WARNING: If the information in this manual is not followed exactly, a
re or explosion may result causing property damage, personal injury
or loss of life. Installation and service must be performed by a qualied
4001609
Version Française: www.enviro.com/fr.html
installer, service agency or the gas supplier.
50-3001
Page 2
Safety Precautions
WARNING:
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious
injury, death, or property damage.
- Do not store or use gasoline or other ammable vapors and
liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Leave the building immeadiately.
• Immeadiately call your gas supplier from a neighbor’s phone.
Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re
department.
- Installation and service must be performed by a qualied
installer, service agency or the gas supplier.
INSTALLER:
Leave this manual with the appliance.
CONSUMER:
Retain this manual for future reference.
This appliance may be installed in an after-market permanently located,
manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases, unless a certied kit is used.
Massachusetts installations (Warning): This product must be installed by a licensed plumber or
gas tter when installed within the Commonwealth of Massachusetts. Other Massachusetts code
requirements: Flexible connector must not be longer than 36in., a shut off valve must be installed;
only direct vent sealed combustion products are approved for bedrooms/bathrooms. A carbon
monoxide detector is required in all rooms containing gas red direct vent appliances. The replace
damper must be removed or welded in the open position prior to installation of a replace insert.
2
Page 3
Safety Precautions
HOT GLASS WILL
CAUSE BURNS
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the
hot viewing glass is provided with this appliance and shall
individuals.
FOR SAFE INSTALLATION AND OPERATION OF YOUR “ENVIRO” HEATER,
PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:
• All ENVIRO gas-red appliances must be installed in
accordance with their instructions. Carefully read all the
instructions in this manual rst. Consult the building
authority having jurisdiction to determine the need for a
permit prior to commencing the installation.
• NOTE: Failure to follow these instructions could cause
a malfunction of the replace, which could result in death,
serious bodily injury, and/or property damage.
• Failure to follow these instructions may also void your
re insurance and/or warranty.
GENERAL
• Installation and repair should be done by a qualied
service person. The appliance should be inspected before
the rst use and, at least, annually by a qualied service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc. It
is imperative the control compartments, burners and
circulating air passageways of the appliance be kept
clean.
• Due to high temperatures, the appliance should be
located out of high trafc areas and away from furniture
and draperies.
Children and adults should be alerted to the
hazards of high surface temperatures and should
stay away to avoid burn or clothing ignition.
• Young children should be carefully supervised when
in the same room as the appliance. Toddlers, young
children and others may be susceptible to accidental
contact burns. A physical barrier is recommended if there
are at risk individuals in the house. To restrict access to a
replace or stove install an adjustable safety gate to keep
toddlers, young children and other at risk individuals out of
the room and away from hot surfaces. Any safety screen,
guard, or barrier removed for servicing an appliance must
be replaced prior to operating the appliance.
• Clothing or other ammable materials should not be
placed on or near the appliance.
3
• A barrier designed to reduce the risk of burns from the
hot veiwing glass is provided with this appliance and shall
be installed for the protection of children and other at-risk
individuals. If the barrier becomes damaged, the barrier
shall be replaced with the manufacturer’s barrier for this
appliance
FOR YOUR SAFETY
• Installation and service must be performed by a qualied
installer, service agency or gas supplier.
• This installation must conform to local codes or, in the
absence of local codes, with the National Fuel Gas Code,
ANSI Z223.1/NFPA 54, or the Natural Gas and Propane
Installation Code, CSA B149.1.
• To prevent injury, do not allow anyone who is unfamiliar
with the stove to operate it.
• To prevent injury, if the pilot or pilot and burners
have gone out on their own, open the glass door and
wait 5 minutes to air out before attempting to relight the stove.
• Always keep the area around these appliances clear of
combustible material, gasoline and other ammable liquids
and vapours.
• These appliances should not be used as a drying rack for
clothing or for hanging Christmas stockings/decorations.
• Due to the paint curing on the stove, a faint odor and slight
smoking will likely be noticed when the stove is rst used.
Open a window until the smoking stops.
Always connect this gas stove to a vent system and vent to
the outside of the building envelope. Never vent to another
room or inside the building. Make sure the specied vent
pipe is used, properly sized and of adequate height to
provide sufcient draft. Inspect the venting system annually
for blockage and signs of deterioration.
WARNING: Failure to position the parts in accordance
with the diagrams in this booklet, or failure to use only
parts specically approved with this appliance, may result in
property damage or personal injury.
WARNING: Do not operate with the glass front removed,
cracked or broken. Replacement of the glass should be done
by a licensed or qualied service person.
• Never use solid fuels such as wood, paper, cardboard, coal,
or any ammable liquids, etc., in this appliance.
• Do not use this appliance if any part has been under water.
Immediately call a qualied service technician to inspect the
appliance and to replace any part of the control system or
any gas control which has been under water.
• Do not abuse the glass by striking it or slamming the door
shut.
• If the Q1C unit is pulled out of its installation, and the vent-
air intake system is disconnected for any reason, ensure that
the vent-air intake pipes are reconnected and re-sealed in
accordance to the instructions noted in
Installation Data Sheet....................................................................................................48
4
Page 5
Codes And Approvals
DIRECT VENT ONLY: This type is identied by the sufx DV. This appliance draws all of its air for
combustion from outside the dwelling, through a specially designed vent pipe system.
This appliance has been tested and approved for installations from 0 feet to 4500 feet (1372 m) above
sea level.
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at
elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate
guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
• This appliance has been tested by INTERTEK and found to comply with the established VENTED
GAS FIREPLACE HEATER standards in CANADA and the USA as follows:
VENTED GAS FIREPLACE HEATER (Q1C; NG/LPG)
TESTED TO: ANSI Z21.88a-2014/CSA 2.33a-2014 VENTED GAS FIREPLACE HEATERS
CAN/CGA 2.17-M91 (R2009) GAS FIRED APPLIANCES FOR HIGH ALTITUDES
This ENVIRO Q1C Fireplace:
• Has been certied for use with either natural or propane gases. (See rating label.)
• Is not for use with solid fuels.
• Is approved for bedroom or bed sitting room. (IN CANADA: must be installed with a listed wall
thermostat. IN USA: see current ANSI Z223.1 for installation instructions.)
• Must be installed in accordance with local codes. If none exist, use current
installation code CAN/CGA B149 in Canada or ANSI Z223.1/NFPA 54 in the
USA.
• Must be properly connected to an approved venting system and not connected
to a chimney ue serving a separate solid-fuel burning appliance.
IMPORTANT NOTICE (Regarding rst re up): When the unit is turned
on for the rst time, it should be turned onto high without the fan on for
the rst 4 hours. This will cure the paint, coal set, gasket material and
other products used in the manufacturing process. It is advisable to open a
window or door, as the unit will start to smoke and can irritate some people.
After the unit has gone through the rst burn, turn the unit off including
the pilot, let the unit get cold then remove the glass door and clean it with
a good gas replace glass cleaner, available at your local ENVIRO dealer.
5
Page 6
Dimensions:
26 7/8"
(683mm)
6 5/8"
(168mm)
4 3/8" (112mm)
15 3/4"
(400mm)
21 1/2"
(548mm)
21" (508mm)
16 1/2"
(420mm)
18 3/4"
(476mm)
24 3/4"
(627mm)
21"
(533mm)
18 3/4" (476mm)
14"
(356mm)
6 5/8"
(168mm)
25 1/4"
(641mm)
5 3/8" (136mm)
27 1/2"
(700mm)
4 3/8"
(112mm)
16 7/8"
(479mm)
3 5/8" (93mm)
14 1/4"
(361mm)
25 1/4" (641mm)
16 7/8"
(429mm)
4 1/2"
(114mm)
14.212"
(361mm)
14.25"
(362mm)
Gas
Line
120v
Plug
ZC
120v
In
Specifications
*Shown
With Modern
Surround and
Extensions*
install Depth:
If the available depth of install is less than 14.25”, the stove depth can be reduced to 12.375”
by removing the cabinet extension brackets; however, doing so will cause the safety screen
to protroud past the front of the surround panel. If a reduced install depth is required, the
extension brackets must be (re)moved. Refer to InItIal InstallatIon - aDjustIng Install Depth
for instructions.
Figure 1. Q1L Dimensions - Top Vent
Figure 2. Q1L Dimensions - Rear Vent
6
Page 7
Operating Instructions
For Your Safety, Read Safety Precautions And
Lighting Instructions Before Operating
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY
RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OF LOSS OF LIFE.
rating label & lighting instructions location:
The rating label plate and lighting instructions are located under the gas valve and attached to the unit
with a length of chain.
lightinganD turning off instructions:
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life
A. This appliance has a pilot which must be lighted by hand. When
lighting the pilot, follow these instructions exactly.
B. BEFORE LIGHTING smell all around the appliance area for gas.
Be sure to smell next to the floor because some gas is heavier
than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS:
Do not try to light any appliance. Do not touch any electrical switch; do
not use any phone in your building. Immediately call your gas supplier
from a neighbor's phone. Follow the gas supplier’s instructions. If you
cannot reach your gas supplier, call the fire department.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to this appliance.
4. Open the front control panel.
5. Turn off the gas control knob clockwise to the “OFF” position.
6. Open door. Wait fIve (5) minutes to clear out any gas. Close door.
Then smell for gas, including near the floor. If you smell gas, STOP!
Follow “B” in the saftey information above on this label. If you don’t
smell gas, go to the next step.
7. Find pilot-located near the center rear of the firebox. Turn the gas
control knob counter-clockwise to “PILOT”. Push the gas
control in fully and hold, keep knob depressed for about 30 seconds
after the pilot is lit. Release knob. If pilot goes out, repeat steps 4
through 5.
C. Use only your hand to push in or turn the gas control knob.
Never use tools. If the knob will not push in or turn by hand,
don’t try to repair it. Call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water.
Immediately call a qualified service technician to inspect the
appliance and to replace any part of the control system and any
gas control which has been under water.
WARNING: This gas valve has a lockout device, which will not allow the
pilot burner to be relit until the thermocouple has cooled.
-If the knob does not pop up when released, stop and immediately call your
service technician or gas supplier.
-If the pilot will not stay lit after several tries, turn the gas control knob
clockwise
8. Turn the gas control knob counter clockwise to the “ON” position.
Flip the burner switch to “ON” then turn the “HI/LOW” knob to the
desired setting.
9. Close the front control panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
to “OFF” and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Open the front control panel and flip burner switch to “OFF”
Figure 3. Lighting Instruction Label
4. Turn the gas control knob clockwise to the “OFF” position.
5. Close the front control panel.
C-12454
7
Page 8
Operating Instructions
pilot light:
1. Turn off the gas to the replace. If not recently done, remove the glass and let the unit air out
for at least ve (5) minutes to clear out any gas. Turn on gas to the heater. Leak test all joints
with soapy water. NEVER USE OPEN FLAME FOR LEAK TESTING.
2. Start the pilot by pressing the gas control knob and turning it to PILOT.
While holding the gas control knob in, press the piezo ignitor several
times until the pilot light starts. Hold the gas control knob in for 30
seconds. Check that the pilot has fully engulfed the thermocouple
assembly (see Figure 4).
3. Start the main burner by turning the gas control knob to ON and then
turn the rocker switch to ON. Check that all burner ports have ame.
Thermopile
Thermocouple
4. Leak test all gas joints again.
Figure 4. Pilot Flame
air shutter:
The air shutter adjustment lever is on the right hand side of the venturi box (see Figure 5).
The air shutter allows the amount of air coming into the replace to be adjusted in order to accommodate
different climates and venting arrangements. Start the pilot and then the burner. Make sure the pilot
ame is burning normally and none of the burner ports are plugged. Let the replace burn for roughly
fteen minutes and then examine the ames, compare the ames to Figure 40.
The ideal ame will be blue at the base and light orange above. The ames should be of medium
height. If the ames look like this, no venturi adjustment is needed. If the ames are fairly short and
mostly blue, the replace is getting too
much air. Therefore, the air shutter
should be closed (pulled out) slightly
until the correct ames are achieved.
Flames that are very orange, with tall,
dark, stringy tips, are not getting enough
air. Open (push in) the venturi until the
ames clean up. If the venturi is opened,
or closed all the way, and the correct
ames cannot be attained, turn off the
gas and contact the dealer.
Less Air
Air Shutter Adjustment
More Air
Warning: Incorrect venturi adjustment
may lead to improper combustion, which
is a safety hazard. Contact the dealer if
there is any concern about the venturi
Figure 5. Air shutter adjustment lever.
adjustment.
remotecontrols:
This replace can use an optional remote control or an optional cordless wall thermostat. If either of
these are to be used to control the replace for the majority of the time, leave the ON/OFF switch (on the
control panel) in the remote/thermostat position. Consult the instructions included with the remote/wall
thermostat for operation guidelines.
8
Page 9
Operating Instructions
For Your Safety, Read Safety Precautions And
Lighting Instructions Before Operating
burner lighting:
A) Make sure the pilot is lit.
B) Turn gas control knob COUNTER CLOCKWISE to ON.
C) Flip the burner switch to ON.
D) Turn HI/LO knob to the desired ame height.
E) Turn on all electrical power to the unit.
NOTE: Check that all burner holes are lit.
TO TURN GAS FIREPLACE OFF:
Flip switch to OFF to turn off burners only.
If the replace is to be turned off for the season,
or for servicing, turn the gas shut off valve to
OFF. DO NOT FORCE IT. If the unit is going to
be serviced, turn off the electrical power to the
unit as well.
NOTE: When the unit is turned on for the rst time, it should be turned onto high, with the fan OFF, for
the rst two to four hours. This will cure the paint, coal set, gasket material, and other products used
in the manufacturing process. It is advised that a door or window be opened as the unit will start to
smoke, which can irritate some people. After the unit has gone through the rst burn, turn the unit OFF,
including the pilot, and let the unit get completely cold. Then remove the glass and clean it with a good
gas replace glass cleaner, available at your local Enviro dealer. See “MaIntenance anD serVIce; glass
Door reMoVal” and “MaIntenance anD serVIce; cleanIng the glass.”
Gas Control
Hi/Low Knob
Piezo Ignitor
Alternate Burner
Switch Location
Figure 6. Control Panel
blowerspeeD:
The blower will come on only when the replace is up to temperature
(approximately 15 minutes). The speed of the fan can be changed by turning
the fan control knob. The blower will continue to operate automatically after the
unit has been shut off (approximately 25 minutes).To turn the blower off, turn
the knob COUNTER CLOCKWISE until it “clicks” off (Figure 7).
It is advisable not to operate the blower below
1
/3 speed as it puts a strain on
the windings of the blower and running the blower at lower speeds could also
cause premature fan failure.
Figure 7. Fan Control
normal sounDs During operation:
Table 1: Normal Sounds
ComponentSound & Reason
Q1C & Surround PanelsCreaking when heating up or cooling down.
BurnerLight pop or poof when turned off; this is more common with LP units.
Temperature SensorClinking when it senses to turn the blower on or off.
Pilot FlameQuiet whisper while the pilot ame in on.
Blower / FanAir movement that increase and decreases with the speed of the blower. The
blower is pushing the heat from the replace into the room.
Gas Control ValveDull click when turning on or off, this is the valve opening and closing.
9
Page 10
Maintenance And Service
routine maintenance:
At least once a year, run through the following procedures to ensure the system is clean and working
properly. Check the burner to see if all the ports are clear and clean. Check the pilot to make sure it is not
blocked by anything. The pilot ame should be blue with little or no yellow on the tips.
Warning: Clearances must be sufcient to allow access for maintenance and service
Warning: Failure to position the parts in accordance with this manual, or failure to use only parts
specically approved with this appliance may result in property damage or personal injury.
The venting system must be periodically examined; it is recommended the examination is done by a
qualied agency.
cleaning the glass:
When the replace has cooled, remove the face of the replace along with the glass. See MaIntenance
anD serVIce - glass Door reMoVal. Check the gasket material on the back of the glass, making sure that
it is attached and intact.
During a cold start up, condensation will sometimes form on the glass. This is a normal condition with all
replaces. However, this condensation can allow dust and lint to cling to the glass surface. Initial paint
curing of the appliance can leave a slight lm behind the glass, a temporary problem. The glass will need
cleaning about two weeks after installation. Use a mild glass cleaner and a soft cloth. Abrasive
cleaners will damage the glass and painted surfaces. Depending on the amount of use, the glass
should require cleaning no more than two or three times a season. Do not clean the glass when it is
hot.
cleaning the firebox:
Remove the coal set carefully, as it is very fragile. Gently remove all the coals and place on a paper towel.
Vacuum the bottom of the rebox thoroughly. Carefully clean any dust off the coal set and remove any
lint from the burner and pilot. At this time, inspect the burner tube for cracking or severe warping. If a
problem is suspected, contact the dealer. Check the coal set for deterioration or large amounts of soot;
a small amount on the bottom side of the coal set is normal. Replace the coal set as in the seconDary
InstallatIon - coal set InstallatIon section. If a new coal set is required, contact your nearest ENVIRO
dealer.
replacingthe glass:
The glass in the replace is a high temperature ceramic. If the glass is damaged in any way, a factory
replacement is required (see parts lIst). Wear gloves when handling damaged glass door assembly
to prevent personal injury. Do not operate with the glass front removed, cracked or broken. Removal
and replacement of the glass from the door must be done by a licensed or qualied service person.
The glass must be purchased from an ENVIRO dealer. No substitute materials are allowed.
Remove the door (see page 11). The replacement glass will come with a new gasket installed. Remove
any silicone remnants from the door. Apply high temperature silicone to the two vertical faces of the
door and install the new piece of glass with gasket (be sure to maintain edge clearances). Apply even
pressure to the glass to allow the silicone to adhere to the gasket material.
10
Page 11
Maintenance And Service
cleaning Decorative surfaces:
Painted and porcelain faces should be wiped with a damp cloth periodically. If a plated face has been
purchased, it should be unpacked/unwrapped carefully to avoid getting anything on the surface of the
nish, including cleaners, polish and nger prints. It is important to note that ngerprints and other
marks can leave a permanent stain on plated nishes. To avoid this, give the face a quick wipe with denatured alcohol on a soft cloth BEFORE lighting the replace. Never clean the face when it is
hot. Do not use other cleaners as they may leave a residue, which can become permanently etched into
the surface.
glass Door removal:
In order to install the coal set, and
for regular cleaning, the glass door
Door Tool Hole
Figure 8. Top latches for glass door
Door Latch Mechanism
must be removed. There are two
(2) door latch mechanisms on top
the glass door as shown in Figure
8. Each latch has a hole at the front
to use the door tool, supplied with
the unit, to pull the mechanisms
straight out and up. When the top
latches are unhooked, lean the
door forward and then lift it up out
of the alignment slots at the bottom
corners of the rebox, shown in
Figure 9.
Alignment Slot
(both corners)
*Parts removed
for clarity*
Figure 9. Bottom Alignment Slots for glass door.
To replace the glass door, simply
reverse the above procedure.
Warning: Do not touch or attempt
to remove the glass door if the
replace is not completely cold.
WARNING: Never operate the
replace with the glass door
removed.
11
Page 12
Maintenance And Service
burner removal:
The burner may need to be removed for a few reasons, including cleaning under the burner, converting
the unit to a different gas type, or to replace the burner altogether. Proceed only when the unit has
completely cooled down.
1. Remove the glass door as shown in the
MaIntenanceanD serVIce - glass Door
reMoVal.
2. Remove the coal set as shown in
SeconDary InstallatIon - coal set
InstallaIon
3. Push the air shutter in until it stops
4. Lift the burner straight up then out.
To re-install the burner follow steps 1-4 in
reverse. When placing the burner back in
the unit be sure to adjust the air shutter
back to the correct setting.
Figure 10. Removing Burner.
fuel conversion:
TO BE INSTALLED BY A QUALIFIED SERVICE AGENCY ONLY
Please read and understand these instructions before installing.
Warning: This conversion kit shall be installed by a qualied service agency in accordance
with the manufacturer’s instructions and all applicable codes and requirements of the
authority having jurisdiction. If the information in these instructions is not followed
exactly, a re, explosion or production of carbon monoxide may result causing property
damage, personal injury or loss of life. The qualied service agency is responsible for
the proper installation of this kit. The installation is not proper or complete until the
operation of the converted appliance is checked as specied in the manufacturer’s
instructions supplied with the kit.
Carefully inspect all parts supplied with this conversion kit. If any parts have been damaged or are
missing, contact your dealer, distributor or courier company to have them replaced before starting this
installation.
12
Page 13
Maintenance And Service
Loosen
Tighten
Conversion Kit Installation:
1. Turn control knob on the gas valve to the “OFF” position and shut the gas supply off at the shut-off
valve upstream of the unit. CAUTION: The gas supply must be shut off prior to disconnecting the
electrical power and before proceeding with the conversion. Allow the valve and unit to cool down
to room temperature.
2. Remove the glass door as shown in the MaIntenanceanD serVIce - glass Door reMoVal.
3. Carefully remove the coal set.
4. Remove the burner as shown in the MaIntenanceanD serVIce - Burner reMoVal.
5. Convert the burner orice(s):
a) Remove the main burner orice with a ½ inch deep socket.
b) Put a bead of pipe-thread sealant or approved Teon tape on the orice threads before installing
into the brass elbow.
c) Install the new orice(s) from the kit into the brass elbow.
6. Convert the pilot injector:
a) Pull the pilot hood straight up to access the pilot injector.
b) Using a
5
/32” or 4 mm Allen key, remove the pilot injector.
c) Install the new pilot injector supplied with this conversion kit. Simply
screw the new injector inside the pilot hood using the Allen key,
d) Reinstall the hood by placing the hood on the assembly, line up the key
way, and snap into place.
7. Convert the SIT gas valve:
a) Remove the black protection cap from the HI/LO knob by hand shown in
Figure 11.
b) Insert a
5
/32” or 4 mm Allen wrench into the
hexagonal key-way of the screw (see Figure 12),
rotate it counter-clockwise until it is free and
extract it.
c) Check that the screw is clean and if necessary
remove dirt.
d) Flip the screw (refer to Figure 13).
e) Using the Allen wrench as shown in Figure 12,
rotate the screw clockwise until a torque of 9
inch lbs. WARNING! Do not over tighten the
screw. It is recommended that you grip the
wrench by the short side.
Figure 11: Removing
valve cap.
13
Figure 12: Removing valve
screw.
f) Verify that if the conversion is from NG to
LPG, the screw must be re-assembled with the
red o-ring visible (refer to Figure 14). If the
conversion is from LPG to NG, the red o-ring of
the screw must be not visible.
Figure 13: Flip valve
screw.
Page 14
Maintenance And Service
Redo-ring
isnotvisible
Redo-ring
isvisible
LPGConfiguration
Figure 14: O-ring on valve screw.
8. Reinstall the burner, coal set, and glass door.
Also refer to seconDary InstallatIon - coal set
InstallatIonin your Owner’s Manual. When re-
installing the burner, ensure that the burner to
pilot shield relationship is similar to what is shown
in Figure 15.
9. Reconnect the main gas line if it was disconnected
and open the shut-off valve at the gas line to the
unit.
g) Re-attach the black protection
cap that was removed in step
a (Figure 11).
10. Use a small brush to apply a warm soapy water
solution to all gas connections (use a half dish
soap and half warm water). If a gas leak is
present, bubbling will occur. Gas leaks can be
repaired by using an approved pipe thread sealant
or approved Teon tape. NEVER USE AN OPEN
FLAME WHEN TESTING FOR LEAKS.
Figure 15. Pilot assembly
beside the burner.
11. Reconnect the electrical power to the unit.
12. Relight the pilot and conrm the ame properly covers both the thermocouple and thermopile (see
Figure 4, page 8). Should the pilot require adjustment, turn the adjustment screw (gure 42, page
35) clockwise to decrease or counterclockwise to increase until the correct ame is achieved.
13. Relight the main burner in both the “HI” and “LO” positions to verify proper burner ignition, operation
and proper ame appearance. Conrm the inlet and manifold pressures are within the acceptable
ranges as directed in section
IntIal IntallatIon - gas lIne connectIonanD testIng. If the Q1 has
been installed at an altitude higher than 2000ft (610m) it is required to de-rate the unit accordingly:
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at
elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate
guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
14. MAKE SURE that the conversion label is installed on or close to the rating label to signify that the
unit has been converted to a different fuel type.
14
Page 15
35 1/4"
(895mm)
25 1/4"
(641mm)
See Table 3
6
15
/16"
(176mm)
Gas
Inlet
Ad
j
ac
e
n
t
w
a
l
l
3 11/16 "
min
(94mm)
Rear
Vent
Top
Vent
41"
(1041mm)
S
t
e
el St
u
d
W
o
od
Framing
25 1/2"
(648mm)
15
Initial Installation
QUALIFIED INSTALLERS ONLY
introDuction:
This section of the owner’s manual is for the use of qualied technicians only. Fireplace placement,
hearths, facing, mantels, and venting terminations will be covered, as well as the gas and electric systems.
There are several installation safety guidelines that must be adhered to. Please carefully read the safety
precautions at the front of this manual.
NOTE: The Q1C comes as a top vent unit but can be converted to a rear vent.
Warning: Clearances must be sufcient to allow access for maintenance and service.
placementanD framing:
The location for the replace can be
along a wall, raised or at oor level, or
in a corner. There are specic framing
measurements for each situation.
The basic opening should have the
dimensions shown in Figure 16.
The replace must have a strong and
level surface to be placed on. The
surface should be made of wood or a
non-combustible material, not carpet.
The framing boards may touch the
top and back standoffs, but only the
supplied insulating material can
be placed between the frame and
the standoffs. A horizontal steel stud
may be used at the height shown to
support the bottom edge of the noncombustible material (see page 22).
Note: Steel stud, if used, must
Figure 16. Dimensions for Framing the Firebox
Firebox Framing
Width25¼”64.1 cm
Height - Rear Vent35¼”89.5 cm
be installed after the unit has
been attached to framing
Height - Top Vent41”104.1 cm
Gas Inlet (Distance
From Back)
Table 2. Framing Dimensions.
Minimal (3 or 4 - sided)17⅛”43.5 cm
Modern or Contemorary16½”41.9 cm
No Surround Panel15¼”38.7 cm
The gas line, ⅜ inch NPT, should be
Brought to the left side of the replace.
The location should be chosen so the
replace will be at least 36 inches (91.4
cm) from drapes, doors and other
combustibles. The framed opening must
be a minimum of 3 11/16” inches (9.4
cm) from the nearest perpendicular wall
(sidewall to the edge of the opening).
Framing Depth
Surround PanelDepth
Table 3. Framing Dimensions.
Page 16
Initial Installation
QUALIFIED INSTALLERS ONLY
rear vent conversion:
For smaller openings the Q1C can be converted from a top vent to a rear vent unit.
Vent Collar
Base Plate
Step 1: Using a T20 screwdriver
Exhaust Spigot
Cover Plate
remove the vent collar, base plate,
cover plate and exhaust spigot (28
screws total) as shown in Figure 17.
Figure 17. Vent Conversion - Step 1
Step 2: Switch the removed parts
around as shown in Figure 18 and
re-install all 28 screws. To correctly
install the base plate keep the
locating notch on each side at the
bottom. Also note the exhaust
spigot uses a lower set of holes
when setup as a rear vent.
Use lower set of
holes
Locating Notch
Figure 18. Vent Conversion - Step 2
16
Page 17
Initial Installation
QUALIFIED INSTALLERS ONLY
insulating material:
Depending on the chosen vent conguration, either one or both pieces of insulating material supplied
with the unit are required for correct installation.
Rear Vent: When using the rear vent conguration both the ceramic board and berglass insulation
are required. Place the ceramic board on top of the unit rst and then place the insulation on top of the
ceramic board as shown in Figure 19.
Top Vent: When using the top vent conguration only the gerglass insulation is required. Cut a notch
in the insulation, to t around the vent collar, and place on top of the unit as shown in Figure 20.
Fiberglass
Insulation
Ceramic
Board
Figure 19. Unit Insulation - Rear Vent
Fiberglass
Insulation
(cut around
vent collar)
Figure 20. Unit Insulation - Top Vent
17
Page 18
Initial Installation
QUALIFIED INSTALLERS ONLY
stanDoffs:
The Q1C is supplied with two sets of standoffs that serve as a framing guide and must be used when the
unit is being installed as a replace. The front set of standoffs mount to sides of the unit (see Figure 21)
and can be adjusted as needed to
account for the thickness of the
wall material. The rear standoffs
attach to the back corners of
the unit and are not adjustable.
Combustible material can
touch the standoffs but must
not encroach past them. If
Mounting Screw
Rear Standoff
Mounting Screw
the Q1C is being installed into a
pre-existing masonary replace
it is not necessary to use the
standoffs. Installation of the
standoffs will require a T20
screwdriver. Remove the installed
screws in the noted locations,
place the standoff over the holes,
and re-install the screws.
Figure 21. Standoff Mounts
Frame up to this
ange
Multiple Holes
for Adjustable
Depth
Front Standoff
No Combustible
Material within
dotted lines
Figure 22. Area created by stanoffs
18
Page 19
Initial Installation
A
B
Outside Wall
Inside Wall
C
D
E
F
Outside Wall
Inside Wall
A
B
C
DE
F
QUALIFIED INSTALLERS ONLY
corner installation:
The dimensions for installing a replace in the corner of a room are depicted in Figures 21 and 24 and
listed in table 4 below. The dimensions will vary depending on the surround panel used, refer to InItIal
InstallatIon - aDjustIng Install Depthto adjust installation depth as needed. Refer to “InItIal
InstallatIon - allowaBle co-axIal Vent confIguratIons” for allowable pipe lengths.
Do not interfere with the structural integrity of the walls.
Corner Installation Dimensions
(Top or Rear Vent)
Dimension - C [Set]15¾” (260mm)
Dimension - E [Set]25¼” (641mm)
Minimal Panel (3 or 4 sided)
7/16” (1103mm)
11/16” (779mm)
9/16” (421mm)
7/16” (1078mm)
Figure 23. Dimensions for a corner installation, rear
Figure 24. Dimensions for a corner installation, top
vented.
Page 20
Initial Installation
A
Minimal15.00 inMinimal12.375 in
QUALIFIED INSTALLERS ONLY
aDjusting install Depth:
The extension brackets installed on the outside of the stove are used to make the front of the surround
panel ush with the safety screen. The Q1 is built with the extension brackets set for a Modern or
Contemporary surround panel. If a different depth is required look at the chart below and follow the
Note: If the smallest install depth is desired (15¼”
[387mm] for replace, 12⅜” [313mm] for insert) the
extension brackets must be removed. Any surround
panel can still be used but the safety screen will protrude
out further than the panel.
REMOVAL:
1. Using a T20 screwdriver, remove the ve (5)
scrrews that secure the Top Extension to the
Cabinet (see Figure 26).
2. Remove the ve (5) screws on each Side
Extension (see Figure 26).
Step 3-5 on next page
Top Cabinet
Extension
Side Cabinet
Extensions
Figure 25: Q1 as Shipped
Figure 26: Removing Extension Screws.
20
Page 21
B
Initial Installation
QUALIFIED INSTALLERS ONLY
3. If using the smallest depth (no surround panel), remove the extension
brackets, re-install the removed screws
and install the standoffs as directed
in the InItIal InstallatIon - stanDoffs
section of the manual (standoffs not
required for insert applications).
4. If using the biggest depth (3 or 4-sided
minimal surround), re-install the
extension brackets in the position noted
in the Figure 28.
5. Install the side standoffs (if required)
onto the side extension brackets using
the forward set of free holes. Adjust the
depth of the side standoffs as needed
(see Figure 27). Also see the InItIal
InstallatIon - stanDoffs section of the
manual.
Top screws that tie
the side brackets
into the top bracket
can be removed to
separate brackets
Screw locations for
side standoffs
Figure 27. Removing Extension Brackets
21
Figure 28. Position of Extension Brackets at
biggest depth
Page 22
Initial Installation
12" (305 mm) Mantle
1¼” (32mm)
thick non-
combustible
floor
12" (305 mm) minimum from wall
If hearth is flush with flooring
2" (51 mm) Mantle
41"
(1041 mm)
minimum
from bottom
of unit
35"
(889 mm)
minimum
from bottom
of unit
10” (254 mm)
Non-Combustible
Facing
7" (178 mm)
minimum from
side of door to
side wall
1/2” (12.7mm)
thick non-
combustible facing
QUALIFIED INSTALLERS ONLY
mantle & non-combustible clearances:
When installing the Q1C as a zero clearance replace the correct clearances and materials must be used:
above unit: A minimum 10” of ½” thick non-combustible facing material, with a R-Value no less than
0.26, must be used (see Figure 29).
in frontof unit: A minimum 12” of 1¼” thick non-combustible material, with a R-Value no less than
2.27 (K-value no less than .55), must be used when the unit is either sitting on the oor or raised within
2’’ of the oor. Approved 1” thick Q1 oor protection is available seperately under part number 50-3016.
When raising the unit 2” - 4” above the oor a minimum 12” of ¾” thick material, with a R-Value no less
than 1.36 (K-value no less than .55), must be used. If raising the unit higher than 4” from the oor, any
combustible material can be used.
aDjacent/siDewall: There must be a minimum distance of 7” from the side of the rebox door to an
adjacent wall composed of combustible material (see Figure 29).
mantle: It is not necessary to install a mantle, but if one is desired the guidelines as shown in Figure 25
below must be followed.
Figure 29. Non-Combustible Clearances
22
Page 23
Initial Installation
42”
41”
40”
39”
38”
37”
36”
35”
1 2 3 4 5 6 7 8 9 10 11 12
M A N T L E H E I G H T
( F R O M U N I T B O T T O M )
M A N T L E D E P T H
Minimum Mantle Clearances
12” MANTLE
2” MANTLE
QUALIFIED INSTALLERS ONLY
mantle: It is not necessary to install a mantle,
but if one is desired the guidelines as shown
in Figures 29 and 30 must be followed.
Figure 30. Mantle Clearances
Direct vent:
WARNING: This appliance has been designed to draw room air for proper heat circulation
from the bottom of the unit, and out the top front. Blocking or modifying these openings in
any way can create hazardous situations.
The vent length for the Q1C must be between 7” (18 cm) and 44ft (13.4 m). This model is vented with
co-axial 4” intake, 6 5/8” exhaust aluminum or stainless steel approved rigid vent leading into a vertical
or horizontal termination cap. The ue collar of this model will t inside of a standard 4” x 6 5/8” vent
and must be either correctly interlocked or fastened, with three screws directly to the vent.
The Q1C may also be converted to a replace insert with the use of a co-linear vent adapter kit (50-
2982) see
InItIal InstallatIon - co-lInear VentIng aDapter KIt. When converted to co-linear venting
the lenth of vent must be between 8’ (2.44m) and 40’ (12.19m). The insert model is vented with
a 3” intake and a 3” exhaust aluminum or stainless steel approved ex vent leading into a vertical
termination cap only. The ue collars of this model will t inside of a standard 3” vent
and must be fastened directly to the vent with three screws. The exhaust vent and air intake are both
located on the top of the unit.
Check periodically that the vents are unrestricted. Also ensure that all direct vent pipes have been
properly sealed and installed after routine inspection or cleaning. The air intake and exhaust pipes must
be installed in the correct locations on the top of the Q1C.
venting fireplace inserts:
When using the co-linear venting adapter kit (50-2982) the Q1C may be installed and vented into any
solid fuel replace that has been installed in accordance with the National, Provincial/State and local
building codes and has been constructed of noncombustible materials. Please reference the information
in Table 11 and Figures 47. An approved chimney liner and rain cap must be used. A throat connector
or ashing must be installed to ensure a tight seal, top performance, safety and efciency. Carefully
follow the manufacturer’s instructions that accompany the chimney liner kit. Use double walled
aluminum ex vent (3” ex conversion piece and 4”x 6 5/8” cap) from the following approved products;
Simpson Dura-Vent (Direct Vent GS). If necessary, remove the vent collar plate from the top of the
insert and connect it securely to the liner with sheet metal screws. Check for any tears in the liner at
this point. IMPORTANT: The screws that hold the vent collar plate in its approved position must be
installed.
NOTE: If the Q1C unit is pulled out of its installation, and the vent-air intake system is disconnected
for any reason, ensure that the vent-air intake pipes are re-sealed with high-temperature sealant and
23
reconnected with three (3) sheet metal screws evenly spaced.
Page 24
Initial Installation
QUALIFIED INSTALLERS ONLY
vent termination restrictions:
N
O
D
E
C
B
L
F
Fixed
Closed
Openable
B
B
Openable
Fixed
Closed
H
G
G
M
B
A
J
I
Termination Cap
Figure 31. Vent Termination Restrictions, refer to Table 5.
LetterCanadian Installation
A12 in (30 cm)Clearance above grade, verandah, porch, deck, or balcony.
B12 in (30 cm) 9 in (23 cm)Clearance from window or door that may be opened.
C12 in (30 cm)*Clearance from permanently closed window (to prevent
D24 in (60 cm)*Vertical clearance to ventilated soft located above the
E18 in (45 cm)*Clearance to unventilated soft.
F12 in (30 cm)*Clearance to outside corner.
G12 in (30 cm)*Clearance to inside corner.
H3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly
I3 ft (91 cm)3 ft (91 cm)*Radial clearance around service regulator vent outlet.
J12 in (30 cm)9 in (23 cm)Clearance to non-mechanical air supply inlet to building, or
K6 ft (1.83 m)3 ft (91 cm) above if within 10
L7 ft (2.13 m
M12 in / 30 cm
N12 in (30 cm)*Clearance horizontally to any surface (such as an exterior
O12 in (30 cm)Clearance above roof line for vertical terminations.
1
)t
+
Air Supply Inlet
Gas MeterG
Restriction Zone
(Termination not allowed)
Table 5: Vent termination clearances.
US Installation
3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly*
ft (3 m) horizontally
7 ft (2.13 m)
12 in / 30 cm*
2
condensation).
terminal, within a horizontal distance of 2 ft (60 cm) from
center line of terminal.
Clearance to each side of center line extended above meter/regulator assembly.
the combustion air inlet to any other appliance.
Clearance to mechanical air supply inlet.
*t
+
Clearance above paved sidewalk or paved driveway located
on public property.
Clearance under verandah, porch, deck, or balcony.
wall) for vertical terminations.
Description
K
A
1
In accordance with the current CSA B149, Natural Gas and Propane Installation Code.
2
In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.
* These numbers are only estimates.
t
A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings
and it serves both dwellings.
+
Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
Clearances are in accordance with local installation codes and the requirements of the gas supplier.
NOTE: Venting terminals shall not be recessed into walls or siding.
24
Page 25
Initial Installation
Framing
Joists/Studs
10”
10”
QUALIFIED INSTALLERS ONLY
venting clearances:
A 1” (25 mm) clearance to combustibles must be maintained around any vertical vent pipe. Around a
horizontal vent pipe, the clearance to combustibles should be 2” (51 mm) above and 1½” (38 mm) on the
sides and bottom. When combustible materials are directly above a 90° elbow, 3” (76 mm) of clearance
are necessary.
Table 6. Vent Pipe Minimum Clearances.
Vertical Pipe to
the Side Walls
Hard
Pipe
1”
(25.4 mm)
A 10” (254 mm) x 10” (254 mm) frame (see Figure 32) will assure the proper support and spacing for
the vent pipe as it passes through the wall. Installations in Canada require that a wall thimble be used for
passing through walls and ceilings. All sealing and vapour barriers must comply with local building codes.
The conguration of the venting pipes depends on the locations
of walls, ceilings, and studs. However, the pipes cannot be of
arbitrary length and arrangement. Because the length of the
vertical and horizontal sections dramatically affects the burning
efciency of the replace, certain guidelines have been set in
The Q1C replace has been tested and certied for use with AMERICAN METAL PRODUCTS “AMERIVENT
DIRECT”, SIMPSON DURAVENT TYPE GS PIPE FOR GAS STOVES. SECURITY CHIMNEY’S “SECURE VENT
DIRECT VENT SYSTEM” and SELKIRK “DIRECT-TEMP VENT SYSTEM” kits are available for horizontal and
vertical venting. When using Simpson Duravent, it is recommended that, before installation, a bead of
RTV High Temperature Silicone should be applied to each outer vent joint, and Mil-Pac to each inner
joint. When planning an installation, it will be necessary to select the proper length of vent pipe for the
particular requirements.
25
WARNING: Do not mix parts from different vent manufacturers’ systems.
Page 26
Initial Installation
QUALIFIED INSTALLERS ONLY
EXCEPTION TO WARNING: This product has been evaluated by Intertek for using a Direct Vent GS
starting collar in conjunction with Secure Vent, Direct-Temp, AmeriVent Direct, and EXCELDirect venting
systems. Use of these systems with the Direct Vent GS starting collar is deemed acceptable and does
not affect the Intertek WH listing of the appliance.
Table 8: Vent part numbers (Must state if galvanized or black wanted, PART NUMBERS).
Direct Vent GSDirect-Temp Secure VentAmeri Vent DirectDescription
The Q1C can be installed in rear vent applications with no vertical rise within the parameters as shown
in Figures 33 and 34.
Approved horizontal termination
18” (46 cm) Max. vent length
Approved through wall thimble
Figure 33. Corner Rear Vent - No Vertical Rise
Max. 1 x 45˚ Elbow
7” (18 cm) Min. vent length
24” (61 cm) Max. vent length
Approved horizontal termination
27
Approved through wall thimble
Figure 34. Flat to Wall Rear Vent - No Vertical Rise
Page 28
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14
HORIZONTAL RUN
ft
VERTICAL RISE
INSTALLATION
PROHIBITED
INSTALLATION
PROHIBITED
Initial Installation
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
HORIZONTAL RUN
QUALIFIED INSTALLERS ONLY
allowable co-axial vent configurations:
Figures 35 & 36 show the range of possible vent congurations if the unit is top or rear vented, for vertical
and horizontal terminations. Any layout that remains within the shaded areas is acceptable. Having the
fewest number of elbows is ideal, as they tend to disrupt air movement. Using 45˚ elbows is preferable to
using 90˚ elbows. Also, a shorter vent system will perform better than a longer one. When top vented, the
total length of horizontal vent pipe can not exceed 14 feet (4.27m) and the total vent length can not exceed
Figure 35. Possible Vent Congurations for Top
Vented Vertical and Horizontal Terminations.
44ft (13.4m). Any combination of rise and
run can be used as long as it lays within the
shaded area (a total of two (2) 90˚ elbows or
four (4) 45˚ elbows can be used. In addition
to what is shown, if a 90˚ elbow is used in
the horizontal plane, 3 feet (91.4cm) must
be subtracted from the allowable horizontal
run (for each 45˚ elbow, 1½ feet must be
subtracted).
Note: Air restrictors (supplied with the
unit) are required for vertical venting runs
of 8ft (2.44m) or taller. See
aIr restrIctor
settIngs for more information
Note: Minimum length of co-linear venting
is 8ft (2.44m) and maximum length is 40ft
(12.19m)
7
13
12
6
11
10
5
9
INSTALLATION
PROHIBITED
8
4
7
6
3
5
VERTICAL RISE
4
2
3
2
1
1
ft
1 2 3 4 5 6 7 8 9
12345
HORIZONTAL RUN
Figure 36. Possible Vent Congurations
for Rear Vented Vertical and Horizontal
Terminations.
28
Page 29
Initial Installation
26 1/2"
(673mm)
12 3/8" (313mm)
or
14 1/4" (362mm)
or
14 15/16" (380mm)
QUALIFIED INSTALLERS ONLY
co-linear venting aDapter Kit (50-2982):
The Q1C can be converted from solid co-axial venting to 3” (76mm) exible co-linear venting to allow
for installation into exisiting masonary replaces (see Figures 31-33). Co-linear venting can not be used
in combustible chimney installations. This adapter kit is for vertical terminations only and can’t be
connected to a chimney ue serving a seperate solid-fuel burning stove or appliance. To adjust the depth
of the unit please refer the the InItIal InstallatIon - aDjustIng Install Depth section of the manual.
Note: The co-linear adapter kit can only be used in the top vent conguration
WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts
specically approved with this appliance may result in property damage or personal injury.
29
Adapter Kit Contents:
Vent Plate Adapter
Ceramic Gasket
Figure 37: Q1 Insert Dimensions
3” Dia. Exhaust
Spigot
Figure 38: Co-Linear Venting Kit Contents
Vent Plate Adapter
Exhaust Spigot
Ceramic Flange
Gasket
Exhaust Spigot
Ceramic Tube
Gasket
Page 30
Initial Installation
Adapter Kit Installation:
QUALIFIED INSTALLERS ONLY
Vent Collar
Base Plate
4” Exhaust Spigot
Cover Plate
Figure 39: Removal of Co-Axial Venting
Vent Plate Adapter
3” Exhaust Spigot
Step 1: Using a T20 screwdriver
remove the vent collar, base plate,
cover plate and 4” exhaust spigot
(28 screws total) as shown in
Figure 32. The vent collar, base
plate, and 4” exhaust spigot will
no longer be used.
Cover Plate
Figure 40: Installation of Co-Linear Vent Kit
Step 2: Install the components
supplied in the adapter kit as
shown using the screws that had
been removed from the unit in
Step 1. The gasket on the bottom
side the vent plate adapter and
exhaust spigot ange gasket will
be sandwiched together when
properly installed.
30
Page 31
Initial Installation
A
QUALIFIED INSTALLERS ONLY
air restrictor settings:
When installing the Q1C with 8ft (2.44M) or more of vertical venting, either co-axial or co-linear, it may be
necessary to restrict the fresh air supply in the rebox to control the combustion and ame appearance.
Using the pair of air restrictors supplied with the unit, install them on each side of the rebox and adjust
to the correct setting as outlined in the gure and table below. To install the air restrictors rst you
must remove the log set, air diffuser, and creamic brick panels (see seconDary InstallatIon - optIonal
porcelaIn panels InstallatIonanD reMoVal) then remove the set screws as shown on each side of the
rebox. Next, install the restrictors at the correct setting and tighten the set screws to hold them in place.
#3
#1
#2
Set Screw
Figure 41: Installation of Air Restrictors
Table 9: Air Restrictor Settings
Air Restrictor Settings
Length of Vertical VentPropaneNatural Gas
Less than 8ft (2.44m) co-linear or co-axialNo Restriction RequiredNo Restriction Required
Through Roof Termination, more than 20ft
(6.1m) to 40ft (12.19m) co-linear
Through Roof Termination, more than 20ft
(6.1m) to 40ft (12.19m) co-axial
Setting #2Setting #3
Setting #1Setting #1
Page 32
Initial Installation
QUALIFIED INSTALLERS ONLY
horizontal termination:
NOTES:
1. Horizontal pipes must not be level. For every 12 inches (305 mm) of horizontal travel
(away from the stove), there should be at least ¼ inch (6.4 mm) of vertical travel. Never
allow the vent to run downward, as this could cause high temperatures or even present
the possibility of a re.
2. The exterior of the horizontal
vent termination must not be
blocked or obstructed.
3. If the vent termination is not
being attached to wood, the
four wood screws provided
should be replaced with material
appropriate fasteners.
4. For buildings with vinyl siding,
a vinyl standoff should be
Elbow
installed between the vent cap
and the exterior wall. Attach
the vinyl siding standoff to
the horizontal termination.
Note that the termination
bolts onto the at portion of
the standoff, providing an air
space between the wall and
the vent termination. The air
gap prevents excessive heat
from possibly melting the vinyl
siding.
5. Horizontal pipes must be
supported every 3 feet (914
mm). Plumber’s all round strap will sufce.
Wall thimble
fire stop
Exhaust
pipe
Combustion air
outer pipe
Figure 42. Horizontal Vent Termination
Horizontal wall
termination
Wall framing
6. When running horizontal pipe, clearances to combustibles must be maintained 1½ inches (38 mm)
sides, 1½ inches (38 mm) bottom, and 2 inches (51 mm) top.
Step 1.
Set the replace in the desired location. Check to determine if wall studs will be in the way when
the venting system is attached. If this is the case, the location of the replace may have to be
adjusted or the venting may have to be offset.
Step 2. Direct vent pipe sections are designed with special twist-lock connections. Dry t the desired
combination of pipe and elbows to the appliance adaptor.
Step 3. With the pipe in the correct position and attached to the replace, mark the wall for a 10 inches
(25.4 cm) x 10 inches (25.4 cm) square hole (see Figure 42). The center of the hole should
match the center line of the horizontal pipe. Cut and frame the hole in the exterior wall where
the vent will be terminated. If the wall being penetrated is made of a non-combustible material
(i.e. masonry or concrete) a 7 inches (17.8 cm) hole is acceptable.
32
Page 33
Initial Installation
QUALIFIED INSTALLERS ONLY
NOTE: For Simpson Duravent only, place a bead of Mil-Pac or Rutland No 78 Stove and Gasket Cement
on the outer edge of the inner exhaust pipe (non-ared end). Push the pipe sections together, then twist
about ¼ turn, making sure the two sections are fully locked. Wrap all seams with foil ducting tape.
Step 4.
With the hole now framed, the wall thimble installed, and the pipe extending into the wall,
proceed to the outside. Attach the termination to the pipe using RTV and Mil-Pac or Rutland No
78 Stove and Gasket Cement to seal joints. The vent pipe must extend into the vent cap at least
1¼ inches (3.2 cm). Secure the connection between the vent cap and the pipe by attaching the
two (2) sheet metal straps, which extend from the vent cap assembly to the outer wall of the
vent pipe. Bend any remaining portion of the strap back towards the vent cap. Security Secure
Vent uses a twist lock cap.
Step 5.
Position the horizontal vent termination in the center of the 10 inches (25.4 cm) square hole
and attach to the exterior wall with the four screws provided. The arrow on the vent termination
should be pointing up. Run a bead of non-hardening mastic around the edges of the vent
cap, to make a seal with the wall. Ensure the proper clearances to combustibles have been
maintained.
vertical termination:
Step 1. Check the instructions for required clearances (air spaces) to combustibles when passing
through ceilings, walls, roofs, enclosures, attic rafters, or other nearby combustible surfaces.
Do not pack air spaces with insulation.
Step 2. Set the gas appliance in the desired location. Drop a plumb bob down from the ceiling to
the position of the appliance ue exit, and mark the location where the vent will penetrate
the ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole
previously drilled in the ceiling, mark the spot where the vent will penetrate the roof. Determine
if ceiling joists, roof rafters, or other framing will obstruct the venting system. You may wish to
relocate the appliance, or to offset, to avoid cutting load bearing members.
Step 3. To install the Round
Support Box/Wall Thimble
in a at ceiling, cut a 10
inch (25.4 cm) square hole
in the ceiling, centered in
the hole drilled in Step 2.
Frame the hole as shown
in Figure 42.
Step 4.
Assemble the desired
lengths of black pipe
and elbows necessary to
reach from the appliance
adapter up through the
Round Support Box.
Insure that all pipe and
elbow connections are
in their fully twist-locked
position.
Elbow Strap
Figure 43. Vertical Vent Termination
Vertical
Termination
Storm Collar
Flashing
Roofing nails
33
Page 34
Initial Installation
H
Dimension‘H’obtainedfromtablebelow.
QUALIFIED INSTALLERS ONLY
STEP 5. Cut hole in the roof centered on the small hole placed in the roof from Step 2. The hole should
be of sufcient size to meet minimum requirements for Clearance to Combustibles, as specied.
Continue to assemble lengths of pipe and elbows necessary to reach from the ceiling support
box up through the roof line. Galvanized pipe and elbows may be utilized in the attic, as well
as above the roof line. The galvanized nish is desirable above the roof line, due to the higher
corrosion resistance.
STEP 6.
Once the pipe sections have been joined, and run up through the hole in the roof, slip an elbow
strap over the exposed sections, bend the support straps outwards, and push the elbow strap
down to the roof level, as shown in Figure 43. Tighten the clamp around the pipe section. Use
a level to make sure the pipe is truly vertical. With roong nails, secure the support straps to
the roof. Seal the nails holes heads with non-hardening mastic. Trim the excess length of the
support straps that extend out beyond the edge of the ashing.
STEP 7.
Slip the ashing over the pipe section protruding through the roof. Secure the base of the
ashing to the roof with roong nails. Use a non-hardening sealant between the uphill edge
of the ashing and the roof. Insure the roong material overlaps the top edge of the ashing.
Verify that you have at least the minimum clearance to combustibles at the roof line.
STEP 8.
Continue to add pipe sections until the height of the vent cap meets the minimum code
requirements. Refer to Figure 44 and Table 10. Note that for steep roof pitches, the vent height
must be increased. In high wind conditions, nearby trees, adjoining roof lines, steep pitched
roofs, and other similar factors can result in poor draft, or down drafting. In these cases,
increasing the vent height may solve the problem.
STEP 9.
Slip the storm collar over the pipe, and push it down to the top of the roof ashing as shown
in Figure 43. Use the non-hardening sealant around the joint between the pipe and the storm
collar.
STEP 10. Twist-lock the vent cap.
Table 10: Minimum ‘H’ for Figure 35.
Roof PitchMinimum Height (H)
Figure 44: Height of Vertical Termination;
Reference Table 8.
FeetMeters
Flat to 7/1210.3
Over 7/12 to 8/121.50.46
Over 8/12 to 9/1220.61
Over 9/12 to 10/122.50.76
Over 10/12 to 11/123.250.99
Over 11/12 to 12/1241.22
Over 12/12 to 14/1251.52
Over 14/12 to 16/1261.83
Over 16/12 to 18/1272.13
Over 18/12 to 20/127.52.29
Over 20/12 to 21/1282.44
34
Page 35
plumber’stapeconnectedtowallstrap
Wallstrap
45°elbows(x2)
Initial Installation
QUALIFIED INSTALLERS ONLY
NOTES:
(1)
If an offset is necessary in the attic to avoid
obstructions, it is important to support the vent pipe
every 3 feet (914 mm), to avoid excessive stress
on the elbows, and possible separation. Wall straps
are available for this purpose (see Figure 45).
(2) When ever possible, use 45° degree elbows instead
of 90° degree elbows. The 45° degree elbow offers
less restriction to the ow of ue gases and intake
air.
(3)
For multi story installations; a ceiling restop is
required at the second oor, and any subsequent
oors (see Figure 46). The opening should be
framed to 10” (254 mm) x 10” (254 mm) inside
dimensions, in the same manner as shown in Figure
32.
(4) Any occupied areas above the rst oor, including
Figure 45: Use of Wall Straps.
closets and storage spaces, which the
vertical vent passes through, must be
enclosed. The enclosure may be framed
and sheet-rocked with standard building
materials. However consult the appliance
manufactures installation instructions
for the minimum allowable clearance
between the outside of the vent pipe, and
the combustible surfaces of the enclosure.
Do not ll any required air spaces with
insulation.
Figure 46: Multi-Story Vent Pipe Installation.
35
Page 36
Initial Installation
The total vent length must be between 8 ft (2.44 m) and 40 ft (12.19 m).
Install a sealed vent cap to prevent leakage of room air up through chimney.
The intake and the exhaust are 3" (76mm).
Measure the height of the chimney beforehand and purchase the appropriate
venting. Never attempt to over-stretch a flexible liner to accommodate the
height of the chimney. Every joint in the venting must be secured with three (3)
#8 x 3/8” HWH sheet metal screws and an appropriate sealant (either silicone
or stove cement).
The flue damper can be fully blocked open or removed for installation of the
unit; the smoke shelves, shields and baffles may be removed if attached by
mechanical fasteners.
The fireplace and fireplace chimney must be clean, in good working order and
constructed of non-combustible materials.
Make sure that all chimney cleanouts are tight fitting and will not permit air to
leak into the chimney.
Refractory, glass doors, screen rails, screen mesh and log grates can be
removed from the fireplace before installing the unit.
Note: Space must be left for gas line on left side of unit for servicing purposes
The base, sidewalls and top structure of the solid fuel rebox cannot be altered with the exception of:
removal of dampers, removal of smoke shelf or bafe, removal of ember catches, removal of log grate,
removal of viewing screen/curtain, and removal of doors. THE ORIGINAL FIREPLACE MAY NEVER BE
RETURNED TO SOLID FUEL USE IN THIS CONDITION.
Figure 47: Solid Fuel Fireplace Installation.
IMPORTANT: If the factory-built replace has no gas access hole(s) provided, an access hole of 1.5 inch
(37.5 mm) or less may be drilled through the lower sides or bottom of the rebox in a proper workmanship
like manner. This access hole must be plugged with non-combustible insulation after the gas supply line
has been installed. Cutting any
sheet-metal parts of the replace,
in which the gas replace insert is
to be installed is prohibited. The
label plate shown on the right,
included with co-linear venting
adapter kit, must be permanently
attached inside the cavity of the
replace in a visible location.
Figure 48: Fireplace Altered Plate.
36
Page 37
Initial Installation
QUALIFIED INSTALLERS ONLY
gas line connectionanD testing:
WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to
this appliance.
GAS LINE CONNECTION
•This stove is equipped with a certied exible pipe located on the left side of the unit terminating
in a 3/8” female NPT tting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2)
installation code in Canada, or in the USA gas installations follow either local codes or the current
edition of the National Fuel Gas Code ANSI Z223.1.
•The efciency rating of this appliance is a product thermal efciency rating determined under
continuous operating conditions and was determined independently of any installed system.
The appliance and its shutoff valves must be
disconnected from the gas supply piping system
Gas Control
Knob
Pilot Adjustment
Screw
during any pressure testing where the pressure
exceeds ½ PSIG (3.45 KPa) or damage will occur
to the valve.
The appliance must be isolated from the gas supply
piping system by closing its individual manual
N
O
T
O
L
I
P
F
O
F
shutoff valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than ½ psig (3.45 KPa).
Always check for gas leaks with a soap
and water solution after completing the
required pressure test.
Inlet
PressureTap
INOUT
Manifold
PressureTap
Figure 49: Fully Labeled Gas Valve.
TO TEST VALVE PRESSURES
The pressure taps are located on the top right of the valve shown in Figure 49.
•Turn set screw 1 turn counter clockwise to loosen,
•Place
5
/16” (8 mm) I.D. hose over pressure tap system.
•Check pressures using a manometer.
•When nished, release pressure, remove hose & tighten set screw.
Min. Manifold Pressure1.6” W.C. (0.40 KPa)6.4” W.C. (1.59 KPa)
Max Supply Pressure7.0” W.C. (1.74 KPa)11.0” W.C. (2.74 KPa)
Min. Supply Pressure4.5” W.C. (1.12 KPa)10.4” W.C. (2.59 KPa)
Max BTU/hr Input20,000 BTU/hr (5.86 KW)18,500 BTU/hr (8.42 KW)
Min. BTU/hr Input13,600 BTU/hr (3.98 KW)14,500 BTU/hr (4.25 KW)
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
Page 38
Initial Installation
QUALIFIED INSTALLERS ONLY
electrical requirements:
The fan will not operate if the appliance is cold. Once the unit is lit and the fan is set to the desired level,
the fan will automatically turn on upon reaching operating temperature. The fan will automatically turn
off after the appliance has cooled down.
Figure 50: Fan wiring diagram.
The replace must be electrically connected and grounded in accordance with local codes or, in the
absence of local codes, with the current CSA C22.1 Canadian Electrical Code Part 1, Safety Standards For
Electrical Installations, or The National Electrical Code ANSI / NFPA 70 in the US.
WARNING: The electrical grounding instructions must be followed. The fan kit is equipped with a threeprong (grounding) plug for your protection against shock hazard, and should be plugged directly into a
properly grounded three-prong outlet. DO NOT cut or remove the grounding prong from this plug.
CAUTION: When servicing controls, label all wires prior to disconnection. Wiring errors can cause
improper and dangerous operation. Verify proper operation after servicing.
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with 18
AWG wire with a temperature rating of 105°C
38
Page 39
Secondary Installation
coal set installation:
The placement of the coal set is not arbitrary. If it is positioned incorrectly, the ames can be “pinched”
and will not burn correctly. Using the pictures provided, carefully set the coal set in place (see Figures 43
through 47). The pictures below feature the optional ledgestone panels installed.
NOTE: The coal set is fragile and should be handled gently.
Figure 51: This is how the
rebox looks with only
the burner, back rest, and
ledgestone panels in place.
Figure 51. Empty rebox with burner installed
Figure 52. Coal Bed Installation.
Step 1: Place the lower coal bed in
the rebox by placing the rear of the
bed on the back rest and front of the
bed on the burner supports. Make sure
the front of the coal bed is touching
the ngers at the front of each burner
mount.
39
Page 40
Secondary Installation
Figure 53. Second Stage Coal Set Installation.
Step 2: Install the two front coal
pieces at the front of the rebox as
shown in Figure 53. The pieces will
sit down in the gap between the
back of the burner and the front
edge of the rebox.
Step 3: Next, install the set of
three coal rocks on the locator
pins at the top of the coal bed.
The at side of the rocks will face
forward when installed correctly
(see Figure 54). Finally, install the
top coal bed by resting it on top of
the lower coal bed ensuring it is
properly centered. The front edge
of the top coal bed will touch the
back side of the front coal pieces
and rest on top of the burner when
correctly installed.
NOTE: While the glass is still
removed, it is recommended that
the gas line be purged by lighting
the pilot.
When lighting the replace for the
rst time since the coal set has been
installed/replaced, watch for ignition
at ALL the burner ports. If a long
delay is noticed, turn the appliance
off and wait for it to cool down.
Then remove the glass and make
sure none of the burner ports are
blocked.
Figure 54. Third Stage Coal Set Installation.
Maintenance: Once a year, the coal set should be removed and
checked for deterioration or large amounts of soot. A small amount
on the bottom side or in the holes of the coal set is normal. Remove
and replace the coal set in the same manner described above. Cracks
on the surface of the lower coal bed are normal and will not effect the
performance.
If a new coal set is required, contact your nearest ENVIRO dealer.
Never operate the replace with the glass door removed.
1. Remove the glass door by following the
instruction in the “
glass Door reMoVal” section and remove the
coal set as outlined in the previous section.
2. Remove the rebox bafe by unscrewing the
two screws indicated in Figure 50 using a T20
screwdriver. Lower the front of the bafe down
Figure 55. Bafe Screws.
3. Next, remove the top brick panel retainers on each side as shown in Figure 56 using a T20 screwdriver.
and then lift it out of the two locating screws at
the rear of the rebox.
MaIntenanceanD serVIce -
4. Carefully remove the left, rear, and right brick panels from the rebox.
5. Install the rear porcelain panel rst by sitting it on the ledge
at the rear of the rebox (see gure 57), then follow with
the left and right panels.
6. Re-install the brick panel retainer screws and brackets
7. Re-install the rebox bafe.
8. Install the top porcelain panel by screwing it to the rebox
bafe as show in Figure 58 using the supplied screws.
9. Re-install the coal set as outlined in the previous section.
10. Re-Install the glass door
Figure 56. Top Panel Retainers.
41
Figure 57. Rear Panel Ledge.Figure 58. Top Panel Screws.
Page 42
Secondary Installation
safety screen installation:
Safety Screen Frame
Right Bracket
Top/Bottom
Bracket
The safety screen supplied with the unit must be
assembled rst before it can be installed. When
installed, the screen should not extrude out any farther
than the surround panel if the cabinet extensions are
still installed.
Safety Screen Assembly
1. Attach the left, right, top/bottom brackets onto
the safety screen using a T20 screwdriver and the
supplied sixteen (16) #8 T20 screws (see Figure
59). Do not over-tighten the screws, doing so
could cause them to strip out of the screen frame.
2. Lift the face upright in front of the replace with
the four (4) hooks pointing towards the replace.
Slide the hooks into the corresponding brackets
on each side of the cabinet (see Figure 61).
Ensure the hooks are secure before releasing the
safety screen.
Top/Bottom
Bracket
Figure 59: Installing Safety Screen Mounts.
Left Bracket
Figure 60: Installing Safety Screen onto
Brackets.
Figure 61: Installing Safety Screen onto
Cabinet Bracket (Parts removed for clarity)
42
Page 43
Trouble Shooting
ProblemPossible CauseSolution
The main burner does not
ignite when called for.
Spark will not light the pilot
after repeatedly pressing the
spark ignitor.
Pilot will not remain lit.Problem with thermocouple
The gas valve may not be on.• Check that the gas control knob is in the “ON” position.
Thermostat is not calling for
heat.
Problem with gas valve.• Use a DC voltmeter to measure the voltage across the
Defective piezo ignitor.• Check connections to ignitor.
Broken spark electrode.• Check for broken ceramic insulation, replace electrode if
Misaligned spark electrode.• If spark is not arcing from electrode to pilot, loosen the
circuit.
• Adjust the thermostat several degrees above ambient
temperature.
TPTH and TP terminals. Main operator voltage: Open
circuit ≥ 325mV Closed circuit ≥ 100mV
• If voltage is not present, check the control circuit for
proper operation.
• If proper control system voltage is present, replace the
gas control.
• If ignitor connections are good but no spark, replace
ignitor.
broken.
screws on the pilot base adjust and tighten.
• Check for proper connection of the thermocouple to the
rear of the valve. If loose, fully tighten.
• Check pilot for full ame impingement around
thermocouple. If ame is too small, check gas pressure,
adjust pilot rate screw, check pilot head for damage.
• Check thermocouple voltage at valve. It must be greater
than 5 mV. If low, replace thermocouple.
Air in gas line (pilot dies while
knob is depressed).
Burners will not remain lit.Problem with thermopile
circuit.
Flame liftingLeak in vent pipe• Check for leaks in vent connections.
Improper vent conguration• Check vent conguration with manual.
Terminal may be recirculating
ue gases
Glass fogs upNormal Condition: after the appliance warms up the glass will clear.
**Due to additives in gas, glass may get hazy during operation** Clean as needed.
Blue FlamesNormal during start up: ames will yellow as the replace heats up.
Flames are burning “dirty” or
sooting
Remote control doesn’t workProblem with the remote• One or more of the batteries are dead. See remote
Flame impingement• Check coal set positioning.
Problem with replace• The on/off switch is turned to OFF.
• Bleed line.
• Check gas line pressure.
• Contact dealer.
• Check gas line pressure .
• Check for ame impingement on thermopile. If low, see
“Pilot will not remain lit”.
• Check thermopile for minimum of 300 mV when burner is
switched on.
• Check wiring to thermostat for breaks.
• Check to see if terminal is on correctly.
• May need to install high wind termination cap.
• Contact dealer.
• Increase primary air by opening the venturi shutter and/
or by opening the vent restrictor.
See also “Burners will not remain lit.”
control instructions.
• The gas control valve is turned to PILOT or OFF.
• The pilot has gone out.
43
Page 44
Parts List
Reference
Number
1Door Release Tool50-2510
2Door Latch Mechanism w/ Spring (set of 2)50-1285
3Firebox Air Restrictors (set of 2)50-2988
4Coal Burner Pilot Shield50-2995
5120 Ceramic Fan Temperature SensorEC-001
13S.I.T. Nova Valve - Convertible50-1421
14Heyco Strain ReliefEC-044
15Domestic Power Cord (115v)EC-042
16Coal Set50-2937
17Tube Burner50-2992
18Door Glass w/ Gasket (19.75 x 17.5in)50-2998
19Door Complete50-2990
20Porcelain Liners Set (4 pieces)50-2939
21Ceramic Brick Liner Set (3 pieces)50-2938
-Ceramic Ledgstone Liner Set (3 pieces)50-2972
-Fireplace Floor Pad 12” x 20”50-3016
22Co-Linear Vent Kit50-2982
23Q1C Owners Manual50-3001
-Q1 Replacement Safety Screen50-3052
-Q1 Conversion Kit - LP to NG (Nova)50-2993
-Q1 Conversion Kit - NG to LP (Nova)50-2983
-12 oz. Can of Matallic Black Touch Up PaintPAINT-12-MB
Part DescriptionPart Number
44
Page 45
Parts Diagram
20
2
4
3
5
13
16
15
14
11
9
12
8
7
6
17
18
19
1
10
21
23
22
45
Page 46
Notes
46
Page 47
Jan 2013
Sher wood Industries Ltd. (“Sher wood”) hereby warrants, subject to the terms and
conditions herein set for th, this product against defects in material and workmanship
during the specied warranty period starting from the date of original purchase at retail.
In the event of a defect of material or workmanship during the specied warranty period,
Sherwood reser ves the right to make repairs or to assess the replacement of a defective
product at Sherwood’s factory. The shipp
ing costs are to be paid by the consumer.
All warranties by Sherwood are set forth herein and no claim shall be made against
Sherwood on any oral warranty or representation.
Conditions
A completed warranty registration must be submitted to Sherwood within 90 days
of original purchase via the online warranty registration page or via the mail-in
warranty registration card provided. Have the installe
r ll in the installation data
sheet in the back of the manual for warranty and future reference.
This warranty applies only to the original owner in the original location from date of
install.
The unit must have been properly installed by a qualied technician or installer, and
must meet all local and national building code requirements.
The warranty does not cover removal and re-installation costs.
Sherwood Industries Ltd. reserves the right to make changes without notice.
Sherwood Industries Ltd. and its employees or representatives will not assume
any damages, either directly or indirectly caused by improper usage, operation,
installation, servicing or maintenance of this appliance.
A proof of original purchase must be provided by you or the dealer including serial
number.
Exclusions
An expanded list of exclusions is available at www.enviro.com/help/warranty.html
This warranty does not cover:
Damage as a result of improper usage or abuse.
Damage caused from over-ring due to incorrect setup or tampering.
Damage caused by incorrect installation.
To the Dealer
Provide name, address and telephone number of purchaser and date of purchase.
Provide date of purchase. Name of installer and dealer. Serial number of the
appliance. Nature of complaint, defects or malfunction, description and part #
of any parts replaced.
Pictures or return of damaged or defective product may be required.
To the Distributor
Sign and verify that work and information are correct.