Enviro Q1C Owner's Manual

Page 1
enviro.com/warranty
Q1C
D I REC T VE N T F I R E PL ACE - N OVA
OWNER’S MANUAL
WARNING: If the information in this manual is not followed exactly, a
re or explosion may result causing property damage, personal injury
or loss of life. Installation and service must be performed by a qualied
4001609
Version Française: www.enviro.com/fr.html
installer, service agency or the gas supplier.
50-3001
Page 2
Safety Precautions
WARNING: FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in serious
injury, death, or property damage.
- Do not store or use gasoline or other ammable vapors and
liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Leave the building immeadiately.
• Immeadiately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
• If you cannot reach your gas supplier, call the re department.
- Installation and service must be performed by a qualied
installer, service agency or the gas supplier.
INSTALLER:
Leave this manual with the appliance.
CONSUMER:
Retain this manual for future reference.
This appliance may be installed in an after-market permanently located,
manufactured (mobile) home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases, unless a certied kit is used.
Massachusetts installations (Warning): This product must be installed by a licensed plumber or
gas tter when installed within the Commonwealth of Massachusetts. Other Massachusetts code
requirements: Flexible connector must not be longer than 36in., a shut off valve must be installed; only direct vent sealed combustion products are approved for bedrooms/bathrooms. A carbon
monoxide detector is required in all rooms containing gas red direct vent appliances. The replace damper must be removed or welded in the open position prior to installation of a replace insert.
2
Page 3
Safety Precautions
HOT GLASS WILL
CAUSE BURNS
DO NOT TOUCH GLASS
UNTIL COOLED.
NEVER ALLOW CHILDREN
TO TOUCH GLASS.

A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appliance and shall
individuals.
FOR SAFE INSTALLATION AND OPERATION OF YOUR “ENVIRO” HEATER, PLEASE CAREFULLY READ THE FOLLOWING INFORMATION:
• All ENVIRO gas-red appliances must be installed in accordance with their instructions. Carefully read all the instructions in this manual rst. Consult the building
authority having jurisdiction to determine the need for a permit prior to commencing the installation.
NOTE: Failure to follow these instructions could cause a malfunction of the replace, which could result in death,
serious bodily injury, and/or property damage.
• Failure to follow these instructions may also void your re insurance and/or warranty.
GENERAL
• Installation and repair should be done by a qualied
service person. The appliance should be inspected before
the rst use and, at least, annually by a qualied service
person. More frequent cleaning may be required due to
excessive lint from carpeting, bedding material, etc. It
is imperative the control compartments, burners and circulating air passageways of the appliance be kept clean.
• Due to high temperatures, the appliance should be located out of high trafc areas and away from furniture
and draperies.
Children and adults should be alerted to the
hazards of high surface temperatures and should stay away to avoid burn or clothing ignition.
• Young children should be carefully supervised when
in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individuals in the house. To restrict access to a
replace or stove install an adjustable safety gate to keep
toddlers, young children and other at risk individuals out of the room and away from hot surfaces. Any safety screen, guard, or barrier removed for servicing an appliance must be replaced prior to operating the appliance.
• Clothing or other ammable materials should not be
placed on or near the appliance.
3
• A barrier designed to reduce the risk of burns from the
hot veiwing glass is provided with this appliance and shall be installed for the protection of children and other at-risk
individuals. If the barrier becomes damaged, the barrier
shall be replaced with the manufacturer’s barrier for this appliance
FOR YOUR SAFETY
• Installation and service must be performed by a qualied
installer, service agency or gas supplier.
• This installation must conform to local codes or, in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
• To prevent injury, do not allow anyone who is unfamiliar
with the stove to operate it.
• To prevent injury, if the pilot or pilot and burners have gone out on their own, open the glass door and wait 5 minutes to air out before attempting to re­light the stove.
• Always keep the area around these appliances clear of combustible material, gasoline and other ammable liquids
and vapours.
• These appliances should not be used as a drying rack for clothing or for hanging Christmas stockings/decorations.
• Due to the paint curing on the stove, a faint odor and slight smoking will likely be noticed when the stove is rst used. Open a window until the smoking stops.
Always connect this gas stove to a vent system and vent to
the outside of the building envelope. Never vent to another room or inside the building. Make sure the specied vent
pipe is used, properly sized and of adequate height to
provide sufcient draft. Inspect the venting system annually
for blockage and signs of deterioration. WARNING: Failure to position the parts in accordance
with the diagrams in this booklet, or failure to use only
parts specically approved with this appliance, may result in
property damage or personal injury.
WARNING: Do not operate with the glass front removed,
cracked or broken. Replacement of the glass should be done
by a licensed or qualied service person.
• Never use solid fuels such as wood, paper, cardboard, coal, or any ammable liquids, etc., in this appliance.
• Do not use this appliance if any part has been under water. Immediately call a qualied service technician to inspect the
appliance and to replace any part of the control system or any gas control which has been under water.
• Do not abuse the glass by striking it or slamming the door
shut.
• If the Q1C unit is pulled out of its installation, and the vent-
air intake system is disconnected for any reason, ensure that the vent-air intake pipes are reconnected and re-sealed in accordance to the instructions noted in
- DIrect Vent
InItIal InstallatIon
Page 4
Table of Contents
Safety Precautions.............................................................................................................2
Table of Contents................................................................................................................4
Codes And Approvals.........................................................................................................5
Specications.............................................................................................................6
Dimensions......................................................................................................6
Rating Label Location..............................................................................................6
Operating Instructions........................................................................................................7
Lighting Instructions................................................................................................7
Pilot Light...............................................................................................................8
Air Shutter...............................................................................................................8
Remote Controls.....................................................................................................8
Burner Lighting.......................................................................................................9
Blower Speed ........................................................................................................9
Normal Sounds During Operation.............................................................................9
Maintenance And Service...................................................................................................10
Routine Maintenance.............................................................................................10
Cleaning The Glass................................................................................................10
Cleaning The Firebox..............................................................................................10
Replacing the Glass...............................................................................................10
Cleaning Decorative Surfaces.................................................................................11
Glass Door Removal..............................................................................................11
Burner Removal....................................................................................................12
Fuel Conversion.....................................................................................................12
Initial Installation............................................................................................................15
Introduction.................................................................................................15
Placement and Framing..........................................................................................15
Rear Vent Conversion.............................................................................................16
Insulating Material.................................................................................................17
Standoffs............................................................................................18
Corner Installation.................................................................................................19
Adjusting Install Depth...........................................................................................20
Mantle and Non-Combustible Clearances.................................................................22
Direct Vent............................................................................................................23
Vent Termination Restrictions................................................................................24
Venting Clearances................................................................................................25
Approved Venting Parts........................................................................................25
Vent Congurations and Restrictor Settings..........................................................25
Horizontal Termination - Rear Vent w/ No Rise.....................................................27
Allowable Co-Axial Vent Congurations.................................................................28
Co-Linear Venting Adapter Kit (50-2982)..............................................................28
Air Restrictor Settings...........................................................................................31
Horizontal Termination..........................................................................................32
Vertical Termination...............................................................................................33
Solid Fuel Fireplace Installation...............................................................................36
Gas Line Connection and Testing.............................................................................37
Electrical Requirements..........................................................................................38
Secondary Installation.......................................................................................................39
Coal Set Installation.............................................................................................39
Optional Porcelain Panels (50-2939) Installation & Removal...................................41
Safety Screen Installation.....................................................................................42
Trouble Shooting...............................................................................................................43
Parts List..........................................................................................................................44
Parts Diagram...................................................................................................................45
Notes..............................................................................................................46
Warranty.................................................................................................................47
Installation Data Sheet....................................................................................................48
4
Page 5
Codes And Approvals
DIRECT VENT ONLY: This type is identied by the sufx DV. This appliance draws all of its air for
combustion from outside the dwelling, through a specially designed vent pipe system.
This appliance has been tested and approved for installations from 0 feet to 4500 feet (1372 m) above
sea level.
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
This appliance has been tested by INTERTEK and found to comply with the established VENTED GAS FIREPLACE HEATER standards in CANADA and the USA as follows:
VENTED GAS FIREPLACE HEATER (Q1C; NG/LPG)
TESTED TO: ANSI Z21.88a-2014/CSA 2.33a-2014 VENTED GAS FIREPLACE HEATERS
CAN/CGA 2.17-M91 (R2009) GAS FIRED APPLIANCES FOR HIGH ALTITUDES
This ENVIRO Q1C Fireplace:
• Has been certied for use with either natural or propane gases. (See rating label.)
• Is not for use with solid fuels.
• Is approved for bedroom or bed sitting room. (IN CANADA: must be installed with a listed wall thermostat. IN USA: see current ANSI Z223.1 for installation instructions.)
• Must be installed in accordance with local codes. If none exist, use current installation code CAN/CGA B149 in Canada or ANSI Z223.1/NFPA 54 in the USA.
• Must be properly connected to an approved venting system and not connected to a chimney ue serving a separate solid-fuel burning appliance.
IMPORTANT NOTICE (Regarding rst re up): When the unit is turned
on for the rst time, it should be turned onto high without the fan on for the rst 4 hours. This will cure the paint, coal set, gasket material and other products used in the manufacturing process. It is advisable to open a
window or door, as the unit will start to smoke and can irritate some people.
After the unit has gone through the rst burn, turn the unit off including
the pilot, let the unit get cold then remove the glass door and clean it with
a good gas replace glass cleaner, available at your local ENVIRO dealer.
5
Page 6
Dimensions:
26 7/8"
(683mm)
6 5/8"
(168mm)
4 3/8" (112mm)
15 3/4"
(400mm)
21 1/2"
(548mm)
21" (508mm)
16 1/2"
(420mm)
18 3/4"
(476mm)
24 3/4"
(627mm)
21"
(533mm)
18 3/4" (476mm)
14"
(356mm)
6 5/8"
(168mm)
25 1/4"
(641mm)
5 3/8" (136mm)
27 1/2"
(700mm)
4 3/8"
(112mm)
16 7/8"
(479mm)
3 5/8" (93mm)
14 1/4"
(361mm)
25 1/4" (641mm)
16 7/8"
(429mm)
4 1/2"
(114mm)
14.212"
(361mm)
14.25"
(362mm)
Gas
Line
120v
Plug
ZC
120v
In
Specifications
*Shown
With Modern
Surround and
Extensions*
install Depth:
If the available depth of install is less than 14.25”, the stove depth can be reduced to 12.375”
by removing the cabinet extension brackets; however, doing so will cause the safety screen
to protroud past the front of the surround panel. If a reduced install depth is required, the
extension brackets must be (re)moved. Refer to InItIal InstallatIon - aDjustIng Install Depth for instructions.
Figure 1. Q1L Dimensions - Top Vent
Figure 2. Q1L Dimensions - Rear Vent
6
Page 7
Operating Instructions
For Your Safety, Read Safety Precautions And
Lighting Instructions Before Operating
WARNING: IF YOU DO NOT FOLLOW THESE INSTRUCTIONS EXACTLY A FIRE OR EXPLOSION MAY
RESULT, CAUSING PROPERTY DAMAGE, PERSONAL INJURY OF LOSS OF LIFE.
rating label & lighting instructions location:
The rating label plate and lighting instructions are located under the gas valve and attached to the unit with a length of chain.
lighting anD turning off instructions:
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life
A. This appliance has a pilot which must be lighted by hand. When lighting the pilot, follow these instructions exactly. B. BEFORE LIGHTING smell all around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor. WHAT TO DO IF YOU SMELL GAS: Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier’s instructions. If you cannot reach your gas supplier, call the fire department.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above on this label.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to this appliance.
4. Open the front control panel.
5. Turn off the gas control knob clockwise to the “OFF” position.
6. Open door. Wait fIve (5) minutes to clear out any gas. Close door. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the saftey information above on this label. If you don’t smell gas, go to the next step.
7. Find pilot-located near the center rear of the firebox. Turn the gas control knob counter-clockwise to “PILOT”. Push the gas control in fully and hold, keep knob depressed for about 30 seconds after the pilot is lit. Release knob. If pilot goes out, repeat steps 4 through 5.
C. Use only your hand to push in or turn the gas control knob. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it. Call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
WARNING: This gas valve has a lockout device, which will not allow the pilot burner to be relit until the thermocouple has cooled.
-If the knob does not pop up when released, stop and immediately call your service technician or gas supplier.
-If the pilot will not stay lit after several tries, turn the gas control knob clockwise
8. Turn the gas control knob counter clockwise to the “ON” position.
Flip the burner switch to “ON” then turn the “HI/LOW” knob to the desired setting.
9. Close the front control panel.
10. Turn on all electric power to the appliance.
11. Set thermostat to desired setting.
to “OFF” and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to the lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Open the front control panel and flip burner switch to “OFF”
Figure 3. Lighting Instruction Label
4. Turn the gas control knob clockwise to the “OFF” position.
5. Close the front control panel.
C-12454
7
Page 8
Operating Instructions
pilot light:
1. Turn off the gas to the replace. If not recently done, remove the glass and let the unit air out
for at least ve (5) minutes to clear out any gas. Turn on gas to the heater. Leak test all joints
with soapy water. NEVER USE OPEN FLAME FOR LEAK TESTING.
2. Start the pilot by pressing the gas control knob and turning it to PILOT.
While holding the gas control knob in, press the piezo ignitor several
times until the pilot light starts. Hold the gas control knob in for 30 seconds. Check that the pilot has fully engulfed the thermocouple assembly (see Figure 4).
3. Start the main burner by turning the gas control knob to ON and then turn the rocker switch to ON. Check that all burner ports have ame.
Thermopile
Thermocouple
4. Leak test all gas joints again.
Figure 4. Pilot Flame
air shutter:
The air shutter adjustment lever is on the right hand side of the venturi box (see Figure 5).
The air shutter allows the amount of air coming into the replace to be adjusted in order to accommodate different climates and venting arrangements. Start the pilot and then the burner. Make sure the pilot ame is burning normally and none of the burner ports are plugged. Let the replace burn for roughly fteen minutes and then examine the ames, compare the ames to Figure 40.
The ideal ame will be blue at the base and light orange above. The ames should be of medium height. If the ames look like this, no venturi adjustment is needed. If the ames are fairly short and
mostly blue, the replace is getting too
much air. Therefore, the air shutter should be closed (pulled out) slightly
until the correct ames are achieved.
Flames that are very orange, with tall, dark, stringy tips, are not getting enough
air. Open (push in) the venturi until the ames clean up. If the venturi is opened,
or closed all the way, and the correct
ames cannot be attained, turn off the
gas and contact the dealer.
Less Air
Air Shutter Adjustment
More Air
Warning: Incorrect venturi adjustment
may lead to improper combustion, which
is a safety hazard. Contact the dealer if
there is any concern about the venturi
Figure 5. Air shutter adjustment lever.
adjustment.
remote controls:
This replace can use an optional remote control or an optional cordless wall thermostat. If either of these are to be used to control the replace for the majority of the time, leave the ON/OFF switch (on the control panel) in the remote/thermostat position. Consult the instructions included with the remote/wall
thermostat for operation guidelines.
8
Page 9
Operating Instructions
For Your Safety, Read Safety Precautions And
Lighting Instructions Before Operating
burner lighting:
A) Make sure the pilot is lit.
B) Turn gas control knob COUNTER CLOCKWISE to ON. C) Flip the burner switch to ON. D) Turn HI/LO knob to the desired ame height. E) Turn on all electrical power to the unit.
NOTE: Check that all burner holes are lit. TO TURN GAS FIREPLACE OFF:
Flip switch to OFF to turn off burners only.
If the replace is to be turned off for the season,
or for servicing, turn the gas shut off valve to
OFF. DO NOT FORCE IT. If the unit is going to
be serviced, turn off the electrical power to the unit as well.
NOTE: When the unit is turned on for the rst time, it should be turned onto high, with the fan OFF, for the rst two to four hours. This will cure the paint, coal set, gasket material, and other products used in the manufacturing process. It is advised that a door or window be opened as the unit will start to smoke, which can irritate some people. After the unit has gone through the rst burn, turn the unit OFF,
including the pilot, and let the unit get completely cold. Then remove the glass and clean it with a good
gas replace glass cleaner, available at your local Enviro dealer. See “MaIntenance anD serVIce; glass Door reMoVal and “MaIntenance anD serVIce; cleanIng the glass.”
Gas Control
Hi/Low Knob
Piezo Ignitor
Alternate Burner
Switch Location
Figure 6. Control Panel
blower speeD:
The blower will come on only when the replace is up to temperature (approximately 15 minutes). The speed of the fan can be changed by turning
the fan control knob. The blower will continue to operate automatically after the
unit has been shut off (approximately 25 minutes).To turn the blower off, turn the knob COUNTER CLOCKWISE until it “clicks” off (Figure 7).
It is advisable not to operate the blower below
1
/3 speed as it puts a strain on the windings of the blower and running the blower at lower speeds could also cause premature fan failure.
Figure 7. Fan Control
normal sounDs During operation:
Table 1: Normal Sounds
Component Sound & Reason
Q1C & Surround Panels Creaking when heating up or cooling down. Burner Light pop or poof when turned off; this is more common with LP units. Temperature Sensor Clinking when it senses to turn the blower on or off. Pilot Flame Quiet whisper while the pilot ame in on. Blower / Fan Air movement that increase and decreases with the speed of the blower. The
blower is pushing the heat from the replace into the room.
Gas Control Valve Dull click when turning on or off, this is the valve opening and closing.
9
Page 10
Maintenance And Service
routine maintenance:
At least once a year, run through the following procedures to ensure the system is clean and working
properly. Check the burner to see if all the ports are clear and clean. Check the pilot to make sure it is not blocked by anything. The pilot ame should be blue with little or no yellow on the tips.
Warning: Clearances must be sufcient to allow access for maintenance and service
Warning: Failure to position the parts in accordance with this manual, or failure to use only parts
specically approved with this appliance may result in property damage or personal injury.
The venting system must be periodically examined; it is recommended the examination is done by a
qualied agency.
cleaning the glass:
When the replace has cooled, remove the face of the replace along with the glass. See MaIntenance
anD serVIce - glass Door reMoVal. Check the gasket material on the back of the glass, making sure that
it is attached and intact.
During a cold start up, condensation will sometimes form on the glass. This is a normal condition with all replaces. However, this condensation can allow dust and lint to cling to the glass surface. Initial paint curing of the appliance can leave a slight lm behind the glass, a temporary problem. The glass will need
cleaning about two weeks after installation. Use a mild glass cleaner and a soft cloth. Abrasive
cleaners will damage the glass and painted surfaces. Depending on the amount of use, the glass
should require cleaning no more than two or three times a season. Do not clean the glass when it is
hot.
cleaning the firebox:
Remove the coal set carefully, as it is very fragile. Gently remove all the coals and place on a paper towel. Vacuum the bottom of the rebox thoroughly. Carefully clean any dust off the coal set and remove any lint from the burner and pilot. At this time, inspect the burner tube for cracking or severe warping. If a
problem is suspected, contact the dealer. Check the coal set for deterioration or large amounts of soot;
a small amount on the bottom side of the coal set is normal. Replace the coal set as in the seconDary InstallatIon - coal set InstallatIon section. If a new coal set is required, contact your nearest ENVIRO
dealer.
replacing the glass:
The glass in the replace is a high temperature ceramic. If the glass is damaged in any way, a factory
replacement is required (see parts lIst). Wear gloves when handling damaged glass door assembly
to prevent personal injury. Do not operate with the glass front removed, cracked or broken. Removal
and replacement of the glass from the door must be done by a licensed or qualied service person.
The glass must be purchased from an ENVIRO dealer. No substitute materials are allowed.
Remove the door (see page 11). The replacement glass will come with a new gasket installed. Remove
any silicone remnants from the door. Apply high temperature silicone to the two vertical faces of the door and install the new piece of glass with gasket (be sure to maintain edge clearances). Apply even pressure to the glass to allow the silicone to adhere to the gasket material.
10
Page 11
Maintenance And Service
cleaning Decorative surfaces:
Painted and porcelain faces should be wiped with a damp cloth periodically. If a plated face has been
purchased, it should be unpacked/unwrapped carefully to avoid getting anything on the surface of the
nish, including cleaners, polish and nger prints. It is important to note that ngerprints and other marks can leave a permanent stain on plated nishes. To avoid this, give the face a quick wipe with denatured alcohol on a soft cloth BEFORE lighting the replace. Never clean the face when it is hot. Do not use other cleaners as they may leave a residue, which can become permanently etched into
the surface.
glass Door removal:
In order to install the coal set, and
for regular cleaning, the glass door
Door Tool Hole
Figure 8. Top latches for glass door
Door Latch Mechanism
must be removed. There are two (2) door latch mechanisms on top the glass door as shown in Figure
8. Each latch has a hole at the front
to use the door tool, supplied with the unit, to pull the mechanisms straight out and up. When the top latches are unhooked, lean the door forward and then lift it up out of the alignment slots at the bottom
corners of the rebox, shown in Figure 9.
Alignment Slot
(both corners)
*Parts removed
for clarity*
Figure 9. Bottom Alignment Slots for glass door.
To replace the glass door, simply reverse the above procedure.
Warning: Do not touch or attempt
to remove the glass door if the
replace is not completely cold.
WARNING: Never operate the replace with the glass door
removed.
11
Page 12
Maintenance And Service
burner removal:
The burner may need to be removed for a few reasons, including cleaning under the burner, converting the unit to a different gas type, or to replace the burner altogether. Proceed only when the unit has
completely cooled down.
1. Remove the glass door as shown in the
MaIntenance anD serVIce - glass Door
reMoVal.
2. Remove the coal set as shown in
SeconDary InstallatIon - coal set
InstallaIon
3. Push the air shutter in until it stops
4. Lift the burner straight up then out.
To re-install the burner follow steps 1-4 in
reverse. When placing the burner back in the unit be sure to adjust the air shutter back to the correct setting.
Figure 10. Removing Burner.
fuel conversion:
TO BE INSTALLED BY A QUALIFIED SERVICE AGENCY ONLY
Please read and understand these instructions before installing.
Warning: This conversion kit shall be installed by a qualied service agency in accordance with the manufacturer’s instructions and all applicable codes and requirements of the authority having jurisdiction. If the information in these instructions is not followed exactly, a re, explosion or production of carbon monoxide may result causing property damage, personal injury or loss of life. The qualied service agency is responsible for the proper installation of this kit. The installation is not proper or complete until the operation of the converted appliance is checked as specied in the manufacturer’s instructions supplied with the kit.
Kit Parts List:
1 - Orice (NG - #46 DMS or LP - 1.2 mm)
1 - Pilot Injector (NG 0.62 mm; LP 0.35 mm) 1 - Installation instruction sheet 1 - Conversion label
Carefully inspect all parts supplied with this conversion kit. If any parts have been damaged or are
missing, contact your dealer, distributor or courier company to have them replaced before starting this installation.
12
Page 13
Maintenance And Service
Loosen
Tighten
Conversion Kit Installation:
1. Turn control knob on the gas valve to the “OFF” position and shut the gas supply off at the shut-off valve upstream of the unit. CAUTION: The gas supply must be shut off prior to disconnecting the
electrical power and before proceeding with the conversion. Allow the valve and unit to cool down to room temperature.
2. Remove the glass door as shown in the MaIntenance anD serVIce - glass Door reMoVal.
3. Carefully remove the coal set.
4. Remove the burner as shown in the MaIntenance anD serVIce - Burner reMoVal.
5. Convert the burner orice(s):
a) Remove the main burner orice with a ½ inch deep socket.
b) Put a bead of pipe-thread sealant or approved Teon tape on the orice threads before installing
into the brass elbow.
c) Install the new orice(s) from the kit into the brass elbow.
6. Convert the pilot injector:
a) Pull the pilot hood straight up to access the pilot injector.
b) Using a
5
/32” or 4 mm Allen key, remove the pilot injector.
c) Install the new pilot injector supplied with this conversion kit. Simply
screw the new injector inside the pilot hood using the Allen key,
d) Reinstall the hood by placing the hood on the assembly, line up the key
way, and snap into place.
7. Convert the SIT gas valve:
a) Remove the black protection cap from the HI/LO knob by hand shown in
Figure 11.
b) Insert a
5
/32” or 4 mm Allen wrench into the
hexagonal key-way of the screw (see Figure 12),
rotate it counter-clockwise until it is free and extract it.
c) Check that the screw is clean and if necessary
remove dirt.
d) Flip the screw (refer to Figure 13).
e) Using the Allen wrench as shown in Figure 12,
rotate the screw clockwise until a torque of 9
inch lbs. WARNING! Do not over tighten the
screw. It is recommended that you grip the
wrench by the short side.
Figure 11: Removing
valve cap.
13
Figure 12: Removing valve
screw.
f) Verify that if the conversion is from NG to
LPG, the screw must be re-assembled with the red o-ring visible (refer to Figure 14). If the conversion is from LPG to NG, the red o-ring of
the screw must be not visible.
Figure 13: Flip valve
screw.
Page 14
Maintenance And Service
Red o-ring
is not visible
Red o-ring
is visible
LPG Configuration
Figure 14: O-ring on valve screw.
8. Reinstall the burner, coal set, and glass door.
Also refer to seconDary InstallatIon - coal set InstallatIon in your Owner’s Manual. When re-
installing the burner, ensure that the burner to pilot shield relationship is similar to what is shown
in Figure 15.
9. Reconnect the main gas line if it was disconnected
and open the shut-off valve at the gas line to the unit.
g) Re-attach the black protection
cap that was removed in step
a (Figure 11).
10. Use a small brush to apply a warm soapy water
solution to all gas connections (use a half dish
soap and half warm water). If a gas leak is present, bubbling will occur. Gas leaks can be
repaired by using an approved pipe thread sealant
or approved Teon tape. NEVER USE AN OPEN FLAME WHEN TESTING FOR LEAKS.
Figure 15. Pilot assembly
beside the burner.
11. Reconnect the electrical power to the unit.
12. Relight the pilot and conrm the ame properly covers both the thermocouple and thermopile (see Figure 4, page 8). Should the pilot require adjustment, turn the adjustment screw (gure 42, page
35) clockwise to decrease or counterclockwise to increase until the correct ame is achieved.
13. Relight the main burner in both the “HI” and “LO” positions to verify proper burner ignition, operation
and proper ame appearance. Conrm the inlet and manifold pressures are within the acceptable
ranges as directed in section
IntIal IntallatIon - gas lIne connectIon anD testIng. If the Q1 has
been installed at an altitude higher than 2000ft (610m) it is required to de-rate the unit accordingly:
In the USA: The appliance may be installed at higher altitudes. Please refer to your American Gas
Association guidelines which state: the sea level rated input of Gas Designed Appliances installed at elevations above 2000 (610 m) feet is to be reduced 4% for each 1000 feet (305 m) above sea level.
Refer also to local authorities or codes which have jurisdiction in your area regarding the de-rate guidelines.
In Canada: When the appliance is installed at elevations above 4500 feet (1372 m), the certied high
altitude rating shall be reduced at the rate of 4% for each additional 1000 feet (305 m).
14. MAKE SURE that the conversion label is installed on or close to the rating label to signify that the
unit has been converted to a different fuel type.
14
Page 15
35 1/4"
(895mm)
25 1/4"
(641mm)
See Table 3
6
15
/16"
(176mm)
Gas
Inlet
Ad
j
ac
e
n
t
w
a
l
l
3 11/16 "
min
(94mm)
Rear Vent
Top
Vent
41"
(1041mm)
S
t
e
el St
u
d
W
o
od
Framing
25 1/2"
(648mm)
15
Initial Installation
QUALIFIED INSTALLERS ONLY
introDuction:
This section of the owner’s manual is for the use of qualied technicians only. Fireplace placement,
hearths, facing, mantels, and venting terminations will be covered, as well as the gas and electric systems.
There are several installation safety guidelines that must be adhered to. Please carefully read the safety
precautions at the front of this manual.
NOTE: The Q1C comes as a top vent unit but can be converted to a rear vent.
Warning: Clearances must be sufcient to allow access for maintenance and service.
placement anD framing:
The location for the replace can be along a wall, raised or at oor level, or in a corner. There are specic framing
measurements for each situation. The basic opening should have the
dimensions shown in Figure 16. The replace must have a strong and
level surface to be placed on. The surface should be made of wood or a non-combustible material, not carpet. The framing boards may touch the top and back standoffs, but only the
supplied insulating material can be placed between the frame and
the standoffs. A horizontal steel stud may be used at the height shown to support the bottom edge of the non­combustible material (see page 22).
Note: Steel stud, if used, must
Figure 16. Dimensions for Framing the Firebox
Firebox Framing
Width 25¼” 64.1 cm
Height - Rear Vent 35¼” 89.5 cm
be installed after the unit has
been attached to framing
Height - Top Vent 41” 104.1 cm Gas Inlet (Distance
From Back)
Table 2. Framing Dimensions.
Minimal (3 or 4 - sided) 17⅛” 43.5 cm Modern or Contemorary 16½” 41.9 cm No Surround Panel 15¼” 38.7 cm
The gas line, ⅜ inch NPT, should be Brought to the left side of the replace.
The location should be chosen so the
replace will be at least 36 inches (91.4
cm) from drapes, doors and other combustibles. The framed opening must
be a minimum of 3 11/16” inches (9.4
cm) from the nearest perpendicular wall (sidewall to the edge of the opening).
Framing Depth
Surround Panel Depth
Table 3. Framing Dimensions.
Page 16
Initial Installation
QUALIFIED INSTALLERS ONLY
rear vent conversion:
For smaller openings the Q1C can be converted from a top vent to a rear vent unit.
Vent Collar
Base Plate
Step 1: Using a T20 screwdriver
Exhaust Spigot
Cover Plate
remove the vent collar, base plate,
cover plate and exhaust spigot (28 screws total) as shown in Figure 17.
Figure 17. Vent Conversion - Step 1
Step 2: Switch the removed parts
around as shown in Figure 18 and re-install all 28 screws. To correctly
install the base plate keep the locating notch on each side at the bottom. Also note the exhaust spigot uses a lower set of holes when setup as a rear vent.
Use lower set of
holes
Locating Notch
Figure 18. Vent Conversion - Step 2
16
Page 17
Initial Installation
QUALIFIED INSTALLERS ONLY
insulating material:
Depending on the chosen vent conguration, either one or both pieces of insulating material supplied
with the unit are required for correct installation.
Rear Vent: When using the rear vent conguration both the ceramic board and berglass insulation are required. Place the ceramic board on top of the unit rst and then place the insulation on top of the ceramic board as shown in Figure 19.
Top Vent: When using the top vent conguration only the gerglass insulation is required. Cut a notch in the insulation, to t around the vent collar, and place on top of the unit as shown in Figure 20.
Fiberglass
Insulation
Ceramic
Board
Figure 19. Unit Insulation - Rear Vent
Fiberglass
Insulation (cut around vent collar)
Figure 20. Unit Insulation - Top Vent
17
Page 18
Initial Installation
QUALIFIED INSTALLERS ONLY
stanDoffs:
The Q1C is supplied with two sets of standoffs that serve as a framing guide and must be used when the
unit is being installed as a replace. The front set of standoffs mount to sides of the unit (see Figure 21)
and can be adjusted as needed to account for the thickness of the wall material. The rear standoffs attach to the back corners of the unit and are not adjustable.
Combustible material can touch the standoffs but must
not encroach past them. If
Mounting Screw
Rear Standoff
Mounting Screw
the Q1C is being installed into a pre-existing masonary replace
it is not necessary to use the
standoffs. Installation of the standoffs will require a T20
screwdriver. Remove the installed screws in the noted locations, place the standoff over the holes, and re-install the screws.
Figure 21. Standoff Mounts
Frame up to this
ange
Multiple Holes for Adjustable
Depth
Front Standoff
No Combustible
Material within
dotted lines
Figure 22. Area created by stanoffs
18
Page 19
Initial Installation
A
B
Outside Wall
Inside Wall
C
D
E F
Outside Wall
Inside Wall
A
B
C
D E
F
QUALIFIED INSTALLERS ONLY
corner installation:
The dimensions for installing a replace in the corner of a room are depicted in Figures 21 and 24 and listed in table 4 below. The dimensions will vary depending on the surround panel used, refer to InItIal
InstallatIon - aDjustIng Install Depth to adjust installation depth as needed. Refer to “InItIal
InstallatIon - allowaBle co-axIal Vent confIguratIons” for allowable pipe lengths.
Do not interfere with the structural integrity of the walls.
Corner Installation Dimensions
(Top or Rear Vent)
Dimension - C [Set] 15¾” (260mm) Dimension - E [Set] 25¼” (641mm)
Minimal Panel (3 or 4 sided)
7/16” (1103mm) 11/16” (779mm)
9/16” (421mm)
7/16” (1078mm)
Figure 23. Dimensions for a corner installation, rear
vented.
Dimension - A 43 Dimension - B 30
Dimension - D 16
Dimension - F 61⅜” (1559mm)
Modern or Contemporary Panel
Dimension - A 42 Dimension - B 30” (762mm)
Dimension - D 15⅞” (403mm)
Dimension - F 60” (1524mm)
No Surround Panel
Dimension - A 39½” (794mm) Dimension - B 27⅞” (562mm)
Dimension - D 13¾” (203mm)
Dimension - F 55⅞” (1123mm)
Table 4. Corner Install Dimensions
19
Figure 24. Dimensions for a corner installation, top
vented.
Page 20
Initial Installation
A
Minimal 15.00 in Minimal 12.375 in
QUALIFIED INSTALLERS ONLY
aDjusting install Depth:
The extension brackets installed on the outside of the stove are used to make the front of the surround
panel ush with the safety screen. The Q1 is built with the extension brackets set for a Modern or Contemporary surround panel. If a different depth is required look at the chart below and follow the
steps below.
Extensions Reduced Extensions
Surround Panel Install Depth Surround Panel Install Depth
Modern 14.25 in Modern 12.375 in
Contemporary 14.25 in Contemporary 12.375 in
Note: If the smallest install depth is desired (15¼” [387mm] for replace, 12⅜” [313mm] for insert) the
extension brackets must be removed. Any surround panel can still be used but the safety screen will protrude out further than the panel.
REMOVAL:
1. Using a T20 screwdriver, remove the ve (5) scrrews that secure the Top Extension to the Cabinet (see Figure 26).
2. Remove the ve (5) screws on each Side
Extension (see Figure 26).
Step 3-5 on next page
Top Cabinet
Extension
Side Cabinet
Extensions
Figure 25: Q1 as Shipped
Figure 26: Removing Extension Screws.
20
Page 21
B
Initial Installation
QUALIFIED INSTALLERS ONLY
3. If using the smallest depth (no surround panel), remove the extension brackets, re-install the removed screws and install the standoffs as directed
in the InItIal InstallatIon - stanDoffs
section of the manual (standoffs not required for insert applications).
4. If using the biggest depth (3 or 4-sided minimal surround), re-install the
extension brackets in the position noted
in the Figure 28.
5. Install the side standoffs (if required)
onto the side extension brackets using the forward set of free holes. Adjust the depth of the side standoffs as needed
(see Figure 27). Also see the InItIal
InstallatIon - stanDoffs section of the
manual.
Top screws that tie
the side brackets
into the top bracket
can be removed to
separate brackets
Screw locations for
side standoffs
Figure 27. Removing Extension Brackets
21
Figure 28. Position of Extension Brackets at
biggest depth
Page 22
Initial Installation
12" (305 mm) Mantle
1¼” (32mm)
thick non-
combustible
floor
12" (305 mm) minimum from wall
If hearth is flush with flooring
2" (51 mm) Mantle
41"
(1041 mm)
minimum
from bottom
of unit
35" (889 mm) minimum
from bottom
of unit
10” (254 mm)
Non-Combustible
Facing
7" (178 mm) minimum from side of door to
side wall
1/2” (12.7mm)
thick non-
combustible facing
QUALIFIED INSTALLERS ONLY
mantle & non-combustible clearances:
When installing the Q1C as a zero clearance replace the correct clearances and materials must be used: above unit: A minimum 10” of ½” thick non-combustible facing material, with a R-Value no less than
0.26, must be used (see Figure 29).
in front of unit: A minimum 12” of 1¼” thick non-combustible material, with a R-Value no less than
2.27 (K-value no less than .55), must be used when the unit is either sitting on the oor or raised within 2’’ of the oor. Approved 1” thick Q1 oor protection is available seperately under part number 50-3016. When raising the unit 2” - 4” above the oor a minimum 12” of ¾” thick material, with a R-Value no less than 1.36 (K-value no less than .55), must be used. If raising the unit higher than 4” from the oor, any
combustible material can be used.
aDjacent/siDewall: There must be a minimum distance of 7” from the side of the rebox door to an adjacent wall composed of combustible material (see Figure 29).
mantle: It is not necessary to install a mantle, but if one is desired the guidelines as shown in Figure 25
below must be followed.
Figure 29. Non-Combustible Clearances
22
Page 23
Initial Installation
42”
41”
40”
39”
38”
37”
36”
35”
1 2 3 4 5 6 7 8 9 10 11 12
M A N T L E H E I G H T
( F R O M U N I T B O T T O M )
M A N T L E D E P T H
Minimum Mantle Clearances
12” MANTLE
2” MANTLE
QUALIFIED INSTALLERS ONLY
mantle: It is not necessary to install a mantle,
but if one is desired the guidelines as shown
in Figures 29 and 30 must be followed.
Figure 30. Mantle Clearances
Direct vent:
WARNING: This appliance has been designed to draw room air for proper heat circulation from the bottom of the unit, and out the top front. Blocking or modifying these openings in
any way can create hazardous situations.
The vent length for the Q1C must be between 7” (18 cm) and 44ft (13.4 m). This model is vented with co-axial 4” intake, 6 5/8” exhaust aluminum or stainless steel approved rigid vent leading into a vertical or horizontal termination cap. The ue collar of this model will t inside of a standard 4” x 6 5/8” vent
and must be either correctly interlocked or fastened, with three screws directly to the vent.
The Q1C may also be converted to a replace insert with the use of a co-linear vent adapter kit (50-
2982) see
InItIal InstallatIon - co-lInear VentIng aDapter KIt. When converted to co-linear venting
the lenth of vent must be between 8’ (2.44m) and 40’ (12.19m). The insert model is vented with a 3” intake and a 3” exhaust aluminum or stainless steel approved ex vent leading into a vertical termination cap only. The ue collars of this model will t inside of a standard 3” vent
and must be fastened directly to the vent with three screws. The exhaust vent and air intake are both located on the top of the unit.
Check periodically that the vents are unrestricted. Also ensure that all direct vent pipes have been
properly sealed and installed after routine inspection or cleaning. The air intake and exhaust pipes must
be installed in the correct locations on the top of the Q1C.
venting fireplace inserts:
When using the co-linear venting adapter kit (50-2982) the Q1C may be installed and vented into any solid fuel replace that has been installed in accordance with the National, Provincial/State and local building codes and has been constructed of noncombustible materials. Please reference the information in Table 11 and Figures 47. An approved chimney liner and rain cap must be used. A throat connector or ashing must be installed to ensure a tight seal, top performance, safety and efciency. Carefully follow the manufacturer’s instructions that accompany the chimney liner kit. Use double walled aluminum ex vent (3” ex conversion piece and 4”x 6 5/8” cap) from the following approved products; Simpson Dura-Vent (Direct Vent GS). If necessary, remove the vent collar plate from the top of the insert and connect it securely to the liner with sheet metal screws. Check for any tears in the liner at this point. IMPORTANT: The screws that hold the vent collar plate in its approved position must be
installed.
NOTE: If the Q1C unit is pulled out of its installation, and the vent-air intake system is disconnected
for any reason, ensure that the vent-air intake pipes are re-sealed with high-temperature sealant and
23
reconnected with three (3) sheet metal screws evenly spaced.
Page 24
Initial Installation
QUALIFIED INSTALLERS ONLY
vent termination restrictions:
N
O
D
E
C
B
L
F
Fixed
Closed
Openable
B
B
Openable
Fixed
Closed
H
G
G
M
B
A
J
I
Termination Cap
Figure 31. Vent Termination Restrictions, refer to Table 5.
Letter Canadian Installation
A 12 in (30 cm) Clearance above grade, verandah, porch, deck, or balcony.
B 12 in (30 cm) 9 in (23 cm) Clearance from window or door that may be opened.
C 12 in (30 cm)* Clearance from permanently closed window (to prevent
D 24 in (60 cm)* Vertical clearance to ventilated soft located above the
E 18 in (45 cm)* Clearance to unventilated soft. F 12 in (30 cm)* Clearance to outside corner.
G 12 in (30 cm)* Clearance to inside corner. H 3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly I 3 ft (91 cm) 3 ft (91 cm)* Radial clearance around service regulator vent outlet. J 12 in (30 cm) 9 in (23 cm) Clearance to non-mechanical air supply inlet to building, or
K 6 ft (1.83 m) 3 ft (91 cm) above if within 10
L 7 ft (2.13 m
M 12 in / 30 cm
N 12 in (30 cm)* Clearance horizontally to any surface (such as an exterior
O 12 in (30 cm) Clearance above roof line for vertical terminations.
1
)t
+
Air Supply Inlet
Gas MeterG
Restriction Zone
(Termination not allowed)
Table 5: Vent termination clearances.
US Installation
3 ft (91 cm) within a height of
15 ft (4.5 m) above the meter/
regulator assembly*
ft (3 m) horizontally
7 ft (2.13 m)
12 in / 30 cm*
2
condensation).
terminal, within a horizontal distance of 2 ft (60 cm) from
center line of terminal.
Clearance to each side of center line extended above me­ter/regulator assembly.
the combustion air inlet to any other appliance.
Clearance to mechanical air supply inlet.
*t
+
Clearance above paved sidewalk or paved driveway located
on public property.
Clearance under verandah, porch, deck, or balcony.
wall) for vertical terminations.
Description
K
A
1
In accordance with the current CSA B149, Natural Gas and Propane Installation Code.
2
In accordance with the current ANSI Z223.1 NFPA 54, National Fuel Gas Code.
* These numbers are only estimates. t
A vent shall not terminate directly above a side walk or paved driveway that is located between two single family dwellings
and it serves both dwellings. +
Permitted only if verandah, porch, deck, or balcony is fully open on a minimum of two sides beneath the oor.
Clearances are in accordance with local installation codes and the requirements of the gas supplier.
NOTE: Venting terminals shall not be recessed into walls or siding.
24
Page 25
Initial Installation
Framing
Joists/Studs
10”
10”
QUALIFIED INSTALLERS ONLY
venting clearances:
A 1” (25 mm) clearance to combustibles must be maintained around any vertical vent pipe. Around a horizontal vent pipe, the clearance to combustibles should be 2” (51 mm) above and 1½” (38 mm) on the sides and bottom. When combustible materials are directly above a 90° elbow, 3” (76 mm) of clearance
are necessary.
Table 6. Vent Pipe Minimum Clearances.
Vertical Pipe to
the Side Walls
Hard
Pipe
1”
(25.4 mm)
A 10” (254 mm) x 10” (254 mm) frame (see Figure 32) will assure the proper support and spacing for the vent pipe as it passes through the wall. Installations in Canada require that a wall thimble be used for
passing through walls and ceilings. All sealing and vapour barriers must comply with local building codes.
The conguration of the venting pipes depends on the locations
of walls, ceilings, and studs. However, the pipes cannot be of
arbitrary length and arrangement. Because the length of the
vertical and horizontal sections dramatically affects the burning efciency of the replace, certain guidelines have been set in
InItIal InstallatIon - allowaBle co-axIal Vent confIguratIons.
Venting terminals can not be recessed into a wall or siding.
Horizontal Pipe to
the Sides & Bottom
1½”
(38.1 mm)
Above an Elbow
Above the Unit
3”
(76.2 mm)
Above an Elbow
Not Above the Unit
3”
(76.2 mm)
Above Horizontal
Vent Pipe
2”
(51 mm)
Wall Frame 8”
(203mm) or less
10”x10”
(25x25cm)
WARNING: This gas appliance must not be connected to a chimney ue serving a separate solid-burning appliances.
Figure 32. Vent Framing For Wall or Ceiling.
approveD venting parts:
Table 7: Approved Vent Manufacturers
Manufacturer Trade Name Nominal Sizes
American Metal Products AmeriVent Direct 4” - 6 5/8” ICC EXCELDirect 4” - 6 5/8” Security Chimneys International LTD Secure Vent 4” - 6 5/8” Selkirk Metalbestos Direct-Temp 4” - 6 5/8” Simpson Dura-Vent Direct Vent GS 4” - 6 5/8”
The Q1C replace has been tested and certied for use with AMERICAN METAL PRODUCTS “AMERIVENT DIRECT”, SIMPSON DURAVENT TYPE GS PIPE FOR GAS STOVES. SECURITY CHIMNEY’S “SECURE VENT DIRECT VENT SYSTEM” and SELKIRK “DIRECT-TEMP VENT SYSTEM” kits are available for horizontal and vertical venting. When using Simpson Duravent, it is recommended that, before installation, a bead of RTV High Temperature Silicone should be applied to each outer vent joint, and Mil-Pac to each inner
joint. When planning an installation, it will be necessary to select the proper length of vent pipe for the particular requirements.
25
WARNING: Do not mix parts from different vent manufacturers’ systems.
Page 26
Initial Installation
QUALIFIED INSTALLERS ONLY
EXCEPTION TO WARNING: This product has been evaluated by Intertek for using a Direct Vent GS starting collar in conjunction with Secure Vent, Direct-Temp, AmeriVent Direct, and EXCELDirect venting systems. Use of these systems with the Direct Vent GS starting collar is deemed acceptable and does not affect the Intertek WH listing of the appliance.
Table 8: Vent part numbers (Must state if galvanized or black wanted, PART NUMBERS).
Direct Vent GS Direct-Temp Secure Vent Ameri Vent Direct Description
908 4DT-6 SV4L6 6” pipe length
4D7 7” pipe length
907 4DT-9 9” pipe length
906 4DT-12 SV4L12 4D12 12” pipe length
904 4DT-24 SV4L24 4D2 24” pipe length
903 4DT-36 SV4L36 4D3 36” pipe length
902 4DT-48 SV4L48 4D4 48” pipe length
945 4DT-EL45 SV4EBR45 4D45B 45° elbow, black
990 4DT-EL90 SV4EBR90 4D90B 90° elbow, black
950 4DT-VS SV4VS Vinyl siding standoff/sheild 942 4DT-WT SV4RSN 4DWT Wall thimble
953 4DT-SC SV4FC 4DSC Storm collar 963 4DT-FS SV4BF 4DFSP Fire stop 988 4DT-WS/B SV4BM 4DWS Wall strap/support/band
970 4DT-HKA SV0SHK 4DHTK1
911 11” to 14 ⅝” pipe, adjustable
4DT-AJ 4D12A 4” to 10” pipe , adjustable
SV4LA12 1½” to 12” pipe , adjustable
943 4DT-AF6 4DF Flashing, 0/12 to 6/12 roof pitch
943S 4DT-AF12 4DF12 Flashing, 7/12 to 12/12 roof pitch
SV4FA Flashing, 1/12 to 7/12 roof pitch
SV4FB Flashing, 8/12 to 12/12 roof pitch
943F SV4F Flat ashing
991 4DT-HVC High wind vertical termination 985 4DT-HHC High wind horizontal termination
Horizontal termination kit (SD: Basic Kit, SEL: Kit A, SC: Standard Kit)
978 4DT-VKC SV0FAK 4DVTK Vertical termination kit
971 4DT-HKB SV0SHK2 4DHTK2
Horizontal termination kit
(SD: Kit A, SEL: Kit B, SC: Kit)
26
Page 27
Initial Installation
QUALIFIED INSTALLERS ONLY
horizontal termination - rear vent with no vertical rise:
The Q1C can be installed in rear vent applications with no vertical rise within the parameters as shown in Figures 33 and 34.
Approved horizontal termination
18” (46 cm) Max. vent length
Approved through wall thimble
Figure 33. Corner Rear Vent - No Vertical Rise
Max. 1 x 45˚ Elbow
7” (18 cm) Min. vent length
24” (61 cm) Max. vent length
Approved horizontal termination
27
Approved through wall thimble
Figure 34. Flat to Wall Rear Vent - No Vertical Rise
Page 28
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
1 2 3 4 5 6 7 8 9 10 11 12 13 14
HORIZONTAL RUN
ft
VERTICAL RISE
INSTALLATION
PROHIBITED
INSTALLATION
PROHIBITED
Initial Installation
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
HORIZONTAL RUN
QUALIFIED INSTALLERS ONLY
allowable co-axial vent configurations:
Figures 35 & 36 show the range of possible vent congurations if the unit is top or rear vented, for vertical
and horizontal terminations. Any layout that remains within the shaded areas is acceptable. Having the
fewest number of elbows is ideal, as they tend to disrupt air movement. Using 45˚ elbows is preferable to using 90˚ elbows. Also, a shorter vent system will perform better than a longer one. When top vented, the total length of horizontal vent pipe can not exceed 14 feet (4.27m) and the total vent length can not exceed
Figure 35. Possible Vent Congurations for Top
Vented Vertical and Horizontal Terminations.
44ft (13.4m). Any combination of rise and
run can be used as long as it lays within the
shaded area (a total of two (2) 90˚ elbows or
four (4) 45˚ elbows can be used. In addition
to what is shown, if a 90˚ elbow is used in
the horizontal plane, 3 feet (91.4cm) must
be subtracted from the allowable horizontal
run (for each 45˚ elbow, 1½ feet must be
subtracted).
Note: Air restrictors (supplied with the unit) are required for vertical venting runs
of 8ft (2.44m) or taller. See
aIr restrIctor
settIngs for more information
Note: Minimum length of co-linear venting
is 8ft (2.44m) and maximum length is 40ft (12.19m)
7
13
12
6
11
10
5
9
INSTALLATION
PROHIBITED
8
4
7
6
3
5
VERTICAL RISE
4
2
3
2
1
1
ft
1 2 3 4 5 6 7 8 9
1 2 3 4 5
HORIZONTAL RUN
Figure 36. Possible Vent Congurations
for Rear Vented Vertical and Horizontal
Terminations.
28
Page 29
Initial Installation
26 1/2"
(673mm)
12 3/8" (313mm)
or
14 1/4" (362mm)
or
14 15/16" (380mm)
QUALIFIED INSTALLERS ONLY
co-linear venting aDapter Kit (50-2982):
The Q1C can be converted from solid co-axial venting to 3” (76mm) exible co-linear venting to allow
for installation into exisiting masonary replaces (see Figures 31-33). Co-linear venting can not be used
in combustible chimney installations. This adapter kit is for vertical terminations only and can’t be
connected to a chimney ue serving a seperate solid-fuel burning stove or appliance. To adjust the depth
of the unit please refer the the InItIal InstallatIon - aDjustIng Install Depth section of the manual.
Note: The co-linear adapter kit can only be used in the top vent conguration WARNING: Failure to position the parts in accordance with these diagrams or failure to use only parts
specically approved with this appliance may result in property damage or personal injury.
29
Adapter Kit Contents:
Vent Plate Adapter
Ceramic Gasket
Figure 37: Q1 Insert Dimensions
3” Dia. Exhaust
Spigot
Figure 38: Co-Linear Venting Kit Contents
Vent Plate Adapter
Exhaust Spigot
Ceramic Flange
Gasket
Exhaust Spigot
Ceramic Tube
Gasket
Page 30
Initial Installation
Adapter Kit Installation:
QUALIFIED INSTALLERS ONLY
Vent Collar
Base Plate
4” Exhaust Spigot
Cover Plate
Figure 39: Removal of Co-Axial Venting
Vent Plate Adapter
3” Exhaust Spigot
Step 1: Using a T20 screwdriver
remove the vent collar, base plate,
cover plate and 4” exhaust spigot (28 screws total) as shown in
Figure 32. The vent collar, base
plate, and 4” exhaust spigot will
no longer be used.
Cover Plate
Figure 40: Installation of Co-Linear Vent Kit
Step 2: Install the components
supplied in the adapter kit as shown using the screws that had been removed from the unit in
Step 1. The gasket on the bottom
side the vent plate adapter and
exhaust spigot ange gasket will
be sandwiched together when properly installed.
30
Page 31
Initial Installation
A
QUALIFIED INSTALLERS ONLY
air restrictor settings:
When installing the Q1C with 8ft (2.44M) or more of vertical venting, either co-axial or co-linear, it may be necessary to restrict the fresh air supply in the rebox to control the combustion and ame appearance. Using the pair of air restrictors supplied with the unit, install them on each side of the rebox and adjust to the correct setting as outlined in the gure and table below. To install the air restrictors rst you
must remove the log set, air diffuser, and creamic brick panels (see seconDary InstallatIon - optIonal porcelaIn panels InstallatIon anD reMoVal) then remove the set screws as shown on each side of the
rebox. Next, install the restrictors at the correct setting and tighten the set screws to hold them in place.
#3
#1
#2
Set Screw
Figure 41: Installation of Air Restrictors
Table 9: Air Restrictor Settings
Air Restrictor Settings
Length of Vertical Vent Propane Natural Gas
Less than 8ft (2.44m) co-linear or co-axial No Restriction Required No Restriction Required
31
8ft (2.44m) - 20ft (6.1m) co-linear or co-axial No Restriction Required No Restricition Required
Through Roof Termination, more than 20ft (6.1m) to 40ft (12.19m) co-linear
Through Roof Termination, more than 20ft (6.1m) to 40ft (12.19m) co-axial
Setting #2 Setting #3
Setting #1 Setting #1
Page 32
Initial Installation
QUALIFIED INSTALLERS ONLY
horizontal termination:
NOTES:
1. Horizontal pipes must not be level. For every 12 inches (305 mm) of horizontal travel
(away from the stove), there should be at least ¼ inch (6.4 mm) of vertical travel. Never
allow the vent to run downward, as this could cause high temperatures or even present the possibility of a re.
2. The exterior of the horizontal vent termination must not be blocked or obstructed.
3. If the vent termination is not
being attached to wood, the four wood screws provided should be replaced with material appropriate fasteners.
4. For buildings with vinyl siding,
a vinyl standoff should be
Elbow
installed between the vent cap and the exterior wall. Attach the vinyl siding standoff to the horizontal termination.
Note that the termination bolts onto the at portion of
the standoff, providing an air space between the wall and the vent termination. The air gap prevents excessive heat from possibly melting the vinyl siding.
5. Horizontal pipes must be supported every 3 feet (914
mm). Plumber’s all round strap will sufce.
Wall thimble fire stop
Exhaust pipe
Combustion air outer pipe
Figure 42. Horizontal Vent Termination
Horizontal wall termination
Wall framing
6. When running horizontal pipe, clearances to combustibles must be maintained 1½ inches (38 mm) sides, 1½ inches (38 mm) bottom, and 2 inches (51 mm) top.
Step 1.
Set the replace in the desired location. Check to determine if wall studs will be in the way when
the venting system is attached. If this is the case, the location of the replace may have to be
adjusted or the venting may have to be offset.
Step 2. Direct vent pipe sections are designed with special twist-lock connections. Dry t the desired
combination of pipe and elbows to the appliance adaptor.
Step 3. With the pipe in the correct position and attached to the replace, mark the wall for a 10 inches
(25.4 cm) x 10 inches (25.4 cm) square hole (see Figure 42). The center of the hole should match the center line of the horizontal pipe. Cut and frame the hole in the exterior wall where the vent will be terminated. If the wall being penetrated is made of a non-combustible material (i.e. masonry or concrete) a 7 inches (17.8 cm) hole is acceptable.
32
Page 33
Initial Installation
QUALIFIED INSTALLERS ONLY
NOTE: For Simpson Duravent only, place a bead of Mil-Pac or Rutland No 78 Stove and Gasket Cement on the outer edge of the inner exhaust pipe (non-ared end). Push the pipe sections together, then twist about ¼ turn, making sure the two sections are fully locked. Wrap all seams with foil ducting tape.
Step 4.
With the hole now framed, the wall thimble installed, and the pipe extending into the wall,
proceed to the outside. Attach the termination to the pipe using RTV and Mil-Pac or Rutland No
78 Stove and Gasket Cement to seal joints. The vent pipe must extend into the vent cap at least
1¼ inches (3.2 cm). Secure the connection between the vent cap and the pipe by attaching the
two (2) sheet metal straps, which extend from the vent cap assembly to the outer wall of the
vent pipe. Bend any remaining portion of the strap back towards the vent cap. Security Secure Vent uses a twist lock cap.
Step 5.
Position the horizontal vent termination in the center of the 10 inches (25.4 cm) square hole
and attach to the exterior wall with the four screws provided. The arrow on the vent termination should be pointing up. Run a bead of non-hardening mastic around the edges of the vent
cap, to make a seal with the wall. Ensure the proper clearances to combustibles have been
maintained.
vertical termination:
Step 1. Check the instructions for required clearances (air spaces) to combustibles when passing
through ceilings, walls, roofs, enclosures, attic rafters, or other nearby combustible surfaces.
Do not pack air spaces with insulation.
Step 2. Set the gas appliance in the desired location. Drop a plumb bob down from the ceiling to
the position of the appliance ue exit, and mark the location where the vent will penetrate the ceiling. Drill a small hole at this point. Next, drop a plumb bob from the roof to the hole previously drilled in the ceiling, mark the spot where the vent will penetrate the roof. Determine if ceiling joists, roof rafters, or other framing will obstruct the venting system. You may wish to
relocate the appliance, or to offset, to avoid cutting load bearing members.
Step 3. To install the Round
Support Box/Wall Thimble in a at ceiling, cut a 10 inch (25.4 cm) square hole
in the ceiling, centered in
the hole drilled in Step 2.
Frame the hole as shown
in Figure 42.
Step 4.
Assemble the desired
lengths of black pipe and elbows necessary to reach from the appliance adapter up through the
Round Support Box. Insure that all pipe and
elbow connections are in their fully twist-locked position.
Elbow Strap
Figure 43. Vertical Vent Termination
Vertical
Termination
Storm Collar
Flashing
Roofing nails
33
Page 34
Initial Installation
H
Dimension ‘H’ obtained from table below.
QUALIFIED INSTALLERS ONLY
STEP 5. Cut hole in the roof centered on the small hole placed in the roof from Step 2. The hole should
be of sufcient size to meet minimum requirements for Clearance to Combustibles, as specied. Continue to assemble lengths of pipe and elbows necessary to reach from the ceiling support box up through the roof line. Galvanized pipe and elbows may be utilized in the attic, as well as above the roof line. The galvanized nish is desirable above the roof line, due to the higher
corrosion resistance.
STEP 6.
Once the pipe sections have been joined, and run up through the hole in the roof, slip an elbow
strap over the exposed sections, bend the support straps outwards, and push the elbow strap
down to the roof level, as shown in Figure 43. Tighten the clamp around the pipe section. Use a level to make sure the pipe is truly vertical. With roong nails, secure the support straps to the roof. Seal the nails holes heads with non-hardening mastic. Trim the excess length of the support straps that extend out beyond the edge of the ashing.
STEP 7.
Slip the ashing over the pipe section protruding through the roof. Secure the base of the
ashing to the roof with roong nails. Use a non-hardening sealant between the uphill edge of the ashing and the roof. Insure the roong material overlaps the top edge of the ashing. Verify that you have at least the minimum clearance to combustibles at the roof line.
STEP 8.
Continue to add pipe sections until the height of the vent cap meets the minimum code
requirements. Refer to Figure 44 and Table 10. Note that for steep roof pitches, the vent height must be increased. In high wind conditions, nearby trees, adjoining roof lines, steep pitched roofs, and other similar factors can result in poor draft, or down drafting. In these cases,
increasing the vent height may solve the problem.
STEP 9.
Slip the storm collar over the pipe, and push it down to the top of the roof ashing as shown
in Figure 43. Use the non-hardening sealant around the joint between the pipe and the storm
collar.
STEP 10. Twist-lock the vent cap.
Table 10: Minimum ‘H’ for Figure 35.
Roof Pitch Minimum Height (H)
Figure 44: Height of Vertical Termination;
Reference Table 8.
Feet Meters
Flat to 7/12 1 0.3
Over 7/12 to 8/12 1.5 0.46 Over 8/12 to 9/12 2 0.61
Over 9/12 to 10/12 2.5 0.76
Over 10/12 to 11/12 3.25 0.99
Over 11/12 to 12/12 4 1.22
Over 12/12 to 14/12 5 1.52 Over 14/12 to 16/12 6 1.83
Over 16/12 to 18/12 7 2.13
Over 18/12 to 20/12 7.5 2.29
Over 20/12 to 21/12 8 2.44
34
Page 35
plumbers tape connected to wall strap
Wall strap
45° elbows (x2)
Initial Installation
QUALIFIED INSTALLERS ONLY
NOTES:
(1)
If an offset is necessary in the attic to avoid
obstructions, it is important to support the vent pipe
every 3 feet (914 mm), to avoid excessive stress
on the elbows, and possible separation. Wall straps
are available for this purpose (see Figure 45).
(2) When ever possible, use 45° degree elbows instead
of 90° degree elbows. The 45° degree elbow offers
less restriction to the ow of ue gases and intake
air.
(3)
For multi story installations; a ceiling restop is
required at the second oor, and any subsequent oors (see Figure 46). The opening should be framed to 10” (254 mm) x 10” (254 mm) inside
dimensions, in the same manner as shown in Figure
32.
(4) Any occupied areas above the rst oor, including
Figure 45: Use of Wall Straps.
closets and storage spaces, which the vertical vent passes through, must be enclosed. The enclosure may be framed and sheet-rocked with standard building materials. However consult the appliance manufactures installation instructions for the minimum allowable clearance between the outside of the vent pipe, and the combustible surfaces of the enclosure.
Do not ll any required air spaces with
insulation.
Figure 46: Multi-Story Vent Pipe Installation.
35
Page 36
Initial Installation
The total vent length must be between 8 ft (2.44 m) and 40 ft (12.19 m).
Install a sealed vent cap to prevent leakage of room air up through chimney. The intake and the exhaust are 3" (76mm). Measure the height of the chimney beforehand and purchase the appropriate
venting. Never attempt to over-stretch a flexible liner to accommodate the height of the chimney. Every joint in the venting must be secured with three (3) #8 x 3/8” HWH sheet metal screws and an appropriate sealant (either silicone or stove cement).
The flue damper can be fully blocked open or removed for installation of the unit; the smoke shelves, shields and baffles may be removed if attached by mechanical fasteners.
The fireplace and fireplace chimney must be clean, in good working order and constructed of non-combustible materials.
Make sure that all chimney cleanouts are tight fitting and will not permit air to leak into the chimney.
Refractory, glass doors, screen rails, screen mesh and log grates can be removed from the fireplace before installing the unit.
WARNING: This fireplace has been converted
for the use with a gas fireplace insert only and
cannot be used for burning wood or solid
fuels unless all original parts have been
replaced, and the fireplace re-approved by the
authority having jurisdiction.
C-11168
QUALIFIED INSTALLERS ONLY
soliD fuel fireplace installation:
Table 11: Min. Fireplace Dimensions
Width Height Depth
Fireplace Dimensions 20¼” (51.4 cm) 27½” (69.8 cm) 12½” (31.7 cm)
Note: Space must be left for gas line on left side of unit for servicing purposes
The base, sidewalls and top structure of the solid fuel rebox cannot be altered with the exception of: removal of dampers, removal of smoke shelf or bafe, removal of ember catches, removal of log grate, removal of viewing screen/curtain, and removal of doors. THE ORIGINAL FIREPLACE MAY NEVER BE RETURNED TO SOLID FUEL USE IN THIS CONDITION.
Figure 47: Solid Fuel Fireplace Installation.
IMPORTANT: If the factory-built replace has no gas access hole(s) provided, an access hole of 1.5 inch (37.5 mm) or less may be drilled through the lower sides or bottom of the rebox in a proper workmanship
like manner. This access hole must be plugged with non-combustible insulation after the gas supply line
has been installed. Cutting any sheet-metal parts of the replace, in which the gas replace insert is
to be installed is prohibited. The label plate shown on the right, included with co-linear venting adapter kit, must be permanently attached inside the cavity of the
replace in a visible location.
Figure 48: Fireplace Altered Plate.
36
Page 37
Initial Installation
QUALIFIED INSTALLERS ONLY
gas line connection anD testing:
WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to
this appliance.
GAS LINE CONNECTION
• This stove is equipped with a certied exible pipe located on the left side of the unit terminating in a 3/8” female NPT tting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation code in Canada, or in the USA gas installations follow either local codes or the current edition of the National Fuel Gas Code ANSI Z223.1.
• The efciency rating of this appliance is a product thermal efciency rating determined under
continuous operating conditions and was determined independently of any installed system.
The appliance and its shutoff valves must be disconnected from the gas supply piping system
Gas Control
Knob
Pilot Adjustment
Screw
during any pressure testing where the pressure
exceeds ½ PSIG (3.45 KPa) or damage will occur
to the valve. The appliance must be isolated from the gas supply
piping system by closing its individual manual
N
O
T
O
L
I
P
F
O
F
shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or
less than ½ psig (3.45 KPa).
Always check for gas leaks with a soap and water solution after completing the required pressure test.
Inlet
PressureTap
IN OUT
Manifold
PressureTap
Figure 49: Fully Labeled Gas Valve.
TO TEST VALVE PRESSURES
The pressure taps are located on the top right of the valve shown in Figure 49.
•Turn set screw 1 turn counter clockwise to loosen,
•Place
5
/16” (8 mm) I.D. hose over pressure tap system.
•Check pressures using a manometer.
•When nished, release pressure, remove hose & tighten set screw.
Table 12: Pressure and BTU Information.
O
L
T
I
P
I
H
L
O
TP TH TP TH
Hi/Low
Knob
37
Natural Gas Propane
Main Orice #46 DMS 1.2 mm
Manifold Pressure 3.5” W.C. (0.87 KPa) 10.0” W.C. (2.49 KPa)
Min. Manifold Pressure 1.6” W.C. (0.40 KPa) 6.4” W.C. (1.59 KPa)
Max Supply Pressure 7.0” W.C. (1.74 KPa) 11.0” W.C. (2.74 KPa) Min. Supply Pressure 4.5” W.C. (1.12 KPa) 10.4” W.C. (2.59 KPa)
Max BTU/hr Input 20,000 BTU/hr (5.86 KW) 18,500 BTU/hr (8.42 KW) Min. BTU/hr Input 13,600 BTU/hr (3.98 KW) 14,500 BTU/hr (4.25 KW)
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
Page 38
Initial Installation
QUALIFIED INSTALLERS ONLY
electrical requirements:
The fan will not operate if the appliance is cold. Once the unit is lit and the fan is set to the desired level,
the fan will automatically turn on upon reaching operating temperature. The fan will automatically turn off after the appliance has cooled down.
Figure 50: Fan wiring diagram.
The replace must be electrically connected and grounded in accordance with local codes or, in the absence of local codes, with the current CSA C22.1 Canadian Electrical Code Part 1, Safety Standards For Electrical Installations, or The National Electrical Code ANSI / NFPA 70 in the US.
WARNING: The electrical grounding instructions must be followed. The fan kit is equipped with a three­prong (grounding) plug for your protection against shock hazard, and should be plugged directly into a
properly grounded three-prong outlet. DO NOT cut or remove the grounding prong from this plug.
CAUTION: When servicing controls, label all wires prior to disconnection. Wiring errors can cause
improper and dangerous operation. Verify proper operation after servicing. If any of the original wire as supplied with the appliance must be replaced, it must be replaced with 18 AWG wire with a temperature rating of 105°C
38
Page 39
Secondary Installation
coal set installation:
The placement of the coal set is not arbitrary. If it is positioned incorrectly, the ames can be “pinched” and will not burn correctly. Using the pictures provided, carefully set the coal set in place (see Figures 43 through 47). The pictures below feature the optional ledgestone panels installed.
NOTE: The coal set is fragile and should be handled gently.
Figure 51: This is how the rebox looks with only
the burner, back rest, and ledgestone panels in place.
Figure 51. Empty rebox with burner installed
Figure 52. Coal Bed Installation.
Step 1: Place the lower coal bed in
the rebox by placing the rear of the
bed on the back rest and front of the bed on the burner supports. Make sure the front of the coal bed is touching
the ngers at the front of each burner
mount.
39
Page 40
Secondary Installation
Figure 53. Second Stage Coal Set Installation.
Step 2: Install the two front coal
pieces at the front of the rebox as shown in Figure 53. The pieces will
sit down in the gap between the back of the burner and the front
edge of the rebox.
Step 3: Next, install the set of
three coal rocks on the locator pins at the top of the coal bed.
The at side of the rocks will face
forward when installed correctly
(see Figure 54). Finally, install the
top coal bed by resting it on top of the lower coal bed ensuring it is properly centered. The front edge of the top coal bed will touch the back side of the front coal pieces and rest on top of the burner when correctly installed.
NOTE: While the glass is still
removed, it is recommended that the gas line be purged by lighting the pilot.
When lighting the replace for the rst time since the coal set has been
installed/replaced, watch for ignition
at ALL the burner ports. If a long
delay is noticed, turn the appliance off and wait for it to cool down. Then remove the glass and make sure none of the burner ports are blocked.
Figure 54. Third Stage Coal Set Installation.
Maintenance: Once a year, the coal set should be removed and
checked for deterioration or large amounts of soot. A small amount on the bottom side or in the holes of the coal set is normal. Remove
and replace the coal set in the same manner described above. Cracks
on the surface of the lower coal bed are normal and will not effect the performance.
If a new coal set is required, contact your nearest ENVIRO dealer.
Never operate the replace with the glass door removed.
40
Page 41
Secondary Installation
optional porcelain panels (50-2939) installation anD removal:
Turn off the gas control knob and allow the
unit to cool.
Please ensure that your porcelain panels have not
been damaged.
To Install Panels:
1. Remove the glass door by following the instruction in the “ glass Door reMoVal” section and remove the
coal set as outlined in the previous section.
2. Remove the rebox bafe by unscrewing the two screws indicated in Figure 50 using a T20 screwdriver. Lower the front of the bafe down
Figure 55. Bafe Screws.
3. Next, remove the top brick panel retainers on each side as shown in Figure 56 using a T20 screwdriver.
and then lift it out of the two locating screws at
the rear of the rebox.
MaIntenance anD serVIce -
4. Carefully remove the left, rear, and right brick panels from the rebox.
5. Install the rear porcelain panel rst by sitting it on the ledge at the rear of the rebox (see gure 57), then follow with
the left and right panels.
6. Re-install the brick panel retainer screws and brackets
7. Re-install the rebox bafe.
8. Install the top porcelain panel by screwing it to the rebox bafe as show in Figure 58 using the supplied screws.
9. Re-install the coal set as outlined in the previous section.
10. Re-Install the glass door
Figure 56. Top Panel Retainers.
41
Figure 57. Rear Panel Ledge. Figure 58. Top Panel Screws.
Page 42
Secondary Installation
safety screen installation:
Safety Screen Frame
Right Bracket
Top/Bottom
Bracket
The safety screen supplied with the unit must be
assembled rst before it can be installed. When
installed, the screen should not extrude out any farther than the surround panel if the cabinet extensions are still installed.
Safety Screen Assembly
1. Attach the left, right, top/bottom brackets onto
the safety screen using a T20 screwdriver and the supplied sixteen (16) #8 T20 screws (see Figure
59). Do not over-tighten the screws, doing so
could cause them to strip out of the screen frame.
2. Lift the face upright in front of the replace with
the four (4) hooks pointing towards the replace. Slide the hooks into the corresponding brackets on each side of the cabinet (see Figure 61). Ensure the hooks are secure before releasing the
safety screen.
Top/Bottom
Bracket
Figure 59: Installing Safety Screen Mounts.
Left Bracket
Figure 60: Installing Safety Screen onto
Brackets.
Figure 61: Installing Safety Screen onto
Cabinet Bracket (Parts removed for clarity)
42
Page 43
Trouble Shooting
Problem Possible Cause Solution
The main burner does not ignite when called for.
Spark will not light the pilot
after repeatedly pressing the spark ignitor.
Pilot will not remain lit. Problem with thermocouple
The gas valve may not be on. • Check that the gas control knob is in the “ON” position. Thermostat is not calling for
heat.
Problem with gas valve. • Use a DC voltmeter to measure the voltage across the
Defective piezo ignitor. • Check connections to ignitor.
Broken spark electrode. • Check for broken ceramic insulation, replace electrode if
Misaligned spark electrode. • If spark is not arcing from electrode to pilot, loosen the
circuit.
• Adjust the thermostat several degrees above ambient
temperature.
TPTH and TP terminals. Main operator voltage: Open circuit ≥ 325mV Closed circuit ≥ 100mV
• If voltage is not present, check the control circuit for
proper operation.
• If proper control system voltage is present, replace the
gas control.
• If ignitor connections are good but no spark, replace
ignitor.
broken.
screws on the pilot base adjust and tighten.
• Check for proper connection of the thermocouple to the rear of the valve. If loose, fully tighten.
• Check pilot for full ame impingement around thermocouple. If ame is too small, check gas pressure,
adjust pilot rate screw, check pilot head for damage.
• Check thermocouple voltage at valve. It must be greater than 5 mV. If low, replace thermocouple.
Air in gas line (pilot dies while knob is depressed).
Burners will not remain lit. Problem with thermopile
circuit.
Flame lifting Leak in vent pipe • Check for leaks in vent connections.
Improper vent conguration • Check vent conguration with manual.
Terminal may be recirculating
ue gases
Glass fogs up Normal Condition: after the appliance warms up the glass will clear.
**Due to additives in gas, glass may get hazy during operation** Clean as needed. Blue Flames Normal during start up: ames will yellow as the replace heats up. Flames are burning “dirty” or
sooting
Remote control doesn’t work Problem with the remote • One or more of the batteries are dead. See remote
Flame impingement • Check coal set positioning.
Problem with replace • The on/off switch is turned to OFF.
• Bleed line.
• Check gas line pressure.
• Contact dealer.
• Check gas line pressure .
• Check for ame impingement on thermopile. If low, see “Pilot will not remain lit”.
• Check thermopile for minimum of 300 mV when burner is
switched on.
• Check wiring to thermostat for breaks.
• Check to see if terminal is on correctly.
• May need to install high wind termination cap.
• Contact dealer.
• Increase primary air by opening the venturi shutter and/
or by opening the vent restrictor.
See also “Burners will not remain lit.”
control instructions.
• The gas control valve is turned to PILOT or OFF.
• The pilot has gone out.
43
Page 44
Parts List
Reference
Number
1 Door Release Tool 50-2510
2 Door Latch Mechanism w/ Spring (set of 2) 50-1285 3 Firebox Air Restrictors (set of 2) 50-2988
4 Coal Burner Pilot Shield 50-2995 5 120 Ceramic Fan Temperature Sensor EC-001
6 Convection Fan only 50-2493
7 FPI Fan Controller (69.5V) 115V W/FS Knob EC-039A 8 Fan Controller Knob W/Decal EC-040
9 S.I.T. Piezo Ignitor EC-023 10 FPI Burner Switch EC-026 11 Control Panel w/ Decal 50-2989 12 S.I.T. Pilot Assembly - Standing Pilot EC-015
- Pilot Assembly Gasket EC-021
13 S.I.T. Nova Valve - Convertible 50-1421 14 Heyco Strain Relief EC-044 15 Domestic Power Cord (115v) EC-042 16 Coal Set 50-2937 17 Tube Burner 50-2992 18 Door Glass w/ Gasket (19.75 x 17.5in) 50-2998 19 Door Complete 50-2990 20 Porcelain Liners Set (4 pieces) 50-2939 21 Ceramic Brick Liner Set (3 pieces) 50-2938
- Ceramic Ledgstone Liner Set (3 pieces) 50-2972
- Fireplace Floor Pad 12” x 20” 50-3016 22 Co-Linear Vent Kit 50-2982 23 Q1C Owners Manual 50-3001
- Q1 Replacement Safety Screen 50-3052
- Q1 Conversion Kit - LP to NG (Nova) 50-2993
- Q1 Conversion Kit - NG to LP (Nova) 50-2983
- 12 oz. Can of Matallic Black Touch Up Paint PAINT-12-MB
Part Description Part Number
44
Page 45
Parts Diagram
20
2
4
3
5
13
16
15
14
11
9
12
8
7
6
17
18
19
1
10
21
23
22
45
Page 46
Notes
46
Page 47
Jan 2013
Sher wood Industries Ltd. (“Sher wood”) hereby warrants, subject to the terms and conditions herein set for th, this product against defects in material and workmanship during the specied warranty period starting from the date of original purchase at retail. In the event of a defect of material or workmanship during the specied warranty period, Sherwood reser ves the right to make repairs or to assess the replacement of a defective product at Sherwood’s factory. The shipp
ing costs are to be paid by the consumer. All warranties by Sherwood are set forth herein and no claim shall be made against Sherwood on any oral warranty or representation.
Conditions
A completed warranty registration must be submitted to Sherwood within 90 days of original purchase via the online warranty registration page or via the mail-in warranty registration card provided. Have the installe
r ll in the installation data
sheet in the back of the manual for warranty and future reference.
This warranty applies only to the original owner in the original location from date of install.
The unit must have been properly installed by a qualied technician or installer, and must meet all local and national building code requirements.
The warranty does not cover removal and re-installation costs.
Sherwood Industries Ltd. reserves the right to make changes without notice.
Sherwood Industries Ltd. and its employees or representatives will not assume any damages, either directly or indirectly caused by improper usage, operation, installation, servicing or maintenance of this appliance.
A proof of original purchase must be provided by you or the dealer including serial number.
Exclusions
An expanded list of exclusions is available at www.enviro.com/help/warranty.html
This warranty does not cover:
Damage as a result of improper usage or abuse.
Damage caused from over-ring due to incorrect setup or tampering.
Damage caused by incorrect installation.
To the Dealer
Provide name, address and telephone number of purchaser and date of purchase.
Provide date of purchase. Name of installer and dealer. Serial number of the
appliance. Nature of complaint, defects or malfunction, description and part #
of any parts replaced.
Pictures or return of damaged or defective product may be required.
To the Distributor
Sign and verify that work and information are correct.
Sherwood Industries Ltd.
6782 Oldeld Road, Victoria, BC . Canada V8M 2A3
Online warranty registration: www.enviro.com/warranty/
Any discolouration of the safety screen.
Warranty for Enviro Gas Products
Category One Year Two Year Limited Lifetime
(7yr)
Parts
1
(unit s erial numbe r required)
Firebox Liner Panels
(excluding porc elain)
Ceramic Steel
Firebox
Heat Exchanger
Burner
Ceramic Logs
2
Ceramic Glass
3
Pedestal / Legs
(excluding ni sh)
Door Assembly
Surround Panels
(excluding ni sh)
Exterior Panels
(excluding ni sh)
Up to 5 years
Electrical Components
Exterior Surface Finishing
4
Labour
1
Whereas warranty has expired, replacement parts will be warrantied for 90 days from part purchase date. Labour not included.
Unit serial number required.
2
Log set and panels excludes wear and tear or breakage caused by cleaning or service.
3
Glass is covered for thermal breakage. Photos of box, inside of door, and unit serial # must be supplied for breakage due to shipping.
4
Exterior Surface nishing covers plating, enamel or paint and excludes colour changes, chipping, and ngerprints.
Travel costs not included.
47
Page 48
Installation Data Sheet
The following information must be recorded by the installer for warranty purposes and future reference.
NAME OF OWNER:
_________________________________________
ADDRESS:
_________________________________________ _________________________________________ _________________________________________
PHONE:___________________________________
MODEL:___________________________________
SERIAL NUMBER:___________________________
DATE OF PURCHASE: _____________ (dd/mm/yyyy)
NAME OF DEALER:
_________________________________________
ADDRESS:
_________________________________________ _________________________________________ _________________________________________
PHONE:___________________________________
NAME OF INSTALLER:
_________________________________________
DATE OF INSTALLATION:___________(dd/mm/yyyy)
NATURAL GAS (NAT) PROPANE(LPG)
INLET GAS PRESSURE:_________in wc
MAIN BURNER ORIFICE:__________# DMS
PILOT ORIFICE #_________OR________in diam.
INSTALLER’S SIGNATURE:
_________________________________________
ADDRESS:
_________________________________________ _________________________________________ _________________________________________
PHONE:___________________________________
MANUFACTURED BY:
SHERWOOD INDUSTRIES LTD.
6782 OLDFIELD RD. SAANICHTON, BC, CANADA V8M 2A3
www.enviro.com
November 30, 2015
C-14478
48
Loading...