stored on ground. Secure cover with adequate tie downs. Be sure that piping connec­tions have protective shipping caps installed.
3. Do not stack equipment any higher than how it was shipped. If equipment has been unpack­aged since receipt from the factory, do not stack without equivalent support between units as was supplied from the factory.
Check assembly and component weights to be sure that the rigging equipment can handle them safely. Note; also check the centers of gravity and any specifi c rigging instructions.
Check for adequate ventilation so fumes do not migrate through ductwork to occupied spaces when welding or cutting around the equipment.
JOHNSON CONTROLS
PRE-INSTALLATION INSPECTION
Do not use fl ow sensor, connecting tubes, coil stubouts or damper shaft as a handle when lifting or moving equipment as damage may occur.
Do not handle by equipment’s heat­ing elements, as permanent damage will occur.
5
FORM ET130.13-NOM3 (708)
While viewing the damper from the discharge of the equipment, disengage the actuator by depressing the manual override button on the side of the actuator and rotate the shaft fully. The damper should close fully and there should be no gaps between the damper gasketing and the inside of the valve.
Units equipped with ECM or 1 horsepower motors will ship from the factory with a removable motor / wheel support installed in the fan housing. It is imperative that this shipping support be removed prior to equipment startup or damage may result to both the motor and the wheel. A label will be affi xed to the outside of the unit next to the power entry point, to identify the presence of this shipping insert.
Manually rotate the fan wheel to assure that there are no obstructions within the fan housing.
Equipment supplied with ECM mo­tors, backward or reverse rotation of the blower is detrimental to the ECM motor.
SEQUENCE OF OPERATION
All fan-powered equipment is supplied with a rectangular discharge and comes in one of two confi gurations:
1. Parallel fl ow with hot water coils mounted on the plenum induction air opening.
2. Series fl ow with hot water coils mounted on the discharge opening.
Either the primary air valve, fan or both can deliver airfl ow to the occupied space. A back draft damper is provided, when the fan is not operating. The ef­fi ciency of this system is the same as standard single duct VAV equipment.
In a typical control sequence applied to parallel fl ow equipment, the air valve is closed to a zero minimum airfl ow before the fan is energized. After the fan has been energized, the reheat will be energized upon a further drop in space temperature. Therefore, little primary air is mixed with the heated air stream.
Series Flow
Fan must be energized prior to intro­duction of air through the primary air valve or the possibilities exist that the fan wheel will operate backwards / counter rotation.
On series fl ow equipment, the fan runs continuously whenever the central air handler is in operation.
In response to the space temperature, the air valve modulates the volume of primary air. The re-heat is typically off during the air valve’s modulation. Should the space temperature decrease to the point at which a decrease in primary air will not maintain the desired temperature, the reheat will be activated to increase the discharge air temperature.
INSTALLATION
Note that for either confi guration, electric heaters (if supplied) are always mounted on the unit discharge opening.
Parallel Flow
On parallel flow equipment, the primary air valve delivers cooled air to the equipment’s outlet. When the space temperature decreases beyond the control of the primary air valve, the fan is started along with the fi rst stage of heat. The fan delivers warm plenum air from the controlled space to the equipment’s outlet, which is mixed with the primary air prior to being delivered to the space.
6
Do not use fl ow sensor, connecting tubes, coil stubouts or damper shaft as a handle when lifting or moving equipment as damage may occur.
Do not handle by equipment’s heat­ing elements, as permanent damage will occur.
FORM ET130.13-NOM3 (708)
Terminal equipment with electric heat must be installed in a horizontal plane with respect to the air stream. Low height equipment can be flipped over in the field to vary or change control section handing.
Consult factory for application utiliz­ing mercury contactors.
Clearances
All equipment covered in this document, including those with electric heat, are ETL listed for 0.0” clearance to combustibles. Refer to NEC and/or local codes for minimum electrical clearances required for service. Equipment should not make contact with any structure located above or below the equipment without appropriate isolation. Equipment supplied with bottom access panels requires sufficient clearance to remove access panels for service.
Duct Connections
All duct connections should be configured and installed in accordance with SMACNA guidelines and all local code requirements. Check to see that duct fasteners are appropriate for the application and do not impinge any internal components. Pay particular attention to internal electrical components.
Fasten and seal all ductwork connections in accordance with project specifications.
Allow a minimum of 1½ duct diameters of straight duct prior to equipment inlet and after equipment discharge.
The diameter of the inlet duct for round valves must be equal to the listed size of the equipment. The round air valve inlet collar of the equipment is 1/8” smaller then listed size in order to allow the round ductwork to slip over the air valve inlet collar.
DO NOT INSERT
DUCTWORK INTO AIR VALVE INLET COLLAR.
Hanging and Mounting Equipment Overhead
Johnson Controls strongly recommends that all equipment be suspended from the upper most ceiling or a structural element of the building, independent of the false ceiling grid. Suspension devices are field supplied, sized and designed by others. Johnson Controls will not accept responsibility for equipment mounting supports. Equipment must be installed in a level horizontal plane. Failure to level equipment properly may prevent proper operation of controls. See Tables 3 and 4 for equipment
weights.
When requested, equipment is supplied with optional hanger brackets for use with (up to) a 3/8” [10mm] diameter hanger rod. See submittal drawings for hanger
bracket locations.
Hanger straps may be utilized as an alternate means of suspending the equipment. Do not secure hanger straps to electric heaters, coils or control enclosures. Hanger straps can be mounted directly to the sides and bottom of equipment casing, such that they do not interfere with working components or access panels using screws that are no longer than 1” [25mm].
When hanging equipment, always use the support method as prescribed for rectangular duct in the job specifications.
When making ductwork connection to air valve inlet collar and insulating air valve inlet, take caution not to damage or remove the flow sensor connections, which are vital to equipment control.
Provide insulation around entire inlet collar (all the way to the equipment casing).
Cut “slits” in the insulation for the flow tubes and secure with duct tape.
Permissible discharge duct connections are straight flanged, slip and drive or drive and screw.
If equipment is to be installed in a location with high humidity, external insulation around the heating coil should be installed.
After all connections are made, check that the entire ductwork system is airtight. In some high-pressure systems, duct sealer may be necessary.
Sound Critical Applications
Flexible duct connectors are not recommended on equipment discharge. The sagging membrane of these fittings can cause turbulence and locally high air velocities that generate noise. Also, lightweight membrane material allows noise to breakout, which can increase sound levels in the space below.
JOHNSON CONTROLS
7
Coil Connections
FORM ET130.13-NOM3 (708)
Power Requirements
Hot water and steam coils are male sweat connection. Use appropriate brazing alloy for system temperature and pressure. Refer to equipment construction submittal drawing for specifi c connection size. MAXIMUM
HYDRONIC SYSTEM OPERATING PRESSURE MUST NOT EXCEED 300 PSIG. MAXIMUM STEAM SYSTEM PRESSURE MUST NOT EXCEED 15 PSIG.
If necessary, you can change coil connection handing on one and two row coils from left-hand to right-hand (and vice-versa) by rotating the coil “like a steering wheel” 180° about its central axis when facing the fi ns. For
three and four row coils, consult factory.
Electrical
All fi eld wiring must comply with NEC and all local codes. Electrical and control diagrams are affi xed to the interior of the control enclosure box.
Minimum circuit ampacity (MCA) designates the maximum operating load of the equipment for sizing wire feeders. Supply Circuit Protection designates the largest breaker in the electrical service panel that can be used to protect the equipment.
Use Copper conductors only.
OPERATION
Start-Up
Thorough safety precautions should always be taken when performing startup and service. Refer to safety considerations at the beginning of this Operation Manual. Only qualifi ed individuals should perform these tasks.
Prior to start-up, the project control sequence/wiring diagram should be obtained and thoroughly understood. If factory supplied analog or DDC controls are utilized, refer to the applicable Operation Manual for start-up and balancing information. Check that all electrical work is fi nished and properly terminated. Check that all electrical connections are tight and that the proper voltage is connected.
Three Phase AC power imbalance must not exceed 2%. Be sure that the following guides are met:
1. AC power is within 10% of rated voltage at rated
frequency. (See equipment nameplate for rat-
ings)
2. AC power is within 5% of rated frequency at rated voltage.
3. A combined variation in the voltage and frequency of 10% (sum of absolute values) of rated values provided the frequency variation does not exceed 5% of rated frequency.
Primary Air Damper and Fan Adjustment
Unit should not be balanced until the incoming power supply is at the permanent voltage condition. All discharge ductwork must be connected. The minimum recommend discharge static pressure for all fan-powered equipment is 0.1” wg. and 0.2” on 3/4hp and larger
(see fan curves located on the Enviro -Tec web site for specifi cs). All foreign materials should be removed
from the duct system. Optional filters should be installed as required.
Unless otherwise specifi ed, the fan motor has three speeds. Fan speed is selected in the electrical control enclosure by one of two methods. For units with dual motors, see Figure 1A showing how the fan speed is selected by placement of a factory supplied jumper wire on a terminal strip. Otherwise see Figure 1B which shows the wire to wire fan speed selection method. Simply insert the male quick connect (from control circuitry) into the female quick connect which corresponds to high (black), medium (blue), or low (red) motor speeds. Units are set to low speed at the factory as standard in order to optimize energy effi ciency. A three position rotary switch is optional.
ELECTRICAL SHOCK HAZARD All power must be disconnected prior to changing jumper or serious injury or death will result.
Check to make sure that heater elements are not damaged, free of all foreign material and proper control interlocks have been made before energizing the electric heater.
8
All fan-power equipment is shipped with an electronic solid state fan speed controller (SCR) for PSC motors. The SCR is located in the control enclosure. Using a 1/8” fl at blade screwdriver, adjusting the manual potentiometer clockwise will increase the motor speed; adjusting the potentiometer counterclockwise will decrease the motor speed.
JOHNSON CONTROLS
Loading...
+ 16 hidden pages